Documente Academic
Documente Profesional
Documente Cultură
Introduction
ELECTRICAL DIVISION
Since 1921 the division undertakes contracts in the entire field of electrical
power engineering.
•Industrial generators.
•Capacitor banks.
•Electric fences.
About Fentons
F e n t o n s L i m i t e d .
S u b s i d i a r y C oD m i v p i a s ni o i en s s . J o i n t V e n t u r e .
1 . E n e r g y N 1 e . t E ( Pl e v c t t ) r i L c t a d l . 1D . i Tv i h s ei o P n a y p h o n e
C o m p a n y L t d .
2 . F e n t o n s C 2 o . m F p i ru e t e & r s S e c u r i t y
( P v t ) L t d . D i v i s i o n .
3 . T e l e c o m m u n i c a t i o n
D i v i s i o n .
P a g i n g D i v i s i o n .
Combination pliers
This pliers used for cutting wires, gripping operation by hand, twisting wires & a number
of other operation required in electrical works.
Screw drivers
The screw drivers are available in different blade sizes.
How ever, the latter method of classification is generally preferred, according to which
cables can be divided in to the following groups;
1. Conduit
Steel conduit
The most common form of conduit used today is screwed steel with a welded seam or
solid drawn (used in hazardous areas where there is a high risk of fire and explosion). A
light gauge conduit is also available with its use restricted to providing protection for
flush PVC cable installations. Two finishes for conduit are: black enamel (dry situations)
and galvanized (for out doors and situations where dampness is present).
The main advantages of steel conduit include its ability to give conductors good
protection against mechanical damage; it allows easy rewiring; fire risks are minimized;
and the conduit can be used as a circuit protective conductor (CPC), through it is
common practice to run a separate CPC in the conduit.
PVC Conduit:
Because the expansion rate for PVC conduit is around five times that of its steel
equivalent, expansion couplers are needed in long runs (at every 8m). Where the conduit
is to be used in damp situations, a special temperatures etc.
The Report on Specialized Industrial Training 5
FENTONS LTD.
Flexible conduit:
Flexible metallic or PVC conduit is often used to make a suitable connection between
rigid conduit systems and, for example, a motor which may be required to be moved for
belt tensioning, a separate circuit protective conductor is needed, run either inside the
conduit or externally.
2. Trunking
Trunking is a fabricated casing for conductors and cables, generally rectangular in shape
with a removable lid which allows the conductors to be laid in rather than be drawn in as
is the case with conduit it is used where a large number of conductors are to be carried, or
follow the same route. Both steel and PVC Trunking are available, with a wide range of
such accessories as bends, T’s ,flanged adaptors, risers and reducers.
The variety of trunking includes plain section, compart mented , skirting, bench, floor
trunking, and busbar trunking. Trunking is not necessarily a complete wiring system in it
self and is thus associated with conduit and MI cables to allow connection to wiring
accessories and their mounting boxes.
Finishes on steel trunking include gray enamel, galvanized and silver enamel on zinc-
coated mild steel.
Skirting trunking: Is used in offices where the services (socket outlets, switches, etc.)
can be sited on the perimeters of rooms.
Bench trunking: Is commonly found in school and laboratories where access to a large
number of socket outlets is required. As the name implies, the trunking units are mounted
on benches.
Floor trunking: Is an alternative to skirting trunking. There are three types: under floor
(where the trunking is set in a concrete floor with flush with the floor surface), and flush
duct trunking (where the lid is mounted flush with the screen) and a finish (such as
parquet wood or tiles) are placed directly on to it.
Cable tray is used to carry sub main cables and multi runs of MI cables. It is widely used
in industrial installations. Where pipe work and other structural features may be done
normal cable runs the tray is basically a flat metal sheet with perforations and either a
simple turned flange of finishes are provided to meet installation conditions: galvanized,
primed with red oxide or yellow chromate, plastic-coated and coated with epoxy resins
(resistant to acids and virtually non-flammable). For large amount of heavy cables runs,
cable ladders are used.
4. Cable Trench
Cable trenches are building by Concrete. All cables run in trenches must be sheathed or
armoured. Main hall is building in to the trenches for entrance the cable trench inside.
5. Cable Duct
Ducts are simply passages provided by builders in the structure of a building to allow
cables to run from points of supply to their terminations. Ducts can be rectangular
channels covered by steel lids or bricks. All cables run in ducts must be sheathed or
armored and cable ladders are used to carry cables through the ducts. Cable ladders are
fixed to the duct wall using thread bars or anchor bolts.
Joint methods
The methods used to join conductors may be reduced to two definite groups. The first
group involves the use of heat to fuse together the surfaces of the joint (e.g. clamping,
bolting, riveting) the following are brief description of the types of jointing method in
each group.
1. Soldering
2. Welding
3. Clamping
4. Bolting
5. Riveting
6. Crimping
7. Mechanical connectors
This joint involves the use of molten metal introduced to the two surfaces to be jointed so
that they are linked by a thin film of the metal which has penetrated in to the surfaces.
The metal used for joining copper surfaces is solder, which is an alloy of tin and led. It
melts at a comparatively low temperature. The grade of solder most suitable for electrical
joints istinman’s solder (60% tin, 40% led; melting point is about 200 C). The
disadvantage of soldering is that it makes the joint a non-separable contact. Soldered
joints in bus bars must be reinforced by bolts or clamps.
2. Welding
This process is some times used for large-section conductors such as bus bars. Welding is
the joining of two metal surfaces by melting adjacent portions so that there is a definite
fusion between them to an appreciable depth. The heat is supplied by a gas torch or an
electric arc. Again the welding joint is a non-separable contact.
3. Clamping
A clamped joint is easy to make, no particular preparation being required, through the
extra mass of metal round. The joints of termination make a larger bulk. How ever the
joint or termination is cooler in operation. This method provides a separable contact.
Surfaces must be clean and in definite mechanical coated. Precautions must be taken to
ensure that the bolt and nuts of the clamp are locked tight.
4. Bolting
This is method involves drilling holes in the material and has the obvious disadvantage of
reducing effectiveness of the material. Contact pressure also tends to be less uniformly
distributed in a bolted joint that in one held together by clamps. Spring washers are
needed to allow for expansion and contraction as the material temperature varies with the
current carried.
5. Riveting
If well made, riveted joints make a good connection. There is the disadvantage, however
that they cannot easily be undone or tightened in-service.
This is a mechanical method. For conductor joints a closely fitting sleeve is placed over
the conductor and crimped by a hydraulically or pneumatically operated crimping tool.
This method is very commonly used now days and provides connection which is
mechanically strong and virtually negligible in its electrical resistance.
7. Mechanical connectors
These consist of one-way or multi-way brass terminals contained in blocks made from
porcelain, bake-lite, nylon, polythene or PVC. Small screws are use to make the
connection. The operating temperature of the block material is important. Porcelain can
be used for high operating conditions, while PVC and polythene tend to become distorted
as the melting – point of 160 C approached in fact, polythene is not recommended for use
as connector- blocks in fixed wiring systems, accessories, luminaries and appliances.
Nylon has a good resistance to deformation at high temperatures.
Termination method
These generally accept a solid- core small diameter connection to accessories and current
using apparatus.
These generally accept a solid- core small diameter conductor. The connection is
soldered.
The end of the conductor is formed in to an eye using round - hosed pliers. The eye
should be slightly larger than the shank of the screw, but smaller than the out side
diameter of the screw head, nut or washers. The eye should be so placed that the rotation
of the screw head or nut tends to close the joint in the eye. If the eye is put the opposite
way round, the rotation of the screw head or nut will tend to untwist the eye to make a
bud, inefficient contact. Sometimes saddle washers are used to titian the shape of the eye.
3. Lug terminals
Connection between conductor end and the terminal’s socket is made by the crimping.
Crimping – select the correct terminal end. Strip the insulation from the cable end, insert
the wire in to the open socket end of terminal and crimp using a crimping tool.
4. Line taps
These are used for making non- tensioned service or T connection to over head lines.
They are available in a range of sizes suitable for copper conductors. A simple shroud is
provided to insulate the line tap when used on covered service cable. There are the
designs for use with aluminum conductors and for conductors. In these instances, the
shroud is filled with weather proof sealing compound, giving protection against climatic
attraction corrosion.
To calculate the voltage drop in volts the tabulated value of voltage drop (mv/A/m) has to
be multiplied by the length of run in meters(L), the design current of the circuit (1b), and
divided by 1000 (to current to volts)
The requirement of BS7671 are deemed to be satisfied for a 230V supply, if the voltage
drop between the origin of the installation and a socket outlet or fixed current using
equipment does not exceed 9.2V at full load
Cable Rating
1 44 44 38
1.5 29 29 25
2.5 18 18 15
4 11 11 9.5
6 7.3 7.3 6.4
10 4.4 4.4 3.8
16 2.8 2.8 2.4
25 1.75 1.75 1.50
35 1.25 1.25 1.10
50 0.93 0.93 0.80
70 0.63 0.63 0.55
95 0.46 0.47 0.41
Switch
Part of an electronic or electric circuit that controls the flow of electric current. In its
simplest form, a switch consists of two metal contacts that are held together so that
current flows through them from, for example, a battery to a bulb (for example, in a
torch). In this case, as current flows through the bulb and back to the battery, the bulb is
illuminated. When the metal contacts are not held together there is a gap in the circuit and
so current cannot flow.
The mechanical contacts may be held together in different ways, depending on the
purpose of the switch and the way in which it has been designed. For example, when a
The consumer unit (or distribution board) contains devices for the protection of the final
circuit against:
1. Over load
2. Short-circuit
3. Earth fault
Over load and short- circuit are carried out usually by one device, a fuse or circuit
breaker.
Earth fault may be carried out by the fuse or circuit breaker provided for over load &
short- circuit or by and RCD.
Direct Contact:
Electrical insulation and enclosures and barriers give protection against direct contact.
Non-sheathed insulated conductors must be protected by conduit or trunking or be with in
a suitable enclosure. A 30A RCD may be provided to give supplementary protection
against direct contact, but must not to be relied upon for primary protection.
Indirect contact:
Protection against indirect contact is given by limiting to safe values the magnitude and
duration of voltages that may appear under earth fault conditions between simultaneously
accessible exposed- conductive parts or earth. This may be effected by the:
(a) Are supplied from isolated safety sources such as a safety isolating transformer
to BS 3535
(b) Have no live part connected to earth or the protective conductor of another
system.
(c) Are enclosed in an insulating sheath additional to their basic insulation
(d) Have no exposed-conductive parts or protective conductors of other systems
or extraneous-conductive parts.
PELV systems must meet all the requirements for SELV except that the circuits are not
electrically separated from earth.
For SELV and PELV systems protection against direct contact need not be provided if
voltages do not exceed the following.
Dry areas Swimming 25V a.c or 60V d.c 25V a.c or 60V d.c
pools, Bath rooms, saunas 12V a.c or 30V d.c Not allowed
Application of RCDs
Following protection devices using for power distribution panel & consumer units.
1. Normal tripping
2. shunt tripping
The over load tripping depends on the operation of the thermally operated bi-metal strip,
which consists of two different metals rolled on each other. Due to the different
coefficient of thermal expansion, the two metals expand differently when heated (for
instance by an electric current flowing through), which results in a deflection. The
deflection depends directly on the duration. After a predetermined deflection (or
temperature), the bi-metal will activate the tripping mechanism. Normally the bi-metal is
selected to carry the line current and can be directly heated, for lower current ratings it
might be necessary to use indirect heating via a heater tape which is wound around the bi-
metal.
Some older designs of miniature circuit breakers still in use, extend the function of the bi-
metal tripping system to trip on short- circuit conditions as well as to support the bi-metal
for faster bending on high short- circuit current, an iron core is attached to the bi-metal.
Such systems normally cause the bi-metal to be over heated and result in an over
stretching. After the fault has been cleared, the bi-metal does not return to its next fault
situation the miniature circuit breaker will trip much earlier than it was design for,
however the distortion is irreversible such circuit breakers may comply with standards
like NEMA (American standards) or JIS (Japanese standards), but would not pass the
more stringent requirements of standards like IEC (International standards), SS
(Singapore standards) and EN (European standards)
For server over load or short-circuit conditions, miniature circuit breakers should provide
an instantaneous tripping facility.
The electromagnetic tripping system consists essentially of a solenoid coil through which
the load current flows. The coil has a fixed iron core plus a movable armature. If the
current exceeds a predermined value the coil produces sufficient electromagnetic force to
attract the movable armature against the for of the re-set spring. The switching
mechanism is activated by the tripping liver to open the contacts
This classical method is used in the so called zero point extinguishing MCBs (ZPE).
ZPE MCBs operate with an arc voltage which is much lower than the supply voltage.
This allows the short-circuit current to flow practically uninfluenced or impeded for the
first half wave of the a.c. cycle only just near the zero or cross over point of the a.c. sine
wave, the arc can be extinguished, in some cases it may even re-ignite. Electromagnetic
short-circuit trip shown in
RCCB’s have a two pole and 4 poles. Phase and Neutral going through the 2 pole RCCB.
3 phase and neutral go through the 4 pole RCCB.
Residual current devices provide the functions of isolation switching and earth leakage
protection of electrical circuits (no over load and short-circuit protection).
They have a residual current operated electromechanical release which operates without
any auxiliary source of supply to open a circuit automatically in the case of an earth
leakage fault between phase & earth greater than or equal to a threshold of 30,100 or
300mA.
Earth fault relay suitable for protection of all electrical circuit. This relay is extremely
accurate easy to set, compact and easy to install with rear terminal connection.
The earth leakage relay has the very best diagnostic (and auto diagnostic) never seen on
the previous generation of earth leakage relays. Particularly, it has three types of tests,
two of which are made automatically by the relay it self.
Every two second the microprocessor checks all the electronic circuit between the input
and output terminals. The test doesn’t generate any interference with the normal relay
operation in case of fault the out put relay trips and the fault LED light-on steady.
PFR’s have a three-phase voltage control for three phase networks without neutral. The
voltage to be controlled is applied to terminals L1, L2, L3, N and feeds the unit too
(green “ON” LED). “Max voltage” and “Min voltage” potential meters establish a control
window around the line rated voltage which value is selected by the rotary switch “Ue”
on the front.
The unit trips when only one of the line voltages (L1-L2, L2-L3, L1-L3) exceeds the set
limits.
i. Normal condition
The Report on Specialized Industrial Training 20
FENTONS LTD.
If the voltage is with in the control window, both out put relays are energized, the “Min”
and “Max” LED’s are off.
II. Maximum voltage trip
When the voltage exceeds the “Max voltage” limit of the control window and the over
voltage remains for more that time “Delay max” the “Max” out put relay de-energizes
and the “Max” out put relay energizes and the “Max” LED switch off.
When the voltage exceeds the “Min voltage” limit of the control window and the under
voltage remains for more than time “Delay min”, the “Min” out put relay de-energizes
and the “Min” LED switches on. When the voltage returns to a value more than “Min
voltage” +3% (hysterics). The reset is automatic, the “Min” out put relay energizes and
the “Min” LED switches off.
3.4 EARTHING
Every exposed-conductive-part (a part which may become live under earth fault
conditions) shall be connected by a protective conductor to the main earthing terminal
1. TT system
2. IT system
3. TN-C system
4. TN-S system
5. TN-CS system
The correct selection of protective devices and their current/voltage ratings depend on,
among other factors, the earthing arrangement of the electrical installation system. The
distribution systems ate classified according to IEC 60364-3 by the method of system
earthing. The basic definition of the system is denoted by using two letters. An addition
of one or two letters may be necessary to indicate neutral and protective conductor
arrangements as well.
The first letter indicates the relationship of the power source and earthing.
The second letter indicates the relationship of the exposed conductive parts of the
installation and the earthing.
In the TN- system an additional code using one or two letters defines the arrangement of
the neutral and protective conductors.
In the TT system, all exposed conductive parts of an installation are connected to an earth
electrode which is electrically independent of the earth all the supply source.
Effective earth connection is some times difficult as the fault loop impedance may not be
as low as required. The fault current limitation in the IT- system is obtained by the
absence of an earth connection from the supply (is obtained neutral) or by in serration of
an impedance between the neutral path and earth.
In the TN- system the fault loop is entirely constituted of conducting elements, so that
high earthing resistances can be avoided. The star point at the power source is directly
earthed, the exposed conductive parts of the installation may be connected to a separate
protective conductor and neutral (as in the TN-C or the TN-CS- system)
The following types of earth electrode are recognized for the purposes of the regulations.
Generally we were used earth pipe for my work station. But earth plate is used for the
lighting arrestor.
At first we should dig a hole. Then insert the galvanized pipe in to the hole. And attack to
the top of the pipe, till come to the ground level. Then insert the sold or chemical in to the
earth pipe, for good resistance to the pipe & ground.
Buildings are protected from lightning by metallic lightning rods extending to the ground
from a point above the highest part of the roof. These rods form a low-resistance path for
the lightning discharge and prevent it from traveling through the structure itself. Power
lines and radio sets with external aerials are protected against lightning by lightning
arresters that consist of a small gas-filled gap between the line and ground wire. This gap
offers a high resistance to ordinary voltages, but a lightning discharge, which has a
potential of tens of millions of volts, causes the gas in the gap to ionize, providing a low-
resistance path to earth for this discharge.
There are several types of lighting arresters in general use. They differ only in
constructional details but operate on the same principle which providing low resistance
path for the surges to the ground. Following are kinds of lighting arresters.
First one fixed lighting arrester then fixed the copper tape to the arrester and termination
to earth plate to the other side of the copper tape.
We must always attach phase(live) wires to the right side of the switch
Phase wire of the socket outlet must be attached to the right.
Fuse is not attach to a neutral wire
The equipments protected by circuit must be clearly noted in the distribution
board
All the socket out let of a room must be connected to a single phase
If there are more than one sub circuits, they must be connected to a distribution
board.
Each equipment of a low voltage must be noted in the distribution board.
The neutral wire of distribution board must be connected neatly according to
their circuit.
On, off switch must be placed closed to its motor.
When wires are sent through mettle cover rubber-bush must attach to the end
of them.
When doing a wires joint with aluminium conductors and copper conductors
they must not be mixed.
If must not good enough to keep a P.V.C wires in an heat of more than 60C.
Equipments with oil in a building must be kept a part from other to avoid
accidents.
More than flexible wire must not be attached to the sealing rose.
Socket must not be fixing in the bath rooms.
All the earth joint must be welded together to end earth wire.
Insulation and resistance must be move than mega ohm.
A socket must be fixed in a height of 150mm from the floor.
The voltage drop of a sub circuit must not be more than 2.5%
The distance between the main switch and its permanents cookers must be less
than 2mm
The power indication lamp should light up. Read the indication directly from the
mega ohm scale on the 500V range and 100V range. Multiply the reading by 0.5 for
250V and 50V and by 2 for 1000V.
Press button first and then button. When the meter pointer deflects up full
scale, press button and take the reading. When an earth resistance value to be
measured is bellow 10Ω, press button and take the reading.
1. Site cleaning
2. Protective wear
3. Safety access
4. Scaffolding / platform
5. Prevention of accident due to falls
6. Prevention of due to electrical failure
7. Prevention of accident due to misuse of machineries
8. Prevention of fire
9. Safety sign
10. First aid
11. Activities for safety
1. Site cleaning
2. Protective wear
3. Safety access
4. Scaffolding / Platform
8. Prevention of fire.
9. Safety signs
Following signs shall be provided at appropriate places according to site situation
/ progress
Safety first
Wear helmets
Watch your head
Dust bin
Max. load
Other sings as required
6.0 Specification
Specification generally consisted of two sections, one being the requirements for
Stranded of workmanship and the other being a specific requirement for the electrical
wiring of the installation. Particular requirements were detailed in individual clauses.
The Electrical Consultant had the responsibilities of ensuring that the Specification
correctly identified and details the work that the electrical contractor was to undertaken;
there be clauses requiring him to accept responsibility for the satisfactory design of the
installation, as well as clauses requiring him to point out any alleged deficiencies or error
in the design at the tender stage of the project. In addition to this, was the general
responsibility upon the electrical installation were safe and designed to a satisfactory
standard.
It some times happens that the client changed the requirement about some aspect of the
work being undertaken or that an incorrect detail was discovered on a drawing or in the
specification. Such variance (as they were called) were generally advised by the
consulting engineer to the architect who then issued an architect’s instruction to the main
contractor who in turn informs the electrical contractor to carry out the extra work in
accordance with terms and condition.
The permanent site staff consists of project Manager, Engineers, Assistant Engineers
Quantity Surveyors, Administrative Officer, & Storekeepers. Duties and responsibilities
of these officers at the work site distribute as follows.
Keeping overall watch on working of all the supervisors & workers to obtain
maximum out put from them.
To control wastage & details provided by the consultants & explain to supervisors.
To prepare reinforcement schedules of the project.
To work out the requirement of different material necessary for work involved.
Security services should be careful checked on daily basis & report promptly all
shortcomings to project manager.
Maintenance & movements of machineries, vehicles & arrangement it requirement
in time.
All transfers of employers from one work site should be organized an in order to
prepare the transfer documents. ( gate passes )
All the copies of attendance sheet & any other document pertaining to site
employee’s from; be care fully packed and dispatched to teed office at the end
every month.
The passes must be issued all sub contractors employees & re-new or alter each 6
months.
Every personal accident looks after the purpose of employees & he should take
action to over come problems as soon as possible.
To get good store handling without wasting the materials or working hours of labors due
to the finishing of materials, the site manager should keep close associated with store
keepers. Main stores managed site stores.
Material Requisition
This is used to issue the material to the workers from the site office. Officers have to fill
this form & sign it & worker give it to stores and store keeper was issued request quantity
for the worker.
When the requested materials are supplied to the site, the store keeper prepares the
“Goods Received Note” by checking quantity of the goods received thoroughly. The
project manager must give the final approval.
Purchase Requisition
If any material is not available or not on sufficient quantities in the site the store keeper
should inform the project manager about the stock levels when a requirement arises a
“Purchase Requisition” is prepared stating the required materials, quantities etc. and
forwarded to the site manager for approval.
Store Requisition
If a material purchasing through the head office stores requisition is prepared. Then
certified it by site manager and forwarded to the head office.
Transfer voucher
To transfer any equipment, material from one site to another site or head office stores to
the site transfer voucher is issued. This is consisting of four copies.
If some thing is taken out from the site the gate pass is issued. Especially for the sub
contractors
Consultant has to design and prepare the details of the project to the satisfaction of the
client has to administer the work till its completion.
In this task consultant has to give details and certification where ever necessary. If all of
his responsibilities be has,
Introduction
It is a highly robust and reliable control system, with a low cost per node.
A wide range of tools is available, allowing third party companies to interface
with both PC based and embedded systems.
A single C-Bus cable connection can control many devices.
C-Bus offers the ultimate flexibility in switching and control. Functions can be
changed, added, removed, moved, reprogrammed, at any position on the network,
at any time — without any cumbersome hard-wiring.
C-Bus is simple to install and commission.
C-Bus can control any type of load, digital and analogue.
Electrical wiring practices have not changed much since the introduction of insulated
installation time, documentation control and overall system cost. Maintenance and
system flexibility can be problematic.
The C-Bus network overcomes these problems. It uses a twisted pair of wires such as
Unshielded Twisted Pair (UTP) Category 5 (Cat-5) Local Area Network (LAN) cable, to
communicate between a building’s light switches and load controlling devices. This same
cable pair also provides the DC supply voltage to the C-Bus devices.
This greatly reduces the number of heavy wires in an installation, while enabling easy
central monitoring and system control.
C-Bus can be expanded to control and monitor a building’s electrical appliances from a
personal computer. Security, air conditioning and other systems can be programmed to
turn on or off at specific times or events. Lighting and temperature can be varied
according to ambient conditions. Inputs, switches and loads can be reconfigured without
reconnecting a single wire.
C-Bus Communications
When a button is pressed on an input unit, a measurement is made of its press duration.
This measurement influences the message that the unit issues in response to the button
press (depending on its programming). This is illustrated in Figure 1.
The relevant C-Bus message is then transmitted over the C-Bus network as indicated by
the dashed line in Figure 2.
The C-Bus message is broadcast over the bus for all C-Bus units to read, as illustrated in
Figure 3. It contains information about the Group Address and the operation to be
performed, such as switch on or off. Only the C-Bus units with the same address will
respond.
C – Bus Wiring
Figure 6 shows how the same two-way control is wired using C-Bus (pink wiring). The
control circuitry is simpler than the conventional method. If a four or eight button switch
is used instead of the two button, the wiring remains the same. Just two conductors are
required to link the C-Bus control.
DESIGN PHILOSOPHY
There are several methods of designing and installing C-Bus. An overview of the
installation approach is shown below.
Installation
Once the design phase has been completed, installation may
begin. Several
simple steps are typically followed:
• Implementation of Programming Requirements of the Design
on a Personal Computer (Build C-Bus Database).
• Unit Initialisation and Programming (One at a Time).
• Cabling and Electrical Installation of the Hardware.
• Finalization and Further Programming of Units on the
Network as required.
Programming Principles
The C-Bus is designed to operate at a safe, extra-low voltage of 36V DC, with optical
and/or galvanic isolation from mains voltages. The installer must ensure that acceptable
wiring practices for extra low voltage cabling are adopted with C-Bus.
In particular, the routing of the C-Bus cable near mains wiring, where physical separation
criteria between cables need to be satisfied. In this respect C-Bus is treated as a data
cable, and the same practices should be employed. The C-Bus, operating at the safe extra
low voltage of 36V DC, allows electrical work to be performed on the C-Bus side while
the system is powered on.
The C-Bus side with short circuit protection ensures that the equipment will not be
damaged if the supply is shorted for an indefinite period. The installer needs to be aware
that shorting the C-Bus Network will disable operation of the C-Bus Network as long as
the short circuit persists. A benefit of the C-Bus method of wiring is that wiring of the C-
Bus Units may be accomplished in a number of ways. The C-Bus Units are all wired in
parallel on the Bus, and the Units may be daisy chained, or be part of a branch/star
structure or a combination of these. Closed loop ring structures are not recommended.
Installation of every Unit on the C-Bus Network requires connection to the Unshielded
Twisted Pair C-Bus Network Cable. This connection is polarity sensitive, and is clearly
marked on the terminal block of the Unit. Clipsal has Category 5 cable for use with C-
Bus (Catalogue Number 5005C305B). The cable features eight single core conductors
(four Unshielded Twisted Pairs (UTP), encased in a pink outer sheathing. Pink has been
chosen in order to distinguish between the C-Bus cabling in an installation. A second
feature is that the cable may for short runs be routed into a switchboard close to mains
cable. The outer sheath insulation resistance is suitable for this application. The following
illustration shows the recommended technique for cable termination giving optimum
performance, and immunity from electromagnetic interference (EMI).