Jockey Pump Controllers • FTA500

Options—The following are available as options to


the controllers:
Circuit Breaker Option
-A Standard Short Circuit Current Rating
200-240V - 65,000 Amps, RMS Sym.
380-480V - 25,000 Amps, RMS Sym.
550-600V - 14,000 Amps, RMS Sym.
NOTE—Consult factory for high interrupting capacity
circuit breakers.

Omit Minimum Run Timer


-B Controller without minimum run timer

Floor Mounting Legs


FTA
-N2 Specify when ordering

Modifications—The following are available as


modifications to the controllers:

Special Enclosures
®
Description—Firetrol FTA500 Jockey Pump Con- -T NEMA Type 3R (IEC IP14)
trollers are intended for use with fire pump systems. -E NEMA Type 4 (painted steel) (IEC IP56)
They are used for pressure maintenance in fire pump -F NEMA Type 4X (#304 stainless steel) (IEC
installations to prevent unnecessary cycling of the IP56)
main fire pump. -G NEMA Type 12 (IEC IP52)
*Note: Only the standard NEMA type 2 enclosures
Approvals—Firetrol jockey pump controllers are are supplied with a red finish - all other painted fin-
listed by Underwriters' Laboratories, Inc., in accor- ishes are supplied Gray as standard. Consult factory
dance with UL508, Standard for Industrial Controls, for special paint color or finish.
and CSA, Standard for Industrial Control Equipment.
They are built to meet or exceed the requirements of Anti-condensation Space Heaters
the approving authorities as well as NEMA and the -H 120 Volt space heater
latest edition NFPA 70, National Electrical Code. -J 120 Volt space heater with thermostat
-K 120 Volt space heater with humidistat
Standard Features—The following are included as -L 240 Volt space heater
standard with each controller: -M 240 Volt space heater with thermostat
„ NEMA Type 2 drip-proof enclosure -N 240 Volt space heater with humidistat
„ Horsepower rated fusible disconnect switch
with Pressure Switches and Recorders
fuseblock and fuses -B 20-675 psi (1.4-46.5 bars) Pressure
„ Horsepower rated motor contactor and overload Switch for freshwater service
relay (Diaphragm Type, Snap Action Switch)
„ HAND-OFF-AUTO selector switch -C 5-250 psi (.35-17.2 bars) Pressure
Switch for seawater/foam service
„ Minimum run timer
(Diaphragm Type, Snap Action Switch)
„ 120V Secondary - Control circuit transformer -D 20-675 psi (1.4-46-5 bars) Pressure
„ 15-290 psi (1-20 bars) Pressure switch, dia- Switch for seawater/foam service
phragm style, snap action type contact and (Diaphragm Type, Snap Action Switch)
15-120 psi (1-8.3 bars) adjustable differential, -SL 0-300 psi (0-20.7 bars) pressure recorder for
suitable for fresh water applications. fresh water service
-SM 0-500 psi (0-34.5 bars) pressure recorder for
fresh water service
-SN 0-1,000 psi (0-69 bars) pressure recorder for
fresh water service

NOTE: Firetrol Brand Jockey Pump controllers DO NOT


CONTAIN MERCURY filled pressure switches.
-SP 0-300 psi (0-20.7 bars) pressure recorder for
sea water/foam service
-SR 0-500 psi (0-34.5 bars) pressure recorder for
sea water/foam service
-SS 0-1,000 psi (0-69 bars) pressure recorder for
sea water/foam service
Alarms
-AC Extra contacts (1 normally open & 1 normally
closed) for remote indication, pump operat-
ing
-AM Contacts for remote indication, pump fail to
start
-BY Contacts for remote indication, pump over-
load
-BW Contacts for remote indication, pump power
failure
-BX Contacts for remote indication, phase reversal/
phase failure

Miscellaneous
-BJ Power ON pilot light
-BZ Elapsed time meter
-S Tropicalization
-R Pump operating pilot light
-GZ 50 Hertz operation

Dimensions and Shipping Weight

(919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27518 USA


PD500-01 (10-22-08) ©ASCO 2008
Specifications
Jockey Pump Controllers • FTA500

The auxiliary jockey pump controller, if required a hidden tool operated defeater mechanism. The
and specified on the plans and specifications, shall disconnect switch shall be capable of being pad-
be factory assembled, wired, and tested and spe- locked in the OFF position with up to three padlocks
cifically designed for this type of service. This for installation and maintenance safety.
controller shall be UL listed, and shall be of the The minimum enclosure rating shall be NEMA
same manufacturer as the main fire pump control- Type 2 (IEC IP11), drip-proof.
ler. All pushbuttons, selector switches, pilot lights
The controller shall incorporate a magnetic shall be NEMA Type 12, oiltight. Pilot lights (when
starter, control circuit transformer, main disconnect specified) shall be transformer type. No pushbuttons
switch, motor fuse block with fuses, HAND-OFF- or pilot lights shall be mounted on the enclosure
AUTOMATIC selector switch and a pressure switch. door.
The pressure switch shall have a range of 15-290 The control circuit transformer shall be of the
psi (1-20 bars) and have an adjustable differential molded winding construction type with built-in
range of 15-120 psi (1-8.3 bars). The pressure molded terminals and shall be fuse protected. The
switch shall be of the diaphragm type utilizing snap- fuse shall be built into the transformer.
action type contacts. The pressure switch shall be The controller manufacturer, prior to shipment,
mounted inside the controller to prevent any unau- shall hook up and test the jockey pump controller as
thorized adjustment and/or accidental damage. The a completed assembly. This test shall include, but
pressure switch shall be directly pipe mounted to a not be restricted to, each function the controller
bulkhead pipe coupling without any other support- may be required to perform including manual start-
ing members. Field connections shall be made stop, automatic start-stop and minimum run timing.
externally at the controller coupling to prevent distor- The manufacturer shall perform a high potential
tion of the pressure switch element and mecha- test of the controller power circuits at not less than
nism. two times the rated voltage plus 1000 Volts.
The controller shall have a running period timer The controller shall be a Firetrol brand.
to prevent too frequent automatic starting of the
jockey pump motor. The timer shall be set to keep
the motor in operation for at least one minute and
interwired with the pressure switch.
The disconnect switch shall be mechanically
interlocked so that the enclosure door cannot be
opened with the handle in the ON position except by