Sunteți pe pagina 1din 4

Software Version 2.16.2.

Project Name
CTCC Office

Product Name Model Name Q'ty


Outdoor Unit(s) MMY-AP3617T8P 1
Outdoor Unit(s) MMY-MAP2407T8P 1
Outdoor Joint(s) RBM-BT24E 1
Indoor Unit(s) MMU-AP0364HP1-E 2
Indoor Unit(s) MMU-AP0484HP1-E 3
Indoor Unit(s) MMU-AP0364HP-E 2
Indoor Unit(s) MMU-AP0154HP1-E 11
Indoor Unit(s) MMU-AP0244HP1-E 2
Indoor Unit(s) MMU-AP0304HP1-E 5
Indoor Unit(s) MMU-AP0077MH-E 4
Indoor Unit(s) MMU-AP0127MH-E 1
Accessories RBC-U31PG(W)-E 25
Accessories RBC-UM21PG(W)-E 5
Y-Joint(s) RBM-BY55E 5
Y-Joint(s) RBM-BY305E 5
Y-Joint(s) RBM-BY205E 6
Y-Joint(s) RBM-BY105E 12

Note: Equivalent length is calculated by coefficient 1.500

- The user is responsible for ensuring that all data entered is correct.
- Equipment selections have been based on the Design Guidelines stated within the Toshiba SMMS-e/SHRM-e/SMMS-i/SHRM-i/MiNi-SMMS/SMMS-7/MiNi-SMMS-e/SMMS Installation Manual.
- It is the responsibility of the consultant or contractor, to verify and confirm that the equipment selection and system design is correct before installation.
- Please note that in the event of future system expansion being allowed for in the system design or a change in cooling/heating requirements, a re-evaluation of the air conditioning system must be made prior to final installation.
Software Version 2.16.2.0

Project Name
CTCC Office

Cooling Outdoor DB (C) 35


Design conditions
Heating Outdoor WB (C) 6

Name Quantity Additional Actual pipe length (m)


Diversity
No Capacity Refrigerant
System name Outdoor model Outdoor Indoor (%) Φ6.4 Φ9.5 Φ12.7 Φ15.9 Φ19.1 Φ22.2 Φ25.4 Φ28.6 Φ34.9 Φ41.3
(kg)
1 MMY-AP3617T8P 36 2 16 124% 18.535 14 : 0/14 24 : 4/20 19 : 10/9 29 : 20/9 24 : 0/24 15 : 9/6 0 : 0/0 29 : 29/0 4 : 4/0 6 : 6/0
2 MMY-MAP2407T8P 24 1 14 128% 20.8 18 : 0/18 32 : 6/26 38 : 14/24 24 : 24/0 38 : 0/38 24 : 24/0 0 : 0/0 0 : 0/0 38 : 38/0 0 : 0/0

Note: Equivalent length is calculated by coefficient 1.500

- The user is responsible for ensuring that all data entered is correct.
- Equipment selections have been based on the Design Guidelines stated within the Toshiba SMMS-e/SHRM-e/SMMS-i/SHRM-i/MiNi-SMMS/SMMS-7/MiNi-SMMS-e/SMMS Installation Manual.
- It is the responsibility of the consultant or contractor, to verify and confirm that the equipment selection and system design is correct before installation.
- Please note that in the event of future system expansion being allowed for in the system design or a change in cooling/heating requirements, a re-evaluation of the air conditioning system must be made prior to final installation.
Software Version 2.16.2.0

Project Name
CTCC Office

Name Design Condition (C) Capacity (kW) Electrical Pipe Length Design ESP Sound Heater
From (m) Height Applicable
No Model Cooling Total Capacity Sensible Capacity Fan Speed PMV Kit air flow setting Pressure
Type Tag name Room Floor System name MCA MOCP Diff (m) Y/N kW Notes
DB WB Rated Corrected Required Rated Corrected Required Outdoor Branch (cfm) (In WG) (dBA)
1 4-way Cassette IDU 1 Concentration Zone MMU-AP0484HP1-E 27 19 14 13.93 (10.76) 8.76 9.8 9.75 7.8 1.44 15 9 3 -0.5 High N
2 4-way Cassette IDU 2 Concentration Zone MMU-AP0364HP-E 27 19 11.2 11.08 (8.60) 6.6 7.7 7.62 5.8 1.44 15 12 3 -0.5 High N
3 4-way Cassette IDU 3 Concentration Zone MMU-AP0364HP-E 27 19 11.2 11.02 (8.60) 6.6 7.7 7.58 5.8 1.44 15 15 3 -0.5 High N
4 4-way Cassette IDU 7 Chill Out Zone MMU-AP0484HP1-E 27 19 14 13.70 (10.76) 8.76 9.8 9.59 7.8 1.44 15 18 3 -0.5 High N
5 4-way Cassette IDU 8 Chill Out Zone MMU-AP0484HP1-E 27 19 14 13.62 (10.76) 8.76 9.8 9.53 7.8 1.44 15 21 3 -0.5 High N
6 4-way Cassette IDU 16 Communication Zone MMU-AP0304HP1-E 27 19 9 8.32 (6.91) 4.91 6.2 5.73 3.76 1.09 15 51 3 -0.5 High N
7 4-way Cassette IDU 17 Communication Zone MMU-AP0304HP1-E 27 19 9 8.28 (6.91) 6.36 6.2 5.7 3.76 1.09 15 54 3 -0.5 High N
8 4-way Cassette IDU 18 Collaboration MMU-AP0154HP1-E 27 19 4.5 4.12 (3.46) 2.14 3.2 2.93 1.5 1 15 57 3 -0.5 High N
9 4-way Cassette IDU 19 4 Pax Meeting Room MMU-AP0154HP1-E 27 19 4.5 4.10 (3.46) 2.14 3.2 2.92 1.5 1 15 60 3 -0.5 High N
10 4-way Cassette IDU 20 Open Discussion MMU-AP0154HP1-E 27 19 4.5 4.08 (3.46) 2.14 3.2 2.9 1.5 1 15 63 3 -0.5 High N
11 4-way Cassette IDU 25 4 Pax Meeting Room MMU-AP0154HP1-E 27 19 4.5 4.06 (3.46) 1.46 3.2 2.89 1.5 1 15 66 3 -0.5 High N
12 Compact 4-way IDU 26 Ph. Booth 4 MMU-AP0077MH-E 27 19 2.2 1.98 (1.69) 0.6 1.8 1.62 0.6 0.33 15 69 3 -0.5 High N
13 Compact 4-way IDU 27 Ph. Booth 3 MMU-AP0077MH-E 27 19 2.2 1.97 (1.69) 0.6 1.8 1.61 0.6 0.33 15 70.5 3 -0.5 High N
14 4-way Cassette IDU 28 Open Discussion MMU-AP0154HP1-E 27 19 4.5 4.01 (3.46) 1.46 3.2 2.85 1.5 1 15 73.5 3 -0.5 High N
15 4-way Cassette IDU 29 Collaboration MMU-AP0244HP1-E 27 19 7.1 6.30 (5.45) 3.75 4.9 4.35 2.35 1.09 15 76.5 3 -0.5 High N
16 4-way Cassette IDU 30 Collaboration MMU-AP0244HP1-E 27 19 7.1 6.30 (5.45) 3.6 4.9 4.35 2.35 1.09 15 76.5 3 -0.5 High N
17 4-way Cassette IDU 4 2 Pax Cockpit MMU-AP0154HP1-E 27 19 4.5 4.26 (3.33) 2.26 3.2 3.03 1.5 1 15 36 3 -0.5 High N
18 4-way Cassette IDU 5 3 Pax Cockpit MMU-AP0154HP1-E 27 19 4.5 4.24 (3.33) 2.26 3.2 3.02 1.5 1 15 39 3 -0.5 High N
19 4-way Cassette IDU 6 2 Pax Cockpit MMU-AP0154HP1-E 27 19 4.5 4.24 (3.33) 2.26 3.2 3.02 1.5 1 15 39 3 -0.5 High N
20 4-way Cassette IDU 9 6 Pax Meeting Room MMU-AP0154HP1-E 27 19 4.5 4.12 (3.33) 2.26 3.2 2.93 1.5 1 15 57 3 -0.5 High N
21 4-way Cassette IDU 23 Meeting Room 8 Pax MMU-AP0154HP1-E 27 19 4.5 3.95 (3.33) 1.97 3.2 2.81 0.82 1 15 84 3 -0.5 High N
22 4-way Cassette IDU 24 Collaboration MMU-AP0364HP1-E 27 19 11.2 9.77 (8.30) 7.88 7.7 6.72 4.79 1.44 15 88.5 7.5 -0.5 High N
23 4-way Cassette IDU 21 Communication Zone MMU-AP0304HP1-E 27 19 9 7.90 (6.67) 5.94 6.2 5.44 3.47 1.09 15 84 3 -0.5 High N
24 4-way Cassette IDU 22 Communication Zone MMU-AP0304HP1-E 27 19 9 7.90 (6.67) 5.94 6.2 5.44 3.47 1.09 15 84 3 -0.5 High N
25 4-way Cassette IDU 10 6 Pax Meeting Room MMU-AP0154HP1-E 27 19 4.5 4.08 (3.33) 2.26 3.2 2.9 1.5 1 15 63 3 -0.5 High N
26 Compact 4-way IDU 12 Ph. Booth 2 MMU-AP0077MH-E 27 19 2.2 1.98 (1.63) 0.6 1.8 1.62 0.6 0.33 15 69 3 -0.5 High N
27 Compact 4-way IDU 13 Ph. Booth 1 MMU-AP0077MH-E 27 19 2.2 1.98 (1.63) 0.6 1.8 1.62 0.6 0.33 15 69 3 -0.5 High N
28 Compact 4-way IDU 11 Vendor Meeting Rm MMU-AP0127MH-E 27 19 3.6 3.23 (2.67) 1.23 2.7 2.42 1.23 0.36 15 69 3 -0.5 High N
29 4-way Cassette IDU 14 Communication Zone MMU-AP0304HP1-E 27 19 9 8.05 (6.67) 5.85 6.2 5.55 3.57 1.09 15 72 3 -0.5 High N
30 4-way Cassette IDU 15 Communication Zone MMU-AP0364HP1-E 27 19 11.2 9.97 (8.30) 6.44 7.7 6.85 4.88 1.44 15 75 6 -0.5 High N

Note: Equivalent length is calculated by coefficient 1.500

- The user is responsible for ensuring that all data entered is correct.
- Equipment selections have been based on the Design Guidelines stated within the Toshiba SMMS-e/SHRM-e/SMMS-i/SHRM-i/MiNi-SMMS/SMMS-7/MiNi-SMMS-e/SMMS Installation Manual.
- It is the responsibility of the consultant or contractor, to verify and confirm that the equipment selection and system design is correct before installation.
- Please note that in the event of future system expansion being allowed for in the system design or a change in cooling/heating requirements, a re-evaluation of the air conditioning system must be made prior to final installation.
Software Version 2.16.2.0

Project Name
CTCC Office

Name Outdoor unit capacity Required Capacity Sound Connect Location Electrical Outdoor to Joint (m) Between Outdoor (m) Main (m)
Max Applicable
No Cooling (kW) Heating (kW) Cooling Heating Pressure of outdoor Main Length (m)
Model Ref. Cycle Name Tag name Indoor unit Diversity Selection V - Φ - Hz MCA MOCP La Lb LA LB LC LD A to B A to C A to D Notes
Nominal Corrected Nominal Corrected (kW) (kW) (dBA) unit
1 MMY-AP3617T8P 100.8 94.88 -- -- 116.87 (94.88) -- 16 124% 180% Above 380/415 - 3 - 50 70.00(35.00 + 35.00) 80.00(40.00 + 40.00) 2 0 0 1 2 0 0 0 0 0
2 MMY-MAP2407T8P 67 62.54 -- -- 75.67 (62.52) -- 14 128% 200% Above 380/415 - 3 - 50 49 63 18 0 0 0 0 0 0 0 0 0

Note: Equivalent length is calculated by coefficient 1.500

- The user is responsible for ensuring that all data entered is correct.
- Equipment selections have been based on the Design Guidelines stated within the Toshiba SMMS-e/SHRM-e/SMMS-i/SHRM-i/MiNi-SMMS/SMMS-7/MiNi-SMMS-e/SMMS Installation Manual.
- It is the responsibility of the consultant or contractor, to verify and confirm that the equipment selection and system design is correct before installation.
- Please note that in the event of future system expansion being allowed for in the system design or a change in cooling/heating requirements, a re-evaluation of the air conditioning system must be made prior to final installation.