DIRECT DRIVEN
DIRECT DRIVEN
Series TDA-V
Features
For commercial and industrial applications where large
volumes of air are required at moderate to high pressure,
special designed integral straightening vanes, reduced
turbulence, provide high performance and low sound level.
Construction
Double flanged casing is produced in mild steel or
galvanised Steel, the impeller having manually adjustable
pitch aerofoil blades is made of PPG, PAG or Aluminium.
Finish
Available in standard finishes of galvanisation or painting.
Operating Temperature
-20°C to +55°C
Motors
Totally enclosed Class ‘F’ motor, to a min. IP54 protection
are fitted as standard. Standard motor up to 2.2kW are
usually supplied on DOL starting, motor 3.0kW and above
are star/delta starting.
Airflow Direction
Kruger Ventilation Industries Pte Ltd certifies that the TDA 315-V shown
herein is licensed to bear the AMCA Seal. The ratings shown are based on Air flowing from impeller to motor is fitted as standard.
tests and procedures performed in accordance with AMCA publication 211
and comply with the requirements of the AMCA Certified Ratings Program.
100 63
62
61 63
γ=1.22kg/m3 60
80 60 62
Total Pressure (Pa)
62
58 60
60
62
64
40 61 62
59 64 44°
42°
58 40°
38°
61 36°
20 34°
32°
58 30°
28°
56 26°
22° 24° Lw(A) [dB(A)]
20°
0
0.08
44°
Absorbed Power (kW)
0.06 40°42°
38°
34° 36°
32°
30°
0.04 28°
24° 26°
22°
20°
0.02
0.00
80
70
Total Efficiency (%)
60
50
40
30 44°
38° 40°42°
20
32° 34° 36°
28° 30°
10 24° 26°
20° 22°
0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 Q [m3/s]
V [m/s]
0 1 2 3 4 5 6 7 8
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings applies to air performance only. dBA levels are not licensed by AMCA international.
TDA 315-V / 12AA/ 5-5/ _ _ / _
2850rpm - 50Hz
450
400
80
78
350 γ=1.22kg/m3 80
78
77
Total Pressure (Pa)
300 79
79
250 77
75
79
200
81
78 79
150
76 44°
81 42°
75 40°
100 78 38°
36°
34°
75
32°
30°
50 73 28°
24° 26°
20° 22° Lw(A) [dB(A)]
0
0.8
Absorbed Power (kW)
0.6
44°
42°
38°40°
0.4 34° 36°
32°
28° 30°
24° 26°
0.2 20° 22°
0.0
80
70
Total Efficiency (%)
60
50
40
30 44°
42°
36°38°40°
20 34°
30° 32°
10 26° 28°
24°
20° 22°
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 Q [m3/s]
V [m/s]
0 2 4 6 8 10 12 14 16
- Performance shown is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings applies to air performance only. dBA levels are not licensed by AMCA international.
TDA 315-V / 12AA/ 5-5/ _ _ / _
1750rpm - 60Hz
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 Q [m3/s]
200
180
160
68
140 γ=1.22kg/m3
67
66 68
Total Pressure (Pa)
120 65
65
67
67
100
65
63
80 67
69
60 66 67
64 69 44°
42°
40 63 40°
38°
66 36°
34°
32°
63 30°
20 28°
61 26°
24°
20° 22° Lw(A) [dB(A)]
0
0.15
Absorbed Power (kW)
0.12 44°
42°
40°
38
0.09 34° 36°
32°
30°
28°
26°
0.06 24°
20° 22°
0.03
0.00
80
70
Total Efficiency (%)
60
50
40
30
42° 44°
38° 40°
20 34° 36°
30° 32°
10 26° 28°
24°
20° 22°
0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 Q [m3/s]
V [m/s]
0 2 4 6 8 10
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings applies to air performance only. dBA levels are not licensed by AMCA international.
TDA 315-V / 12AA/ 5-5/ _ _ / _
3450rpm - 60Hz
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 Q [m3/s]
700
600
84
83
500 83 84
γ=1.22kg/m3
81 83
Total Pressure (Pa)
83
400
81
79
83
300
85
82
83
200 44°
80 85
40°42°
79 38°
82 36°
34°
100 79
32°
30°
28°
24° 26°
77
1.0
Absorbed Power (kW)
44°
0.8 40° 42°
38°
36°
34°
32°
0.6
28° 30°
26°
24°
0.4 20° 22°
0.2
0.0
80
70
Total Efficiency (%)
60
50
40
30 44°
38° 40° 42°
20 34° 36°
30° 32°
10 24° 26° 28°
20° 22°
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 Q [m3/s]
V [m/s]
0 2 4 6 8 10 12 14 16 18 20
- Performance shown is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings applies to air performance only. dBA levels are not licensed by AMCA international.
DIRECT DRIVEN
Series TDA-V
Features
For commercial and industrial applications where large
volumes of air are required at moderate to high pressure,
special designed integral straightening vanes, reduced
turbulence, provide high performance and low sound level.
Construction
Double flanged casing is produced in mild steel or
galvanised Steel, the impeller having manually adjustable
pitch aerofoil blades is made of PPG, PAG or Aluminium.
Finish
Available in standard finishes of galvanisation or painting.
Operating Temperature
-20°C to +55°C
Motors
Totally enclosed Class ‘F’ motor, to a min. IP54 protection
are fitted as standard. Standard motor up to 2.2kW are
usually supplied on DOL starting, motor 3.0kW and above
are star/delta starting.
Airflow Direction
Kruger Ventilation Industries Pte Ltd certifies that the TDA 355-V shown
herein is licensed to bear the AMCA Seal. The ratings shown are based on Air flowing from impeller to motor is fitted as standard.
tests and procedures performed in accordance with AMCA publication 211
and comply with the requirements of the AMCA Certified Ratings Program.
* All Dimension in mm
355
8° x Ø10
Ø355
Ø395
Ø435
140 68 68
65 65 67
120
64
γ=1.22kg/m3 65 68
100 64 66
Total Pressure (Pa)
64
66
80
65
60 67
63
66 44°
42°
40°
40 38°
66 36°
34°
64 32°
61
30°
20 28°
26°
24°
Lw(A) [dB(A)]
0
0.20
Absorbed Power (kW)
0.15
44°
42°
40°
36° 38°
32° 34°
0.10 30°
28°
26
24°
0.05
0.00
80
70
Total Efficiency (%)
60
50
40
44°
30 42°
38° 40°
20 34° 36°
30° 32°
28°
10 24° 26°
0
0.0 0.2 0.4 0.6 0.8 1.0 Q [m3/s]
V [m/s]
0 2 4 6 8 10
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
TDA 355-V / 12AA/ 5-5/ _ _ / _
2850rpm - 50Hz
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 Q [m3/s]
700
600
85
85
500
γ=1.22kg/m3 82 82
84
81 85
82
Total Pressure (Pa)
400
83
81
83
81
300
82
80 84
200 44°
83 42°
40°
38°
83 36°
34°
81 32°
100 30°
78 28°
26°
24°
Lw(A) [dB(A)]
0
1.5
Absorbed Power (kW)
1.2
44°
38° 40°42°
0.9 34° 36°
32°
30°
28°
0.6 26°
24°
0.3
0.0
80
70
Total Efficiency (%)
60
50
40
44
30
38° 40°42°
34° 36°
20
30° 32°
28°
10 24° 26°
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 Q [m3/s]
V [m/s]
0 5 10 15 20
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international.
TDA 355-V / 12AA/ 5-5/ _ _ / _
1750rpm - 60Hz
240
220
73
200 73
70
180 γ=1.22kg/m3 70 72
69
70 73
160
Total Pressure (Pa)
69 71
140
69 71
120
70
100
72
80 68
44°
71 42°
60 40°
38°
71 36°
34°
40
69 32°
66 30°
28°
26°
20 24
Lw(A) [dB(A)]
0
0.30
0.25
Absorbed Power (kW)
42°44°
38°40°
0.20 34° 36°
32°
30°
28°
0.15 26°
24°
0.10
0.05
0.00
80
70
Total Efficiency (%)
60
50
40
30 42°44°
38° 40°
20 34° 36°
32°
28° 30°
10 24° 26°
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 Q [m3/s]
V [m/s]
0 2 4 6 8 10 12
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international.
TDA 355-V / 12AA/ 5-5/ _ _ / _
3450rpm - 60Hz
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 Q [m3/s]
1000
900
800
89 89
86
700 γ=1.22kg/m3 86 88
85
86 89
Total Pressure (Pa)
600
85 87
500 85 87
400 86
88
300 84
44°
87 42°
40°
38°
87 36°
200 34°
85 32°
30°
82 28°
100 26°
24°
Lw(A) [dB(A)]
0
2.4
2.0
Absorbed Power (kW)
44°
42°
1.6 36 38° 40°
32° 34°
30°
1.2 28°
26°
24°
0.8
0.4
0.0
80
70
Total Efficiency (%)
60
50
40
44°
30 40° 42°
34° 36° 38°
20 32°
28° 30°
10 24° 26°
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 Q [m3/s]
V [m/s]
0 5 10 15 20
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
DIRECT DRIVEN
Series TDA-V
Features
For commercial and industrial applications where large
volumes of air are required at moderate to high pressure,
special designed integral straightening vanes, reduced
turbulence, provide high performance and low sound level.
Construction
Double flanged casing is produced in mild steel or
galvanised Steel, the impeller having manually adjustable
pitch aerofoil blades is made of PPG, PAG or pressure-
casted Aluminium.
Finish
Available in standard finishes of galvanisation or painting.
Operating Temperature
-20°C to +55°C
Motors
Totally enclosed Class ‘F’ motor, to a min. IP54 protection
are fitted as standard. Standard motor up to 2.2kW are
usually supplied on DOL starting, motor 3.0kW and above
are star/delta starting.
Kruger Ventilation Industries Pte Ltd certifies that the TDA 400-V shown
herein is licensed to bear the AMCA Seal. The ratings shown are based on
Airflow Direction
tests and procedures performed in accordance with AMCA publication 211
and comply with the requirements of the AMCA Certified Ratings Program.
Air flowing from impeller to motor is fitted as standard.
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Q [m3/s]
100
90
69
80
71
70 γ=1.22kg/m3 68
68
Total Pressure (Pa)
60 65 69
67
50 65
67
62
61 71
40
67
67
42°
30 71 40°
62 38°
36°
68 34°
20 32°
30°
62 28°
26°
61 24°
10 22°
20°
18°
Lw(A) [dB(A)]
0
0.10
42°
Absorbed Power (kW)
0.08 40°
38°
36°
34°
0.06
32°
30°
0.04
28°
26°
24°
0.02 22°
20°
18°
0.00
80
70
Total Efficiency (%)
60
50
40
26° 42°
30 18° 20° 22° 24° 28° 30° 32° 34° 36° 38° 40°
20
10
0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Q [m3/s]
V [m/s]
0 1 2 3 4 5 6 7
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (KW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international.
TDA 400-V / 12AA/ 5-5/ _ _ / _
1450rpm - 50Hz
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 Q [m3/s]
250
200
80
73
γ=1.22kg/m3 79
79
Total Pressure (Pa)
150
81
78
78
78
77
73
100
72 83
79
78
42°
73 83 40°
38°
36°
50 79 34°
32°
30°
73 28°
26°
72 24°
22°
20°
18° Lw(A) [dB(A)]
0
0.4
Absorbed Power (kW)
42°
0.3 40°
38°
36°
34°
0.2 32°
30°
28°
0.1 26°
24°
22°
20°
18°
0.0
80
70
Total Efficiency (%)
60
50
40
24° 26° 28° 40° 42°
30 18° 20° 22° 30° 32° 34° 36° 38°
20
10
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 Q [m3/s]
V [m/s]
0 2 4 6 8 10 12
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (KW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international.
TDA 400-V / 12AA/ 5-5/ _ _ / _
2850rpm - 50Hz
800
97
700
100
γ=1.22kg/m3 96
600
97
99
Total Pressure (Pa)
500 99
96 96
94
400 91 102
89
96
300 97
42°
102 40°
90 38°
36°
200 97 34°
32°
30°
90 28°
26°
100 89
22° 24°
18° 20°
Lw(A) [dB(A)]
0
3.0
2.5
Absorbed Power (kW)
42°
40°
2.0 38°
36°
34°
1.5 32°
30°
1.0 28°
26°
24°
0.5 22°
18° 20°
0.0
80
70
Total Efficiency (%)
60
50
40
24° 26° 28° 40° 42°
30 18° 20° 22° 30° 32° 34° 36° 38°
20
10
0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 Q [m3/s]
V [m/s]
0 5 10 15 20
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (KW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international.
TDA 400-V / 12AA/ 5-5/ _ _ / _
1150rpm - 60Hz
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 Q [m3/s]
140
74
120
76
100 73
γ=1.22kg/m3 73
75
71
Total Pressure (Pa)
80
72
71 72
67 76
60
66
72 72
42°
77 40°
67 38°
40
36°
73 34°
32°
30°
67 28°
20 26°
66 24°
22°
20°
18°
Lw(A) [dB(A)]
0
0.20
Absorbed Power (kW)
42°
0.15 40°
38°
36°
34°
0.10 32°
30°
28°
0.05 26°
24°
22°
18° 20°
0.00
80
70
Total Efficiency (%)
60
50
40
26° 42°
30 18° 20° 22° 24° 28° 30° 32° 34° 36° 38° 40°
20
10
0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 Q [m3/s]
V [m/s]
0 2 4 6 8 10
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (KW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international.
TDA 400-V / 12AA/ 5-5/ _ _ / _
1750rpm - 60Hz
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 Q [m3/s]
320
85
280
87
240
84
γ=1.22kg/m3 84
86
200 83
Total Pressure (Pa)
83
82 83
160
78
77 88
120 83
83
42°
89 40°
78 38°
36°
80 84 34°
32°
30°
78 28°
26°
40 76 24°
22°
20°
18°
Lw(A) [dB(A)]
0
0.7
0.6
Absorbed Power (kW)
42°
0.5 40°
38°
36°
0.4 34°
32°
0.3 30°
28°
0.2
26°
24°
0.1 20° 22°
18°
0.0
80
70
Total Efficiency (%)
60
50
40
26° 42°
40°
30 18° 20° 22° 24° 28° 30° 32° 34° 36° 38°
20
10
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 Q [m3/s]
V [m/s]
0 2 4 6 8 10 12 14
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (KW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international.
TDA 400-V / 12AA/ 5-5/ _ _ / _
3450rpm - 60Hz
0.0 0.4 0.8 1.2 1.6 2.0 2.4 2.8 3.2 3.6 Q [m3/s]
1300
1200
1100 102
1000
105
100
900 γ=1.22kg/m3
102
800 104
Total Pressure (Pa)
104
700 100
99 101
600
96
94 106
500
100
102 42°
400 108 40°
95
38°
36°
300 102 34°
32°
30°
95 28°
200
26°
94 24°
22°
100 18° 20°
Lw(A) [dB(A)]
0
5.0
42°
Absorbed Power (kW)
4.0 40°
38°
36°
3.0 34°
32°
30°
2.0
28°
24° 26°
1.0 22°
20°
18°
0.0
80
70
Total Efficiency (%)
60
50
40
24° 26° 28° 30° 40° 42°
30 18° 20° 22° 32° 34° 36° 38°
20
10
0
0.0 0.4 0.8 1.2 1.6 2.0 2.4 2.8 3.2 3.6 Q [m3/s]
V [m/s]
0 5 10 15 20
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (KW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international.
DIRECT DRIVEN
Series TDA-V
Features
For commercial and industrial applications where large
volumes of air are required at moderate to high pressure,
special designed integral straightening vanes, reduced
turbulence, provide high performance and low sound level.
Construction
Double flanged casing is produced in mild steel or
galvanised Steel, the impeller having manually adjustable
pitch aerofoil blades is made of PPG, PAG or pressure-
casted Aluminium.
Finish
Available in standard finishes of galvanisation or painting.
Operating Temperature
-20°C to +55°C
Motors
Totally enclosed Class ‘F’ motor, to a min. IP54 protection
are fitted as standard. Standard motor up to 2.2kW are
usually supplied on DOL starting, motor 3.0kW and above
are star/delta starting.
Kruger Ventilation Industries Pte Ltd certifies that the TDA 450-V shown
herein is licensed to bear the AMCA Seal. The ratings shown are based on
Airflow Direction
tests and procedures performed in accordance with AMCA publication 211
and comply with the requirements of the AMCA Certified Ratings Program.
Air flowing from impeller to motor is fitted as standard.
90
62 63
80
61
61 62
70 γ=1.22kg/m3 59
58
Total Pressure (Pa)
60
50 57
60
64
40 56 38°
36°
62 34°
30 32°
60 30°
28°
20 56 26°
24°
22°
53 20°
10 18°
16°
Lw(A) [dB(A)]
0
0.15
38°
Absorbed Power (kW)
0.12
36°
34°
32°
0.09
30°
28°
0.06 26°
24°
22°
20°
0.03 18°
16°
0.00
80
70
Total Efficiency (%))
60
50
40 38°
34° 36°
28° 30° 32°
30 26°
24°
20 20° 22°
16° 18°
10
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 Q [m3/s]
V [m/s]
0 1 2 3 4 5 6 7 8
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- dBA levels are not licensed by AMCA International. The AMCA Certified Ratings Seal applies to air performance only.
TDA 450-V / 12AA/ 5-5/ _ _ / _
1450rpm - 50Hz
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 Q [m3/s]
250
200
73
74
72
γ=1.22kg/m3 73
70 72
Total Pressure (Pa)
150
69 71
68
75
100
67 38°
36°
73 34°
32°
71
30°
50 28°
26°
67
24°
22°
64 20°
18°
16°
Lw(A) [dB(A)]
0
0.6
0.5
Absorbed Power (kW)
38°
0.4 36°
34°
32°
0.3 30°
28°
0.2 26°
24°
22°
20°
18°
0.1 16°
0.0
80
70
Total Efficiency (%))
60
50
40 38°
34° 36°
30° 32°
30 28°
24° 26°
20 20° 22°
16° 18°
10
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 Q [m3/s]
V [m/s]
0 2 4 6 8 10 12
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA International.
TDA 450-V / 12AA/ 5-5/ _ _ / _
2850rpm - 50Hz
800
90 91
700 89
90
90
γ=1.22kg/m3 84
600
86
88
Total Pressure (Pa)
500 85
400 84 92
38°
36°
90 34°
300
32°
88
30°
200 28°
84 26°
24°
22°
81 20°
100 18°
16°
Lw(A) [dB(A)]
0
5
Absorbed Power (kW)
38°
3 36°
34°
32°
30°
2 28°
26°
24°
22°
1 18° 20°
16°
0
80
70
Total Efficiency (%))
60
50
40 38°
34° 36°
28° 30° 32°
30 26°
24°
22°
20 20°
16° 18°
10
0
0.0 0.6 1.2 1.8 2.4 3.0 3.6 4.2 Q [m3/s]
V [m/s]
0 5 10 15 20 25
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA International.
TDA 450-V / 12AA/ 5-5/ _ _ / _
1150rpm - 60Hz
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 Q [m3/s]
160
140
120 68
66
γ=1.22kg/m3
67
64 66
100
Total Pressure (Pa)
65
63
80 62
69
60 61 38°
36°
67 34°
32°
40 65 30°
28°
61 26°
24°
20 58
22°
20°
18°
16°
Lw(A) [dB(A)]
0
0.30
0.25
Absorbed Power (kW)
38°
0.20 36°
34°
32°
0.15 30°
28°
0.10 26°
24°
22°
20°
0.05 18°
16°
0.00
80
70
Total Efficiency (%))
60
50
40 38°
36°
34°
30° 32°
30 26° 28°
24°
22°
20 20°
16° 18°
10
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 Q [m3/s]
V [m/s]
0 2 4 6 8 10
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA International.
TDA 450-V / 12AA/ 5-5/ _ _ / _
1750rpm - 60Hz
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 Q [m3/s]
350
300
78
79
77
78
250 75
γ=1.22kg/m3 77
74
Total Pressure (Pa)
76
200
150 80
73
38°
72
36°
78 34°
100 32°
76
30°
28°
72 26°
24°
50 22°
69 20°
18°
16°
Lw(A) [dB(A)]
0
1.0
Absorbed Power (kW)
0.8 38°
36°
34°
0.6 32°
30°
28°
0.4 26°
24°
22°
20°
0.2 18°
16°
0.0
80
70
Total Efficiency (%))
60
50
40 38°
34° 36°
28° 30° 32°
30 26°
24°
20 18° 20° 22°
16°
10
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 Q [m3/s]
V [m/s]
0 2 4 6 8 10 12 14 16
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA International.
TDA 450-V / 12AA/ 5-5/ _ _ / _
3450rpm - 60Hz
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 Q [m3/s]
1300
1200
1100 94 95
93
1000
94
93
91
900 γ=1.22kg/m3
90 92
800
Total Pressure (Pa)
700 89
600 96
88
500 38°
36°
94
34°
400 32°
92 30°
300 28°
88 26°
24°
200 22°
85 20°
18°
100 16°
Lw(A) [dB(A)]
0
8
7
Absorbed Power (kW)
6 38°
36°
5 34°
32°
4 30°
28°
3 26°
24°
22°
2 20°
18°
16°
1
0
80
70
Total Efficiency (%)
60
50
40 38°
34° 36°
28° 30° 32°
30 26°
22° 24°
20 18° 20°
16°
10
0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 Q [m3/s]
V [m/s]
0 5 10 15 20 25 30
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA International.
DIRECT DRIVEN
Series TDA-V
Features
For commercial and industrial applications where large
volumes of air are required at moderate to high pressure,
special designed integral straightening vanes, reduced
turbulence, provide high performance and low sound level.
Construction
Double flanged casing is produced in mild steel or
galvanised Steel, the impeller having manually adjustable
pitch aerofoil blades is made of PPG, PAG or pressure-
casted Aluminium.
Finish
Available in standard finishes of galvanisation or painting.
Operating Temperature
-20°C to +55°C
Motors
Totally enclosed Class ‘F’ motor, to a min. IP54 protection
are fitted as standard. Standard motor up to 2.2kW are
usually supplied on DOL starting, motor 3.0kW and above
are star/delta starting.
Kruger Ventilation Industries Pte Ltd certifies that the TDA 500-V shown
herein is licensed to bear the AMCA Seal. The ratings shown are based on
Airflow Direction
tests and procedures performed in accordance with AMCA publication 211
and comply with the requirements of the AMCA Certified Ratings Program.
Air flowing from impeller to motor is fitted as standard.
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 Q [m3/s]
180
160
67
140
γ=1.22kg/m3
66
68
120 68
Total Pressure (Pa)
68 68
100 68
65 67
68
70 68
80
67
60
69
40 68 34°
32°
30°
67 28°
66 26°
20
67 22° 24°
16° 18° 20° Lw(A) [dB(A)]
14°
0
0.3
Absorbed Power (kW)
0.2 34°
32°
30°
28°
0.1 26°
22° 24°
18° 20°
14° 16°
0.0
80
70
Total Efficiency (%))
60
50
40
30° 32° 34°
30 28°
26°
20 22° 24°
16° 18° 20°
14°
10
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 Q [m3/s]
V [m/s]
0 1 2 3 4 5 6 7 8 9
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
TDA 500-V / 12AA/ 9-9/ _ _ / _
1450rpm - 50Hz
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 Q [m3/s]
400
350
79
300 γ=1.22kg/m3 77
80
80
250 80
Total Pressure (Pa)
79
79
77 79
200 80
81 80
79
150
81
100 79 34°
32°
30°
79 28°
50 77
26°
22° 24°
18° 20°
78
14° 16° Lw(A) [dB(A)]
0
1.0
Absorbed Power (kW)
0.8
34°
32°
0.6
30°
28°
0.4 26°
22° 24°
18° 20°
0.2 14° 16°
0.0
80
70
Total Efficiency (%)
60
50
40
28° 30° 32° 34°
30
26°
24°
20 18° 20° 22°
14° 16°
10
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 Q [m3/s]
V [m/s]
0 2 4 6 8 10 12 14
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
TDA 500-V / 12AA/ 9-9/ _ _ / _
2850rpm - 50Hz
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 Q [m3/s]
1500
97
1200
95
γ=1.22kg/m3 97
97
97
97
Total Pressure (Pa)
900 97
96 97
94
98 97
600 96
98
96 34°
32°
300 30°
95 28°
94
26°
24°
22°
18° 20°
95
14° 16° Lw(A) [dB(A)]
0
0.3
Absorbed Power (kW)
0.2 34°
32°
30°
28°
26°
0.1
22° 24°
18° 20°
14° 16°
0.0
80
70
Total Efficiency (%))
60
50
40
30 28° 30° 32° 34°
26°
22° 24°
20 18° 20°
14° 16°
10
0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 Q [m3/s]
V [m/s]
0 5 10 15 20 25
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
TDA 500-V / 12AA/ 9-9/ _ _ / _
1150rpm - 60Hz
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 Q [m3/s]
250
72
200
71
γ=1.22kg/m3 73
73
73 73
Total Pressure (Pa)
150 73
71 72 73
75 73
100 72
74
73 34°
32°
50 30°
72 28°
71
26°
24°
72 22°
16° 18° 20°
14° Lw(A) [dB(A)]
0
0.3
Absorbed Power (kW)
0.2 34°
32°
30°
28°
0.1 26°
22° 24°
18° 20°
14° 16°
0.0
80
70
Total Efficiency (%))
60
50
40
30 28° 30° 32° 34°
26°
20 22° 24°
16° 18° 20°
14°
10
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 Q [m3/s]
V [m/s]
0 1 2 3 4 5 6 7 8 9 10 11
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
TDA 500-V / 12AA/ 9-9/ _ _ / _
1750rpm - 60Hz
500
84
γ=1.22kg/m3
84
400 84
Total Pressure (Pa)
84 84
83
83
300 82 84
86 84
83
200
85
84 34°
32°
30°
100 83 28°
82 26°
24°
20° 22°
83
1.6
34°
1.2 32°
30°
0.8 28°
26°
24°
22°
0.4 18° 20°
14° 16°
0.0
80
70
Total Efficiency (%))
60
50
40
30 28° 30° 32° 34°
26°
24°
20 20° 22°
14° 16° 18°
10
0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 Q [m3/s]
V [m/s]
0 2 4 6 8 10 12 14 16
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (KW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
DIRECT DRIVEN
Series TDA-V
Features
For commercial and industrial applications where large
volumes of air are required at moderate to high pressure,
special designed integral straightening vanes, reduced
turbulence, provide high performance and low sound level.
Construction
Double flanged casing is produced in mild steel or
galvanised Steel, the impeller having manually adjustable
pitch aerofoil blades is made of PPG, PAG or pressure-
casted Aluminium.
Finish
Available in standard finishes of galvanisation or painting.
Operating Temperature
-20°C to +55°C
Motors
Totally enclosed Class ‘F’ motor, to a min. IP54 protection
are fitted as standard. Standard motor up to 2.2kW are
usually supplied on DOL starting, motor 3.0kW and above
are star/delta starting.
Kruger Ventilation Industries Pte Ltd certifies that the TDA 560-V shown
herein is licensed to bear the AMCA Seal. The ratings shown are based on
Airflow Direction
tests and procedures performed in accordance with AMCA publication 211
and comply with the requirements of the AMCA Certified Ratings Program.
Air flowing from impeller to motor is fitted as standard.
160
71
140 69
γ=1.22kg/m3 70
70
120 69 71
Total Pressure (Pa)
69
100
73 70 71
80
60
71
32°
30°
28°
40 70 26°
24°
70 22°
20°
20 72 18°
16°
12° 14° Lw(A) [dB(A)]
0
0.5
Absorbed Power (kW)
0.4
0.3 32°
30°
28°
26°
0.2 24°
22°
20°
18°
14° 16°
0.1 12°
0.0
80
70
Total Efficiency (%)
60
50
40
32°
28° 30°
30 24° 26°
22°
20°
20
16° 18°
14°
10 12°
0
0.0 0.5 1.0 1.5 2.0 2.5 Q [m3/s]
V [m/s]
0 1 2 3 4 5 6 7 8 9 10
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
TDA 560-V / 12AA/ 9-9/ _ _ / _
1450rpm - 50Hz
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 Q [m3/s]
400
350
83
81
81
300 γ=1.22kg/m3 81
80 82
250
Total Pressure (Pa)
80
80 82
84
200
150
82
32°
30°
100 28°
81 26°
24°
80 22°
50 20°
83
18°
16°
14°
12° Lw(A) [dB(A)]
0
1.5
Absorbed Power (kW)
1.2
32°
30°
0.9 28°
26°
24°
0.6 22°
20°
18°
14° 16°
0.3 12°
0.0
80
70
Total Efficiency (%)
60
50
40 32°
26° 28° 30°
30 24°
22°
20°
20 16° 18°
14°
10 12°
0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 Q [m3/s]
V [m/s]
0 2 4 6 8 10 12 14 16
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
TDA 560-V / 12AA/ 9-9/ _ _ / _
2850rpm - 50Hz
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 Q [m3/s]
1600
1400
100
98
1200 γ=1.22kg/m3 99
99
96 99
1000
Total Pressure (Pa)
96
97 98
800 100
600
98
32°
400 30°
97 28°
26°
97 24°
22°
200 20°
99 18°
16°
12° 14° Lw(A) [dB(A)]
0
12
10
Absorbed Power (kW)
32°
8 30°
28°
6 26°
24°
22°
4 20°
18°
16°
14°
12°
2
0
80
70
60
Total Efficiency (%))
50
40
32°
26° 28° 30°
30 24°
22°
20 20°
16° 18°
14°
10 12°
0
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 Q [m3/s]
V [m/s]
0 5 10 15 20 25 30
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
TDA 560-V / 12AA/ 9-9/ _ _ / _
1150rpm - 60Hz
76
200 75
75
γ=1.22kg/m3 75
74 76
74
Total Pressure (Pa)
150
74 76
78
100
76
32°
30°
75
28°
26°
50 24°
74 22°
20°
77
18°
16°
14°
12° Lw(A) [dB(A)]
0
0.8
0.7
Absorbed Power (kW)
0.6
32°
0.5 30°
28°
0.4 26°
24°
0.3 22°
20°
18°
0.2 14° 16°
12°
0.1
0.0
80
70
Total Efficiency (%)
60
50
40
30° 32°
30 24° 26° 28°
22°
20°
20
16° 18°
14°
10 12°
0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 Q [m3/s]
V [m/s]
0 1 2 3 4 5 6 7 8 9 10 11 12
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
TDA 560-V / 12AA/ 9-9/ _ _ / _
1750rpm - 60Hz
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 Q [m3/s]
600
500 87
86
85
γ=1.22kg/m3
86 87
84
400
Total Pressure (Pa)
84
85 86
300 88
200 86
32°
30°
85 28°
26°
100 24°
85 22°
20°
88 16° 18°
14°
12° Lw(A) [dB(A)]
0
3.0
2.7
Absorbed Power (kW)
2.4
2.1
32°
1.8 30°
28°
1.5 26°
1.2 24°
0.9 20° 22°
18°
16°
0.6 14°
12°
0.3
0.0
80
70
Total Efficiency (%))
60
50
40
32°
28° 30°
30 26°
22° 24°
20 20°
16° 18°
12° 14°
10
0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 Q [m3/s]
V [m/s]
0 5 10 15 20
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA internationa
DIRECT DRIVEN
Series TDA-V
Features
For commercial and industrial applications where large
volumes of air are required at moderate to high pressure,
special designed integral straightening vanes, reduced
turbulence, provide high performance and low sound level.
Construction
Double flanged casing is produced in mild steel or
galvanised Steel, the impeller having manually adjustable
pitch aerofoil blades is made of PPG, PAG or pressure-
casted Aluminium.
Finish
Available in standard finishes of galvanisation or painting.
Operating Temperature
-20°C to +55°C
Motors
Totally enclosed Class ‘F’ motor, to a min. IP54 protection
are fitted as standard. Standard motor up to 2.2kW are
usually supplied on DOL starting, motor 3.0kW and above
are star/delta starting.
Kruger Ventilation Industries Pte Ltd certifies that the TDA 630-V shown
herein is licensed to bear the AMCA Seal. The ratings shown are based on
Airflow Direction
tests and procedures performed in accordance with AMCA publication 211
and comply with the requirements of the AMCA Certified Ratings Program.
Air flowing from impeller to motor is fitted as standard.
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 Q [m3/s]
250
84
82 83
200
γ=1.22kg/m3 79
81
80
Total Pressure (Pa)
150 82
80
77
81
100 78 82
79 40°
78 38°
81 36°
34°
32°
79 30°
50 28°
79
26°
24°
78
22°
20°
18°
16° Lw(A) [dB(A)]
14°
10° 12°
0 8°
1.2
Absorbed Power (kW)
0.9
40°
38°
36°
34°
0.6 32°
30°
28°
26°
24°
0.3 22°
20°
16° 18°
10° 12° 14°
8°
0.0
80
70
Total Efficiency (%)
60
50
40
40°
32° 34° 36° 38°
30 28° 30°
26°
24°
20 20° 22°
18°
10 16°
10° 12° 14°
0 8°
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 Q [m3/s]
V [m/s]
0 3 6 9 12
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
TDA 630-V / 12AA/ 12-12/ _ _ / _
1450rpm - 50Hz
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 Q [m3/s]
600
95
500
93
94
γ=1.22kg/m3
92
400
87 91
92
Total Pressure (Pa)
93
91
300 88
92
89
93
200 89 40°
90 38°
92 36°
34°
32°
30°
90 28°
100 26°
24°
89
22°
20°
18°
16° Lw(A) [dB(A)]
14°
0 8° 10° 12°
4
Absorbed Power (kW)
3 40°
38°
36°
34°
2 32°
30°
28°
26°
24°
1 22°
20°
16° 18°
10° 12° 14°
8°
0
80
70
Total Efficiency (%)
60
50
40 40°
38°
30° 32° 34° 36°
30 28°
26°
20 22° 24°
20°
18°
10 16°
14°
10° 12°
0 8°
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 Q [m3/s]
V [m/s]
0 3 6 9 12 15 18
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
TDA 630-V / 12AA/ 12-12/ _ _ / _
1150rpm - 60Hz
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 Q [m3/s]
360
89
320
87
88
280
γ=1.22kg/m3 85 86
240
85
87
Total Pressure (Pa)
85
200 82
86
160
83
87
83
40°
120 38°
84 86 36°
34°
32°
80 30°
84
28°
26°
24°
40 22°
83 20°
18°
16° Lw(A) [dB(A)]
10° 12° 14°
0 8°
2.0
Absorbed Power (kW)
1.5 40°
38°
36°
34°
1.0 32°
30°
28°
26°
24°
0.5 22°
18° 20°
14° 16°
8° 10° 12°
0.0
80
70
Total Efficiency (%)
60
50
40
38° 40°
30 30° 32° 34° 36°
28°
26°
20 22° 24°
20°
18°
10 16°
14°
8° 10° 12°
0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 Q [m3/s]
V [m/s]
0 3 6 9 12 15
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
TDA 630-V / 12AA/ 12-12/ _ _ / _
1750rpm - 60Hz
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 Q [m3/s]
900
800 99
700 97
γ=1.22kg/m3 98
96 97
600
Total Pressure (Pa)
96
500 97
96
93
96
400
94 97
300 40°
94
93 38°
97 36°
34°
200 32°
30°
95 28°
26°
24°
100 22°
93 20°
18° Lw(A) [dB(A)]
16°
12° 14°
0 8° 10°
6
Absorbed Power (kW)
40°
5 38°
36°
4 34°
32°
30°
3 28°
26°
2 24°
22°
20°
1 16° 18°
10° 12° 14°
8°
0
80
70
Total Efficiency (%)
60
50
40 40°
38°
32° 34° 36°
30 28° 30°
26°
20 22° 24°
20°
18°
10 16°
14°
10° 12°
0 8°
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 Q [m3/s]
V [m/s]
0 3 6 9 12 15 18 21 24
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
DIRECT DRIVEN
Series TDA-V
Features
For commercial and industrial applications where large
volumes of air are required at moderate to high pressure,
special designed integral straightening vanes, reduced
turbulence, provide high performance and low sound level.
Construction
Double flanged casing is produced in mild steel or
galvanised Steel, the impeller having manually adjustable
pitch aerofoil blades is made of PPG, PAG or pressure-
casted Aluminium.
Finish
Available in standard finishes of galvanisation or painting.
Operating Temperature
-20°C to +55°C
Motors
Totally enclosed Class ‘F’ motor, to a min. IP54 protection
are fitted as standard. Standard motor up to 2.2kW are
usually supplied on DOL starting, motor 3.0kW and above
are star/delta starting.
Kruger Ventilation Industries Pte Ltd certifies that the TDA 710-V shown
herein is licensed to bear the AMCA Seal. The ratings shown are based on
Airflow Direction
tests and procedures performed in accordance with AMCA publication 211
and comply with the requirements of the AMCA Certified Ratings Program.
Air flowing from impeller to motor is fitted as standard.
0 1 2 3 4 5 6 Q [m3/s]
350
300 85
84
γ=1.22kg/m3 80
79 85
250
84
79 84
80
78
Total Pressure (Pa)
200 83
80
82
78
150
82
79
40°
81 38°
100 36°
34°
78 32°
30°
79 28°
26°
50 24°
80
22°
20°
18°
16°
Lw(A) [dB(A)]
0
2.5
Absorbed Power (kW)
2.0
40°
38°
1.5 36°
34°
32°
1.0 30°
28°
26°
22° 24°
0.5 20°
16° 18°
0.0
80
70
Total Efficiency (%)
60
50
40
30° 32° 34° 36° 38° 40°
28°
30 22° 24° 26°
16° 18° 20°
20
10
0
0 1 2 3 4 5 6 Q [m3/s]
V [m/s]
0 2 4 6 8 10 12 14
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international.
TDA 710-V / 14AA/ 12-12/ _ _ / _
1450rpm - 50Hz
0 1 2 3 4 5 6 7 8 9 Q [m3/s]
800
700 96
95
600 γ=1.22kg/m3 90 96
95
95
91 90
500 89
Total Pressure (Pa)
94
91
93
400
89
300 93
90
40°
92 38°
36°
34°
200 89 32°
30°
28°
90 26°
24°
100 90 22°
20°
18°
16°
Lw(A) [dB(A)]
0
8
Absorbed Power (kW)
6 40°
38°
36°
34°
4 32°
30°
28°
26°
24°
2 22°
20°
18°
16°
0
80
70
Total Efficiency (%)
60
50
40
30° 32° 34° 36° 38° 40°
26° 28°
30 20° 22° 24°
16° 18°
20
10
0
0 1 2 3 4 5 6 7 8 9 Q [m3/s]
V [m/s]
0 5 10 15 20
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international.
TDA 710-V / 14AA/ 12-12/ _ _ / _
1150rpm - 60Hz
0 1 2 3 4 5 6 7 8 Q [m3/s]
500
450
400
85
γ=1.22kg/m3 84 90
350 89
89
85 84
83
Total Pressure (Pa)
300
88
85
83 87
250
200
84 87
40°
150 86 38°
36°
34°
83 32°
30°
100 28°
84 26°
24°
84 22°
50 20°
18°
16°
Lw(A) [dB(A)]
0
4.0
Absorbed Power (kW)
40°
3.0 38°
36°
34°
2.0 32°
30°
28°
26°
24°
1.0 22°
20°
18°
16°
0.0
80
70
Total Efficiency (%)
60
50
40
40°
26° 28° 30°32° 34° 36° 38°
30 20° 22° 24°
16° 18°
20
10
0
0 1 2 3 4 5 6 7 8 Q [m3/s]
V [m/s]
0 5 10 15 20
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international.
TDA 710-V / 14AA/ 12-12/ _ _ / _
1750rpm - 60Hz
0 1 2 3 4 5 6 7 8 9 10 11 Q [m3/s]
1200
100
1000
99
γ=1.22kg/m3 96
94 100
99
800
94 100
Total Pressure (Pa)
93
99
96
98
600 93
94 98
400 40°
97 38°
36°
34°
94 32°
30°
94 28°
200 26°
24°
95 22°
20°
18°
16°
Lw(A) [dB(A)]
0
14
12
Absorbed Power (kW)
40°
10 38°
36°
8 34°
32°
6 30°
28°
26°
4 24°
22°
20°
18°
2 16°
0
80
70
Total Efficiency (%)
60
50
40
30° 32° 34° 36° 38° 40°
28°
30 22° 24° 26°
16° 18° 20°
20
10
0
0 1 2 3 4 5 6 7 8 9 10 11 Q [m3/s]
V [m/s]
0 5 10 15 20 25
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international.
DIRECT DRIVEN
Series TDA-V
Features
For commercial and industrial applications where large
volumes of air are required at moderate to high pressure,
special designed integral straightening vanes, reduced
turbulence, provide high performance and low sound level.
Construction
Double flanged casing is produced in mild steel or
galvanised Steel, the impeller having manually adjustable
pitch aerofoil blades is made of PPG, PAG or pressure-
casted Aluminium.
Finish
Available in standard finishes of galvanisation or painting.
Operating Temperature
-20°C to +55°C
Motors
Totally enclosed Class ‘F’ motor, to a min. IP54 protection
are fitted as standard. Standard motor up to 2.2kW are
usually supplied on DOL starting, motor 3.0kW and above
are star/delta starting.
Kruger Ventilation Industries Pte Ltd certifies that the TDA 800-V shown
herein is licensed to bear the AMCA Seal. The ratings shown are based on
Airflow Direction
tests and procedures performed in accordance with AMCA publication 211
and comply with the requirements of the AMCA Certified Ratings Program.
Air flowing from impeller to motor is fitted as standard.
0 1 2 3 4 5 6 7 8 Q [m3/s]
350
89
300
86
88 89
γ=1.22kg/m3
250 88
87
Total Pressure (Pa)
82
200 86
83
82
150
83
32°
82 30°
83 28°
100 26°
24°
22°
83
20°
50 18°
83 16°
14°
12°
Lw(A) [dB(A)]
0
3
Absorbed Power (kW)
32°
2 30°
28°
26°
24°
22°
1 20°
18°
16°
14°
12°
0
80
70
Total Efficiency (%)
60
50
10
0
0 2 4 6 8 Q [m3/s]
V [m/s]
0 2 4 6 8 10 12 14
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
TDA 800-V / 14AA/ 12-12/ _ _ / _
1450rpm - 50Hz
0 1 2 3 4 5 6 7 8 9 10 11 12 Q [m3/s]
800
100
700
97
99 100
600 γ=1.22kg/m3 99
98
500
Total Pressure (Pa)
93
97
94
400 93
94
300 32°
92 30°
94 28°
26°
200 24°
22°
94 20°
18°
100 94 16°
14°
12°
Lw(A) [dB(A)]
0
10
Absorbed Power (kW)
8 32°
30°
6 28°
26°
24°
4 22°
20°
18°
16°
2 14°
12°
0
80
70
Total Efficiency (%)
60
50
10
0
0 1 2 3 4 5 6 7 8 9 10 11 12 Q [m3/s]
V [m/s]
0 5 10 15 20
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
TDA 800-V / 14AA/ 12-12/ _ _ / _
1150rpm - 60Hz
0 1 2 3 4 5 6 7 8 9 10 Q [m3/s]
500
450 94
91
93 94
400
γ=1.22kg/m3 93
350
92
Total Pressure (Pa)
300 91 87
88
250 87
88
200
87
32°
30°
88 28°
150 26°
24°
22°
100 88
20°
18°
88 16°
50 14°
12°
Lw(A) [dB(A)]
0
5
Absorbed Power (kW)
4 32°
30°
28°
3
26°
24°
2 22°
20°
18°
16°
1 14°
12°
0
80
70
Total Efficiency (%)
60
50
10
0
0 1 2 3 4 5 6 7 8 9 10 Q [m3/s]
V [m/s]
0 5 10 15
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
TDA 800-V / 14AA/ 12-12/ _ _ / _
1750rpm - 60Hz
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Q [m3/s]
1200
105
1000
102
104 105
γ=1.22kg/m3
104
800 103
Total Pressure (Pa)
97
102
600 98
98
98
32°
400 97 30°
99 28°
26°
24°
98 22°
200 20°
18°
98 16°
14°
12°
Lw(A) [dB(A)]
0
18
16
Absorbed Power (kW)
14 32°
30°
12
28°
10 26°
8 24°
22°
6 20°
18°
4 16°
14°
12°
2
0
80
70
Total Efficiency (%)
60
50
10
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Q [m3/s]
V [m/s]
0 5 10 15 20 25
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
DIRECT DRIVEN
Series TDA-V
Features
For commercial and industrial applications where large
volumes of air are required at moderate to high pressure,
special designed integral straightening vanes, reduced
turbulence, provide high performance and low sound level.
Construction
Double flanged casing is produced in mild steel or
galvanised Steel, the impeller having manually adjustable
pitch aerofoil blades is made of PPG, PAG or pressure-
casted Aluminium.
Finish
Available in standard finishes of galvanisation or painting.
Operating Temperature
-20°C to +55°C
Motors
Totally enclosed Class ‘F’ motor, to a min. IP54 protection
are fitted as standard. Standard motor up to 2.2kW are
usually supplied on DOL starting, motor 3.0kW and above
are star/delta starting.
Kruger Ventilation Industries Pte Ltd certifies that the TDA 900-V shown
herein is licensed to bear the AMCA Seal. The ratings shown are based on
Airflow Direction
tests and procedures performed in accordance with AMCA publication 211
and comply with the requirements of the AMCA Certified Ratings Program.
Air flowing from impeller to motor is fitted as standard.
0 1 2 3 4 5 6 7 8 9 10 11 12 Q [m3/s]
450
400
87
87
350
γ=1.22kg/m3
87
300 86
89
Total Pressure (Pa)
86
84
250
200 86
85
32°
30°
150 85 28°
26°
24°
22°
100 20°
83 18°
16°
86 14°
50 12°
10°
Lw(A) [dB(A)]
0
6
5
Absorbed Power (kW)
32°
4 30°
28°
3 26°
24°
22°
2 20°
18°
16°
14°
1 12°
10°
0
80
70
Total Efficiency (%)
60
50
22° 24° 26° 28° 30° 32°
40 20°
18°
30 16°
14°
12°
20 10°
10
0
0 1 2 3 4 5 6 7 8 9 10 11 12 Q [m3/s]
V [m/s]
0 5 10 15
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA internationa
TDA 900-V / 14AA/ 12-12/ _ _ / _
1450rpm - 50Hz
0 3 6 9 12 15 18 Q [m3/s]
1000
900 100
800
γ=1.22kg/m3 98
97
700
95
98
97
Total Pressure (Pa)
600
500 97
97
400 32°
30°
96 28°
26°
300 24°
22°
20°
200 95 18°
16°
97 14°
100 12°
10°
Lw(A) [dB(A)]
0
20
Absorbed Power (kW)
15 32°
30°
28°
26°
10 24°
22°
20°
18°
5 16°
14°
12°
10°
0
80
70
Total Efficiency (%)
60
50
22° 24° 26° 28° 30° 32°
40 20°
18°
30 16°
14°
12°
10°
20
10
0
0 3 6 9 12 15 18 Q [m3/s]
V [m/s]
0 5 10 15 20 25
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA internationa
TDA 900-V / 14AA/ 12-12/ _ _ / _
1150rpm - 60Hz
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Q [m3/s]
600
94
500
92 91
γ=1.22kg/m3
89
92
400 91
Total Pressure (Pa)
300 91
91
32°
30°
90 28°
200 26°
24°
22°
20°
89
18°
100 16°
91 14°
12°
10°
Lw(A) [dB(A)]
0
10
Absorbed Power (kW)
8 32°
30°
6 28°
26°
24°
4 22°
20°
18°
16°
14°
2 12°
10°
0
80
70
Total Efficiency (%)
60
50
22° 24°
40 20° 26° 28° 30° 32°
18°
30 16°
14°
10° 12°
20
10
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Q [m3/s]
V [m/s]
0 5 10 15 20
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
TDA 900-V / 14AA/ 12-12/ _ _ / _
1750rpm - 60Hz
0 2 4 6 8 10 12 14 16 18 20 22 Q [m3/s]
1400
105
1200
103 102
102
γ=1.22kg/m3
1000
100 103
101
Total Pressure (Pa)
800
101
101
600 32°
30°
100 28°
26°
24°
400 22°
20°
99 18°
16°
200 101 14°
12°
10°
Lw(A) [dB(A)]
0
35
30
Absorbed Power (kW)
32°
25 30°
28°
20 26°
24°
15 22°
20°
18°
10 16°
14°
12°
5 10°
0
80
70
Total Efficiency (%)
60
50
22° 24° 26° 28° 30° 32°
40 20°
18°
30 16°
14°
10° 12°
20
10
0
0 2 4 6 8 10 12 14 16 18 20 22 Q [m3/s]
V [m/s]
0 5 10 15 20 25 30
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA internationa
DIRECT DRIVEN
Series TDA-V
Features
For commercial and industrial applications where large
volumes of air are required at moderate to high pressure,
special designed integral straightening vanes, reduced
turbulence, provide high performance and low sound level.
Construction
Double flanged casing is produced in mild steel or
galvanised Steel, the impeller having manually adjustable
pitch aerofoil blades is made of PPG, PAG or pressure-
casted Aluminium.
Finish
Available in standard finishes of galvanisation or painting.
Operating Temperature
-20°C to +55°C
Motors
Totally enclosed Class ‘F’ motor, to a min. IP54 protection
are fitted as standard. Standard motor up to 2.2kW are
usually supplied on DOL starting, motor 3.0kW and above
are star/delta starting.
Kruger Ventilation Industries Pte Ltd certifies that the TDA 1000-V shown
herein is licensed to bear the AMCA Seal. The ratings shown are based on
Airflow Direction
tests and procedures performed in accordance with AMCA publication 211
and comply with the requirements of the AMCA Certified Ratings Program.
Air flowing from impeller to motor is fitted as standard.
0 2 4 6 8 10 12 Q [m3/s]
300
250
85
γ=1.22kg/m3 83
85
87 83
200
84
87
Total Pressure (Pa)
87 82
83
150
85
70
84
28°
26°
100 68 24°
22°
85
68
20°
18°
16°
84 14°
50 12°
10°
84 8°
6°
4°
Lw(A) [dB(A)]
0
3
Absorbed Power (kW)
28°
26°
24°
2 22°
20°
18°
16°
1
14°
10° 12°
6° 8°
4°
0
80
70
Total Efficiency (%)
60
50 28°
14° 16° 24° 26°
12° 18° 20° 22°
40
10°
30 8°
6°
4°
20
10
0
0 2 4 6 8 10 12 Q [m3/s]
V [m/s]
0 2 4 6 8 10 12 14
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
TDA 1000-V / 14AA/ 12-12/ _ _ / _
950rpm - 50Hz
0 2 4 6 8 10 12 14 16 Q [m3/s]
450
91
400
91
89
350 93 89
γ=1.22kg/m3 91
93
93 89
300
89
Total Pressure (Pa)
250
91
90 77
28°
200
26°
75
24°
150 91
22°
75 20°
18°
100 16°
91 14°
12°
10°
91 8°
50 6°
4°
Lw(A) [dB(A)]
0
8
Absorbed Power (kW)
6 28°
26°
24°
22°
4 20°
18°
16°
2 12° 14°
8° 10°
4° 6°
0
80
70
Total Efficiency (%)
60
50 28°
14° 16° 18° 20° 22° 24° 26°
40 12°
10°
30 8°
6°
4°
20
10
0
0 2 4 6 8 10 12 14 16 Q [m3/s]
V [m/s]
0 5 10 15 20
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
TDA 1000-V / 14AA/ 12-12/ _ _ / _
1450rpm - 50Hz
0 4 8 12 16 20 24 Q [m3/s]
1200
1000
103
γ=1.22kg/m3 103
101
103 101
800 103
103
Total Pressure (Pa)
103 101
100
600
101
100 88
28°
26°
400 86 24°
22°
101 20°
86 18°
16°
101
14°
200 12°
10°
101 8°
6°
4°
Lw(A) [dB(A)]
0
25
28°
Absorbed Power (kW)
20 26°
24°
15 22°
20°
18°
10 16°
14°
5 10° 12°
8°
6°
4°
0
80
70
Total Efficiency (%)
60
50
14° 16° 26° 28°
18° 20° 22° 24°
40 12°
10°
30 8°
6°
4°
20
10
0
0 4 8 12 16 20 24 Q [m3/s]
V [m/s]
0 5 10 15 20 25 30
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
TDA 1000-V / 14AA/ 12-12/ _ _ / _
875rpm - 60Hz
0 3 6 9 12 15 Q [m3/s]
400
350 89
89
87
300 γ=1.22kg/m3 91 87
89
91
91 87
250
Total Pressure (Pa)
87
200
89 75
88
28°
26°
150 73 24°
22°
89 20°
73 18°
100
16°
89
14°
12°
10°
50 89 8°
6°
4°
Lw(A) [dB(A)]
0
6
5
Absorbed Power (kW)
28°
26°
4 24°
22°
3 20°
18°
2 16°
14°
12°
10°
1 8°
4° 6°
0
80
70
Total Efficiency (%)
60
50 26° 28°
14° 16° 18° 20° 22° 24°
40 12°
10°
30 8°
6°
4°
20
10
0
0 3 6 9 12 15 Q [m3/s]
V [m/s]
0 2 4 6 8 10 12 14 16 18
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
TDA 1000-V / 14AA/ 12-12/ _ _ / _
1150rpm - 60Hz
0 2 4 6 8 10 12 14 16 18 20 Q [m3/s]
700
600 96
96
94
γ=1.22kg/m3 98 94
500 96
98
98 94
Total Pressure (Pa)
400 94
95
94 82
300 28°
26°
80 24°
22°
96
200 20°
80 18°
16°
14°
95 12°
100 10°
95 8°
6°
4°
Lw(A) [dB(A)]
0
14
12
Absorbed Power (kW)
28°
10 26°
24°
8 22°
20°
6 18°
16°
4 14°
12°
8° 10°
2 6°
4°
0
80
70
Total Efficiency (%)
60
50 26° 28°
14° 16°
18° 20° 22° 24°
40 12°
10°
30 8°
6°
4°
20
10
0
0 2 4 6 8 10 12 14 16 18 20 Q [m3/s]
V [m/s]
0 5 10 15 20 25
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
TDA 1000-V / 14AA/ 12-12/ _ _ / _
1750rpm - 60Hz
0 5 10 15 20 25 30 Q [m3/s]
1600
1400 106
106
104
104
1200 γ=1.22kg/m3 107
106
107
107
1000 104
Total Pressure (Pa)
104
105
800
93
104
28°
26°
600 91
24°
22°
105
91 20°
400 18°
16°
105 14°
12°
10°
200 105 8°
6°
4°
Lw(A) [dB(A)]
0
45
40
28°
Absorbed Power (kW)
35 26°
30 24°
22°
25 20°
20 18°
16°
15
14°
10 12°
8° 10°
4° 6°
5
0
80
70
Total Efficiency (%)
60
50 26° 28°
14° 16° 18° 20° 22° 24°
40 12°
10°
30 8°
6°
4°
20
10
0
0 5 10 15 20 25 30 Q [m3/s]
V [m/s]
0 5 10 15 20 25 30 35
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories)
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international
DIRECT DRIVEN
Series TDA-V
Features
For commercial and industrial applications where large
volumes of air are required at moderate to high pressure,
special designed integral straightening vanes, reduced
turbulence, provide high performance and low sound level.
Construction
Double flanged casing is produced in mild steel or
galvanised Steel, the impeller having manually adjustable
pitch aerofoil blades is made of PPG, PAG or pressure-
casted Aluminium.
Finish
Available in standard finishes of galvanisation or painting.
Operating Temperature
-20°C to +55°C
Motors
Totally enclosed Class ‘F’ motor, to a min. IP54 protection
are fitted as standard. Standard motor up to 2.2kW are
usually supplied on DOL starting, motor 3.0kW and above
are star/delta starting.
Kruger Ventilation Industries Pte Ltd certifies that the TDA 1120-V shown
herein is licensed to bear the AMCA Seal. The ratings shown are based on
Airflow Direction
tests and procedures performed in accordance with AMCA publication 211
and comply with the requirements of the AMCA Certified Ratings Program.
Air flowing from impeller to motor is fitted as standard.
0 2 4 6 8 10 12 14 16 Q [m3/s]
300
250 93
92
93
γ=1.22kg/m3 92
91 90
200
89
Total Pressure (Pa)
94
150 89
92
78
26°
89 24°
77 22°
100 20°
89
18°
85 16°
14°
12°
50 91 10°
8°
91
6°
4°
2°
0° Lw(A) [dB(A)]
0
5
Absorbed Power (kW)
4 26°
24°
22°
3 20°
18°
16°
2 14°
12°
8° 10°
1 6°
2° 4°
0°
0
80
70
Total Efficiency (%)
60
50
20° 22° 24° 26°
40 12° 14° 16° 18°
10°
8°
30 6°
4°
20 2°
0°
10
0
0 2 4 6 8 10 12 14 16 Q [m3/s]
V [m/s]
0 2 4 6 8 10 12 14 16
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international.
TDA 1120-V / 14AA/ 12-12/ _ _ / _
950rpm - 50Hz
0 2 4 6 8 10 12 14 16 18 20 Q [m3/s]
500
100
99
400 100
99
γ=1.22kg/m3 97
96
98
Total Pressure (Pa)
300 100
98 96
85
26°
200 96
24°
84 22°
96 20°
18°
91 16°
14°
100 12°
98 10°
8°
6°
98 4°
2°
0° Lw(A) [dB(A)]
0
12
Absorbed Power (kW)
10
26°
8 24°
22°
20°
6 18°
16°
4 14°
12°
8° 10°
2 4° 6°
0° 2°
0
80
70
Total Efficiency (%)
60
50
22° 24° 26°
18° 20°
40
10° 12° 14° 16°
8°
30 6°
4°
20 2°
0°
10
0
0 2 4 6 8 10 12 14 16 18 20 Q [m3/s]
V [m/s]
0 2 4 6 8 10 12 14 16 18 20
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international.
TDA 1120-V / 14AA/ 12-12/ _ _ / _
1450rpm - 50Hz
0 4 8 12 16 20 24 28 32 Q [m3/s]
1200
1000 110
109
110
γ=1.22kg/m3 109
108 108
800
107
Total Pressure (Pa)
111
600 106
110
96
26°
24°
106 95 22°
400 20°
106
18°
102 16°
14°
12°
200 108 10°
8°
6°
108 4°
2°
0° Lw(A) [dB(A)]
0
40
Absorbed Power (kW)
26°
30
24°
22°
20°
20 18°
16°
14°
12°
10 10°
6° 8°
2° 4°
0°
0
80
70
Total Efficiency (%)
60
50 26°
18° 20° 22° 24°
40 12° 14° 16°
10°
8°
30 6°
4°
2°
20 0°
10
0
0 4 8 12 16 20 24 28 32 Q [m3/s]
V [m/s]
0 5 10 15 20 25 30
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international.
TDA 1120-V / 14AA/ 12-12/ _ _ / _
875rpm - 60Hz
0 2 4 6 8 10 12 14 16 18 20 Q [m3/s]
400
98
350 97
98
97
96 95
300 γ=1.22kg/m3
94
250 98
Total Pressure (Pa)
94
96
200 83
26°
24°
94 82 22°
150 20°
94
18°
89 16°
100 14°
12°
96 10°
8°
50 6°
96 4°
2°
0° Lw(A) [dB(A)]
0
8
26°
Absorbed Power (kW)
24°
6
22°
20°
18°
4 16°
14°
12°
2 10°
6° 8°
4°
0° 2°
0
80
70
Total Efficiency (%)
60
50
20° 22° 24° 26°
16° 18°
40 10° 12° 14°
8°
30 6°
4°
2°
20 0°
10
0
0 2 4 6 8 10 12 14 16 18 20 Q [m3/s]
V [m/s]
0 5 10 15 20
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international.
TDA 1120-V / 14AA/ 12-12/ _ _ / _
1150rpm - 60Hz
0 2 4 6 8 10 12 14 16 18 20 22 24 26 Q [m3/s]
700
104
600 103
104
103
102 102
γ=1.22kg/m3
500
101
104
Total Pressure (Pa)
400
103 100
90
26°
300 24°
100 89 22°
20°
100
18°
200 96 16°
14°
12°
102 10°
100 8°
6°
102 4°
2°
0°
Lw(A) [dB(A)]
0
20
Absorbed Power (kW)
16 26°
24°
22°
12 20°
18°
8 16°
14°
12°
8° 10°
4 6°
2° 4°
0°
0
80
70
Total Efficiency (%)
60
50
22° 24° 26°
18° 20°
40 12° 14° 16°
10°
8°
30 6°
4°
20 2°
0°
10
0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 Q [m3/s]
V [m/s]
0 5 10 15 20 25
- Performance certified is for installation type D - ducted inlet, ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
- Power ratings (kW) does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA Standard 301. Values shown are for inlet Lwi(A) sound power level for installation
type D - ducted inlet, ducted outlet, rating include the effect of duct end correction.
- The AMCA Certified Ratings Seal applies to air performance only. dBA levels are not licensed by AMCA international.
Kruger Ventilation Industries Pte Ltd
No. 17 Tuas Avenue 10 Singapore 639141 - Tel. +65 68611577 - Fax +65 68613577 CNo. - CAT015.E0 November 2006
Website: www.krugerfan.com