Sunteți pe pagina 1din 7

1378 IEEE Transactions on Power Delivery, Vol. 13, No.

4, October 1998

C osed Loop

P.W. Lehn M.R. Iravani


Department of Electrical and Computer Engineering
University of Toronto
Toronto, Ontario M5S 3 6 4
Canada

Abstract- This paper presents a new approach for t h e formation regarding its dynamic control or performance
dynamic control of FACTS apparatus, such as t h e STAT- has been published. As a result, the transient response
CQM and UPFC, which utilize voltage source inverters
(VSI) as t h e main building block. The control concept is of such equipment to faults and load fluctuations is un-
based on a linearization of the dq inverter model. Feed- available. In addition, the effect of system variations
forward techniques which are traditionally used for t h e on the closed loop dynamic performance of the overall
approximate decoupling of d and q-axis control a r e dis-
carded in favour of a high gain full state feedback ap-
system is also poorly documented.
proach which assigns both closed loop system poles and, This paper focuses on the control of a single VSI tak-
more importantly, their associated eigenvectors. Experi- ing into the account the effect of possible loading on
mental validation of t h e approach is carried out on a lab-
oratory STATCQM setup. Due to the nonlinear n a t u r e
the dc bus. The concepts are therefore applicable to
of t h e VSI equations and the uncertainty of ac system pa- both control of the STATCOM and of the excitation
rameters, actual closed loop system dynamics can s t r a y stage of a UPFC. Modeling and control of the system
quite dramatically from the desired. Root locus analy- is carried out in the synchronous dq-frame, as is quite
sis is therefore performed t o investigate the small signal
system dynamic behaviour. The loci demonstrate t h a t standard [3], [4].Although still based on the dq-frame
t h e effect of system nonlinearity on the closed loop poles model, the control design strays from the standard tech-
is virtually eliminated by t h e proposed control. T h e ef- niques which attempt to approximately decouple d and
fect of a c system parameter variations is also shown t o
be minimal.
q-axis quantities. Instead, a linear multi-variable ap-
proach based on state space theory is employed, which
Keywords- FACTS, STATCOM, control, dynamic mod- permits the entire eigenstructure of the closed loop sys-
eling tem t o be assigned [ 5 ] . The proposed approach yields
better dynamic decoupling of the d and q-axis currents
I. INTRODUCTION than is achieved by conventional techniques. This al-
lows higher feedback gains to be used which reduces the
Recent advances in the power handling capabilities inverter response time and attenuates any disturbances
of static switches has made the use of the voltage which might enter the system.
source inverters (VSI) feasible at both the transmission In order to confirm positive simulation results, the
and distribution levels. As a result, a variety of VSI proposed control scheme is implemented in a DSP con-
based equipment such as the static compensator (STAT- troller board and tested on a 5kVA laboratory setup.
COM) and the unified power flow controller (UPFC) The dynamic performance of the experimental system
have joined the previous generation of semiconductor proved excellent under all tests performed. Although
based equipment t o make flexible ac transmission sys- both simulation and experimental testing validate the
tems (FACTS) possible. proposed design, no quantitative measure of the robust-
The ability of this new FACTS equipment t o control ness of the controller to parameter variations is readily
system power flows as well as improve system stability obtained from a handful of specific tests. To ensure the
have been well documented [l],[a]. In spite of the in- robustness of the controller, as well as to offer insight
terest in this FACTS equipment however, very little in- into t o the interaction between the ac system and the
VSI dynamics, a root locus analysia is performed.
PE-198-PWRD-0-12-1997 A paper recommended and approved by
the IEEE Transmission and Distribution Committee of the IEEE Power II. THE STATCOM DYNAMIC MODEL
Engineering Society for publication in the IEEE Transactions on Power
Delivery Manuscript submitted July 16, 1997; made available for Figure 1 shows the schematic diagram of a STAT-
printing December 12, 1997. COM, where the inverter ‘on’ state switch resistances,
are lumped in with the transformer leakage resistance,
while switching losses are approximated by a shunt dc
side resistance. Due to the nature of the VSI, the ac
currents always sum to zero, independent of the ac sys-
tem connection. Only two of the three line currents can
0885-8977/98/$10.00 0 1997 IEEE
1379

111. VSI CONTROL


Since current control of the VSI has eclipsed phase
amplitude control, inverter dynamics have improved
dramatically. With conventional current controllers,
emphasis has been primarily on attempting to decouple
the d and q-axis current regulators through feedforward.
PI controllers are then typically employed in each of the
u v v two approximately decoupled loops to reach the speci-
sa sb sc
fied reference inputs [3],[7]. DC link voltage is left t o be
Fig. 1. Schematic of the basic STATCOM regulated through an additional, e-xternal control loop.
Since the synchronous frame is referenced to the ac
therefore be define as system states, and these will be system bus, under balanced steady state conditions the
taken t o be a, and i b . The current in phase c will then system q-axis voltage is zero. As a result, the power
simply be a linear combination of the two defined states. out of the ac bus is simply given by P, = 3/2V,did, i.e.
Based on the model of Figure 1, the system can be rep- the power is proportional to the d-axis current. Based
resented by three differential equations. on this, the external control loop regulating the dc link
d i a / d t = -R/Lia + l/L(-vta + vSa) (1) voltage is used t o supply the d-axis current reference
command, and thereby regulate the power into the ca-
d i b l d t = -R/Lib -I-1/L(-vtb -I-V s b )
(2) pacitor. This approach leads to reasonably rapid re-
dvdc/dt = -Vdc/RdcC f idc/C - il/c (3) sponse, although finally the bandwidth of such control
is limited by
The equations are coupled by a power balance across
the inaccuracy of the assumption that the power P,
the ideal inverter. Since an inverter with a floating dc
out of the ac bus is equal to the power into the dc ca-
link is used, its terminal voltage can have no zero se-
pacitor - this is true only if the system is balanced and
quence component. The current i d c can therefore be
in the steady state
expressed as a function of the two ac currents and two
0 the need for three PI regulators, each of which has
system inputs, U t a and vtb .
a detrimental effect on the phase margin of the closed
loop system
Vdcidc +
= 2vtaia 2vtbib + Vtaib + Vtbia (4) 0 the fact that the approximate decoupling considers
Assuming the system voltage also has no zero se- only dq coupling resulting from the ac side inductance
quence component, all voltages and currents can be first and neglects the fact that the quantities are also cou-
uniquely represented by equivalent space phasors and pled, albeit t o a lesser extent, through the dc capacitor
then transformed into the synchronous frame [6]. Trans- voltage.
forming the equations and employing the power balance
equation (4),yields the complete VSI model in the dq- A . The Linearized Model
frame: To allow the equations to be expressed in standard
d i d l d t = -R/Lid +W i q 1/L(-vtd f U&) (5) state variable form, the states are collected in the vec-
tor x while the controllable inputs, which are the VSI
di,/dt = -wid - R / L i q + l/L(-vtq + vSq) (6) terminal voltages, are represented by U. All other quan-

- 3(vtdid + vtqiq) ----


dvdc - vdc il
tities are considered disturbances, and will be lumped
- (7) into the vector d . The definitions are therefore as fol-
dt 2cvdc RdcC C
lows:
where Vsd and vsq are the d and q-axis components of r - .

the ac bus voltage. The quantities V t d and vtq are the


d and q-axis components of the VSI terminal voltage,
neglecting all harmonics which are near to, or above,
the VSI switching frequency. For implementation these Using these definitions, the equations ( 5 ) - (7) can be
quantities must be converted into a modulation index, expressed as
ma, and phase, 6, as per equation (8). The modulation
j , = f(x, U, d , t ) . (9)
index and phase should however not be directly used
as system inputs as this would unnecessarily introduce from which the linearized equations are readily deter-
additional nonlinearities into they system equations. mined using the Jacobian. The resulting linearized ma-
trix equation is given by
x = Ax + Buf Ed. (10)
Since the equations are based on the Jacobian evaluated
(IC is a constant whose amplitude depends on the mod- at a particular operating point, they only accurately rep-
ulation technique used) resent the system at, or in the vicinity of, this point. As
1380

will be seen later however, the application of high gain Ed


feedback t o the system will help minimize the effect of
nonlinearities which in turn results in a very low sensi-
n
tivity t o variations in the selected operating point. X
r
3. Eigenstructure Assignment
Given the linearized equations, a full state feedback
gain matrix can be designed based on the principle of Fig. 2. Block diagram of the STATCOM with full state feedback
complete eigenstructure assignment [ 5 ] . Eigenstructure applied
assignment is made possible by the fact that a single
input is generally sufficient to place the closed loop sys- Applying full state feedback t o the system and allow-
tem poles a t a desired location. In cases where more ing for an external reference input x, yields the block
than one input is available it is often possible t o stip- diagram shown in Figure 2 . The corresponding system
ulate further design criteria. For the two input system equation, (12), is obtained by letting U = -K(x - x,).
of the VSI, it is in fact possible to define both closed
loop pole locations of the linearized model, as well as t o k = A x - BK(x - x T ) + E d (12)
completely decouple the ac reactive current from the dc
It is worth mentioning that the identical feedback ma-
capacitor voltage and the d-axis current.
trix, K, could have been obtained by taking an optimal
Naturally pole locations must be chosen wisely and control approach, with the appropriate state and in-
can clearly not be selected beyond the limitations im- put weights. The eigenstructure assignment technique
posed by the transport delay of the inverter. In addition, however, avoids the task of explicitly specifying these
if a large dc capacitor is used, then the mode associated weights, and instead allows the closed loop dynamics t o
with the capacitor voltage must be kept slow. If the be manipulated more directly.
capacitor pole is placed too far into the left hand plane,
then excessively large charging/discharging currents will C. Elimination of Steady State Errors
result when the dc voltage reference is changed or the
The dynamics of the VSI are determined by the con-
voltage is disturbed.
stant state feedback resulting from the eigenstructure
Since the mode associated with the capacitor volt-
assignment. Even in the case of a linear system, full
age may be up to an order of magnitude slower than
state feedback does not necessarily guarantee a step re-
the desired response speed of the reactive current con-
sponse with zero steady state error. For linear systems,
troller, it is clearly important for the eigenstructure t o
however, these errors can be entirely eliminated by ap-
be such, that this mode doesn’t appear in i,. This is a
propriate feedforward. While the nonlinearity of the
dynamic constraint and can therefore only be achieved
VSI equations prevents exact elimination of its steady
by eigenstructure assignment, since quasi-steady state
state error, the linearized equations can be used to give a
assumptions do not hold in this time frame.
first order approximation to the amount of feedforward
In addition t o this constraint, it is also desired that
which should be applied.
the system display no oscillatory behaviour and be well
The feedforward term is added to the system input,
damped. This is accomplished by ensuring the closed
yielding a new input to the VSI.
loop eigenvalues lie on the negative real axis. Due t o
the nature of the system equations it is possible t o meet =v - K(x - x,)
U (13)
all of these constraints simply by selecting the system
poles t o be at {-A,-A, -7). The single pole at -11, Since the external input v is not a function of the
corresponding t o the charging and discharging of the state, its introduction affects only the steady state and
capacitor, would generally be the nearest to the origin. not the dynamic system performance. In the steady
Employing these pole locations results in a closed loop state, all state derivatives are zero. If zero steady state
system disturbance response which has the form error is desired then x = x, and

0 AX, + Bv, - BK(x - x,) + E d . (14)


Since the number of states exceeds the number of in-
puts, the matrix B is not invertible and it is not possible
The reactive current response therefore has a time t o specify an arbitrary steady state x, and find the as-
constant determined purely by the selected pole loca- sociated input. Only certain states can be reached by
tion -A. This pole can be moved as far into the left the application of a constant input.
hand plane as the transport delay of the inverter per- It is, however, not our intention t o regulate all three
mits. X can be of the order of half the inverter switching system states. While the dc bus voltage and the reac-
frequency (A x f,/2). tive current, must be controlled to their reference input
1381

vdues, the d-axis current may take on whatever value


necessary to achieve these two references. As a result,
equation (14) can be reformulated to solve for the two
inputs and the d-axis current which will yield the de-
sired steady state dc bus voltage and reactive current.
This is accomplished by partitioning of the A matrix.

While the small signal input to the actual VSI is given


by (13), only two state reference values, the reactive cur-
rent, x z r , and dc capacitor voltage, xgr, are external in-
Fig. 3. The experimental setup.
puts. The remaining reference quantities are calculated
according to equation (15). The final block diagram of
the closed loop system with feedforward is the same as notch filter must be employed in the feedback path. In
Figure 2 except with the input v, added to summing addition, a certain degree of low pass filtering is also
junction C2. necessary due to anti-aliasing and noise constraints. As
Indeed it may be seen that model errors stemming a result, the dynamics of the voltage control loop will
from inexact representation of the inverter switching primarily be dictated by the bus voltage filters in the
losses or errors in the parameter values used are not feedback path.
compensated for. These errors are small however, since In spite of the detailed nature of the STATCOM
all VSI components values can be directly measured, model, augmenting the STATCOM model with the AC
and do not change. Contrary to the VSI parameter val- system model does not, in general, lead to improved PI
ues, all ac system parameters have been neglected from voltage controller designs. This is a consequence of the
the analysis. While their effect on the dynamic sys- wide variation in AC system configuration which may
tem performance should not be overlooked, inclusion of exist.
the term Ed in equation (15) eliminates their effect on
IV. EXPERIMENTAL SETUP
steady state quantities.
The proposed control was designed analytically and
D. AC Voltage Control then tested by digital simulation. The simulation model
Traditional techniques are used for ac voltage ampli- employed the nonlinear system equations (5) - (7) in
tude regulation. For high voltage transmission level ap- addition to a second order Pad6 approximation of the
plications where no particular load or load area is com- inverter transport delay. After rigorous simulation tests
pensated for, the only manner of voltage regulation is were performed, the control was implemented on a 5kVA
through the introduction of a PI voltage control loop. laboratory model. Figure 3 shows a schematic of the
Such a control loop has a relatively slow response, in the experimental setup.
order of one or even two cycles. While this may seem Both the system and STATCOM parameter values
extremely slow, the entire philosophy behind VAR com- used are given in the table below.
pensation for voltage support is based on quasi-steady STATCOM
state arguments and it is therefore impossible to achieve kVAb = 5 kVA
response times of much less than a cycle. vb = 110 v vb 110 v
For PI voltage controller design, a simplified STAT-
COM model can be employed. By referring back t o
equation ( l l ) , it can be inferred that the reactive cur- C = 4900 DF V, = 118 V
rent of the STATCOM has the same impulse response as
+
the transfer function 1/(Xs 1). In addition, from pha- Control of the STATCOM is performed by a 50MHz
sor analysis, the effect of a reactive current injection on DSP, while the actual inverter gating signals are calcu-
the magnitude of the local bus voltage can be approx- lated in an FPGA. Sinusoidal PWM is employed in the
imated by AlVl M X J , , where X, is the equivalent experimental setup with a carrier frequency of 2880 Hz.
system reactance at the bus. Employing these relations The carrier frequency was selected to give the SPWM
allows the PI voltage controller to be designed using inverter the same transport lag as would exist in a 48
traditional transfer function based control techniques. pulse application. A vector control scheme with a 1440
Since it is important that minor bus voltage imbalance Hz switch frequency would exhibit the same lag.
not result in a STATCOM reference reactive current Independent of the switching strategy that is adopted,
with a second harmonic component, a second harmonic the dynamics of the system are primarily dictated by the
1382

4
3
0
- - $
3
4O
72
J -1
0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04
1.
h
3
n

.-
-1 -I

0 0005 001 0015 002 0025 003 0035 0.04 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04
1321 1.321

~I,,/ , , , , , , , { 1.
1.240 0.005 0.01 0.015 002 0025 0.03 0035 0.04
1.24
0 0.005 0.01 0.015 0 02 0.025 0.03 0.035 0.04
time (s) time (s)

Fig. 4. System response to a change in the reference reactive Fig. 5 . System response to a change in the reference reactive
power command from -0.5 to +0.5pu. power command from $0.5 to - 0 . 5 ~ ~ .

number of discrete voltage vectors which can be imple- h 05


mented in one period. The specific strategy used pre-
dominantly affects only steady state conditions, such as
the harmonic spectra of the voltage and current wave-
forms. 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04

The controller was designed to yield closed loop poles


of (-1800, -1800, -400) when the reactive current is
zero, the dc capacitor voltage is at its nominal value
of 1.277pu, and the ac bus voltage is at 1 . 0 3 ~ ~ . .e451
0
,
0.005
,
0.01
,
0.015
,
0.02
,
0.025
I

0.03
,
0.035
4
0.04
V. EXPERIMENTAL RESULTS
1.32r
1-
' r - - - - - l

The inner control loop which regulates the STAT- h


3 13-
Q
% J-
COM states is first tested. The objective is to follow I; 28:
a reactive current reference command, i,, , while main- p 126-
taining the dc link voltage at a fixed value stipulated 124l I
0 0.005 0.01 0.015 0.02 0.@5 0.03 0.035 0.04
by ?Jdcr. Figure 4 shows the STATCOM response t o a time (s)
step change in the reactive current command from neg-
ative half rated, to positive half rated current. Figure 5 Fig. 6. System response to a step change in the dc load current
from 0 to f0.46pu.
shows the same step change, in the opposite direction.
Real and reactive currents as well as the dc voltage are
all show=, along with their reference values. a 2.3 kW load is switched in across the dc capacitor of
It is apparent from the traces that the lack of an in- the 5 kVA inverter. The resulting transient response is
tegral component in the control loop results in steady depicted in Figure 6. The closed loop system dynamics
state errors in the reactive current which are too small can clearly be seen in this figure. The real ac current
t o be distinguished from background noise. Only in the which is comprised of two components, as per equation
dc capacitor voltage can a slight steady state error be (ll),rapidly equalized the power imbalance. This is
seen. This can be distinguished only because the volt- accomplished with a time constant of 1 / X In addition
age is very stable and noise levels axe low. Appropriate the slower mode, with time constant 1/77, charges the
' capacitor back to its pre-disturbance level.
selection of the pole location associated with the dc ca-
pacitor voltage can easily maintain steady state error It should be realized that the existence of a dc volt-
well below 1%of the reference dc voltage level. age sag under these circumstances is unavoidable. This
One additional test is performed on the inner control results from the fact that the dc current from the capac-
loop. Although in STATCOM applications there is no itor t o the load can be instantaneously varied while the
external drain on the dc capacitor voltage, in UPFC and reactance on the ac side of the inverter impose a con-
other applications this is not the case. A comprehensive straint on the maximum rate of change of current into
control strategy should therefore be capable of rejecting the inverter.
such disturbances t o the dc bus. In order to test this Aside from keeping the dc voltage sag small, it is here
1383
1.03 I I

’ 3i 0.97
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2

S
Q
v

.-d-1 Iqr
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2

h
1
7
Q
v
. . . . . . . . . . . . . . . . . . . . . . . .
e o .......................

.-G-1
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
time (s) time (s)
Fig. 7. Response of the voltage controller to tripping of a feeder Fig. 8. Response of the voltage controller to tripping of a load
(SI opens). (S3 opens).

very clearly seen from the traces that the controller also with the actual FACTS equipment were needed in the
decouples the reactive current regulation from both dc design, i.e. the transformer impedance, the dc capacitor
bus voltage and d-axis current variations. value and an approximate model of the inverter losses.
As already stated in Section 111, an external voltage This evokes two questions regarding the dynamic per-
control loop can be introduced to regulate the ac bus formance of the closed loop system:
voltage amplitude. Ac bus voltage variations can result 1) how does the operating point affect the dynamics
from either changes in source or load configurations, and 2) how does the introduction of, and variations in, the
both these scenarios are investigated. Referring back t o ac system impedance affect the dynamics.
Figure 3, it can be seen that two similar feeders as well Clearly the test cases presented show that the closed
as two separate loads are connected to the STATCOM loop dynamic performance of the STATCOM is excel-
bus through breakers (5’1t o 5’4). lent at least under certain system conditions. Also, the
Figure 7 depicts the transient response of the system test cases were chosen to be representative of the types
when one of the two feeder trips off (SIopens) while of disturbances a STATCOM might be subject t o in the
supplying both loads. The droop characteristic of the field. Nonetheless, neither of these facts ensures that the
voltage controller results in the post-event ac voltage system even remains stable under other, untested condi-
being somewhat lower than the reference, while the pre- tions. To resolve this uncertainty, a root locus approach
event voltage was somewhat higher. It is clear that this is used which can at least ensure whether the system is
scenario represents a case where the impedance between stable in some range about an operating point.
the ideal ac system voltage and the STATCOM termi- Consider first how the operating point affects the
nals changes rather dramatically. This change, however, closed loop system dynamics. The operating point of
seems t o have little effect on the closed loop performance the STATCOM is uniquely d e h e d if the steady state
of the STATCOM. ac bus voltage amplitude, dc bus voltage amplitude and
The last test performed is that of a tripping of a part the reactive current are known. Neither the ac nor the
of the load. Figure 8 show the transient response to the dc voltages vary more than a few percent from their
tripping off of the 6kVA load. Performance similar t o nominal values, due to practical constraints. The effects
that of the last case is seen. of variations in these quantities on the system dynamics
are therefore secondary to the effect of reactive current
VI. DISCUSSION OF RESULTS changes. Applying the fixed linear controller designed in
As demonstrated by the experimental results, the in- Section I11 t o the open loop nonlinear system equations,
ner STATCOM control loop appears to function nearly yields the set of closed loop nonlinear equations. Lin-
identically under all conditions. This seems counter- earizing these new equations about i, = 0 yields closed
intuitive since the controller is designed based only on loop eigenvalues which are located at the specified lo-
a linearization about one specific operating point. Also, cations (since this is the operating point for which the
with exception of the PI voltage controller, the entire feedback matrix was designed). Due to the nonlinear-
control structure was designed without the knowledge ity of the equations, however, at other values of reactive
of ac system parameters under either nominal or contin- current the eigenvalues are not at the same location.
gency conditions. Only the parameter values associated Figure 9 gives the root locus as the reactive current
1384

system in any way, since the poles basically remain on


- m
the real axis. It should be noted that the transient re-
2- 50-
sults of Figures 4 to 6 were all carried out with an ac
system impedance of 0 . 1 6 ~ and
~ therefore already re-

-4
;
a
m
O- i flect the associated rightward shift of the system roots.
In addition it should be mentioned that it is better for
.4
s -=O the system poles to move towards the right rather than
the left due t o the introduction of ac system reactance,
since a leftward movement of the poles would cause the
transport delay of the inverter to become problematic.
Fig. 9. Root locus as the reactive current increases from -1 to 1
pu (note unequal axis scaling). VII. CONCLUSIONS
The linearized dq-frame model is used to design a
multi-variable control for STATCOM and UPFC ap-
plications. Complete eigenstructure assignment is em-
ployed t o ensure reactive current regulation is dynami-
cally decoupled from the other system states, while the
required feedforward terms are found for elimination of
steady state errors.
Experimental tests on a 5kVA laboratory STATCOM
demonstrated that the resulting closed loop system dis-
played rapid and well damped response under all system
conditions. Root locus analysis verified that the closed
Fig. 10. Root locus as the system reactance increases from 0 to
0.2pu, with i, = 0 (note unequal axis scaling). loop VSI dynamic performance could be made nearly
independent of both operating point and ac system pa-
rameter values by appropriate controller design.
is varied from -1pu t o i-lpu. As can be seen, the closed
loop dynamics vary only slightly with the changing op-
erating point. This is a result of the high feedback
ACKNOWLEDGMENTS
gain minimizing the effect of the nonlinearity in the sys- The authors would like to acknowledge the contribu-
tem equations. Since the poles remain very near the tions of Dr. R. Bonert and Mario Schwegmann whose
help made the experimental validation possible.
real axis, the desired nonoscillatory system behaviour is
maintained, independent of reactive current. References
To ensure that ac system parameter variations also [l] L. Gyugyi, “Dynamic compensation of ac transmission lines
by solid-state synchronous voltage sources,” IEEE n u n s . o n
don’t adversely affect the closed loop STATCOM dy- PWRD, vol. 9, p&. 904-911, April 1994.
namics, an additional root locus analysis is performed. [2] R. MihaliE, P. Zunko, I. PapiE, and D. Povh, “Improve-
The system of Figure 3 is again used, with switches ment of transient stability by insertion of FACTS devices,”
in I E E E / N T U A Athens Power Tech Conference Proceedings,
SI,S3 and S4 open. Assuming that the XIR ratio of pp. 521-525, September 1993.
the ac system stays approximately constant, the system 131 C. Schauder and H. Mehta, ‘‘Vector analysis and control
impedance is allowed t o vary from 0 to 0.2~14while the of advanced static VAR compensators,” IEE Proceedings-C,
vol. 140, pp. 299-306, July 1993.
reactive current supplied by the STATCOM is held at [4] C. Schauder et al., “Operation of &lo0 W A R TVA STAT-
zero. It should be expected that such a parameter vari- CON,” I E E E P E S Winter Power Meeting, February 1997.
ation move both open and closed loop system poles, but [5] J. D’Azzo and C. Houpis, Linear Control System Analysis and
Design. New York: McGraw-Hill, 1995.
t o varying degrees. In addition, the voltage at the ac sys- [6] P. Vas, Vector Control of A C Mnchines. New York: Oxford
tem bus which the STATCOM transformer is connected University Press, 1990.
to, will no longer be constant. As a result this parame- [7] V. Blasko and V. Kaura, “A new mathematical model and
control of a three-phase ac-dc voltage source converter,” IEEE
ter variation also causes a slight shift in operating point T r a n s . on Power Electronics, vol. 12, pp. 116-123, January
which must also be accounted for. It is assumed that 1997.
the voltage behind the system’s transient reactance is P.W. Lehn received the B.Sc. and M.Sc. degrees in electrical
constant. engineering from the University of Manitoba in 1990 and 1992.
From 1992 until 1994 he was employed by the Network Planning
The case where the system reactance is zero corre- Group of Siemens AG, in Erlangen, Germany. He is presently a
sponds t o roots lying a t the locations specified by the Ph.D. candidate in the Department of Electrical and Computer
pole placement (since ac system reactance was neglected Engineering at the University of Toronto.
M.R. Iravani received his B.Sc. degree in electrical engineering
in the pole placement). As the system reactance in- in 1976 from Tehran Polytechnique University and started his ca-
creases, the poles move as shown in Figure 10. In this reer as a consulting engineer. He received his M.Sc. and Ph.D.
degrees also in electrical engineering from the University of Man-
case the two poles which were placed in the fax left hand itoba, Canada in 1981 and 1985 respectively. Presently he is a
plane move towards the origin somewhat. This does professor a t the University of Toronto. His research interests in-
slow the dynamics a little, but does not destabilize the clude power electronics and power system dynamics and control.

S-ar putea să vă placă și