FEATURES

Jammed Valve Protection


CONTROL UPGRADES
Jammed Valve Auto Forward / Reverse Sequence

BULLETIN 450-10000
UEC-3-MPC POSITION CONTROLLER Anti-Torque Switch Hammer Protection THE UNIVERSAL ELECTRONIC CONTROLLER

ISSUE 04/11
WITH 4-20 mA INPUT SIGNAL Opto-isolation of Inputs
Monitor Relay
The UEC-3 includes the basic software and default
Internal 24 Volt D.C. Control Supply Output
settings for accurate positioning and modulating
control. Just add the limitorque A/D converter, 24-125 VA.C. or D.C. Control Supply Inputs
analog board and feedback potentiometer to
convert the UEC-3 into a precise position
Instantaneous Reversal
Local Direction indication on Push button Station
The UEC-3 from Limitorque
controller. The UEC-3-MPC includes automatic
pulse mode to prevent over shoot at the set point.
Lost Phase Protection
Selectable Phase Discriminator / Auto Phase Correction
An Intelligent Control System
System operating parameters may be easily re- Yellow LED Indicates Phases Correctly Connected
configured by the user. These include deadband
Red LED Indicates all Phases Present
and gain adjustments and selectable ‘Lock-in-
Selectable Two, Three or Four Wire Control
Last’ or ‘Fail-to-Close’ position on loss of input
signal. Electrical Interlock / Inhibit Circuits
Selectable Open or Close on Emergency Shut-Down
DDC-100 TWO-WIRE DISTRIBUTED Selectable Stay-put on Emergency Shut-Down
DIGITAL CONTROL SYSTEM Motor Thermostat

The UEC-3’s SBC (sin g le board computer) Selectable Position or Torque Seating
provides unrivalled control compared to Selectable Clockwise / Counter Clockwise Motion
conventional hard-wired actuator installations. By Variable Duty Cycle (2 speed timer) in Both Directions
adding a single plug-in communications card, Simplified Wiring Schematics
actuators can be controlled over a twisted-pair Comprehensive Diagnostic Port
redundant loop network form a control room PT20SD-20mA Current Position Transmitter
interface. In addition to significant savings in
Potentiometer
cabling, hardware, labour, etc., the DDC-100 Two
Upgrade to UEC-3-MPC Position Controller
Wire Control System provides vastly improved
plant visibility, maintenance diagnostic data, and Upgrade to DDC-100 Two Wire Control
control and data gathering of associated ESD on Irrespective of Mode
equipment such as pumps, fans and mixers. STANDARD
OPTIONAL

LIMITORQUE INDIA LTD.


WORKS & MARKETING OFFICE
Plot No. 148, Sector-24, Faridabad - 121 005 QUALITY
ASSURED
Phone : 0129-4047884, Fax : 0129-4042451 COMPANY

E-mail : sales@limitorqueindia.com, limitorque@vsnl.com ISO 9001:2008

Website : www.limitorqueindia.com
BRANCH SALES OFFICES :
CHENNAI 165, Broadway, 3rd Floor, Chennai - 600 108 Phone : 044-25227716 Fax : 044-25224616 E-mail :libacom@vsnl.com
DELHI E-45/2, Phase-II, Okhla Industrial Area, New Delhi - 110 020 Phone : 011-26389567, 26384375 Fax : 011-26386790
MUMBAI 215, Neelam,108, Dr. R.G. Thandani Marg, Off Worli Seaface Road, Mumbai - 400 018 Phone : 022-24935682, 30405682
Fax : 022-24965943, E-mail : bso@limitorqueindia.com, libabom@vsnl.net
KOLKATA Chatterjee International Centre, Suit No. 6, 17th Floor, 33-A, Chowringhee Road, Kolkata - 700 071,
Phone : 033-22260509, 22172253 Fax : 033-22268249
E-mail : kso@limitorqueindia.com, limitorque@sify.com, limitorque2008@gmail.com
PUNE 1/103, Gera Garden, Koregaon park road, Pune-411001 Tele Fax-020-26111472 E-mail : pune@limitorqueindia.com
SURGE SUPPRESSION INSTANTANEOUS REVERSAL
THE UNIVERSAL ELECTRONIC CONTROLLER High level surge suppression, to A time delay of 500 mS, incorporated
SPECIAL FEATURES
prevent damage to the control into the control logic of the reversing 2-SPEED OPERATION IN BOTH
The UEC - 3 is a micro-processor based control system for the complete range of module or loss of functionality, has contactors, allows the actuator to be DIRECTIONS
Limitorque actuators. It offers a unique combination of features to provide been included on all local and remote reversed without first pressing ‘stop’. For the prevention of hydraulic
complete flexibility in the design of yours control system while insuring control input circuits. In compliance This also reduces motor current shocks, (e.g. water hammer), etc, a
with EEC-EMC directive surges and prolongs the life of the two speed timer is available in the
maximum operating integrity. 89/ 336/EEC. contactors. closing and opening directions. It is
JAMMED VALVE PROTECTION OPTO-ISOLATED INPUTS DIP switch selectable and triggered
CLOCKWISE / COUNTER 3 WIRE CONTROL PROTECTION FEATURES by an intermediate limit switch which
CLOCKWISE TO ‘CLOSE’ Simple three wire connection and The UEC-3 logic circuits provide All remote control inputs are ‘opto-
automatic protection against a isolated’ in order to protect the may be set any where in the valve
ROTATION DIP switch settings allow the AUTOPHASE CORRECTION
jammed valve condition in either the actuator logic circuits from high- travel. The ‘ON’ and ‘OFF’ pulse
Normally pre-set in the factory but actuator to be configured for: The UEC-3 monitors the rotation of times are set at default levels of 2.0
may be changed in the field by DIP the incoming 3-phase supply and open or close position, i.e. the torque voltage transients that might occur in
(a) OPEN and CLOSE inching mode, required to operate the valve is the control cabling. seconds ‘ON’ and 10.0 seconds ‘OFF’,
switch selection. automatically corrects the actuator but may be reconfigured to different
with intermediate STOP when signal controls to ensure that the motor greater than the stall torque of the
REMOTE CONTROL FROM is removed. (b) OPEN and CLOSE actuator. This is detected if the intervals.
always runs in the correct direction
24-125V AC OR DC SUPPLY maintained mode, with out position limit switches fail to reset MOTOR OVER LOAD LOCAL DIRECTION INDICATION
throughout the life of the unit.
As standard, the users remote control intermediate STOP but retaining after a preset time (depending on the PROTECTION When the actuator is operating , the
The feature is selectable on/off
supply may range from 24v to 125V instantaneous reversal. actuator speed and the valve travel The motors have two/three local pushbutton station LED’s will
according to customers preference. A
AC or DC turns), when the appropriate t hermost at s emb edded in t he ‘flash’ to indicate the direction of
4 WIRE CONTROL yellow LED illuminates when the
REMOTE CONTROL FROM phases are correctly connected. A red contactor is automatically de- windings for protection against travel; one LED changing to ‘steady’
A four wire connection and
INTERNAL 24V DC SUPPLY LED indicates that all three phases energized. overheating. On detection of a at the end of travel and the other
appropriate DIP switch settings
The use of an internal 24v DC power are present. thermostat trip, the UEC-3 will LED turning off.
provide OPEN and CLOSE AUTO-RETRY ON JAMMED
supply and opto-isolated inputs aut omat ically de-energize t he
maintained control, plus LOST PHASE PROTECTION VALVE DETECTION COMPREHENSIVE DIAGNOSTIC
reduces voltage drop problems, thus contactor except in the case of :-
Intermediate STOP by pushbutton, as If one or more phases are lost the PORT (Optional),
allowing control from remote volt- If a jammed valve is detected, an
well as the instantaneous reversal control circuit will be prevented from (a) An ESD signal is present at the This port has access to the state of a
free contacts over long distances, and automatic reverse/forward cycle is
feature. energizing the contactors. However, terminals, when the actuator will number of circuits on the UEC-3
simplifying the customers control initiated to maximize the benefit of
if an ESD signal is present, the loss of try to complete it’s travel to the board and by plugging In a ‘ hand
MONITOR RELAY the lost motion hammer blow effect in
system. pre-selected position. held’ diagnostic tool or PC the
Monitors various functions of the only one phase will be ignored and the actuator drive and thus gives it
EMERGENCY SHUTDOWN - ESD actuator and provides a remote the actuator will attempt a shutdown another chance to free the valve. If (b) This action has been enabled by operator may quickly diagnose fault
A remote signal applied to the UEC-3 indication or alarm if a fault occurs in the direction selected, providing this retry is unsuccessful, then further prior DIP switch selection on the conditions, presence of inhibit or ESD
will override any existing signal, and the unit is no longer available for the actuator is already in motion electrical operation is inhibited and UEC-3 board. signals, etc.
providing the actuator is in ‘remote’, remote control. This relay is normally prior to the loss of that phase. the operator will need to move the
and send the valve to its pre-selected enregized (1xSPDT contact) but will valve manually with the hand wheel.
ANTI- HAMMER PROTECTION
shutdown position. DIP switch de-energize if: The jammed valve state may be reset
Torque switch hammer may occur
selectable to give ‘CLOSE’, ‘OPEN’, * Local/Off/Remote selector switch is not by sending a signal in the reverse
when a ‘maintained’ control signal is
‘STAYPUT’ or ‘IGNORE’ mode. in ‘remote’ position. direction.
present and the gearing in the
Motor thermostat may be by passed *One or more phases of the 3-phase actuator is non-locking, typically in
during ESD- selectable by DIP switch supply are lost.
high speed applications. The UEC-3
if desired ESD can be made possible
irrespective of selector switch
position i.e. (LOCAL / STOP/
*Internal control supply is lost.
*Motor thermostat has tripped.
prevents this by monitoring both the
‘close’ and ‘open’ torque switches.
A comprehensive,
*Local ‘stop’ button is depressed. Once a torque switch has operated,
REMOTE) as a special feature.
SELECTABLE 2, 3 or 4 WIRE
*Jammed valve detected.
*Contactor fails to energize.
the control circuit prevents re-
energization of the contactors in the
electronic valve control
CONTROL same direction until a signal in the
Simple remote control connections
and DIP switch selections provide a
ELECTRICAL INTERLOCK/
SEQUENCE CONTROL
The connection of remote contacts
reverse direction has been applied. package to protect
variety of control options with a
minimum of wiring schematics.
and setting of a DIP switch provides
the means to either prevent electrical
operation completely (functional
equipment
2 WIRE CONTROL
Achieved by using a remote set of
make/break contacts (e.g. on/off
switch) and only two wires. The
lockout) or until another operation
has been completed (interlock or
sequence control). This is effective in
and processes.
actuator will rotate in one direction either or both the opening and
when contact makes and in the other closing directions and in both ‘Local’
direction when it breaks. Directional or ‘Remote’ modes, but will be
mode may be selected by DIP switch. overridden by an ESD signal.