Metal-enclosed single busbar, Solid and Air-Insulated switchgear

IEC Medium Voltage Switchgear up to 24 kV

Xiria E
Extendable switchgear for distribution substations
and commercial / industrial applications
Automotive

Powering
business
worldwide
Aerospace

Eaton delivers the power inside hundreds of products that


are answering the demands of today’s fast changing world.
We help our customers worldwide manage the power
they need for buildings, aircraft, trucks, cars, machinery
and entire businesses. And we do it in a way that
consumes fewer resources.

Next generation Powering Greener Buildings


transportation and Businesses
Truck
Eaton is driving the Eaton’s Electrical Group is a
development of new leading provider of power
technologies – from hybrid quality, distribution and control
drivetrains and emission control solutions that increase energy
systems to advanced engine efficiency and improve power
components – that reduce fuel quality, safety and reliability.
consumption and emissions in Our solutions offer a growing
trucks and cars. portfolio of “green” products
and services, such as energy
Higher expectations audits and real-time energy
consumption monitoring.
We continue to expand our
Eaton’s Uninterruptible Power
aerospace solutions and
Supplies (UPS), variable-speed
services to meet the needs of
drives and lighting controls help
new aviation platforms,
Hydraulics including the high-flying light jet
conserve energy and increase
efficiency.
and very light jet markets.

Building on our strengths


Our hydraulics business
combines localised service and
support with an innovative
portfolio of fluid power
solutions to answer the needs
of global infrastructure projects,
including locks, canals and
dams.

Hydraulics
Electrical

2
MV Switchgear Technology
is in our DNA

Eaton’s knowledge and understanding of industries,


applications, technology and products enables us to offer
customers safe, reliable and high performance solutions.
We have been part of the Medium Voltage switchgear
technology creation and therefore carry what’s needed
with us – always!

Complete MV switchgear solutions


The series of Eaton Medium Voltage systems offers switchgear
and components for applications in distribution networks (main
stations, substations and transformer stations) and industrial
power supplies. These technically high quality systems are air- or
epoxy-resin insulated and are always equipped with circuit-
breakers based on proprietary vacuum interrupters.

The medium voltage switchgear systems carrying Eaton’s brand


are based on the use of vacuum circuit-breakers combined with
solid insulation material. This is an environmentally-friendly
technology in comparison with the methods used by many other
suppliers, which use SF6 as an insulation medium.

Eaton thus has a wide range of switching systems and


components that offer an environmentally friendly solution for
every application. Additionally, Eaton’s global service network
provides maximum customer support in all regions of the world.

Industry leading vacuum and solid insulation technology


Through more than eighty years of innovation and experience,
Eaton has developed environmentally friendly vacuum interrupters
capable of reliably switching both normal load currents and high
stress fault currents.

Eaton is one of the few companies in the world producing vacuum


interrupters and has succeeded in developing world class products
with international patents. This has been achieved through
company acquisitions over the years of Westinghouse®, Cutler-
Hammer®, MEM® and Holec®.

Eaton’s range of To increase the dielectric strength of the vacuum interrupter,


Eaton has also designed vacuum interrupters that are encapsulated
SF6 free switchgear in epoxy resin material. The medium voltage IEC circuit breaker
for Medium Voltage family utilizes this solid insulation technology that has been
catering to a wide range of applications for more than 40 years.

3
Xiria The Product Family
Xiria is the name of Eaton's product family for a new generation of medium voltage
switchgear. The Xiria family started more than a decade ago with the introduction of
the Xiria ring main unit.
This ring main unit consists of a block containing three panels. Due to the quick acceptance and
worldwide interest in more configurations, Eaton consequently developed a four, five and two panel
block. Due to the fact that the individual units cannot be coupled and are limited in the number of
panels and protection and control equipment, the single panel version was developed. This single
panel version is called Xiria E. E in this case stands for Extendable.
The Xiria family includes multiple possibilities and configurations for Power consumption metering.
These configurations are indicated as Xiria M-versions. M stands for metering. The transformers for
power consumption metering can be either integrated into the block-type Xiria switchgear or housed
in a separate metering panel. This dedicated metering panel can be integrated with both the current
block type switchgear and the new single extendable panels.

Xiria
(Block type)

Xiria M
(Metering)

Xiria E
(Extendable)

The complete solution


By adding the Xiria E panel to heavy duty applications and Some applications are:
the current range of Xiria a commercial buildings. With • Distribution substations • Office buildings
complete family, based on the the new Xiria E panel it is also for utilities • Infrastructure projects
same and proven key techno- possible to use the system in • Wind power plants (tunnels, subways, airports)
logies, is created. The Xiria applications with higher • Bigger industrial applications • Universities
block type system is already specifications and a bigger • Hotels • Hospitals
frequently used for transformers number of panels. • Shopping centres • Data centers
stations, small industries,

4
Xiria E
Modular Switchgear for Smart Grid Applications
Xiria E is the name of Eaton's new medium voltage
switchgear for smart grid applications. The system is
characterised by its high level of operational safety and
suitable for applications up to 24 kV.
The Xiria E switchgear is reduced, as no regular testing
designed around Eaton's of gas pressure or other routine
proven vacuum interrupters, maintenance is needed and
which require no maintenance there is no high end-of-life cost
and are certified for 30,000 associated with ultimately
operation cycles. disposing of the equipment.
All live parts in the available With panel dimensions of only
panels are single pole 500 mm width and a provision
insulated. The used materials for cable connection from the
are shaped specifically to front, the Xiria E system is
provide optimum insulation economical in its use of
combined with excellent valuable floor space, and easy
thermal characteristics. In to accommodate in even the
addition, the insulation is most restricted environments.
configured to provide effective For locations where there is no
control over electric fields possibility to exhaust an
around the used components, internal arc into cellar, the
thereby minimizing any risk of system has the possibility to
internal arcing. exhaust into the room. This is
Within the Xiria E panels both realized by means of a special
the primary parts and the chimney at the back side with
mechanisms are housed in a integrated arc absorbers.
fully enclosed housing which When it comes to the safety of
protects the whole system the operating personnel the
against environmental Xiria E design leaves nothing to
influences. chance. All parts are fully
The use of vacuum interrupters enclosed by an internal arc
and solid insulation means that tested safe metal housing.
the Xiria E is environmentally Besides that the panels in the
friendly. These technologies system are provided with direct
ensure that this system is a visible indication of the
conservational alternative to integrated earthing and
switchgear systems using ON/OFF-position by means of
Sulfur Hexafluoride (SF6) gas inspection windows in the
for insulation. The cost of front.
ownership is also significantly

5
Features and Benefits
(quick overview)

Safe in Use Low Total Cost of Ownership


• Visible isolation by means Low initial costs due to:
of inspection windows in • Panels with only 500 mm
the front width
• Compartments protected • Cable connection from the
against penetration of front / wall standing
objects arrangement
• Capacitive voltage detection • No need for external arc
system for verification of channel
safe isolation from supply
• 12 kV and 24 kV panels in
• Logical mechanical and same housing
electrical interlocks prevent
formal operation
No costs during service due to:
• Smooth contemporary • Robust design with
design minimum number of parts
(routine tested in factory)
• Long-life solid insulated
components as insulation
Environmental Friendly medium
• Minimized number of • Maintenance free vacuum
components circuit-breaker and load-
break switch
• Environmental-friendly
design with respect to the • Primary parts and
materials used mechanism installed in a
fully sealed for life enclosed
• No use of SF6-gas for
housing
switching and insulation
• No SF6 pressure checks
• Energy efficient production
and assembly with
environmental energy Low end of life disposal cost
sources due to:
• Minimal number of • Vacuum switching
transition points in primary technology
design enable low energy • Solid insulation with air as
loss during operation isolating medium
• Only Re-usable and / or • Recycling or re-use of
recyclable materials used materials

User Friendly Reliable and Safe in


Operation
• Cable connection and user
interfaces for operation on • Complete design certified
the same front side of the in accordance with IEC
panel standards
• Ergonomic cable connection • Arc fault tested according
height IEC 62271-200
• Cable (secondary) entry • Quality assurance in
points on both sides of the accordance with
low voltage compartment DIN EN 9001
top plate • Routine tested
• Secondary cable terminals • Single pole insulated
positioned on a good primary parts within one
reachable place in the low compartment
voltage compartment
• Primary parts and
• Clear and simple straight- mechanism in sealed for
forward operation panels life fully enclosed housing
• Protected voltage
transformers

6
Basic Design
The Xiria E system is In addition, the number of panels capable of being used in
an installation is unlimited as several sections can easily be
modular in construction. connected. As the panels can be quickly assembled and
This ensures that any connected, flexible commissioning of the switchgear is possible.
panel combination and The panels in the Xiria E system are compact (500 mm wide),
resulting in considerable savings in costs and installation space.
sequence is possible.

7
4
3

5
6
12

11 13

10 16

14

9 15

Circuit-breaker panel (example)

1. Low Voltage compartment 6. Inspection window 12. Change-over switch


2. Protection relay 7. Mechanism 13. Vacuum interrupter
3. Control panel with operation 8. Cable cones 14. Current transformers
of the circuit-breaker and 9. Cable clamps 15. Voltage transformers
change-over switch
10. Earth bar 16. Coil and resistor for
4. Mimic diagram protection against
11. Busbar
5. Voltage detection system ferroresonance

7
Main Components
Vacuum circuit-breaker
The vacuum circuit-breaker uses a simple and reliable spring
charging mechanism for operation of the vacuum interrupters.
The mechanism contains a low number of moving parts and
makes no use of lubricants. It is completely housed in a sealed
for life enclosure and therefore needs no maintenance.

Features
• With environmental friendly vacuum interrupters
• Simple spring charging mechanism
• No use of lubricants
• Housed in a sealed for life enclosure
• Manual or motor-operated
• Position indication by means of inspection windows and
mechanical indicators
• Auxiliary contacts for Open/Closed position

2-position change-over switch


All panels are equipped with a change-over switch positioned
in the same sealed for life enclosure as the circuit-breaker.
The change-over switch consists of three shafts connected to
the busbars or earthing points. Since it is mechanically interlocked
the change-over switch can only be operated when the circuit
breaker is in the open position.

Features
• Manual-operated switch with 2 positions (service / earthed)
• Maintenance free
• Housed in sealed for life enclosure
• Auxiliary contacts for service / earthed positions
• Position indication by means of inspection windows and
mechanical indicators
• Mechanically interlocked with the vacuum circuit-breaker

Busbars
The busbars in the panel are housed in the same sealed for life
enclosure as the circuit-breaker and change-over switch. To prevent
a possible internal arc all busbars are single phase insulated.

Features
• Single phase insulated
• Air insulated
• Housed in a sealed for life enclosure
• Simple and robust construction
• Easy to couple

8
Eaton Core Technologies
Solid insulation
Polycarbonate and Thermo- and cooling purposes. In the
plastic elastomer (TPE) is used many years of experience with
as high-quality primary insulation design and manufacturing of
materials around live parts. insulation materials, we learned
By applying Polycarbonate and to construct smart single phase
TPE for solid insulation our insulated constructions. Xiria
design engineers can shape the utilizes optimal field control
parts specifically for optimal through the special design of
insulation, robust construction all primary components.

Electrical field control


With conventional shapes for initiate avalanches resulting in
primary components like flash-overs. In-depth knowledge
busbars and conductors, the about breakthrough phenomena
electrical field between the and field steering techniques
phases and between phase and enable us to prevent flash over
earth is non-uniformly completely. The result is a
distributed. In areas with high particular compact design.
field, partial break-through can

Vacuum technology: safe, compact and reliable


Eaton vacuum interrupters A typical feature of Eaton
consist of a ceramic cylinder, vacuum interrupters is that
housing a fixed and movable they are characterised by very
contact. Movement of the low arc voltage and short arc
contact under vacuum times, resulting in very low arc
conditions is facilitated by a energy. Contacts wear in a
bellow. A shield surrounding vacuum interrupter is therefore
the contacts prevents the virtually negligible. Vacuum
insulators from becoming interrupters are maintenance
contaminated by metal vapour free and are certified up to
produced during current 30,000 operation cycles.
interruption. This shield also
ensures good potential
distribution over the insulator.

9
Reliable and Safe in Operation
Eaton's proven technologies Experience and knowledge
gained over many years in the
have been integrated in the areas of cast resin technology,
design and development of vacuum technology and
the Xiria in order to ensure electrical field control have
been implemented.
that the switchgear is safe
The system has been
and has high operational thoroughly arc fault tested
reliability throughout its according to the latest standard
complete lifetime. IEC 62271-200.

Preventing an internal arc


Within the Xiria design there are different technologies used to prevent an open arc.

Single pole insulated primary


parts
All high voltage parts are single
pole insulated. The insulation
materials used for this are
Polycarbonate and Thermo- Sealed for life fully enclosed
plastic elastomer (TPE), both housing
high-quality materials with
optimal insulation characteristic Both the primary parts of the
resulting in minimised unit and the mechanisms are
dimensions. housed in a fully enclosed
(sealed for life) housing which
protects the whole system
Use of Electrical Field control against environmental
influences and therefore makes
Engineers designed the whole it maintenance free. This
construction of primary parts, compartment can be classified
housed in the sealed for life as non-accessible and has an
tank, based on Eaton's key IP degree of IP55.
technology for electrical field
control. By means of special
shapes and dimensions the
possibility of an open arc is
minimized.

Protected Voltage
transformers
Ferro resonance can cause that
voltage transformers are
damaged and consequently
initiate an internal arc in the
switchgear. Our design
prevents that the voltage
transformers are affected by
ferroresonance. A resistor and
a saturable coil are installed in
the tertiary circuit of the
voltage transformer.

10
Routine tests assembled, a thorough visual Engineers therefore did every- IEC 62271-200. Within the Xiria
inspection is carried out, thing necessary in design and design a double prevention
Various prescribed routine
together with mechanical, construction to prevent internal philosophy is used. Firstly, the
tests are carried out during
functional and electrical checks. arcs, despite the fact that it is design is constructed in such a
the production of the switch-
very rare for an operator to be in way that an internal arc is
gear. To assure quality, all
Philosophy on Internal arcs front (without operating) of the prevented. In the unlikely case
processes are in accordance
switchgear at exactly the same that an internal arc could occur,
with DIN EN 9001. This means Eaton always puts extra focus time that an internal fault the Xiria is equipped to provide
that at every stage of on creating safe switchgear for occurs. maximum safety to the
production the components, operators at all times. One of
Eaton supports the philosophy operator, and to control and
circuit-breakers and current the biggest potential threats to
that it is best to avoid internal minimise damage to the rest of
transformers are inspected for operators is an internal arc in
arcs than to cure, in line with the switchgear and room.
correct functioning. When the switchgear.
entire installation has been the relevant standard

Controlling an internal arc


An internal arc in switchgear causes an overpressure supported by the release of fire and smoke.

By design, vacuum and air/solid expensive arc channel may be No phase-to-phase short
insulated switchgear has the installed, that guides the arc circuits minimises pressure
least environmental impact output outside the switch
Within the Xiria all high voltage
after an internal arc event. The room. The Xiria design is
parts are single pole insulated.
impact of an arc is twofold: an constructed in such a way that
The advantage of this single
internal impact (in the both impacts are significantly
pole construction is that the
switchgear) and external impact reduced and consequently a
only conceivable internal fault is
(in the switch room). less complicated arc channel is
a single-phase short circuit, e.g.
The overpressure created by an needed.
due to a cable connection
internal arc will, in standard failure (when single core cables
switchgear, be guided out of are connected, as is the normal
the switchgear by means of a practice nowadays).
pressure relief duct. Next to
the duct a complicated and

Arc absorber reduces


output impact
In case it is not possible to vent
into the cable cellar or into an
adjacent room, the Xiria design
offers the possibility to safely
vent into the switch room. In
this case a special arc chimney
is installed at the backside of
the panel. This arc chimney
contains integrated arc
absorbers that break and filter
gasses and fire significantly.

11
Safe in Use
The Xiria design contains some special features that guarantee the operator to work
safely with the different panel types.

What you see is what you get!


Visible isolation by means Earth position
of inspection windows in
the front
When carrying out operational
actions and work on the cables,
it is vital to have unambiguous
status indications. When it
comes to safety of the
operating personnel Eaton
leaves nothing to chance. That
is why the Xiria design is fitted
with directly visible isolation by
means of inspection windows Operating position
in the front which makes the
isolating distance between the
cable and busbar system
directly visible. A visible, short-
circuit proof earthing can take
place via the load-break switch
or circuit-breaker.

Capacitive voltage detection Logical mechanical and switch when the circuit-breaker Smooth temporary design
system for verification of safe electrical interlocks prevent is switched on. All mechanical
All compartments of the Xiria
isolation from supply mal operation interlocks are constructed in
panels are designed in such a
such a way that they directly
Each panel type within the Xiria Within the Xiria design mis- way that the system is safe to
block the mechanism.
family is equipped with a operation by an operator is touch from the outside. By
standard three-phase Voltage prevented by using different using a smooth and smart
Detection System for voltage interlocks. The interlocks are Switching to service position design it is not possible for the
testing to IEC 61243-5. The mechanical and electrical. For is only possible with closed operator to injure himself by
VDS shows the operator if the example electrical and cable compartment moving parts or parts that stick
panel is isolated from supply or mechanical interlocks prevent The door of the cable out of the switchgear when
not. to operate the change-over compartment can only be moving in front of the
standard opened when the switchgear.
circuit-breaker is in the earthed
position. After the door is
removed it is possible to switch
off the circuit-breaker for cable
testing. Next switching on to
service position is only possible
with the door positioned back
again.

Compartments protected
against penetration of
objects
Within the Xiria design it is also
not possible to accidentally
penetrate the switchgear by
part of a body or a tool.
For the latter all high voltage
compartments have an IP55
degree.

12
Low Total Cost of
Ownership
The Xiria design guarantees very low costs related to
owning the switchgear during its entire lifetime.
The life-time costs can be split in the initial costs, installation cost,
service cost and finally, costs for disposal of the switchgear.
All costs of owning the switchgear are influenced by different
features of the switchgear. Within Xiria all these features are
constructed in such a way that the costs for the owner are as low
as possible of course with no concessions to the quality of the
switchgear.

Low initial costs Arc chimney with integrated No SF6-gas pressure checks Low end of life disposal
arc absorbers
Initial costs consist of purchase, Switchgear that uses SF6-gas cost
transport, building and A standard option (in case there as an insulation medium has a
installation costs. is no possibility to vent down leakage rate. To maintain the Full recycling or re-use of
or backwards) that reduces the isolation level within this type materials
Panel width only 500 mm switchroom dimension is the of switchgear, the pressure of
Xiria arc chimney with the SF6 tanks must be checked The primary parts of the Xiria
By using a combination of solid integrated arc absorbers. In and refilled on a regular basis have a lifetime of at least 30
insulation technology, electrical normal switchgear, gasses during the unit's lifetime. years. Depending on the
field control and vacuum caused by an internal arc are Within the Xiria, an owner does location where the system is
technologies, Eaton's engineers guided out of the switchroom not have to incur the extra installed the lifetime can be
managed to construct Xiria E by means of an extra duct and costs involved in checking and extended. If for what reason
panels with a width of arc channel connected to the maintaining the required the decision is made not to use
maximum 500 mm. Because a switchgear. These additions insulation level. The the switchgear anymore the
typical switchgear installation require extra switch room combination of vacuum Xiria can be handed over to
normally consists of a large space and consequently interrupters for switching, solid Eaton again. Next the switch-
number of panels, this compact increasing initial building cost. insulation and clean air as the gear will be dismantled and the
design significantly reduces the insulation medium, is different materials can, and
switch room size. The compact environmentally friendly and will, be categorised. Because
design also makes Xiria E highly no toxic materials are used in
flexible and economically
Low service cost during maintains the same quality
the Xiria, dismantling is a less
level during the complete
attractive when existing operation lifetime of Xiria. complicated, more cost
installations are being replaced. Service cost consists of effective and environmentally
maintenance, failure and friendly operation. The
Primary parts and
Cable connection from the consequential cost. Besides dismantled and categorised
mechanism installed in a
front (back-to-wall that the technical lifetime of materials will be, depending on
fully sealed for live enclosed
arrangement) parts or modules will the material, recycled or re-
housing
determine the replacement used.
Cable connection from the The biggest influence on the
cost of the equipment.
front is a feature that saves quality of the primary and
building costs. Due to this front moving parts in switchgear, has
connection the rear of the Robust "lean" design with
minimum number of parts the environment in and outside
Xiria E can be installed close to the switchroom. These
the wall of a building, again Costs during service of a environmental influences could
reducing building cost. switchgear can be caused by in the end cause damage to the
damaged parts requiring switchgear that should be
12 kV and 24 kV panels in replacement, or by repaired. To prevent any
same housing maintenance parts that will not environmental influence on
reach their expected lifetime if the most critical parts in the
The 12 kV and 24 kV versions
they are not serviced. Xiria, all of these parts are
are both accommodated in the
same compact housing. This Within the Xiria design a housed in a fully sealed for live
means substantial savings on minimal number of enclosure (IP55).
building costs because the components are used. This
same switchroom can be used robust design with only the Product quality guaranteed
when the operating voltage is necessary parts is designed by prescribed routine testing
increased (upgrading). based on experience of building in the factory
switchgear for more than a
During production of the
century.
panels, various prescribed
routine tests are carried out by
specialists, making sure that
the panels achieve the quality
that they are designed for.

13
User friendly
First of all requirements is a safe and reliable installation. Easy and ergonomic connection of cables
Number two is an installation that is convenient and Primary cables Secondary cables
efficient to operate.
The cable cones of Xiria are Connecting the secondary
The second aspect does not always get the attention it deserves, positioned on a height of cables is carried out by
but for Xiria most certainly did. The Xiria panels are designed to be 700 mm from floor level. This entering the low voltage
user friendly and are easy to operate. height makes it relatively easy compartment of the Xiria E
Primarily, all operations can be carried out on the front side of the for operators to connect the from the top. The low voltage
panel. This means that both cable connection and user interface primary cables. There is also cable terminals are positioned
for operation are positioned at the same front side of the panel. enough space in the cable in such a way that the operator
The logically arranged control panel enable operators to do their compartment to connect the can connect the cables easily
job as efficiently and safe as possible. required number of cables within the compartment whilst
with connectors available on standing in front of the Xiria E.
the market.

Clear and simple control panel


The control panel on the Xiria is breaker is requested a push
positioned on a convenient button will be installed in the
height for the operator. It is control panel for achieving this
directly connected to the function.
mechanism. The mechanism is provided
The mechanism is a hand with viewing windows on the
operated or hand/motor front for direct visual indication
operated spring charged of the earthed position of the
mechanism, connected to the change-over switch and the
vacuum interrupters and the ON/OFF-position of the main
change-over switch. It is vacuum interrupter. The front
operated via two rotating shafts operating panel is also provided
on the front provided with the with a black and white single
necessary mechanical inter- line intuitive mimic, showing
locks to avoid wrong operation. the positions of the vacuum
For example an interlock is interrupter and the Earth/Busbar
built-in that prevents operation position of the change-over
of the change-over switch switch.
when the circuit-breaker or Each panel is provided with a
load-break switch is in the ON- voltage detector mounted on
position. Another standard the front. It is connected via
feature on the control panel is internal wiring to capacitive
the padlocking of the earthed sensors inside the cable
position. For padlocking the connection cones. It shows the
position, the most common presence of the primary voltage
padlocks available in the market on all three phases of the
can be used. primary cables connected to
Manual operation of the the panel.
switchgear is achieved with In case advanced protection
one operating handle. This and control equipment is
handle can be used for requested, the low voltage
switching the circuit-breaker, compartment positioned on top
load-break switch and change- of the panel, will house these.
over switch. Operation is done
by inserting the handle in the
access holes in the front. In
case a motor-operated circuit-

14
Environmentally
friendly
Like all Eaton's other medium voltage switchgear, Xiria
is designed to be an environmentally friendly product
throughout the whole chain.
One of the key strategic initiatives of Eaton is to provide environ-
mentally friendly products. Eaton realises that for this they should
look at their total product chain, from design to dismantling. The
optimal situation is that for each phase there is no damage to the
environment and at the end, all materials can be re-used again in
the same product (the Cradle-to-Cradle principle). The product
chain can be divided into four main blocks. These blocks are the
design (materials used) of the product, the assembly of the
product, the usage phase of the product and finally the
dismantling of the product.
Eaton's production plant in Hengelo (the Netherlands) acts entirely
in accordance with the rules and procedures of ISO 14001
environmental certificate during development and production
processes.

Environmentally friendly design Efficient use of materials No service checks on site


With respect to the design of switching medium, vacuum Besides the energy sources, Because Xiria is designed for
switchgear, the vision "the less technology is used within the special focus was placed on a lifetime of at least 30 years,
number of components the interrupters of the Xiria circuit- the efficient use of material the system needs no energy
better" applies. This because breakers. Xiria can be during assembly. For example, usage for maintenance
every part must be manu- completely recycled at the end sheet steel plates are cut with activities during this long
factured and therefore impacts of its life without any problem. as little waste material as period. Due to the green
on the environment. Next, possible. Residual material is insulation and switching
applies the affect of different No use of SF6 gas for used within other product technology, there is also no
materials on the environment. insulation or switching components. leakage of the SF6-gas during
its lifetime and no need for
Within medium voltage extra maintenance activities on
Use of minimised number of
switchgear SF6-gas is being SF6 pressure checks.
components
used, because of its good
Xiria is designed to use the insulating properties. Emissions
minimum of materials and of SF6-gas from switchgear
resources, without affecting contribute significantly to the
the strength of the system. threat of the greenhouse effect
Minimal energy loss Re-use or recycling of
For example, Eaton reduced and associated climate change. during operation materials
the number of components SF6 is on the list of greenhouse
dramatically, compared to gasses in the Kyoto protocol. To prevent energy loss by the During dismantling Xiria
conventional switchgear, by system itself, Xiria uses a switchgear is demounted into
SF6 is the most potent of the minimum number of primary parts and thereafter categorized
using an simple spring charging six main greenhouse gasses,
mechanism and integrated change-over points. All the per material. Next the parts will
with a Global Warming available change-over points be recycled or re-used.
compartments. This also Potential (GWP) of 23,000.
ensures straight forward use optimal surface contacts Because Xiria uses no SF6,
assembly with low labour cost. In the 1980s, the Holec group, and by this, prevent extra there is no loss of this gas
as it was then, made a energy losses over these during dismantling of the
Materials with no/less fundamental choice not to use points. switchgear.
impact on the environment SF6 as a switching and
insulation medium for medium
Eaton selects materials with voltage equipment. In the
care. It is essential that they 1980s, Holec had SF6 techno-
are safe for personnel and the logy available in-house. The
environment - not just during main reason for not using any
use, but at the end of service SF6 in medium voltage equip-
life too. ment was the complexity of
Within Xiria a combination of the treatment required for the
solid (cast resin) insulation and toxicity of the gasses that have
air as insulation medium is been in contact with an arc,
used. The solid insulation and the need for additional
technology, in combination with safety measures when used in
electrical field calculations, public locations such as
provides a very compact, residential areas and shopping
environmentally friendly design centres.
for the switchgear. As the

15
Exactly how you want it
Simple configuration, coupling and extension
Every application of this type of
system is unique, so Eaton
offers a large number of
different panel types and field
versions. If, in due course, the
end-user needs additional
capacity in the form of more
panels, Xiria E can easily be
extended to the right or left.

Flexible application of secondary apparatus, protection relays and substation automation


Eaton realises that end-users Range of Voltage Protection and Control Smart Grids
have their own direction with transformers equipment
Equipment for (remote or local)
respect to the use of secondary
All Xiria E panels can be fitted The protection and control communication between
apparatus, protection relays and
with cast-resin insulated equipment is located in the low panels or automation systems
substation automation within
voltage transformers (of the voltage compartment. This can also be installed in the low
the switchgear. The need for
requested transformer ratio and compartment is completely voltage compartment. For
customer specific apparatus
class) for the voltage separate and has its own instance an Eaton remote
and relays was taken into
measurement on the cable access door. There is space on terminal unit (RTU) can be
account during the develop-
side, or on the busbar side. the door for equipment such as applied. Having this possibility
ment of the Xiria E. This
Both transformers can be protection relays, test plugs, makes the system the perfect
resulted in a system that
(dis-)connected safely and meters, etc. solution for current and future
enables end-users to integrate
easily. The Xiria E is standardised Smart Grid applications.
apparatus according to their
specification. Thanks to the for the Eaton relays series.
large number of protection and Range of Current However the Xiria E is adaptable
control options, end-users will transformers for the installation of other
always be able to construct an The epoxy resin insulated brands. In case more than one
Xiria E system that conforms current transformers are of the relay is required, the low
exactly to your requirements. ring core type. They are voltage compartment can be
positioned around the primary extended.
conductors behind the cable
cones or around the primary
cables. All common
transformer ratios, outputs, Eaton remote terminal unit (RTU).
rated currents and classes are
possible.

16
Product Range

Circuit-breaker panel Transformer panel Load-break switch panel

Option Option Option

M M M

Option Option Option Option Option Option

Option Option Option

Busriser panel Busbar sectionalizer panel

Option Option

M M

Direct busbar panel Metering panel


Option

Option Option

Option

Circuit- Load-break Change-over Motor Second Capacitive Voltage Current


breaker switch switch operation cable voltage detection transformer transformer
system at the cable

17
Dimensions (mm)

Circuit-breaker panel Metering panel


Transformer panel
Load-break switch panel
Busriser panel
Busbar sectionaliser panel
Direct busbar panel

Standards
Xiria E complies with the following international standards
IEC 62271-1 Common specifications for high-voltage switchgear and
control gear standards
IEC 62271-100 High-voltage alternating-current circuit-breakers
IEC 62271-102 Alternating current disconnectors and earthing switches
IEC 62271-103 High-voltage switches
IEC 62271-200 A.C. metal-enclosed switchgear and control gear for rated voltages
above 1 kV and up to and including 52 kV
IEC 62271-304 Additional requirements for enclosed switchgear and control gear
from 1 kV to 72.5 kV to be used in severe climatic conditions
IEC 60529 Degrees of protection provided by enclosures
IEC 60044-1 Instrument transformers - Part 1: Current transformers
IEC 60044-2 Instrument transformers - Part 2: Inductive voltage transformers
EN 50181 Plug-in type bushings above 1 kV up to 36 kV
ISO 9001-2000 Quality
ISO 14001 Environmental management

18
Electrical Data
General 3.6 kV 7.2 kV 12 kV 17.5 kV 24 kV

Rated voltage kV 3.6 7.2 12 17.5 24


Impulse withstand voltage kV 40 60 75 / 95 95 125
Power frequency withstand voltage kV-1m 10 20 28 / 38 / 42 38 50
Rated frequency Hz 50/60 50/60 50/60 50/60 50/60
Loss of service continuity LSC2B LSC2B LSC2B LSC2B LSC2B
Partition class PM PM PM PM PM
Internal Arc Classification (IAC) AFL AFL AFL AFL AFL
Internal arc resistance kA - s 20 - 1 20 - 1 20 - 1 20 - 1 20 - 1
Internal arc resistance with absorber kA - s 16 - 1 16 - 1 16 - 1 16 - 1 16 - 1
Internal arc resistance cable compartment kA - s 16 - 1 16 - 1 16 - 1 16 - 1 16 - 1
Internal arc resistance cable comp. alternative kA - s 20 - 1 20 - 1 20 - 1 20 - 1 20 - 1
Degree of protection in service IP31D IP31D IP31D IP31D IP31D
Degree of protection with doors/covers open IP2X IP2X IP2X IP2X IP2X
Ambient air temperature range °C -25 +40 -25 +40 -25 +40 -25 +40 -25 +40

Busbar system
Rated normal current A 630 630 630 630 630
Rated short-time withstand current kA - s 20 - 1 20 - 1 20 - 1 20 - 1 20 - 1
Rated short time withstand current alternative kA - s 20 - 3 20 - 3 20 - 3 20 - 3 20 - 3
Rated peak withstand current kA 50 50 50 50 50

Load break switches


Rated normal current A 630 630 630 630 630
Rated active load break current A 630 630 630 630 630
Rated short-circuit making current kA 50 50 50 50 50
Rated short-time withstand current kA - s 20 - 1 20 - 1 20 - 1 20 - 1 20 - 1
Rated short-time withstand current alternative kA - s 20 - 3 20 - 3 20 - 3 20 - 3 20 - 3
Rated Cable Charging Breaking Current A 31.5 31.5 31.5 31.5 31.5
Mechanical Endurance Class M2 5000 x M2 5000 x M2 5000 x M2 5000 x M2 5000 x
Mechanical Endurance Class as Earth Switch M0 M0 M0 M0 M0
Mechanical Endurance Class Disconnector M0 M0 M0 M0 M0
Electrical Endurance Class E3 E3 E3 E3 E3
Electrical Endurance Class as Earth Switch E2 E2 E2 E2 E2

Circuit-breakers
Rated normal current A 630 630 630 630 630
Rated breaking current kA 20 20 20 20 20
Rated short-circuit making current kA 50 50 50 50 50
Rated Capacitive Switching Current Class C2 C2 C2 C2 C2
Rated Cable Charging Breaking Current A 31.5 31.5 31.5 31.5 31.5
DC Time Constant msec 45 45 45 45 45
DC Component % <20 <20 <20 <20 <20
Mechanical Endurance Class M1 M1 M1 M1 M1
Mechanical Endurance Class as Earth Switch M1 M1 M1 M1 M1
Mechanical Endurance Class Disconnector M0 M0 M0 M0 M0
Electrical Endurance Class E2 E2 E2 E2 E2
Rated short-time withstand current kA - s 20 - 1 20 - 1 20 - 1 20 - 1 20 - 1
Rated short-time withstand current alternative kA - s 20 - 3 20 - 3 20 - 3 20 - 3 20 - 3
Minimum tripping time msec 80 80 80 80 80
Mechanism type O - 3 min - CO - 3 min - CO

Transformer panel
Rated normal current A 200 200 200 200 200
Rated breaking current kA 20 20 20 20 20
Rated short-circuit making current kA 50 50 50 50 50
Rated Capacitive Switching Current Class C2 C2 C2 C2 C2
Rated Cable Charging Breaking Current A 31.5 31.5 31.5 31.5 31.5
DC Time Constant msec 45 45 45 45 45
DC Component % <20 <20 <20 <20 <20
Mechanical Endurance Class M1 M1 M1 M1 M1
Mechanical Endurance Class as Earth Switch M1 M1 M1 M1 M1
Mechanical Endurance Class Disconnector M0 M0 M0 M0 M0
Electrical Endurance Class E2 E2 E2 E2 E2
Rated short-time withstand current kA - s 20 - 1 20 - 1 20 - 1 20 - 1 20 - 1
Rated short-time withstand current alternative kA - s 20 - 3 20 - 3 20 - 3 20 - 3 20 - 3
Minimum tripping time msec 80 80 80 80 80
Mechanism type O - 3 min - CO - 3 min - CO

19
Eaton’s electrical business is for harsh and hazardous
a global leader with expertise environments; and engineering
in power distribution and services. Eaton is positioned
circuit protection; backup through its global solutions to
power protection; control answer today’s most critical
and automation; lighting and electrical power management
security; structural solutions challenges.
and wiring devices; solutions

Eaton medium voltage products in the energy chain

Mining
Power plants 2 3 5 6 7 8

Offshore and
Green energy marine 6 7
1 2 5
Infrastructure
2 3 5 6 7 8

Commercial buildings
1 2 4 5 6 7

Main
stations
Heavy industry 5 6 7 8
6 7 8 Distribution
substations
3 5 6 7 8 Shops and
offices

Transformer
stations 1 2
Residential
applications

Power generation Solutions and


Process Services
industry Industry
2 5 6 7 8 1 3 4 5 6 7 8
Green energy
1 2

1 Magnefix 2 Xiria (blocktype) 3 Xiria E (extendable) 4 Xiria M (metering solutions)

5 SVS 6 Power Xpert® FMX 7 Power Xpert® UX 8 MMS

The information provided in this document


reflects the general characteristics of the
Eaton Industries (Netherlands) B.V. referenced products at the time of issue and
P.O. Box 23 may not reflect their future characteristics.
7550 AA Hengelo Eaton Corporation reserves the right to
The Netherlands modify the contents of this document and
© 2015 Eaton Corporation the characteristics of the referenced
Tel.: +31 (0)74 - 246 40 10 All rights reserved. products without prior notification.
Fax: +31 (0)74 - 246 40 25 Eaton Corporation does not assume liability
info.electric@eaton.com Form No. BR02200010U_06 / 607.3141_06 for potential errors or omission of information
www.eaton.eu/xiria-e March 2015 in this document.