FAIRBANKS FIRE PUMPS Section 916 Page 201

STANDARD FIRE PUMP ACCESSORIES Date April 2006

1/2" NPT OUTLET E

FLOAT-OPERATED
AIR RELEASE VALVE

D
1/2" PIPING BY
OTHERS (SEE NOTE 5)
CASING RELIEF VALVE
3-1/2" (89) DIA. SUCTION AND 3/4" NPT OUTLET
DISCHARGE GAUGES WITH
1/4" SHUT-OFF COCKS
C
VALVE INLET SIZE "B"
(PIPING BY OTHERS)

"A" PIPE TAP IN


“A” CASING DISCHARGE
PIPE SIZE
TAP SIZE
2.5” 1823F
3” 1824F
4” 1823F NOTES:
4” 1824F 1. Dimensions are in inches (mm) and may
vary ± 1/4” (6).
5” 1822F
2. Accessories shown are shipped loose for
5” 1823F field installtion.
5” 1824F 1-1/4" 3. Casing relief valve is to be adjusted to
6” 1822F appropriate pressure upon field installtion
4. Casing relief valve is furnished on electric
6” 1822HHF
motor driven units only.
6” 1823HHF
CASING RELIEF VALVE 5. Two stage pumps require both vent taps
6” 1823F piped to air release valve.
6” 1824F VALVE 6. Suction guage range is 30”-0-150 PSI for
SYSTEM
6” 1825F INLET “C” suction pressures up to 75 PSI, or 30”-0-
G.P.M. 300 PSI for suction pressures over 75 PSI.
8” 1822F SIZE - “B”
7. Discharge gauge range is 0-300-PSI for
8” 1825F 250 pumps with rated discharge pressures up
10” 1823F 500 to 150 PSI, or 0-600 PSI for pumps with
10” 1824DF 750 rated discharge pressures over 150 PSI.

8” 1824F 1000 3/4” 4-1/2”


2" 1250 (114)
10” 1824F
1500 FLOAT OPERATED AIR RELEASE VALVE
12” 1824F
ALL VERTICAL 3/4" 2000 SYSTEM
(1840) MODELS 2500 OPERATING “D” “E”
ALL 2-STAGE 1-1/4" 3000 PRESSURE
1” 5-1/2”
(1920) MODELS 3500 (140) UP TO 175 P.S.I. 5-7/8” (149) 3-3/4” (95)
2800/5800 MODELS 3/4” 4000 OVER 175 P.S.I. 6-11/16” (170) 5-5/8” (143)
FAIRBANKS FIRE PUMPS Section 916 Page 205
OPTION 79 - MAIN RELIEF VALVE Date June 1, 2007
Supersedes Section 916 Page 205
OPTION 80 - WASTE CONE Dated October 1, 2006

"A" MAIN RELIEF VALVE INLET SIZE "A" MAIN RELIEF VALVE INLET SIZE

C F

B E

Y Y
WASTE CONE WASTE CONE

D "X" 125# ANSI FLANGE G "X" 125# ANSI FLANGE


RELIEF VALVE OUTLET RELIEF VALVE OUTLET

K Spring-Operated Main Relief Valve K Pilot-Operated Main Relief Valve


K 125# INLET FLANGE K 125# INLET FLANGE
K 250# INLET FLANGE K 250# INLET FLANGE
K Enclosed Waste Cone K Enclosed Waste Cone
PUMP INLET SPRING-OPERATED PILOT OPERATED WASTE CONE
RATING A FLANGE MAIN RELIEF VALVE MAIN RELIEF VALVE
G.P.M. RATING B C D E F G X Y
6 14-7/8 4
125#
250 3 5-7/8 21-1/4 6-1/8 (152) (378) (102) 5 11
500 (149) (540) (155) 6 15-1/4 4-3/8 (279)
250#
(152) (387) (111)
7-5/8 16-15/16 5-1/16
125#
750 4 6-7/16 22-5/8 6-5/8 (194) (430) (129) 8 11-1/2
1000 (163) (575) (168) 7-15/16 17-1/4 5-3/8 (292)
250#
(202) (438) (137)
1250 10 19-7/8 6
125#
1500 6 8-1/2 36 9-3/8 (254) (505) (152) 10 11-1/2
2000 (216) (914) (238) 10 20-3/8 6-1/2 (292)
250#
2500 (254) (518) (195)
12-3/4 22-7/8 8
125#
3000 8 (324) (581) (203) 12 12
Not Available
3500 12-3/4 22-7/8 8-1/2 (305)
250#
(324) (581) (216)
4000 12-3/4 22-7/8 8
8 125#
4500 Not Available (324) (581) (203) 14 22.5
5000 12-3/4 22-7/8 8-1/2 (406) (565)
250#
(324) (581) (216)
NOTES:
1. All dimensions are in inches (mm) and may vary ± 1/4
(6). 4. Relief valve discharge is intended to be piped to waste.
2. Valves are available with inlet flange ratings of 125# or Refer to factory if discharge is to be piped to a line
250#. All waste cones have 125# flange ratings. where back pressure is present.
3. Dimensions for conventional relief valves are not affected 5. Maximum operating pressure for valves rated for 125# is
by flange rating. 175 PSI.
6. Maximum operating pressure for valves rated for 250# is
Section 916 Page 206 FAIRBANKS FIRE PUMPS
Date April 2006 AUTOMATIC AIR RELEASE VALVE

4-3/4 (121)
1/2 NPT" OUTLET

5-1/4
(133)

HYDR8AC
(VAL-MATIC VM15A)
OR APPROVED EQUAL USED
WITH HORIZONTAL FIRE PUMPS
WORKING PRESSURE UP TO 300 PSI
(FM APPROVED)
1/2" NPT INLET

9-1/2 (241)

2" NPT OUTLET

12
(305)

HYDR8AD
(VAL-MATIC #102)
USED WITH VERTICAL TURBINE FIRE PUMPS
WORKING PRESSURE UP TO 300 PSI

2" NPT INTLET

NOTES:
1. All dimensions are in inches (mm) and may vary ± 1/4 (6).
FAIRBANKS MODEL 1800 & 1900 PUMPS Section 916 Page 251
DIESEL BATTERIES, RACKS, & CABLES Date April 2006

POS NOTES:

11 1. Dimensions are in inches (mm) and may vary ± 1/4" (6).


2. Batteries are 12 volt, lead-acid type D-8D,
(279) approximately 95 Ibs. each, dry.
NEG 3. Batteries are shipped dry. Electrolyte (approx.19 quarts
per battery) must be procured locally.
POS 4. Refer to Section 916 page 252 for exact number of
batteries & cables to be furnished based on the
11 diesel engine manufacturer and model used.
(279) 5. Battery racks are fabricated steel, approximately
20 Ibs. each.
NEG
6. Each rack holds 2 batteries. Racks are not to be
stacked.
20.75
(527)
BATTERY

16.25
(419)
BATTERY
5.5 (140) RACK

20.5 23.5
(521) (597)

60" or 80"
NOTES: POSITIVE CABLE (1524 or 2032)
1. All cables are SAE J55BA type SGT with
tensile attachment of 700-800 lbs.
2. Positive & negative cables 60" (1524) long 17/32 DIA. HOLE (TYPICAL)
are 2/0 gauge; positive & negative cables 80" 60" or 80"
(2032) long are 3/0 gauge.
3. Terminal clamps have steel reinforced (1524 or 2032)
inserts.
NEGATIVE CABLE
4. Not all cable types are required for every
engine. Refer to Section 916 page 252 for
cable applicability. 12"
INTERCONNECTING (305)
CABLE
Section 916 Page 252 FAIRBANKS MODEL 1800 & 1900 PUMPS
Date October 2006 DIESEL BATTERY CABLE DIAGRAMS
Supersedes Section 916 Page 252
Dated April 2006

12 VOLT SYSTEM
REQUIRED COMPONENTS ENGINE APPLICABILITY

POS
(1) BATTERY RACK CUMMINS: 6BTA 5.9-F1
(2) BATTERIES 6BTA 5.9-F2
12V (2) POSITIVE CABLES 6BTA 5.9-F4
(2) NEGATIVE CABLES 6CTA 8.3-F1
NEG 6CTA 8.3-F2
6CTA 8.3-F3
POS

CLARKE-DETROIT:
12V VMFP-04HN VMFP-04HT
NEG VMFP-06HT VMFP-T6HT
VMFP-L6HR VMFP-T6HR
JU4H-UF10 JU4H-UF20
JU4H-UF30 JU4H-UF40
JU4H-UF50 JU6H-UF30
JU6H-UF50 JU6H-UF60
JW6H-UF30 JW6H-UF40
JW6H-UF50 JW6H-UF60

EDWARDS: ALL MODELS

NOTES:
1. Clarke “VMFP,” “JU4H” & “JU6H” Engines require cable sets of different lengths. On these engine
models, a 2/0 guage postive and negative cable set 60” (1524 mm) long, and a 3/0 guage positive
and negativecable set 80” (2032 mm) long are furnished.
2. Refer to Section 916, Page 251 for details of batteries, racks and cables.

POS

24 VOLT SYSTEM
NEG
REQUIRED COMPONENTS ENGINE APPLICABILITY
POS
24V
(2) BATTERY RACKS CLARKE-DETROIT:
(4) BATTERIES DDFP-08FH DDFP-08FA
(2) POSITIVE CABLES
NEG (2) NEGATIVE CABLES CATERPILLAR:
(2) INTERCONNECTING ALL MODELS
POS CABLES

NEG

POS
24V

NEG
Section 916 Page 256 FAIRBANKS FIRE PUMPS
Date April 2009 SINGLE WALL FUEL TANKS WITH FITTINGS
Supersedes Section 916 Page 256
Dated April 2006
19
11
2
17

16 DIESEL FUEL TANKS:


10 15 1 1. Tanks are constructed and labeled in accordance with UL-142.
21 18 2. Fittings shown are consistent with N.F.P.A. 30 and UL-142.
7
3. Tank to be pitched toward drain 1/4” per foot with outlet on the same elevation
20
as engine fuel pump. Means of elevating tank (by others) may be required.
21
5 4. Usable tank volume is total capacity less 5% for sump and 5% for expansion.
3 9
8

C D E F 6"

12 "A" DIA.
22
14

L
13
2" NPT CPLGS. FOR
CUST. FURN. LEGS H

4 G
B FUEL SUPPLY

FUEL RETURN 14

NOMINAL USABLE
TANK SIZE VOLUME A B C D E F G H L Z
IN GALLONS IN GALLONS
119 105 24 (609) 61 (1548) 6 (152) 6 (152) 6 (152) 19 (482) 37 (939) 14 (355) 3 (76) 4
187 165 30 (761) 61 (1548) 6 (152) 6 (152) 6 (152) 19 (482) 37 (939) 16 (406) 3 (76) 4
300 270 38 (964) 61 (1548) 6 (152) 6 (152) 6 (152) 19 (482) 37 (939) 23 (584) 3-3/4 (95) 4
359 320 36 (914) 73 (1853) 6 (152) 6 (152) 6 (152) 31 (787) 44 (1117) 23 (584) 3-3/4 (95) 4
572 515 48 (1218) 73 (1853) 6 (152) 6 (152) 6 (152) 31 (787) 44 (1117) 30 (761) 4-3/4 (121) 4
849 766 64 (1626) 61 (1548) 6 (152) 6 (152) 6 (152) 19 (482) 44 (1117) 30 (761) 4-3/4 (121) 4
1100 993 64 (1626) 79 (2007) 6 (152) 6 (152) 6 (152) 37 (940) 44 (1117) 30 (761) 4-3/4 (121) 6

COMPONENTS FURNISHED BY OTHERS COMPONENTS FURNISHED BY FAIRBANKS MORSE


ITEM NO. QTY. REQ’D DESCRIPTION ITEM NO. QTY. REQ’D DESCRIPTION
20 1 “Z” Diameter Piping for Vent 1 1 2” NPT Lockable Fuel Cap
21 1 1/2” Tubing and Fittings or 2 1 2” Screened Tank Vent
1/2” Black Pipe 3 1 Fuel Gauge 1-1/2” NPT
22 1 3/4” Tubing and Fittings or 4 1 1” NPT Drain Plug
3/4” Black Pipe 5 1 2” NPT Pipe Plug
NOTES 7 1 1/2” Tee
1. All dimensions are in inches and may vary ± 1/4". 8 1 1/2” Close Nipple
2. Components shown are shipped loose for field assembly. 9 1 2” Fuel Fill Pipe
3. Illustration is for component identification only. Actual installation must meet 10 1 “Z” x “Z” x 2” Tee
local codes and all applicable standards.
11 1 “Z” Coupling
4. Item 10 may consist of a combination of fittings.
5. Refer to Section 916 page 259 for details of Fairbanks-furnished components. 12 1 3/4” NPT Lockable Fuel Valve
6. Items 11 & 17 not required for 515 gallon tanks. 13 1 3/4” Close Nipple
14 2 Fuel Hoses for Supply & Return
(Furnished by Engine Mfr.)
15 1 2” Street Elbow
16 1 “Z” x “Z” x 2” Tee
17 1 “Z” Close Nipple
18 1 “Z” x 6” Nipple
19 1 “Z” Emergency Vent
FAIRBANKS FIRE PUMPS Section 916 Page 259
FITTINGS FOR DIESEL FUEL TANKS Date April 2009
Supersedes Section 916 Page 259
Dated April 2006

NOTES
1. All dimensions are in inches and may vary ± 1/4".
2. Components shown are shipped loose for field assembly.
3. Illustration is for component identification only. Actual installation must meet
local codes and all applicable standards.
4. Refer to Section 916 pages 255 through 258 for the location and applicability
of each component shown above
FAIRBANKS FIRE PUMPS Section 916 Page 261
DIESEL ENGINE MUFFLERS Date June 1, 2007
Supersedes Section 916 Page 261
B Dated October 1, 2006

A DIA.

MUFFLER INLET & OUTLET


SIZE – 150# ANSI FLANGE

MUFFLER COMMERCIAL RESIDENTIAL CRITICAL


ENGINE INLET & GRADE GRADE GRADE
MODEL OUTLET "A" "B" WGT "A" "B" WGT "A" "B" WGT
CUMMINS
CFP33 & CFP39 3” 8 36 39 8 42 42 12 42 68
CFP59, CFP83, CFP6E, CFP9E 4" 10 36 48 10 46 50 14 54 115
CFP11E 5" 10 42 55 10 54 60 16 61 140
CLARKE FIRE PROTECTION
JU4H-UF10, -UF12 & UF14 3" 8 36 39 8 42 42 12 42 68
JU4H-UF20, -UF22 & UF24
JU4H-UF30, -UF32 & -UF34
JU4H-UFH8, UFH0 & -UFH2
JU4H-UF40, -UF42 & -UF44 4" 10 36 48 10 46 50 14 54 115
JU4H-UF50, -UF52, UF54 & -UF58
JU4R-UF09, -UF11, -UF13, -UF19
JU4R-UF21 & -UF23 3" 8 36 39 8 42 42 12 42 68
JU4R-UF40, -UF49, -UF51, -UF53 4" 10 36 48 10 46 50 14 54 115
ALL JU6H-SERIES 5" 10 42 55 10 54 60 16 61 140
JW6H-UF30 (JDFP-06WA) & -UF38 5" 10 42 55 10 54 60 16 61 140
JW6H-UF40 (JDFP-06WR) & -UF48
JW6H-UF50 & -UF58 6" 12 42 65 12 54 60 20 74 175
JW6H-UF60
ALL JX6H-SERIES 8" 18 50 150 18 62 145 24 75 215
CATERPILLAR
3406B-DIT, -DITA 6" 12 42 65 12 54 60 20 74 175
3412-DIT, PH-0 & PH-1 8" 128 50 150 18 62 145 24 75 215
3421-DITA, PH-0 8" 18 50 150 18 62 145 24 75 215
3412-DITA, PH-1 DUAL 6" 12 42 130 12 54 120 20 74 350
FAIRBANKS MODEL 1800 & 1900 Section 916 Page 301
DIESEL ENGINE DRIVEN FIRE PUMP Date April 2006

COOLING WATER PIPING DATA

BY-PASS VALVES
NORMALLY CLOSED GAUGE

TO

ENGINE

REGULATOR VALVES
STRAINERS SOLENOID
VALVE

FROM

PUMP

VALVE "A" VALVE "B"

This instructional data explains the installation and shutdown to prevent the waste of cooling water. (One
operation of the cooling system for UL listed, FM red wire must be connected to terminal #1 of the engine
approved Fire Pump engines equipped with heat junction box, the other red wire to terminal #11 of the
exchangers. engine junction box, and the green wire grounded to the
engine block. Refer to applicable wiring diagrams.)
Engines equipped with heat exchangers use an engine
mounted water pump to circulate jacket water around 4. The valves in the BYPASS Iine of the loop are nor-
the tubes of the heat exchanger to maintain proper mally CLOSED. They should ONLY be opened to pro-
jacket water temperatures. Cooling water, supplied by vide cooling water to the engine if the regulator valve
the Fire Pump, is piped through the tubes and dis- or solenoid valve require repair.
charged to waste.
5. Valves "A" and "B" are normally OPEN. They should
REQUIREMENTS ONLY be closed if repair is required to the regulator
valve or solenoid valve.
The loop portion of the cooling water supply piping,
shown above, incorporates all components required 6. The gauge indicates back pressure on the cooling
by NFPA and is sized to provide the required volume water discharge. The recommended back pressure to
of water at the proper pressure for the heat exchang- assure adequate flow is 15-20 PSI and should not
ers of the engine models listed in Table A. exceed the allowable pressure shown in Table A.

Model 1800 & 1900 pumps are shipped from the plant 7. Since cooling loop components are subject to
with the loop piped between the pump and engine. bumps and movement during shipping. all compo-
The pipe and loop sizes are determined by the engine nents must be checked for pipe strain and leakage
model. prior to initial startup.

COMPONENTS INSTALLATION -COOLING WATER OUTLET

1. A flushing type strainer is used to protect the regu- The cooling water outlet piping from the engine heat
lator valve, solenoid valve and the tubes of the heat exchanger must be at least the size listed in Table A.
exchanger from foreign material. The piping must be short, have no valves and dis-
charge into an open waste cone. If deviations from the
2. The regulator valve is used to control the volume requirement of discharge to an open waste cone are
and pressure of the cooling water. permitted by the authority having jurisdiction, the
proposed plumbing must be reviewed to assure that
3. The solenoid valve opens automatically when the the back pressure created wiII not reduce the cooling
engine is started and closes automatically on engine water flow to below that required for the engine.