1. Overview:
Achieve automatic and manual control of turbine speed governors with accident shutdown
and sequence closing functions. Besides, we provide a set of oil pressure unit and its control
system as well.
2. Function:
 Manual operation on site to achieve opening and closing of guide vane;
 Receive command from computer monitoring system to realize automatic unit start-
up and stop ,emergency shutdown;
 Provide unit over-speed protection through closing the guide vane;
 Carry out guide vane sequence closing function to meet the regulation and protection
requirements;
 Continuously provide stable and reliable oil pressure system.
3. Parameters:
 Technical specification for dual-circuit power supply device:
DC: DC220V/110V±15%,2A;
AC: AC220V/110V±15%,2A;
 Specification for input signals of electrical devices:
Feedback signal of unit frequency fg: PT voltage at generator terminal 0.2V-180V;
frequency measurement range 0.5-100Hz;
Feedback signal of grid frequency fs: PT voltage at bus bar 80V-180V; frequency
measurement range 0.5-100Hz;
 Feedback signal of servomotor travel(displacement transmitter), water head, water
pressure and power: DC 0-5V or 4-20mA; resolution <0.05%;
 Output control quantity specification - rated output current: 2.7A;
 Time for unit start-up and stop:
When guide vane is fully open: 2 - 50 s adjustable;
When guide vane is fully closed: 2 - 50 s adjustable;
When unit blade is fully open: 2 - 100 s adjustable;
When unit blade is fully closed: 2 - 100 s adjustable;
 Operation ambient conditions:
Altitude: Not higher than 5,000 M;
Environment air temperature: -20℃-50℃;
Relative humidity : Not greater than 95%, no condensation.
Turbine Speed Governor Monitoring System Software

1. Overview:
Function:
·Governor control functions;
·Real-time diagnosis, fault tolerance and fault protection functions;
·Smart debugging and computer-aided analysis functions
Features:
·Information display and fault recall;
·Flexible parameter setting;
·Network communication (IEC61850);
·Unit high-end control strategies (GPSS, non-linear robustness, smart start-up strategy, S
characteristic resistance);
·Redundancy control technique of servo motor and proportional servo valve
Key parameters
·Frequency measurement precision: ≤ 0.002%;
·Static speed dead band of servomotor: Ix ≤ 0.02%;
·Unit speed fluctuation within 3 minutes of automatic no-load operation: ≤ ±0.10%;
·Immobility time of servomotor: Tq≤ 0.15s;
·Inaccuracy of turbine blade follow-up system: Is ≤ 1.0%;
·Reliability indexes:
Overall fault rate: FR = 25692.5044 FITS @55℃
Mean time between failures: MTBF = 38921.8584 hrs @55℃
Hardware fault-free probability of first year: MR = 0.798463 @55℃
·PID parameter adjustment range :
Proportional gain KP: 0.01-20;
Integral gain KI: 0-20 1/s;
Differential gain KD: 0-20s;
·Regulation range of permanent droop Bp: 0-10% (Step length:1%);
·Regulation range of manual speed dead band:  Adjustable in software (0.01Hz by level);
·Regulation range of electric opening limit: 0-100%;
·Regulation range of "rated frequency ": 45Hz-55Hz;
·Regulation range of "rated power ": 0~120%pr.