Documente Academic
Documente Profesional
Documente Cultură
Service Manual
MSII 6-10KVA
0
Table of Contents
2
Chapter 1 Product Introduction
1.1. Symbols on the LCD Display Panel
2 Battery Low
3 Battery Abnormal
4 UPS Overloading
3
17 Next Page
19 Enter or Re-confirm
4
1st stage DC BUS capacitor pre-charge
1 Er01 abnormal after 50 seconds or Battery Fuse
fails
5
ID Numbers are in conflict in Parallel System
17 Er17 or ID number Error in single unit
EEPROM’s data error. Its values are reset to
18 Er18 default.(Nomral/220V/adj0%/+/-3Hz/low
sensitivity)
19 Er19 Reserved
25 Er25 Reserved
6
35 CEr1 Utility voltage out of range
Remarks:
1:When one of the Er06, EPO, Er23, Er24, Er28, Er32 ,or Er33 error message
occurs, the UPS will have no output and lock itself immediately.(please refer
to Chapter 2.6.6)。
2:If the bypass voltage is normal(within specs), but one of the Er01, Er02, Er03,
Er05, Er13, Er14, Er20, Er22, Er26, Er29 or Er30 error message occur, the
UPS will transfer to Bypass loop and lock itself. (please refer to Chapter
2.6.6)。
3:If the bypass voltage is normal(within specs), one of the Er04, Er08, Er09,
Er10, Er11 or Er12 error message occurs, the UPS will transfer to Bypass
loop, then try to transfer back to Inverter mode automatically. If the symptoms
happen 4 times in one hour, the UPS will lock itself; otherwise, the error
messages and the times of the error messages will be clear and reset
automatically.
4:If the Er16, Er17, Er21, Er27, Er31 or Er34 error message occurs, the inverter
of the UPS will have no output and the user is prohibited to turn on the UPS
from the front panel.
7
1.2. Panel explanation
1.2.1. Front Panel Function Explanations
1 3 4 2 11 12
1 2 3 4 5 6 7
8
9
10
11
12
5 9 7 10 6 8
LCD Display
Green LED lights up to indicate the UPS has the capability to run under
redundancy mode.
Green LED steadily lights up to indicate that the utility input voltage is within
the window; the LED flashes flickeringly to indicate that the utility input
Go to next page
8
1.2.2. Rear Panel Explanation
G
T N V C o m m u n ic a t i o n N e t w o r k
R S 232
N o t I n te n d e d t o
T N V C o m m u n ic a t i o n
N e tw o rk
S lo t
E x t. B a t te r y
G
-
N
E P O
E P O
S lo t 2 (C H B ) S lo t 1 ( C H A )
S N M P A d a p t e r O n ly
I
F F
J
C B 2 C B 1
B y p a ss In p u t U t ilit y I n p u t
B reaker B reaker
SW 1
M anual By pa ss
U t i l it y I n p u t
B re a k er
K IN V I
E x te rn a l B a tte ry
L
G
-
O U T PU T IN P U T
G 2 N 22 L21 G 1 N 1 L12
L
E x te rn a l C h a rg e r L 2 1 - N 2 2 : U P S O U T P U T L 1 2 - N 1 : U T IL IT Y IN P U T
G 2 : O U T P U T E A R T H G 1 : IN P U T E A R T H
G R O U N D G R O U N D
+
-
H P
P A T. N O .:
U S 69 06 501 ,T W 2 026 68
PA T. N O .:
U S 6 906501, TW 2026 68
O
N o rm a l
T r ip
P
M
R T 10K G I J P
N
A
B
C D
F L
B A N P I
R T 6K
C G F L D E
9
A RS232 Port
B Terminal Resistor for Parallel function
C CAN Bus Connection Port for Parallel System
D Customer Options Slot 1
E Customer Options Slot 2
F Cooling Fan
G External Battery Connector
H External Charger Connector
I Utility Input Breaker CB1
J Bypass Input Breaker CB2(for Dual Input Model Only)
K CAM Switch(Maintenance Bypass Switch)
L Input/Output Terminal Block
M Fixing Holes for External Charger Cabinet
N EPO(Emergency Power Off): Short to enable the function
O Thermal breaker for the protection of Load in abnormal condition: CB3
P Air Ventilation Hole
10
1.3. Communication Port Explanation
When the optional interface cards are used together with onboard RS232
port in communication, the EPO signals will get the highest priority in control
command, then the SNMP/WEB card , then the shutdown command at the DCE
card & also R2E, RSE and USE, then onboard RS232 port get the lowest priority.
5
9 4
8
3
7 2
6
1
11
Pin 3: RS232 Rx
Pin 2: RS232 Tx
Pin 5: Ground
12
Chapter 2 Installation and Operation
The packing condition and the external outlook of the unit should be
inspected carefully before installation. Retain the packing material for future use.
2.1. Unpacking
RT model A 1 A 2 A 3
x4 x4 x1
B 1 B 2 B 3
fo r 2 U
fo r 3 U
x2
x2 x2
S 1 S 2 S 3 S 4
x2 x4 x8 x6
RT10K only
A 1 X 1
A 2 X 1
A 3 X 1
a) Package for the UPS with Isolation transformer & dual input:
Ditto, but with additional 3pcs wire No 7.
b) Package for the UPS without isolation transformer but dual input:
Ditto, but with additional 1pcs wire No. 7.
(p.s. Wire No. 7 is to be used at the input/output terminal block of the UPS.
Please refer to Chapter 2.4 for installation.
13
2.2. Selecting Installation Position
It is necessary to select a proper environment
to install the unit, in order to minimize the
possibility of damage to the UPS and extend the
life of the UPS. Please follow the advice below:
S 3
S 3 S 3
B 1 B 2 S 4 B 1 B 3 S 4
14
2.4. Terminal Block Explanation
Tower model
O U TP U T IN P U T
B Y PA S S (D IM T Y P E O N L Y )
IN P U T
G 2 : O U T P U T E A R TH G R O U N D L 1 2 -N 1 : U T IL IT Y IN P U T
G 1 : IN P U T E A R T H G R O U N D
RT6K model
RT10K model
TB1
TB2
15
● L11-N1: the terminal for Bypass Input to provide the power source when the
UPS is working under bypass mode.
● L12-N1: the terminal for Utility Input to provide the power source when the
UPS is working under Utility mode.
● G1: the terminal for UPS Input Ground.
● L21、N21、L22、L23、N22: the terminals for UPS Output.
● G2: the terminal for UPS Output Ground.
Remarks:
1. The maximum current for each terminal is 30Arms.
2. If the UPS is DIM(Dual Input) type, also Utility and Bypass Sources are the
same, you shall short L11 and L12 together.
3. If the UPS is SIM(Single Input) type, you can only supply AC source to UPS
from L12-N1 terminal.
4. When the Isolation transformer is NOT installed into the tower type UPS, the
UPS output terminals will be L22-N22.
5. When the Isolation transformer is installed into the tower type UPS:
a. For 100/110/115/120Vac system, you may connect as shown in below.
110Vac
6KVA (Max)
b. For 200/100Vac, 220/110Vac, 230V/115Vac, or 240/120Vac, or
240/208/120Vac system,
You may connect as shown in below.
16
● Use Mounting Cable Tie to fix cables.
Tower model 6000C model 6KRT model
E x te rn a l B a tte r y
E x te r n a l C h a rg e r
T1
10KRT model
5. Please refer to the specs of input current, output current and recommended
conductors listed as below :
17
2.6. Operation Test and Installation Instruction
A1.
A2
B.
18
2.6.1.5. Then, the UPS is on Bypass Mode now and it will proceed self-test
automatically. If there is no abnormal message occurred, it means the
pre-startup of the UPS is successful and the charger starts to charge
the batteries.
2.6.1.6. Press the UPS On Switch for approx. 3 seconds, then the Buzzer
sounds twice and the LCD display changes from drawing B to drawing
C.
2.6.1.7. Then, the UPS is under self-test mode again, the LCD display will
illustrate from drawing C to drawing D and remain approx. 4 seconds
under battery mode, then illustrate from drawing E1 to drawing F if the
self-test is successful.
* It shows “test”.
E1
E2
* It shows
“Fail” in self-test
19
F
2.6.1.8. In case of failure in self-test, the LCD display will illustrate from
Drawing D to drawing E2, then an error code or error status will be
shown on the screen.
2.6.1.9. Your start-up operation of the UPS is completely now. Make sure the
UPS is plugged onto the wall receptacle for charging at least 8 hours
and the batteries of the UPS are fully charged.
2.6.2.1. Make sure the UPS you have already been installed at least 1
set(20pcs) of 12V/7AH batteries.
2.6.2.2. Push the UPS On Switch once for approx. 5 seconds to awake the
UPS, and then the buzzer sounds twice. The LCD display will illustrate
from drawing A to drawing G, and keep awake for approx. 15 seconds.
2.6.2.3. Press the UPS On Switch of the UPS again for about 3 seconds till
the LCD display illustrates from drawing G to drawing H, then the UPS
will be in self-test Mode. The UPS may offer energy to the output in a
minute, and the LCD display illustrates as drawing I. In case of failure in
pushing the UPS On Switch within 15 seconds, the UPS will
automatically turn off. You then have to go through step 2.6.2.1 to
2.6.2.3 once again.
20
H
2.6.3.1. If you would like to check the measured values & figures detected by
the UPS, please use scroll up and scroll down key pads. When
you use scroll down key pad, the LCD display will illustrate in sequence
as Drawing C(Voltage from Utility Input) Drawing I1(Voltage from
Bypass Input) Drawing J(Frequency from Utility Input) Drawing
K(Frequency from Bypass Input) Drawing L(UPS Output Voltage)
Drawing M(UPS Output Frequency) Drawing N(UPS Output Load
%)Drawing O(UPS Battery Voltage) Drawing P(UPS Inner
Temperature).
I1
* It shows
frequency from Utility Input.
21
K
22
* It shows UPS Inner Temperature
2.6.4.1. After UPS completely starts up, press key pad to change the LCD
display screen to drawing Q1.
Q1
Q2
2.6.4.2. Press key pad to scroll down the screen and check the UPS
settings. The LCD display will show in sequence between Drawing
Q1(buzzer) Drawing R1(Self-test) Drawing S1(Bypass Voltage
Windows) Drawing T(Output Frequency Synchronization Window)
Drawing U(Inverter Output Voltage) Drawing V1(UPS Operation
Mode) Drawing W(Output Voltage Micro Tune Value) Drawing
X(UPS Id) Drawing Y(Parallel function status).
R1
23
R2
S1
S2
24
U
V1
V2
* It shows the
UPS is operated in “Eco mode”.
V3
V4
25
W
2.6.4.3. Press scroll up key pad, you may execute special functions. The
Functions includes buzzer ON (as drawing Q1), or buzzer OFF (as
drawing Q2, Alarm silence for UPS Warning) and self-test OFF (As
drawing R1) or self-test ON. (as drawing R2. UPS will execute battery
test for 10 seconds. If the self-test is successful, it will show as Drawing
E1; otherwise, it will show as drawing E2 & error message in the same
time.)
2.6.5.1. Make sure the UPS is not “On” yet. Press On Switch and scroll
down key pads simultaneously for approx. 3 seconds, the buzzer
will sound twice, the LCD display screen shows as drawing Q1, then the
UPS is under setting mode now.
26
2.6.5.2. To scroll down the LCD screen, you may refer to Chapter 2.6.4.2
2.6.5.3. Except Buzzer(as drawing Q1 & Q2) and Self-test(as drawings R1 &
R2), all the rest default settings may be changed by pressing scroll up
key pad.
2.6.5.3.1.Drawings S1 and S2 mean the bypass input acceptable window, it can
be 184Vac~260Vac or 195Vac~260Vac.
2.6.5.3.2.Drawing T means the bypass frequency window of the Inverter Output,
the acceptable setting values are ±3Hz and ±1Hz.
2.6.5.3.3.Drawing U means the acceptable Inverter Output Voltage, of which
voltage is 200Vac, 208Vac, 220Vac, 230Vac, or 240Vac.
2.6.5.3.4.Drawing V1, V2, V3 and V4 mean the operation modes of the UPS, of
which alternative is Online, Eco(Economic) mode, fixed 50Hz Output or
fixed 60Hz Output.
2.6.5.3.5.Drawing W means the adjustments of the Inverter Output, which may
be calibrated as 0%, +1%, -1%, +2%, -2%, +3%, or -3%.
2.6.5.3.6.Drawing X means a specified address & position of the UPS when the
UPS is in Parallel mode. The settable numbers are from 1st to 4th. The
number must be 1st if the UPS is not in parallel.
2.6.5.3.7.Drawing Y means the parallel function status. The “P 01” means parallel
function disabled and the “P 02” means parallel function enabled.
2.6.5.4. When all the setting changes are done, you have to press enter key
Pad to save all the changes when the LCD screen shows as drawing Z,
then, the LCD screen will show as drawing AA to complete the setting
changes. If you don’t want to change those settings, you may press
“OFF” key pads for 5 seconds, then the LCD screen turns to
Drawing AA directly, which means your setting changes are invalid.
AA
27
2.6.5.5. Turn Off the breaker of Utility Input.
2.6.5.6. Your Setting changes are complete.
2.6.6. UPS Is Off Due to Unknown Reason and Its Trouble Shooting
2.6.6.1. If there is a serious abnormal condition occurred, the UPS will lock it
itself in “OFF” position as shown in drawing AA and a abnormal
message will show on the LCD screen.
2.6.6.2. After 3 seconds, all messages will be locked except Bypass
messages(LED & LCD ). In case the Utility is abnormal after
the UPS is locked, the LED will be extinguished and the LCD
will be shown on the LCD screen.
2.6.6.3. To release the UPS lock, please proceed the followings:
2.6.6.3.1.Check those error messages recorded.
2.6.6.3.2.Check to see Chapter 1 to trouble shoot the problem of the UPS.
Otherwise, consult your local distributor for service.
2.6.6.3.3.Press Off key pad for 5 seconds and buzzer will sound twice.
2.6.6.3.4.Turn Off the Breaker of Utility Input.
2.6.6.3.5.The UPS lock problem is solved now but you shall contact with your
Local distributor to make sure the error message shown is solved.
2.6.7.1. Press Off key pad for about 5 seconds, the Inverter output will be
turned off, then the output load is supplied by Bypass loop and the LCD
screen shows as drawing B.
2.6.7.2. Turn Off the breakers of UPS Utility and Bypass Input.
2.6.7.3. The UPS is turned off completely.
28
2.6.8.1. It is for UPS maintenance only. A Non-authorized technician is not
allowed to operate the following procedures. If there is any damage
under unauthorized condition, your warranty will be void immediately.
2.6.8.1.1.Press the Off key pad for approx. 5 seconds, the LCD screen shows
as drawing B and the UPS output is on bypass mode.
2.6.8.1.2.Release the cover of the CAM Switch (Maintenance Bypass Switch)
first, then turn on the CAM Switch to “Bypass” mode, and at the right-
hand upper Corner of the LCD screen will show sign.
2.6.8.1.3.Turn off the UPS Utility breaker as well as Bypass Input Breaker, you
then may proceed UPS maintenance now.
2.6.8.1.4.To repeat 2.6.1.4, you may put the UPS back to normal working mode,
then turn back the CAM switch to “INV” mode, fasten back the cover
and repeat 2.6.1.5 to 2.6.1.9 The UPS will switch back to inverter mode.
2.6.8.1.5.It is required to go through 2.6.8.1.1 first, then go through 2.6.8.1.2 If
you skip 2.6.8.1.1., the UPS will alert for 10 seconds to warn that the
procedure is abnormal, which may damage the UPS due to uncertain
Utility status. The UPS will switch back to Inverter mode immediately if
you turn the CAM switch back to “INV”.
29
Chapter 3 System Block Diagram and PCB Wiring Diagram
Filter
d Bypass automatic
1 2
f
1
V2
b
Filter
h m
c g r
p Filter
2
SW 2
N
1 2 1 s
e n 2 1 T1 5
1
FU SE FUSE 3
V1 q UPS Output
Switch o 4
a 5 4 8
FU SE N 6
2
N i N
Charger
t u v w
1
k
1
l B ATTE R Y j B A TTE R Y
2
External battery module Internal battery Communication Extend solt Interface card Remote box
a. UPS Utility Input: to provide the AC source to the UPS rectifier circuit and
charger.
b. UPS Bypass Input: to provide the AC source to the UPS Bypass Input and
Maintenance Bypass loop.
c. UPS Utility Input Breaker: to protect the UPS Rectifier circuit from over-
current.
d. UPS Bypass Input Breaker: to protect the UPS Bypass circuit from over-
current.
e. EMI Filter on UPS Utility Input : to eliminate the magnetic interference from
AC Source or UPS Utility Input.
f. EMI Filter on UPS Bypass Input: to eliminate the magnetic interference from
AC Source or UPS Bypass Input.
g. Fuse for UPS Utility Input: to provide over-current protection for UPS
Rectifier Circuit.
h. Rectifier and Booster: When Utility is normal, they will converts the AC to DC
and correct input power factor. When Utility is abnormal, the batteries will be
boosted to provide the DC voltage to the Inverter.
i. Input fuse for Battery: to protect batteries when DC-Booster is out of order.
j. Charger: the battery charging device.
k. Internal Battery: When AC abnormal, it provide the backup power from the
batteries.
l. External Battery Bank: To provide longer backup time by adding additional
Battery bank.
m. Inverter Generator: To convert the DC voltage to AC voltage
30
n. Inverter Output Switch: Only when the UPS is overloaded or abnormal, or the
UPS is working on ECO mode or if EPO(Emergency Power Off) is activated,
the Switch will be opened.
o. Auto Bypass Loop: When the UPS is overloaded or abnormal, the UPS will
Switch the UPS from inverter output to bypass output automatically.
p. UPS Output Fuse: When the UPS is overloaded, the fuse will open.
q. UPS Output EMI Filter: To eliminate the magnetic interference from the UPS
Output and avoid the interference caused by the output load and the UPS.
r. CAM Switch(Maintenance Bypass Switch): Through this switch, the output
load can be supplied by Bypass Source, so a routine maintenance job can be
proceeded without interruption of the systems connected to the output.
s. UPS Isolation Transformer:
t. Communication: RS232 serial port & RJ45 parallel port with CAN technology.
u. Optional Slots: for variety use of interfaces provided such as SNMP card, 2 nd
RS232, USB, Relay Contact Board, etc.
v. Optional Interface Boards: WEB/SNMP card, Dry Contact Board, RS485
card, USB card, 2nd RS232 card, etc.
w. Remote Control Box: To provide remote monitoring and control functions.
31
3.2. Unit Wiring Diagram
3.2.1. The MSII6Kva UPS is composed of six(6) boards. Please find the description as
below:
Item Description Part No. Function UPS model
To generate all control
signals and also MSII 6K
1 Control MSDI0XX
AC/DC detecting MSII 10K
signals.
AC/DC、DC/DC、AC/
MSDD0XX AC and circuit MSII 6K
2 Power(Driver)
working power supply.
MSED0XX MSII 10K
MSII 6K
3 EPO MSXN0XX Emergency Power Off
MSII 10K
MSDM0XX To control and display MSII 6K
4 LCD Display
MSDM3XX UPS Status and values MSII 10K
MSII 6K
5 Charger MSDC0XX Battery Charger
MSII 10K
MSDF0XX UPS Input noise MSII 6K
6 I/P EMI filter filtering and surge
MSEF0XX protection MSII 10K
MSDF4XX UPS Output noise MSII 6K
7 O/P EMI filter
MSEF4XX filtering MSII 10K
8 DC Capacitor MSEB0XX DC Energy for Inverter
Suppress inrush
9 Relay MSEK0XX current from isolated MSII 10K
transformer
Protect output device
10 Fuse or Terminal MSEZ2XX or Terminal for power MSII 10K
connection
32
3.2.2. Unit Wiring Diagram of MSII 6K
To extend slot
RS-232
CN1 CN3 CN7
For PC MSDI0XX
MSDM0XX or
MSDM3XX
black/yellow
Flat cable shielding cable
blue/red
To cam switch CN24
black/red CN6 CN14 red
red CN7 To External Battery
and External Charger
CN3~5 CN23
CN2
CN10~12 black
CN13/14 CN6
CN7/9 CN1
CN8/11 CN10
CN2
To
Fan
Utility input
blue
brown
brown
brown
blue
brown
blue
blue
J2 J5
J1 J2 J4
J5/6 AC output
MSDF4XX
J1 J4
J2 J7/8
brown MSDF0XX
blue
Bypass input
blue
33
3.2.3. Unit Wiring Diagram of MSII 10K
To extend slot
RS-232
CN1 CN3 CN7 MSDM0XX or
For PC MSDI0XX
MSDM3XX
RJ-45 Flat cable
CN2 CN6
For parallel J2 J3
To cam switch
black/red black/yellow
orange/blue Connect tobether shielding cable
From transformer
blue/red
CN4
CN1 CN3 CN31 red CN14
red CN2 To Battery
MSED0XX
To Fan
CN12
CN5
MSDC0XX CN21
black white CN22
black
CN19
brown
red
CN24 W4 W3 CN26
CN20
Utility input
black
CN25
black
black
black
white
white
black
white
CN1 CN2
black
CN6 MSEB0XX MSEZ2XX
CN11 CN2 CN4 CN7
MSEF4XX Fuse
CN3 CN8 CN5
black
CN3 CN1
brown
AC output MSEF0XX
blue white
34
Chapter 4 Unit Test, Calibration Setting Explanation
4.1. VR Function Explanation
PCB Number Function Location
MSDC0XX Adjust Charger Output Voltage VR1
CHEC0XX Adjust Charger Output Voltage VR1
4.2.3. Overload time out versus Inverter mode and Bypass mode
35
4.2.4. DC BUS Voltage Regulation
200
205
220 341
225
230 360
235
240 370
245
385
36
4.3. Startup Procedure for Debug UPS
4.3.1. Connect an AC 220Vac/50(60)Hz onto L11 & L12.
4.3.2. Remove the output loads connected to the UPS and remove the battery
connecting wires of the UPS.
4.3.3. Remove the Fuse of utility input (MSII 6K : F2 of the MSDD0XX PCB, MSII
10K : F1 and F2 of the MSEF4XX).
4.3.4. Remove the control wires CN13 & CN14 of the MSDC0XX PCB and
measure the DC Bus voltage by using multi-meter.(MSII 6K-MSDD0XX
PCB: Bus + is to measure CN19 to the upper end of C38 and Bus – is to
measure CN19 to the upper end of C37, MSII 10K-MSEB0XX PCB : Bus +
is to measure CN1 to CN2 and Bus – is to measure CN2 to CN23.)
4.3.5. Turn off CB2 and turn on CB1.
4.3.6. Push key pad and key pad for approx. 3 seconds till buzzer beeps
twice, then the UPS will go to service mode.
4.3.7. Push key pad for a second till the buzzer beeps twice,and LCD
displays from Sr01 to Sr02. Measure the waveform of the PFC and
Inverter IGBT gate, it shall be a square wave with voltage/frequency at
-6Vdc ~ +15Vdc / 20KHz, then buzzer will beep once.
4.3.8. Push key pad for a second till buzzer beeps twice. The LCD displays
from Sr02 to Sr03, then the UPS proceeds the 1st stage soft start, which
means charger is charging the BUS + & -, then buzzer will beep once.
4.3.9. Push key pad for a second till buzzer beeps twice. The LCD displays
from Sr03 to Sr04, then the UPS proceeds the 2nd stage soft start, which
means battery SCR is turned on to charge the BUS + & -, then the buzzer
will beep once.
4.3.10. Push key pad for a second till buzzer beeps twice. The LCD displays
from Sr04 to Sr05, then UPS proceeds the 3rd stage soft start, which means
the DC voltage is boosted up to the desired voltage(Please refer to Chapter
4.2.4, the DC Bus Voltage Regulation) then buzzer will beep once.
4.3.11. Push key pad for a second till buzzer beeps twice. The LCD displays
from Sr05 to Sr06, then the UPS proceeds the voltage setting from Inverter
Soft Start to Inverter Output, then the buzzer will beep once.
4.3.12. Push key pad for a second till buzzer beeps twice. The LCD displays
form SR06 to OFF, then the UPS proceeds DC Bus discharging. The UPS
will shut itself off automatically after discharged.
4.3.13. Turn off CB1 and put the Fuse of utility input back.
4.3.14. Turn On both CB1 and CB2.
4.3.15. The LCD displays “oFF”, then measure the output of the UPS is nominal
voltage such as 220Vac/50(60Hz) or not.
4.3.16. Adjust the voltage of Bypass Input at 170Vac/50(60)Hz and check if the
UPS output voltage is near 0Vac?
37
4.3.17. Adjust the voltage of Bypass Input at nominal voltage such as
220Vac/50(60)Hz.
4.3.18. Push key pad for 3 seconds until buzzer beeps twice, then the UPS
proceeds AC start procedure. When self-test is executed completely, the
UPS will switch from bypass output to Inverter output. Measure the UPS
output waveform to see whether it is stable.
4.3.19. Change the frequency of Utility to 56Hz, the UPS will switch to Backup
Mode automatically.
4.3.20. UPS will go back to Utility mode once the Utility frequency goes back to
50Hz.
4.3.21. Connect the control wire of the Charger and push the function key to
execute self-test, then the UPS will detect this abnormal condition and
display battery abnormal on the LCD.
4.3.22. Use Scroll up key pad and Scroll down key pad to see if any
abnormal display content or values on the LCD panel.
4.3.23. Push key pad for 5 seconds until buzzer beeps twice, then UPS will
shut off and close the input of Utility.
4.3.24. Your UPS Unit test is done completely.
PC
Fig 4.4-138
4.4.2. Disconnect the isolation transformer if any; otherwise, it is not possible to
measure whether the UPS output waveform is in balance or not.
4.4.3. Connect a 220Vac/50(60)Hz to the UPS to start up the UPS and make sure
it is on Line Mode.
4.4.4. Without output load connected, please connect a fixture in parallel.(The
fixture is made with 1M ohms resistors and 1uF/63V capacitor in serial. Then,
measure the two ends of 1uF/63V capacitor to see whether the DC voltage is
below 20mV.
4.4.5. Connected a 6Kva/4200W resistor load to the output and repeat 4.4.4
39
Setting parameter and command
Setting Calibration
parameter
Calibration
Step 1
Calibration
Step 2
Fig 4.5.1
4.5.1.4. Enter the desired parameter to the “Setting parameter and command”,
of Fig 4.5.1. then click “write” icon.
4.5.1.5. If buzzer beeps twice, it means your setting is successful.
4.5.1.6. If the buzzer beeps continuously, it means your setting is in failure.
Please repeat 4.5.1.2 to 4.5.1.5 For error message, please refer to 1.1..
4.5.2. Calibration: It is divided into two parts, one is front panel calibration and the
other is PC calibration
Notice :
The calibration with load connected doesn’t include the power loss of
the galvanic isolation transformer; therefore, the load can only be
connected behind the output filter as indicated as A & B(the UPS with
galvanic isolation transformer or the output terminal bar(the UPS
without galvanic isolation transformer.)
40
A B
Notice :
For No load Inverter calibration, you are required to use the setting
software to do it. The Calibration from the front panel is just only for the
calibration with load connected.
41
key:+/- adjustment
key:next item
key:Your adjustments are done completely, new data is written into EEPROM,
then Escape from the Calibration mode. If the UPS beeps twice, it means
your Setting is successful; on the contrary, if the UPS beeps continuously, it
means your setting is in failure.
key:Give up this calibration and turn off the UPS.
Adjustable Parameters:
Adjustable Items Specifications Remarks
AC Input Voltage 220Vac Including Rectified & Bypass input
Inverter Voltage 220Vac
Load % >30%
Battery Voltage 273.7Vdc
4.5.2.1.5.The UPS will escape from the calibration mode if the calibration is not
finished in 10 minutes and go to shutdown automatically and show “Line
OFF” on LCD panel.
4.5.2.1.6.Tuning the values shown on the LCD display are the same as that on
the meter, then you may go to next Calibration item.
4.5.2.1.7.The load% on LCD panel means the higher value of VA or W; therefore,
you are recommended to use Resistance Load to go for calibration. To
make sure the calibration is precisely, you are also recommended to use
full load to calibration the UPS(MSII 6K : 6KVA/4.2KW,MSII 10K:
10KVA/7KW).
4.5.2.1.8.The sequence of the LCD display is shown as Output VoltLOAD%.
4.5.2.1.9.After all the items desired are calibrated, press key and write them
into EEPROM.
4.5.2.1.10. When the UPS beeps twice, the UPS will go to shutdown and show
“Line OFF”on the LCD panel. And then re-start the UPS to check if all
values which have been calibrated on the LCD panel is the same as
those on the Power Meter.
4.5.2.1.11. If the buzzer beeps intermittently and continuously, it means your
calibration is in failure. Please repeat 4.5.2.1.1 to 4.5.2.1.10(Please
refer to Chapter 1.1 Error code).
42
Caution:
You are suggested to connect with 80% to 100% load in order to make sure the
tolerance of the calibrated values will be smaller and the values will be more
accurate. All values can be calibrated except the value of load% if the output
load of UPS are less than 30% when you proceed calibrated action.
Make sure the tolerance of the adjustable range will be less than 8% for
Voltage and 15% for Load; otherwise, the setting will be in failure and the
error code will be shown on the LCD panel.
The values of both “load%” and “output voltage” must be round to Integer.
4.5.2.2. PC Calibration
4.5.2.2.1.Execute step 4.5.2.1.1 to 4.5.2.1.3
4.5.2.2.2.The adjustable parameters are the same as that in the chapter 4.5.2.1.
4.5.2.2.3.Set the communicaton baud rate to 2400. Set “With Transformer” in the
calibration setting to “No” as shown below.(Only the one with MS20068B
and MS30068B program is required to proceed this setting.)
2400 (Megatec)
43
MS30068B MS3006B8
2400(Megatec)
2400(Megatec)
4.5.2.2.10. Fill the output voltage measured by the power meter to Fig4.5-1
Calibration Step2, then click ”Calibration2” icon .
4.5.2.2.11. Press Calibration 2 icon after the figure is filled, then buzzer will beep
twice to show the calibration is complete.
4.5.2.2.12. After calibration, the output voltage will be changed and remained for
approx. 4 seconds. Please quickly check with Power meter if the output
voltage shown as below:
4.5.2.2.12.1. The output voltage shall be 220.7 +/-0.3V (220.4V~221.0V) if no
transformer is installed.
4.5.2.2.12.2. Othewise, please refer to the followings if there is a transformer
installed.
44
4.5.2.2.13. The UPS will shut off automatically once the output voltage is changed
over 4 seconds. It means your calibration is compelete.
4.5.2.2.14. In case if the output voltage is not matched with 4.5.2.2.12, it means
the calibration is in failure. You have to shut off the UPS, and repeat
4.5.2.2.2 to 4.5.2.2.12
Caution:
You are suggested to connect with 80% to 100% load in order to make sure
the tolerance of the calibrated values will be smaller and the values will be
more accurate. All values will be calibrated except the value of load% if the
output load of UPS are less than 30% when you proceed calibrated action.
Make sure the tolerance of the adjustable range will be less than 8% for
Voltage and 15% for Load; otherwise, the setting will be in failure and the
error code will be shown in the LCD panel.
The UPS will escape from calibration mode if the setting is not complete in
10 min. after the UPS is in the calibration mode.
The values of both “load%” and “output voltage” must be round to Integer.
The input voltage in the Calibration2 shall be accurate; therefore, make
sure you will round the value to 1st decimal place.
4.5.3. The Calibration procedure for the output voltage of UPS without load.
4.5.3.1. The maximum output voltage in difference for each UPS in parallel
system shall not be excessive 1V when they are connected at NO load;
otherwise, the UPSs will fail in parallel connection. As long as the
greatest difference between the lowest-voltage UPS and the highest-
voltage UPS at no load is over 1V, you are required to proceed the
Output Voltage Calibration procedure.
4.5.3.2. Execute 4.5.2.2.2~4.5.2.2.3
4.5.3.3. Click ”Skip Step1” icon, then execute 4.5.2.2.8~4.5.2.2.14
4.5.3.4. The calibration for the output voltage at no load is compelete.
45
The Wiring Diagram of the Transformer(The red lines indicated below are for the
connections of the no load in calibration.)
Fig 4.5-2 The turns ratio of Primary and Secondary of the transformer is 1 to 1.
46
Input Coil、 0V~240V, Output Coil、0V~120V
Calibration2 Block、I/P Voltage Else system、O/P Voltage 120V system
Fig 4.5-3 The turns ratio of primary and secondary of the transformer is 2 to 1.
Fig 4.5-4 The turns ratio of Primary and secondary of the transformer is 1 to 1.
Fig 4.5-5 The turns ratio Primary and Secondary of the transfomer is 208 to 120.
47
4.6. Frequency Converter(CVCF Mode)Setting Notice
4.6.1. The UPS can be set as Frequency Converter(CVCF mode). If the UPS is
Dual Input Model, you have to make sure the Bypass Input Breaker is set at
“OFF” position; on the contrary, if the UPS is Single Input Model, you have to
remove the power wire of the Bypass Input. (Of which location is between the
CN16(or CN22) of the power board MSDD0xx and the J4 of the filter board
MSDF4xx for MSII 6K, Of which location is between the CN25 of the power board
MSED0xx and the CN6 of the filter board MSEF4xx for MSII 10K.)
48
Chapter 5 Customer Options Slots
5.1. R2E(2nd RS-232 ) card
5.1.1. CN1 is for RS232 DB9.
5.1.2. For communication protocol, please
refer to Chapter 1.3.1
5.1.3. Installation Position: slot1(CHA-CN4)
or slot 2(CHB-CN5).
5.2.1. CN1 is for the function of the terminal resistor. Short pin1-2 to enable the
function and short pin2-3 to disable it.
5.2.2. CN2 for RS485 and CN3 for remote power.
5.2.3. Definition
CN2
1 2 3 1 Ground
2 A/Data+
3 B/Data-
CN3
1 2 1 AC+
2 AC-
5.2.4. Installation Position: slot1.
49
5.3. USE(USB) card
5.3.1. CN1 for USB.
5.3.2. Definition
5.3.2.1. Comply with USB version
1.0,1.5Mbps
5.3.2.2. Comply with USB HID Version 1.0.
5.3.2.3. The Pin Assignments of the USE card:
1 VCC (+5V)
2 D-
3 D+
4 Ground
1 2 3 4 5 6 7 8 9 10
5.4.2. The shutdown function will be activated, after a +6~+25Vdc is put between
pin9 and pin10 for 5 seconds.
5.4.3. The capacity of each relay contact is 40Vdc/25mA.
5.4.4. Installation Position: slot1(CHA-CN7) or slot 2(CHB-CN8).
5.4.5. Flexible signal output for N.C.(Normal close) or N.O.(Normal open) contact
by shorting pin1-2 or pin2-3 from JP1-5.
5.4.6. The shutdown function will be enabled in 1 minute after blackout occurs if
the pin1-2 of both CN1 and CN6 be shorted by cap. Or, the shutdown function
can only be enabled by pin9-10 of CN3 if the pin2-3 of both CN1and CN6 be
shorted by cap. (Refer to 5.4.2)
50
5.5. SNMP Cards
5.5.1. SNMP/WEB card
5.5.1.1. For installation, please refer
to the user’s manual
attached with the card. .
5.5.1.2. InstallationPosition: slot
2(CHB).
51
The Installation of those Interface Cards
52
Chapter 6 Hot Swappable Battery Replacement
1. Unscrew the bottom of the front panel as indicated in Step. 1 as below.
2. Remove the front panel as indicated in Step 2.
53
6. Turn the battery pack handle at 90 degree as shown in Step 6.
7. Remove the battery packs from the UPS as shown in Step 7.
54
Chapter 7 Trouble Shooting
If there is a abnormal condition occurred, the LCD display will show an error code
as indicated at Chapter 1.1. Please follow the troubleshooting indicated below.
55
7.1. Error Code Er01
7.1.1. Definition:The UPS is in the 1st stage soft start procedure, but the DC bus
voltage can not reach 50Vdc within 5 seconds, or can not reach anticipative
charging voltage (about either present 80% of battery voltage or present output
voltage of charger) within 30 seconds.
7.1.2. Flow Chart
56
57
7.2. Error Code Er02
7.2.1. Definition:The UPS is in 2nd stage soft start procedure, but the DC Bus
can not reach and maintain anticipative charging voltage after 2 seconds (approx.
present 85% of peak voltage of utility, either present 80% of battery voltage or
output voltage of charger)
7.2.2. Flow Chart
58
7.3. Error Code Er03
7.3.1. Definition:The UPS is in 3rd stage soft start procedure, but the DC bus
voltage can not reach to anticipative charging voltage within 30 seconds (Please
refer to Chapter 4.2.4) 。
7.3.2. Flow Chart
59
7.4. Error Code Er04
7.4.1. Definition:It means the UPS Inverter Output is Abnormal.
7.4.2. Flow Chart
60
7.5. Error Code Er05
7.5.1. Definition:It means the battery is weak or bad after self test is executed.
7.5.2. Flow Chart
61
7.6. Error Code Er06
7.6.1. Definition:It means the UPS is protected from short-circuited.
7.6.2. Flow Chart
62
7.7. Error Code EPO
7.7.1. Definition:It means the UPS enters into EPO(Emerge Power Off)mode.
7.7.2. Flow Chart
63
7.8. Error Code Er08
7.8.1. Definition:It means the DC Bus of the UPS is protected from over-
voltage.
7.8.2. Flow Chart
64
7.9. Error Code Er09
7.9.1. Definition:It means the DC Bus of the UPS is protected from under-
voltage.
7.9.2. Flow Chart
65
7.10. Error Code Er10
7.10.1. Definition:It means the UPS Inverter is protected from over-current.
7.10.2. Flow Chart
66
7.11. Error Code Er11
7.11.1. Definition:It means the UPS is protected from over-heat.
7.11.2. Flow Chart
67
7.12. Error Code Er12
7.12.1. Definition:It means the UPS inverter is protected from overloaded.
7.12.2. Flow Chart
68
7.13. Error Code Er13
7.13.1. Definition:It means the charger is out of order.
7.13.2. Flow Chart
69
7.14. Error Code Er14
7.14.1. Definition:It means the fan of the UPS is abnormal.
7.14.2. Flow Chart
70
7.15. Error Code Er15
7.15.1. Definition:It means Maintenance Bypass Switch(CAM Switch) is not
used properly, or the Maintenance Bypass Switch is activated when the
UPS is in CVCF mode.
7.15.2. Flow Chart
Er15
It is just a procedure
error message of
maintenance bypass
END
71
7.16. Error Code Er16
7.16.1. Definition:It means the output parameter set error in parallel system.
7.16.2. Flow Chart
72
7.17. Error Code Er17
7.17.1. Definition:It means the ID number is in conflict in parallel system or ID
number error in single unit.
7.17.2. Flow Chart
73
7.18. Error Code Er18
7.18.1. Definition: It means the data inside of the EEPROM on the control board
is abnormal and the data is set as default values.
7.18.2. Flow Chart
Er18
Re-calibrate MSDI0XX
PCB by MSDN2XX PCB
and re-setup UPS or replace
MSDI0XX PCB
END
74
7.19. Error Code Er20
7.19.1. Definition:It means the capacitor in the DC Bus of the UPS can not be
discharged.
7.19.2. Flow Chart
75
7.20. Error Code Er21
7.20.1. Definition:It means the communication error in parallel system or can’t
find the UPS which ID =1.
76
7.21. Error Code Er22
7.21.1. Definition:It means the SCR in UPS bypass loop or the output fuse is
abnormal.
7.21.2. Flow Chart
77
7.22. Error Code Er23
7.22.1. Definition:It means the SCR, Relay of the UPS in Inverter loop or output
fuse is abnormal.
7.22.2. Flow Chart
78
7.23. Error Code Er24
7.23.1. Definition:It means there is voltage in bypass loop when the UPS is
operated in CVCF mode.
7.23.2. Flow Chart
Er24
Remove input
source from L11
terminal
END
79
7.24. Error Code Er26
7.24.1. Definition:It means the PFC of the UPS is protected from over-current.
7.24.2. Flow Chart
80
7.25. Error Code Er27
7.25.1. Definition:It means the UPS isn’t operated in normal mode in parallel
system.
7.25.2. Flow chart
81
7.26. Error Code Er28
7.26.1. Definition:It means when the UPS is operated in bypass mode, there is
an overload time out occurred. (Please refer to Chapter 4.2.3)
7.26.2. Flow Chart
82
7.27. Error Code Er29
7.27.1. Definition:It means the charger voltage is higher than 300Vdc and the
charger is been off.
7.27.2. Flow Chart
83
7.28. Error Code Er30
7.28.1. Definition:It means the inverter balance error over than 30 seconds.
7.28.2. Flow Chart
84
7.29. Error Code Er31
7.29.1. Definition:It means the capacity of driver board is less than control
board setting value.
85
7.30. Error Code Er32
7.30.1. Definition:It means the signal of sync error occurred in communication
for parallel function.
7.30.2. Flow Chart
86
7.31. Error Code Er33
7.31.1. Definition:It means the isolated transformer of the UPS is protected
from over-heat.
7.31.2. Flow Chart
87
7.32. Error Code Er34
7.32.1. Definition:It means the balance function conflict in parallel system.
7.32.2. Flow Chart
88
7.33. Calibration Error Code CEr1
7.33.1. Definition:It means the input voltage of the UPS is excessive of
adjustable range.
7.33.2. Flow Chart
89
7.34. Calibration Error Code CEr2
7.34.1. Definition:It means the bypass input voltage of the UPS is out of
adjustable range.
7.34.2. Flow Chart
90
7.35. Calibration Error Code CEr3
7.35.1. Definition:It means the Inverter Output Voltage of the UPS is out of
adjustable range.
7.35.2. Flow Chart
91
7.36. Calibration Error Code CEr4
7.36.1. Definition:It means the output load level of the UPS is out of adjustable
range.
7.36.2. Flow Chart
92
7.37. Calibration Error Code CEr5
7.37.1. Definition:It means the battery voltage of the UPS is out of adjustable
range.
7.37.2. Flow Chart
93
7.38. Calibration Error Code CEr6
7.38.1. Definition:It means the output voltage of the UPS is out of adjustable
range.
7.38.2. Flow Chart
94
Chapter 8 Appendex A
8.1. PCB Installation Position
8.1.1. The PCB of MSII 6K Installation Position
MSDI0XX PCB
MSDD0XX PCB
MSDC0XX PCB
MSDF0XX PCB
MSDF4XX PCB
MSXN0XX PCB
MSDM0XX PCB
NET AGENT II
95
8.1.2. The PCB of MSII 10K Installation Position
MSDI0XX PCB
MSED0XX PCB
MSEZ2XX PCB
MSEB0XX PCB
MSDC0XX PCB
MSEF4XX PCB
MSXN0XX PCB
MSEF0XX PCB
MSEK0XX PCB
MSDM0XX PCB
NET AGENT II
YL-3
96
8.2. The PCB of MS6KRT & 6000C Installation Position
MSDI0XX PCB
MSDF0XX PCB
MSDD0XX PCB
MSDC0XX PCB
MSDF4XX PCB
MSDM3XX PCB
MSXN0XX PCB
97
8.3. The PCB of MS10KRT Installation Position
MSDI0XX PCB
MSED0XX PCB
MSDF4XX PCB
MSEF0XX PCB
MSXN0XX PCB
MSEB0XX PCB MSDC0XX PCB
98
8.4. PCB Placement
8.4.1. MSDI0XX PCB
99
Internal power ckt
Inverter choke
PFC choke boost choke
Inverter choke
100
Rectifier PFC & booster Inverter Inverter SCR Bypass SCR
Inverter relay
Internal power ckt
101
Rectifier PFC & booster Inverter Bypass SCR Inverter relay
Inverter SCR
8.4.4. MSDC0XX PCB
102
8.4.5. MSDM0XX PCB
103
MSDF0XX PCB
104
8.4.7. MSEF0XX PCB
105
8.4.8. MSDF4XX PCB
106
8.4.9. MSEF4XX PCB
107
8.4.10. MSEB0XX PCB
108
8.4.12. MSEK0XX PCB
109
Chapter 9 Appendex B – Parallel System Installation Guide
9.1. Important Safety Instruction
9.1.1. A professional technician is required while installing those UPS.
9.1.2. Read the Installation guide carefully before those UPS are installed, so as
to avoid any potential installation procedure error occurred to cause injury in the
personnel or damage in the UPS
9.1.3. Because of “LITTLE LEAKAGE CURRENTS” generated by the EMI filter of
the UPS, it is necessary to double ensure if the earth of the UPS is properly
grounded before AC Mains is connected with.
9.1.4. The parallel function of the UPS can only be enabled in Normal Mode.
9.1.5. Before any parallel installation is proceeded, make sure the difference of
the inverter voltage of each UPS in parallel at NO load shall be less than 1Vac.
Please consult with authorized dealer if the voltages in difference are over 1Vac
9.1.6. Make sure the RJ45 communicating wire is connected tightly during parallel
mode; otherwise, it might cause outage or damage of both the UPSs and the
output device.
9.1.7. Only two terminal resistors on the rear panel of the two(2) or four(4) of the
UPS in parallel shall be set at “On” position and the rest of them shall be set at
“Off” position; otherwise, the parallel operation of those UPS might be abnormal
or damaged.
9.1.8. Make sure those UPS in parallel are with the same ratings and types. For
instance, the UPS without galvanic transformer can not be in parallel with the
UPS with galvanic transformer. While installing those UPS, please add a
40Arms/250Vac and 30Arms/250Vac NFB(Non-fuse Breaker)at the input and
output of each UPS to avoid any potential hazard when the UPS is in the
maintenance mode.
110
9.2. Parallel System Installation Operation
T1 X 4
T2 X 4
T3 X 1
C 1 X 1
C 2 X 1
F1 X 1
9.2.2. Selecting Installation Position
Air flow in
Fig. 9-1
111
9.2.2.1.2.The design of the air flow of the convertible UPS is to flow in from the
front ventilation holes to the rear ventilation holes as indicated in Fig.
9.2. Air flow
in
Air flow
out Fig. 9-2
9.2.2.2. Select an installation position with at least 30 cm around the UPS and
Battery bank , where may provide a good ventilation condition as
indicated in Fig. 9-3.& 9-4
112
9.2.2.3. After the installation position of the UPS is properly arranged, Please
lock the casters of the UPS firmly as indicated in Fig. 9-5.
Fig. 9-5
9.2.3.1. Make sure those wires & cables used in the input, output and battery
are separately installed. Do not intercross or mix those wires & cables
together to avoid from any unnecessary noise interference.
9.2.3.2. The communication connecting wires for parallel function and other
wires for control signals, including RJ45, RS232, RS485, USB, EPO
and Shutdown shall be kept away from those wires and cables
mentioned in 9.2.3.1. If there is no possibility to avoid such from
happening, please put them at 90 degree or least distance 20cm as
indicated in Fig. 9-6.
20cm
90°
A
A B
B A B
Incorrect Correct
A Communication or Control signal wires
B Power wires & cables
Fig. 9-6
9.2.3.3. Because of “Little Leakage Currents” generated by the EMI filter of the
UPS, it is necessary to double ensure if the earth of the UPS is properly
grounded and the current leakage breaker is installed before AC Mains
is connected with or the output device is connected to the UPS.
113
9.2.3.4. Please refer to the specs of input current, output current and
recommended conductors listed as below:
114
9.2.4. Start-up Operation Procedure
I O I O I O I O
INPUT OUTPUT
Max. 25M; all Input Power cables shall be with the same
length.
Max. 25M, all Output Power cables shall be with the same
length.
Fig. 9-7
115
9.2.4.3. Arrange the power cables and wires as well as the control signal wires
as indicated in Fig. 9-8, 9-9, 9-10, then make sure all the circuit breaker
at input & output ends are set at “Off” position.
9.2.4.4. For maintenance purpose, you are recommended to purchase a MTBS
box.
9.2.4.5. Set two terminal resistors of two of four UPS at “On” position as
indicated in Fig. 9-8, &. 9-9.
9.2.4.6. Turn on the input breaker (CB1 and CBi) of the Utility, all the
parameters of those UPS in parallel shall be set the same, then set the
parallel mode as well as the IDs of the UPS.
9.2.4.7. Reset all UPS and make sure them at “OFF” status.
9.2.4.8. If there is the MTBS box installed, make sure the switch is on “Bypass”
position. Check to see if the UPS is on Bypass mode with output
voltage available.
9.2.4.9. Turn on the output device (CB2) and the output device is supplied by
the MTBS Box.
9.2.4.10. Turn on the output breaker of those UPS (CBo) and turn the switch of
the MTBS Box at “UPS” position. The output device is supplied by the
UPS Bypass loop.
9.2.4.11. Turn on those UPS individually and make sure those UPS are in
Inverter mode.
9.2.4.12. Your installation operation is complete.
116
Set the two terminal resistors of two(2) or
four(4) UPS to at “On” positions.
T
1
CBo
CBo
CBo
CBo
CBi
CBi
CBi
CBi
CB2 CB1
Load MTBS BOX Utilit
y
Fig. 9-8
117
Set the two terminal resistors of two(2) or
four(4) UPS to at “On” positions.
CBi
T2
T3
T2
T2
CBi
T2
T2
CBo
CB2 CB1
MTBS BOX
Load Utility
Fig.9-9
118
Be careful
F1
Fig. 2-10
119
9.3. Maintenance Operation Procedure
9.3.1. Please refer to the user manual of the UPS to make all UPS switch to
bypass supply mode.
9.3.2. Please switch MTBS BOX to BYPASS position first. And then switch off all
output breakers( CBo). Now the load is supplied through MTBS BOX
from Bypass.
9.3.3. Please make sure the UPS which needs to be maintained is completely
shutdown first. And then switch off the output breakers(CBo) and input
breakers(CBi). Now you can maintain them.
9.3.4. Please repeat 9.2.4.3 to 9.2.4.12 to make sure the load is supplied from the
UPS now..
9.3.5. The maintenance work is finished.
120