Sunteți pe pagina 1din 27

OVR Three Phase Vacuum Recloser

Instruction Bulletin: 15 – 38 kV

Page 0
TABLE OF CONTENTS
Description Section Number Page Number
Safety Notices................................................................................ 1.0 ............................. 2

Introduction .................................................................................... 2.0 ............................. 2

Receiving, Handling and Storage .................................................. 3.0 ............................. 3

General Description ....................................................................... 4.0 ............................. 5

Standard Production Tests ............................................................ 5.0 ............................. 7

Operation ....................................................................................... 6.0 ............................. 7

Operational Checks Prior to Installation......................................... 7.0 ............................. 8

Installation...................................................................................... 8.0 ............................. 9

Inspection, Maintenance and Adjustment ...................................... 9.0 ........................... 17

Direct Replacement of the Complete Pole Assembly .................. 10.0 ........................... 18

LIST OF ILLUSTRATIONS
Figure Number Description Page Number
Figure 1 Hazardous Voltage Nameplate 2
Figure 2 Recloser Lifting Detail 4
Figure 3 Pole Mounting Assembly Drawing 11
Figure 4 Pole Mount Ground Connections 12
Figure 5 Substation Mounting Assembly Drawing 13
Figure 6 Substation Mounting Base Plan 14
Figure 7 Substation Ground Connections 15
Figure 8 Contact Wear Measurement/Adjustment 17
Figure 9 Pole Assembly 19
Figure 10 Indicator Assembly 20
Figure 11 Trip Handle Cover 20
Figure 12 High Voltage Cabinet Layout 21
Figure 13 Typical Connection Diagram 15/27 kV 22
Figure 14 Typical Schematic Diagram 15/27 kV 23
Figure 15 Low Voltage Control Cabinet Dimensions 24
Figure 16 Recloser Nameplate 25

LIST OF TABLES
Table Number Description Page Number
Table 1 Power Requirements 7
Table 2 Pole Mounting Dimensions 10
Table 3 Substation Mounting Dimensions 13

Page 1
Figure 1 – Hazardous Voltage Nameplate

1.0 SAFETY NOTICES injury to service personnel, or could damage


equipment or render it unsafe. These warnings do not
The OVR Medium Voltage three phase Recloser cover every conceivable method in which service
should be installed within the design limitations as (whether or not recommended by ABB) may be
described on its nameplate and in these instructions. performed. Secondly, ABB cannot predict or
investigate all potential hazards resulting from all
Follow your company’s safety procedures. conceivable service methods. Anyone using service
procedures or tools, whether or not recommended by
This recloser should not be used by itself as the sole ABB, must satisfy himself thoroughly that neither
means of isolating a high voltage circuit. For the personal safety nor equipment safety will be
safety of personnel performing maintenance jeopardized by the service method or tools selected.
operations on the recloser or connecting equipment, All information contained in this manual is based on
all components should be electrically disconnected by the latest product information available at the time of
means of a visible break and securely grounded. printing. The right is reserved to make changes at any
time without notice.
This product is intended to be operated and
maintained by qualified persons thoroughly trained 2.0 INTRODUCTION
and knowledgeable of the hazards involved. This
publication is written only for such qualified persons In the interest of clarity, a single identification number
and is not intended to be a substitute for adequate is used for each individual item throughout this book in
training and experience in the safety procedures for every relevant figure or diagram.
this device.
These instructions do not attempt to provide the user
Warning of this equipment with every possible answer to
questions, which may occur in the application,
Detailed descriptions of standard repair procedures, operation and maintenance of the product. Also, as
safety principles, and service operations are not improvements in parts and assemblies are made,
included. It is important to note that this document some parts may differ in appearance than depicted in
contains some warnings and cautions against some illustrations; however, functionality will be equivalent.
specific service methods that could cause personal

Page 2
The type OVR vacuum recloser is a sophisticated,
high-voltage, three-phase device incorporating three
vacuum interrupters driven by three separate
magnetic actuators. The vacuum interrupter and the SHIPPING
current sensor are both embedded in a pole cast with SCREW

an advanced Hydrophobic Cycloaliphatic epoxy.


Together with the specialized control functions, the
recloser will sense an overload and automatically
open. Then after a pre-set time delay, the recloser will
close again. If the overload condition still exists, the
recloser will again trip and reclose. Standard OVR
controls, the PCD, will allow up to five reclosing packed with the recloser should be kept with the unit.
operations before the recloser will lock open. The The low-voltage control cabinet provides a convenient
source of the fault condition must then be removed place to keep this instruction book, schematic
before normal service can be restored. diagram, connection diagram, frame assembly
drawing, high voltage wiring diagram, and outline
Satisfactory performance of the recloser is contingent drawing of the unit. Additional copies, and a certified
upon correct installation, adequate maintenance and test report, may be obtained upon request from the
service of the product. Careful study of these local ABB sales office. Remove the shipping screw
instructions will permit the user to obtain maximum from the LV cabinet and discard. See Illustration
benefit from this device. above.

3.0 RECEIVING, HANDLING AND STORAGE 3.2 Handling


The OVR recloser comes with two brackets that
Each recloser is assembled and tested at the factory attach to the sides of the cabinet and provide
prior to being prepared for shipment. This equipment provisions for lifting the recloser. A four-point lift is
is packed and shipped in perfect condition from the strongly recommended using the loops in these
factory. If damage is noticed, call the carrier at once brackets (See Figure 2). If the unit is shipped
for inspection, and request an inspection report. File a unassembled, these brackets will be located in one of
formal claim with the carrier, supported with the paid the shipping boxes.
freight bill, inspection report, and invoice. The local
ABB sales office should be notified. Caution - Exercise care during lifting to avoid
damage to the bushings. For substation frames
3.1 Receiving Inspection shipped assembled, lift the frame off the pallet (taking
Upon receipt, it is important to inspect promptly to be care not to damage the poles) and place in the
certain that the correct material has been received. In desired location. Then remove the lifting brackets from
case of shortage, immediately notify the local ABB the frame and mount to the recloser for lifting. Do not
sales office. Check all parts against the shipping list, place the recloser on an uneven surface, as damage
as they are unpacked. Instructions and literature to the open/close indicators may occur.

Page 3
Lifting Points
4 point lifting recommended

4 HOLES FOR BOLTING


TO THE FRAME

USED IN POLE
FRAME

USED IN
SUBSTATION
FRAME

Figure 2 – Recloser Lifting Detail

Page 4
3.3 Storage separate assembly comprised of a vacuum interrupter
Important: The Recloser and Control Cabinets must and current sensor encapsulated in an advanced
be stored in the upright position to avoid moisture hydrophobic Cycloaliphatic epoxy (HCEP) molded
buildup. pole assembly, and coupled to a magnetic actuator.

For prolonged storage, indoor storage is 4.2 Housing


recommended. If either cabinet is stored outdoors, The cover of the recloser housing (High voltage
there are two options to prevent condensation cabinet) is removable and is retained by two bolts.
problems. The first option consists of energizing the The position indicators for each phase are mounted in
anti-condensation heaters inside the high voltage the floor of the cabinet and are visible from below.
cabinet and the low voltage control cabinet. The recloser nameplate that shows rating information,
serial number, shop order number, and
The second option is to have each unit pretreated at manufacturing date is mounted on the right-hand side
the factory with a special vacuum wrapping to of the housing. A heater is provided to prevent
prevent water penetration. Do not remove plastic condensation and must be energized at all times.
wrapping until installation. See factory
representative for more information. 4.3 Pole Assembly
Figure 9 on page 19 shows the details of the pole
The low voltage control cabinet comes with assembly. The top terminal stud (5) is attached
rechargeable batteries that should have power of the directly to the fixed contact stud on the top end of the
proper voltage and frequency supplied to the input of vacuum interrupter (7). The current transfer assembly
the charger assembly. A periodic check of battery (12) is fastened to the lower end of the vacuum
voltage is also advised. interrupter. In the current transfer assembly, contacts
transfer current from the moving contact of the
NOTE: Battery is disconnected for transport. vacuum interrupter to the current transfer assembly,
Reconnect prior to use. which is directly connected to the lateral horizontal
stud terminal (6). The lateral stud terminal passes
If the Recloser is not to be placed in service through a ring-type current sensor (11) before it exits
immediately, it is essential that proper care be the molded assembly. The two leads carrying the
exercised in handling and storage to ensure transformer’s secondary current output are also
good operating condition in the future. encapsulated and brought down to a terminal block
mounted on the floor of the high voltage cabinet.
4.0 GENERAL DESCRIPTION
NOTE: In the event the control cable is disconnected
4.1 High-Voltage Assembly from the recloser, resistors installed across the CT
The high-voltage assembly of the OVR consists of leads in the recloser cabinet will prevent voltage
three individual phase poles mounted onto a buildup on the CT secondary.
common housing. Each of the OVR poles is a

Page 5
The magnetic actuator assembly is attached to the A 45 W thermostatically controlled heater is provided
molded pole assembly by four hex posts. to prevent condensation. (Note that the thermostat
only controls the control cabinet heater. The recloser
The magnetic actuator incorporates a very powerful cabinet heater is constantly energized.) A typical unit
permanent magnet assembly. When the armature is comes standard with 48 V DC batteries. These
in contact with the upper pole piece, the magnet batteries are rated to last 48 hours during a loss of
produces a holding force in excess of 300-500 lbs. AC if fully charged. The batteries should be checked
Attached to the armature are two stainless steel periodically and replaced every three to five years.
guide rods. The upper guide rod (or Adjusting Rod) This assumes an average ambient of 25 degrees C.
is attached to the lower end of the main operating
rod (or pushrod), which connects directly to the The large blue 270,000µF capacitor is the “trip”
moving contact of the vacuum interrupter. The lower capacitor. It stores the energy necessary to ensure
guide rod (or Actuator Shaft) mounts the opening proper operation of the magnetic actuator under all
spring, Armature, and the indicator assembly. operating conditions. It also decouples any
Disassembly of the magnetic actuator is not dependency on opening and closing due to poor
recommended. Lubrication or maintenance is not battery condition (e.g., low charge, high
required and will void warranty. Should an actuator impedance/shorted cell, missing battery, etc.).
fail to operate, contact ABB for service.
4.4.2 PCD Control
4.4 Control NOTE: For recloser control cabinets containing an

4.4.1 Low Voltage Control Cabinet ISD (Intelligent Switching Device) interposing relay

A separate weatherproof cabinet houses the low refer to the ISD Instruction Bulletin number

voltage control components. A hinged panel allows IB38-400-1 for information.

front and rear access to the control components.


The control supplied with the OVR is the
Other devices can be mounted on the sidewalls of
microprocessor-based PCD Power Control Device.
the cabinet. Connections to the recloser are made
This sophisticated controller integrates most of the
through a plug-connected, shielded 24-pin cable.
normal recloser control functions into a single device,
Make sure the gasket is installed at both ends of the
providing a wide range of metering and remote
Control Cable to avoid water ingress into either High
control options. For details on programming,
or Low voltage cabinets. The hinged door has
operating, and testing the PCD refer to Instruction
provisions for a ½ inch diameter padlock shackle.
book on the supplied CD. For details on the overall

For power, communication, and control inputs to the control circuit, refer to the specific wiring diagrams

control cabinet, the floor is equipped with removable supplied with the recloser. Table 1 below shows

access plate and two knockout holes. A knockout is voltage and power requirements for the OVR recloser

also provided for a radio antenna connection. On the with a PCD control. Note – Batteries could take up

rear inside wall of the control cabinet, there are three to 48 hours to charge after initial power-up.

studs to for mounting a radio, modem or other user


The PCD can be powered by 120 VAC or 240 VAC.
equipment. Contact your ABB representative for
See connection diagram for details.
more information.

Page 6
Table 1: Power Requirements:
Nominal Allowable Nominal VA Maximum VA Anti-Condensation
Control Voltage Burden Burden Heater VA
Voltage Range Burden

48 VDC 38-56 VDC 20 See below 45


125 VDC 70-150 VDC 20 See below 45
250 VDC 200-280 VDC 30 75 45
120 VAC 102-132 VAC 30 75 45
240 VAC 208-254 VAC 30 75 45

5.0 STANDARD PRODUCTION TESTS 6.0 OPERATION

Standard production tests include: 6.1 Closing


1. Verification of all wiring per connection diagrams. In the open position, the armature rests against a
2. Electrical operation: Close and trip. Overcurrent spacer in the actuator assembly. The armature is held
response and automatic reclosing. there by the opening spring and a small force
3. Check functioning of all manual controls on the developed by the magnet. When the coil is energized
PCD: Local/remote, non-reclosing, ground fault with the correct polarity, the magnetic flux generated
bypass, etc. is in the same direction as the magnet assembly. The
4. Three readings of contact pole resistance are armature is drawn into the coil and brought into
made on each phase of a complete recloser. contact with the upper pole piece. In this position, the
5. 60 Hz Voltage Withstand: The complete recloser coil is de-energized and the armature is held in
is tested (a) between live parts tank, (b) across position by the magnet alone. As the armature is
open contacts, and (c) between phases. In drawn into the coil, the Operating Rod (Figure 9),
compliance with ANSI C37.60, applied test which is attached to the Adjustment rod, moves the
voltage is 50 kV for 15.5 kV rated maximum moving contact of the vacuum interrupter to the closed
voltage, 60 kV for 27 kV rated maximum voltage, position. The actuator has more stroke than the
and 70 kV for 38 kV rated maximum voltage. Test vacuum interrupter. The interrupter contacts make
duration is 1 minute. contact before the actuator has completed the stroke.
6. Wiring Insulation: The terminal block connections The additional movement of the operating rod after
(with the foil leads and microprocessor controller) the contact closes is needed for the contact pressure
are given an over-voltage test of 1500 volts AC to spring to compress at the top of the operating rod.
ground. Test duration is one minute. This “over travel”, or contact wipe, allows for contact
The test duration can be reduced to one second if wear in service and helps provide low contact
1800 VAC is used for the over-voltage test. resistance.
7. Minimum Trip and Time-Current Test.

Page 7
6.2 Opening Caution: Do not ground either side of the battery or
When the coil is energized with the reverse polarity, attach ground to the terminals of the actuator
the magnetic flux generated opposes the force operating coils. This will result in permanent damage
generated by the magnet assembly. This reduces the to the unit.
holding force and the armature is released. The
opening spring (with an initial assist from the contact 7.1 Electrical Close – PCD
pressure spring) drives the operating rod to the open Observe the position-indicating LEDs located to the
position. right of the OPEN and CLOSE pushbuttons on the
front panel of the PCD. If the LED next to the OPEN
6.3 Mechanical Opening pushbutton is illuminated (or Green), the recloser is
If the electrical system becomes disabled or de- opened. To close depress the CLOSE push button.
energized, the high voltage unit may be safely opened The PCD will initiate a closing pulse to each actuator
mechanically. Manual opening is performed by pulling simultaneously (if in three phase mode) and the
down on the yellow trip lever located on the side of the recloser will move to the closed position. The CLOSE
HV unit. See Figure 11 (8). This will mechanically LED will illuminate. The duration and amplitude of the
open all three poles simultaneously. closing pulse is precisely controlled by the PCD.
An optional CLOSE BLOCK feature is available for
manual trips. 7.2 Electrical Trip - PCD
Observe the position-indicating LEDs located to the
7.0 OPERATIONAL CHECK PRIOR TO right of the Open and Close pushbuttons. If the
INSTALLATION CLOSE LED is illuminated (or red), the recloser is
closed. To trip, depress the OPEN push button. The
Note: Verify Low Voltage (LV) cabinet used is for PCD will initiate a tripping pulse to each actuator (if in
specific recloser voltage range. For example, a 15 or three phase mode) and the recloser will move to the
27kV OVR control cabinet will work on any VR-3S open position. The duration of the tripping pulse is
recloser but not the OVR 38kV recloser. A 38 kV controlled by the PCD.
OVR control cabinet must be used for the 38 kV OVR
but it cannot be used on any VR-3S recloser. Note: The IEC CLOSE and TRIP LED and Pushbutton
colors are the opposite from that described above (i.e.
The recloser should be tested for mechanical and ANSI). The IEC color convention for CLOSE is Green
electrical operation before it is energized in the power and OPEN is red.
system. Make the necessary control power
connections, including the cable between the high Note: When OPEN and CLOSE LEDs are both out,
voltage compartment and the low voltage control this indicates one of two poles are open or closed and
cabinet. If necessary, remove the cover of the high is normal with reclosers operating in single-phase
voltage compartment to observe the mechanical mode.
operations. Note: In the event of a malfunction, the OPEN and
CLOSE LEDs will alternately blink Red and Green.

Page 8
The front panel of the PCD also has control push and the housing. Connect the high voltage to the
buttons for several standard recloser functions. When top terminals.
these functions are activated, an LED adjacent to the 2. Stand clear more than one to three meters before
push button provides indication. Push buttons PROG energizing the high voltage source.
1 and PROG 2 are mounted below the standard 3. Do not exceed 37.5 kV AC for any voltage class
functions. These buttons are pre-programmed for the Recloser. Do not apply voltage for more than 60
following: seconds.
4. If internal flashover occurs, isolate the phases and
PROG 1 – Battery Test. This applies only when the test each one independently to identify the
batteries are supplied in the control cabinet and the defective interrupter. Any defective pole assembly
UPS module is included in the PCD. A Battery Failed must be replaced prior to the recloser being
message will appear if the Battery test does not pass. placed in service.

PROG 2 – Not currently used. 8.0 INSTALLATION

7.2 Vacuum Test Procedure The OVR recloser can be installed in a substation
It is recommended to perform a dielectric (Hi-Pot) test frame, pole-mounting frame, or can be mounted into a
on each interrupter to verify that there has been no customer supplied structure. However, it is required
loss of vacuum during transportation or handling. that in all of the mounting methods the recloser be
Experience has indicated that while a vacuum vertical and level, and securely fastened. Follow your
interrupter with the vacuum seal intact will withstand company guidelines and various codes for setting the
37.5 kV AC across the open contacts, the same height of the recloser, securing the frame to the pole
interrupter open to normal atmosphere will flashover or foundation, and making connections.
at the gap at a much lower voltage.
Important:
RADIATION WARNING: High voltage applied across • The bend radius of the Control Cable is 7
an open gap in a vacuum can produce X-radiation. No inches. Be careful not to bend the cable below
radiation is emitted when the recloser is closed since a radius of 7 inches to avoid damage to the
no gap exists. Also, when the recloser is open to the cable.
specified contact spacing in service or tested within • The H1 and H2 terminal Spade Connectors
the voltages specified, X-radiation at one meter is are equipped with 3/8” Silicon Bronze
below the level of concern. A danger could exist at fasteners which must be torqued to between
voltages above or contact spacing below that 15-20 lbs.
specified on the nameplate.
8.1 Mounting
1. With the recloser in the open position, jumper the The recloser is shipped with either a pole mounting
three top terminals together. Connect the three frame, substation frame or no frame.
lateral terminals and ground the lateral terminals The next section explains the recommended
installation procedure for each frame:

Page 9
8.1.1 Pole Mounting (Refer to Figures 3 – 4) it is recommended to install the frame without the
For pole frames, do the following: transformers and then install them once the
1. Attach the lifting brackets to the sides of the recloser and VT mounting brackets are on the
recloser as indicated in the section on lifting. pole. Alternatively, if it is desired to mount VTs on
2. If the frame is not shipped assembled, put it the frame before mounting the frame on the pole,
together on a flat surface per the assembly 6. Perform the following:
instructions. Follow the drawing closely, making a) Without mounting the recloser to the frame,
sure to use the correct bracket for mounting the install and wire the VTs on the frame.
recloser frame to the pole. b) Lift the frame up onto the pole using a four-
3. Install mounting bolts (not supplied) in the pole for point lift at the corners of the frame.
the recloser and the control cabinet. c) With the lifting bracket attached to the
4. Lift the recloser by the lifting bracket at four points recloser, lift the recloser up onto the frame
and bolt the frame to the two holes on the bottom and bolt into place.
of the bracket at both sides of the recloser. 7. Bolt the pole-mounting bracket to the control
5. Once mounted, lift the assembly onto the bolts in cabinet and then bolt the control to the pole.
the pole. If Voltage Transformers (VTs) are used, 8. Make sure all hardware is tight.

CAUTION: DO NOT EXCEED 50 LBS CANTILEVER FORCE ON ANY OF THE TERMINALS


IN ANY DIRECTION. FAILURE TO COMPLY WILL RESULT IN PERMANENT DAMAGE!

Page 10
Table 2: Pole Mounting Dimensions
Rating Units A B C D E F G H

15/27 kV in 49.82 41.75 15.50 11.10 28.04 38.01 25.30 15.44


15/27 kV mm 1265.5 1060.5 393.7 282.1 712.3 965.5 642.7 392.1
38 kV in 49.82 41.75 15.50 12.30 28.04 44.00 29.80 15.44
38 kV mm 1265.5 1060.5 393.7 314.0 712.3 1119.0 759.0 392.1

Figure 3 – Pole Mounting Assembly Drawing

Page 11
TRANSFORMER

SURGE ARRESTOR
GROUND WIRE
SHOWN AWAY
SURGE
FROM POLE FOR
CLARITY. ARRESTOR CONTROL CABLE

GROUNDWIRE
MUST BE ROUTED HIGH VOLTAGE
DOWN THE POLE CABINET
AND MUST BE MOUNTING FRAME
WITHIN 8 INCHES
OF BOTH THE
CONTROL CABLE
AND SUPPLY
VOLTAGE CABLES. LOW VOLTAGE
CABINET SUPPLY VOLTAGE

POLE GROUND

EARTHING RESISTANCE
MUST BE BELOW 10 OHMS IN
DRY SUMMER CONDITIONS

Figure 4 – Pole Mount Ground Connections

8.1.2 Substation Mounting 4. Lift the recloser over the top of the frame and
(Refer to Figures 5 – 7) lower into place.
1. With the lifting brackets mounted to the 5. Bolt the control cabinet to the cross-members on
substation frame, lift the frame off the pallet and the side of the substation frame.
move into position. 6. Make sure all hardware is tight.
2. Bolt the frame to the pad and raise the upper
portion to the desired height. The frame allows
adjustment in 3” increments.
3. Remove the lifting brackets from the frame and
bolt to the sides of the recloser.

Page 12
Table 3: Substation Mounting Dimensions
Rating Units B C D L M N O P Q R
15/27
in 42.06 15.50 11.10 95.80 65.6 48.00 52.38 22.00 29.06 27.90
kV
15/27
mm 1068.2 393.7 282.1 2433.3 1666.0 1219.2 1330.5 558.8 738.2 708.6
kV
38 kV in 42.06 15.50 12.30 95.80 65.60 48.00 52.38 22.00 29.06 34.90
38 kV mm 1068.2 393.7 314.0 2433.3 1666.0 1219.2 1330.5 558.8 738.2 888.6

CAUTION: DO NOT EXCEED 50 LBS CANTILEVER FORCE ON ANY OF THE


TERMINALS IN ANY DIRECTION. FAILURE TO COMPLY WILL RESULT IN
PERMANENT DAMAGE!

Figure 5 – Substation Mounting Assembly Drawing

Page 13
Figure 6 – Substation Mounting Base Plan

Page 14
Ground wire shown away
for clarity. Ground wire
must be within 8 inches of TRANSFORMER
both the control cable and
supply voltage cables.

Earthing resistance CONTROL


must be below 10 HIGH CABLE
ohms in dry summer VOLTAGE
CABINET
conditions.
SUPPLY
VOLTAGE

LOW
VOLTAGE GROUND
CABINET

Figure 7 – Substation Ground Connections

8.1.3 No Frame The recloser high voltage cabinet includes a standard


1. With the lifting brackets mounted to the recloser, NEMA 2 hole drilled stainless steel pad on the rear for
lift the frame off the pallet and move into position. grounding. Any voltage transformers used should be
2. If an alternate customer-provided bracket is used grounded to the main ground wire leading from the
for mounting the recloser, use caution when lifting recloser to ground.
the recloser. Do not lift the recloser by the poles,
as this may cause damage to the poles. To ground the low voltage control cabinet, use the
connector provided (see the shipping bag in the
Caution – Do not use forklift to move recloser to control cabinet) which accepts a #6 - 2/0 AWG
avoid damage to the indicator cups. conductor. Ground the control cabinet to the main
ground wire from this external connector. All ground
8.2 Grounding wire used must be #4 AWG minimum.
Grounding is important to ensure proper operation of
all electronic components to prevent penetration of Both the high voltage cabinet and low voltage control
EMC noise and other transients into the sensitive cabinet are to be firmly grounded in series when
electronic circuits (PCD, modems, radios, etc.) installed. See Figures 4 and 7 for more detail.

Page 15
8.3 Arrester Protection If it is desired to obtain control power from one of the
Surge arresters must be supplied on both the source three VTs used for metering, jumpers must be added
and load sides of the recloser. It is recommended that to the control cabinet distribution terminal block to
the arrester grounds be connected to the recloser connect one of the voltage sources to the control
ground and continued to the pole ground. The leads power input. Following the wiring diagram, in the
connecting to the arresters should be as short as control cabinet, add a connection from terminal block
feasible to limit stray inductance and to maximize the point VA1 (alternatively VB1 or VC1) and VN to the
arrester’s effectiveness. control power inputs. Check all terminal block
connections for proper tightness. For details of the
8.4 Control Power overall control circuit refer to the specific wiring
Control power is supplied as indicated on the attached diagrams supplied with the recloser.
wiring diagram. If 240 VAC is used, verify the
240/120VAC connections for the heaters before 8.5 Line Connections
applying power. If 240 VAC is used the ground fault The recloser is connected in series with the line and
receptacle will need to be powered via a 240/120 does not require to face one direction or the other.
step-down transformer. However, there are two considerations:
1. The voltage transformer used for supply power
Caution should be exercised when connecting the Hot must be installed on the source side of the
and Neutral to the desired source. If 240VAC is used, recloser in order to avoid unnecessary drain on
the GFI receptacle should be labeled accordingly. the battery backup system when the circuit is
open at the recloser.

If the control is supplied with an optional 2-pin power 2. When voltage transformers are used for metering

connector and power cable, connect the AC source to and protection purposes, they must be installed

this cable. Otherwise, one of the knockouts may be on the source side. The top terminal of the poles

used or the removable plate drilled to suit for conduit. must also be connected to the source side. This is
necessary for proper power flow metering, and for

Three phase voltage wiring can be provided from the the directional protection elements to work

recloser to the low voltage control cabinet terminal according to programmed settings.

block and then on to the voltage inputs on the PCD


control for metering and voltage dependent protection 8.6 Final Inspection

purposes. When the recloser cabinet is supplied with When the recloser has been installed and all

a 5-pin connector at the bottom, the customer may mechanical and electrical connections completed,

connect the VTs through the recloser as shown on the EXCEPT ENERGIZING THE POWER LINE, the

wiring diagram. Otherwise, wire the three VTs directly following points of inspection are recommended:

to the terminal block in the control cabinet. It is not 1. Ensure the recloser is properly leveled and

necessary to wire any voltage inputs directly to the securely anchored.

back of the PCD relay. 2. Make a final check of tightness of all hardware.
3. Securely tighten terminal and ground connections.
4. Check control cable entrance fittings for tightness.

Page 16
5. Ensure that the high voltage and low voltage the upper end of the operating rod ensures that
control cabinets are grounded. proper contact pressure is maintained in the
6. Operate the recloser from the control box to verify closed position. Contact erosion reduces the
normal operation. compression of the over-travel spring, which in
7. If the recloser has been improperly stored or it is turn increases the contact travel (Total travel of
suspected that the unit was handled roughly the actuator is fixed).
during shipping, it is advisable to check the A 2.5 mm gauge is provided with the recloser to
recloser alignments (Vacuum Interrupter (VI) allow easy confirmation of the allowable contact
contact wipe, micro-switches, etc.) Contact your erosion. See Figure 8.
ABB representative if necessary. a. Make sure the Recloser is in the Open
position.
9.0 INSPECTION MAINTENANCE AND b. Connect an ohmmeter across the H1 and H2
ADJUSTMENT terminals.
c. Insert the 2.5mm gauge into the holes in the
The OVR is a simple device and will require minimal Actuator Housing. See Figure 8.
maintenance if handled properly and depending on d. Insert a large Screwdriver or punch into the
the frequency of operation and local environmental slot located on the actuator shaft. See Figure
conditions. 8.
e. Pry on the screwdriver to force the shaft
To a large extent, the safety and successful upwards as far as can be moved.
functioning of any apparatus or system connected f. The ohmmeter should indicate approximately
with the recloser depends on the proper installation zero resistance. If the ohmmeter reads open
commissioning and programming of the unit. the contact erosion limit has been reached
and the pole will need to be replaced.
To provide long, reliable service, the recloser should g. Remove 2.5 mm gauge and screwdriver from
be inspected at regular intervals. Operating actuator.
experience, environmental conditions, the number of
operations, the magnitude of current and any unusual
2.5mm
service conditions will guide you in establishing a Gauge
maintenance schedule. The following check list is a
minimum guide:
1. Check the molded pole assemblies for external
damage and clean if contamination is evident. The
poles the can be cleaned with a mild detergent. Screwdriver
2. Checking contact wear - As a vacuum interrupter or punch

continues to switch current, material from the


contacts slowly erodes away, and the moving
contact is driven deeper into the interrupter by the Figure 8 – Contact Wear
operating mechanism. The over-travel spring at Measurement/Adjustment
Slot in actuator
shaft

Page 17
3. Verify that the recloser operates correctly using DC. The value should not exceed 150 micro-
the electrical controls. ohms.
4. A Hi-Pot test can be performed to verify the 6. Battery Test: Press the “PROG 1” button on the
vacuum integrity. front of the PCD. The PCD will display a “Delta V”
voltage. This value should not exceed 10 percent
of the nominal battery voltage (i.e., 4.8 V for a 48
V battery). A returned value of 99 V for the “Delta
V” indicates that the battery has a very low
charge, is disconnected, or has failed. A “Pass”
or “Fail” message will be also given with the Delta
RADIATION WARNING: High voltage applied
indication.
across an open gap in a vacuum can produce X-
radiation. No radiation is emitted when the
Note:
recloser is closed since no gap exists. Also, when
If the vacuum interrupters or embedded current
the recloser is open to the specified contact
transformers require replacement, the pole assembly
spacing in service or tested within the voltages
is designed for ease of replacement as a complete
specified, X-radiation at one meter is below the
unit. The assembly includes the molded pole and
level of concern. A danger could exist at voltages
actuator component. This can be installed as a direct
above or contact spacing below that specified on
replacement.
the nameplate.

10.0 Direct Replacement of the Complete Pole


a. With the recloser in the open position, jumper
Assembly (Reference Figures 9 – 12)
the three top terminals together and the three
lateral terminals. Ground the lateral terminals
With the pole in the closed position:
and the housing. Connect the high voltage to
1. Remove the trip handle cover (9) (See Figure 11).
the top terminals.
This will allow the trip shaft to rotate out of the
b. Stand clear more than one meter before
way.
energizing the high voltage source.
2. Disconnect the pole wiring from the right-hand
c. Do not exceed 37.5 kV for 15 kV, 45 kV for 27
side of the terminal block.
kV, and 53 kV for 38 kV reclosers, and do not
3. Remove the four bolts holding the pole mounting
apply for more than 60 seconds.
flange to the top of the housing and withdraw the
d. If internal flashover occurs, isolate the phases
pole assembly using a suitable lifting device.
and test each one independently to identify
4. Clean the sealing surface on the housing to
the defective interrupter. Any defective pole
remove remnants of the previous gasket.
assembly must be replaced prior to the
5. Install new gasket onto the Pole housing.
recloser being placed in service.
6. Using a suitable lifting device, carefully install the
new pole onto the housing being careful not to
5. Contact Resistance: Measure contact resistance
pinch wires or bend the large washers that
with suitable equipment rated not less than 100 A
engage the manual trip shaft.

Page 18
7. Install the four pole mounting bolts. Loosely install trip washers may need to be adjusted. Use
all four bolts before tightening. adjacent poles as guide.
8. Return the trip shaft to its normal position and re-
install the trip handle cover. The new pole manual

1 Molded Part
2 Magnetic Actuator
3 Operating Rod
4 Micro switch
5 Top Terminal Stud
11 (H1)
6 Lateral Terminal Stud
6 (H2)
7
7 Vacuum Interrupter
8 Adjustment Rod
9 Pole Gasket
12 10 Indicator Cup
11 Current Transformer
3 12 Current Transfer
Assembly
13 Actuator Shaft

4
8

2
13

10

Figure 9 – Pole Assembly

Page 19
Figure 10 – Indicator Assembly

Figure 11 – Trip Handle Cover

Page 20
ITEM 29 – MECHANICAL TRIP LEVER
ITEM 2 – MAGNETIC ACTUATOR
ITEM 30 – ANTI-CONDENSATION HEATER
ITEM 31 – 24-PIN CONTROL CABLE
ITEM 1 – POLE ASSEMBLY
ITEM 32 – OPEN/CLOSE INDICATORS
ITEM 33 – GROUND PAD - NEMA 2 HOLE DRILLED

Figure 12 – High Voltage Cabinet Layout

Page 21
Figure 13 – Typical Connection Diagram 15/27 kV

Page 22
Figure 14 – Typical Schematic Diagram 15/27 kV

Page 23
Low Voltage Control Cabinet Dimensions

Figure 15 – Low Voltage Control Cabinet Dimensions

Page 24
Figure 16 – Recloser Nameplate

Page 25
1VAL264001-MB REV B February 2004

ABB Inc.
655 Century Point
Lake Mary, FL 32746 U.S.A
For sales & marketing contact your local
Representative or:
Telephone: +1-407-732-2000
1-800-929-7947
Fax: +1-407- 732-2029
www.abb.com/mediumvoltage

S-ar putea să vă placă și