Documente Academic
Documente Profesional
Documente Cultură
Table of Content:
A. Protection Relays Setting on 132kV Transformer Relay Panels for Transformer Bays
E01, E03, E06, and E08
B. Protection Relays Setting on 132kV Line Relay Panels for Line Bays E07 (132kV NRW-
2) and E09 (132kV NRW-4).
C. Protection Relays Setting on 132kV Line Relay Panel for Line Bay E02 (132kV
Badomali Line BDL-1).
D. Protection Relays Setting on 132kV Relay Panel For Line Bay E04 (132kV NRW-1)
Note:
Protection Relay Settings on 15kV System are required to be coordinated with given below 132kV
Protection Relay Settings.
Comments on Rev-3:
1. Settings are revised after recommended revised settings given by WAPDA in letter Ref#
GM(WPPO)/CE-IV/13827-29 for OC &EF relays of Bay E02(Badomali line BDL-1) , E04(Narowal
line NRW-1) and Step up Transformer Bays E01,E03,E06 & E08.
2. Settings are revised to correct some typographical mistakes of rev-1, in OC & EF relay settings
of Buscoupler Bay.
Comments on Rev-4:
1. After meeting with IE of Fichtner GmbH on 25-02-2011, new setting Id>>= 8 x Iref for
transformer differential relay MiCOM P631and I>= 1.0 x In with TMS= 0.27 for transformer
overcurrent relay MiCOM P122 for all four transformers have been decided.
Location:
132kV Transformer Relay Panels: =E01+R1, E03+R1, E06+R1, E08+R1.
CT Ratios For Differential Protection (Similar For All 132kV Transformer Bays)
HV 132kV Transformer Feeder CT : 400/1, 5P20
LV 15kV Transformer Feeder CT: 3000/1, 5P20
MiCOM P631 provides a very fast differential protection function. With automatic CT ratio matching and
vector group compensation, makes this relay an ideal solution even for the most demanding applications.
The individual reference currents for each winding of the transformer are calculated by P631 on the basis of
the set reference power and the set primary nominal voltages of the transformer.
Where:
The P631 calculates the matching factors on the basis of the reference currents and the set nominal currents
of the system current transformers.
kam,a= 1.306
kam,b = 1.113
Where:
Differential Setting:
2) Idiff>
3) Idiff>>
4) Idiff>>>
5) m1
6) IR,m2
7) m2
1) Idiff>:
Differential initial setting should be set above the steady-state magnetizing current of the transformer.
Unbalance current checking in regarding with the tap changer position on highest (1) and lowest (17) tap
positions.
Secondary current at highest tap & lowest tap position with selected CT multiplier:
= 0.99958 x Iref
Differential Current on highest and lowest tap position with selected CT Multiplier:
2.) Idiff>>
This setting is to be set just above the inrush current rms value so that blocking of the triple slope
characteristic by second harmonic restraint or by saturation detector is removed.
Normally the transformer Inrush current may go from 4-8 times the rated current.
In order to prevent transformer from false tripping which may be possible if inrush current is higher, Setting
of 8 x Iref = 2.450 kA is recommended by Independent Engineer ( Fichtner GmbH) ,
We can verify the setting if { 2-phase min short circuit current )/ Set value} >= 1.5
Therefore , 3-phase short circuit value from 3 generators = 132000/ (1.732 x 86.35)= 0.88kA
With all four trafo, we have
3-phase short circuit value = 0.88kA x 4= 3.52 kA
Three phase min short circuit current at 132kv side = 7.1 kA ( contribution from Wapda and generators both)
Since by exclusive case (the energizing only from the system without any transformer with generators),
3.1kA/ (8xIref) = 3.1kA/2.450kA=1.26 which is less than 1.5 but > 1.2.
By operation only one transformer two phase short circuit current will be = {(Root3) x (7.1 – (3 x 0.88)) =
3.88kA
Since 3.88kA/(8 x Iref)= 3.88/2.450= 1.58 which is > 1.5
Hence the selected setting has the necessary sensitivity in most possible cases - it is in order
Id>> = 8 x Iref
3.) I diff>>>
This is a simple instantaneous unrestrained highest differential over current setting. It is not influenced by
restraining current (triple slope characteristics), harmonic restraint, overfluxing restraint or saturation
detector. Hence for fast fault clearance, Id>>> could be set below the current for a fault at the transformer
terminals. Such a fault involves the bus fault level as it is not limited by the winding impedances.
This is set greater than the transformer inrush current and below the fault at the transformer terminals.
Idiff>>> should be less than 20.07 x Iref. Hence the selected setting
Idiff>>> = 8 x Iref
4) m1
This is the second section of the tripping characteristic covers the load current range, so that in this section
we must reckon not only with the transformer magnetizing current, which appears as differential current, but
also with differential current that can be attributed to the transformation errors of the current transformer sets.
The second section of the tripping characteristic forms a straight line, the slope of which should correspond
to the cumulative total error of the participating current transformer sets. The curve slope m1 can be set.
The differential and restraining current variables for each measurement system are calculated from the
current variables after amplitude and vector group matching. The Following equation is used to calculate the
differential and restraining current.
Differential current on highest and lowest tap position with selected ct multiplier:
As calculated above,
Differential current on highest tap position = 0.1863 x Iref
Therefore:
For highest tap position: IR = 0.9541 x Iref, & Idiff = 0.1863 x Iref
For Lowest tap position: IR = 1.0551 x Iref & Idiff = 0.2167 x Iref
Therefore:
For highest tap position: IR = 0.9541 x Iref, & Idiff = 0.3888 x Iref
For Lowest tap position: IR = 1.0551 x Iref & Idiff = 0.4090 x Iref
It is clear from above values that the differential current on relay during full load current on highest and
lowest tap positions of the transformer is outside the operating region with selected Id>=0.22 and m1= 0.2
Hence the selected setting
m1= 0.2
5) IR,m2
This is the second knee point of the tripping characteristic determines the end of the overcurrent zone in the
direction of increasing restraining current in fault free operation.
It is recommended to set half the maximum through fault current.
Max through fault current = rated current at lowest tap / % imp of trf at lowest tap
= 340.2/0.1310
= 2.597kA
Corresponding ct secondary current = (2597/400) x 1.306 = 8.479 x Iref
Max through fault current = rated current at highest tap / % imp of trf at highest tap
= 278.3/0.1445
= 1.926kA
Corresponding ct secondary current = (1926/400) x 1.306 = 6.288 x Iref
Half the max. through fault current on lowest tap position = 8.479/2 = 4.24 x Iref
Half the max. through fault current on highest tap position = 6.288/2 = 3.144x Iref
Therefore 4.24 to be set based on half the maximum through fault current.
6.) m2
The third slope m2 characteristics are to accommodate ct errors during heavy through fault conditions. There
is no specific advantage in setting the slope m2 very closer to the through fault operating conditions. It is
desirable to give a safety factor 1.5 for the differential current.
Max through fault current at lowest tap position = 8.479 x Iref (as calculated above)
Max through fault current at highest tap position = 6.288 x Iref (as calculated above)
Max through fault current at highest and lowest tap positions at LV side:
Therefore:
For highest tap position: IR = 6.6025 x Iref, & Idiff = 1.935 x Iref
For Lowest tap position: IR = 8.054 x Iref & Idiff = 2.482 x Iref
The following equation is used to calculate the boundary of the operating region.
As the boundary is very close to actual operating differential current at max. and minimum tap positions,
therefore we take m2=0.5 to recalculate for suitability of setting as given below.
With Id> = 0.22 and m1 = 0.2 and m2 = 0.5:
It is clear from above values that the differential current on relay during maximum through fault current on
highest and lowest tap positions of the transformer is outside the operating region with selected m2=0.5
Operating region should be away from the differential current region, the slope is set to 0.5.
m2=0.5
Configuration:
Function Settings:
-m1: 0.2
-m2: 0.5
-IR, m2: 4.3 Iref
-Op. Mode Inrush: Not phase-Selective
nd
-Inrush 2 Harmon: 20%
-I0 filt a Enab: Yes
-I0 filt b Enab: No
-O/Flux Blk Enab: No
-O/Flux 5th Harmon :20%
-Op.del.,trip sig: 0.00s
-Hyst. Effective: No
Location:
132kV Transformer Relay Panels: =E01+R1, E03+R1, E06+R1, E08+R1.
CT Ratio For Backup O/C Protection (Similar For All 132kV Transformer Bays):
HV 132kV Transformer Feeder CT : 400/1, 5P20
MiCOM P122 serves as backup protection for 132kV side transformer winding.
The O/C Pickup setting is usually 115% of the maximum overload acceptable.
This is slightly above the maximum current at end tap position of 340.2A. Normal inverse curve is selected.
As recommended by independent engineer of Fichner GmbH, setting of 400 A (taking into account the max.
possible overload of transformer) is selected.
The 132kV-OC protection is set to operate with a delay of about 1.1sec (950ms+150ms) on the maximum
through fault current of 2.187kA at 132kv side.
The 132kV earth fault stage is set to 20% of the rated transformer current of 306.2A. The 132kV earth fault
protection at the transformer neutral is set to operate with a delay of about 1.1 sec ( 950ms+150ms) on the
maximum through fault current of 2.187kA at 132kV side.
Required earth fault setting Ie>= 20% of 306.2= 0.2 x 306.2= 61A
The instantaneous protection is set to 120% of the max 132kV through fault current.
The time delay of 0.1 sec stabilizes the I>> stage against any kind of transient phenomena. Definite time
curve is selected.
Location:
132kV Transformer Relay Panels: =E01+R1, E03+R1, E06+R1, E08+R1.
CT Ratio For CB Failure Protection (Similar For All 132kV Transformer Bays):
HV 132kV Transformer Feeder CT : 400/1, 5P20
CB FAIL EARTH:YES
Description: Enable/Disable the Circuit Breaker Failure protection on earth.
Location:
132kV Line Relay Panels: =E07+R1 and =E09+R1
CT Ratio: 1200/1
VT Ratio: (132KV/1.732)/(110V/1.732)
Lynx conductor:
Rail conductor:
-Zone 1: 85% of impedance of protected line and trips independently with 0s delay.
-Zone 2: Impedance of protected line + 50% of impedance of adjacent shortest T/L and trip delay time
350ms delay.
-Zone 3: Impedance of protected line + 120% of impedance of adjacent longest T/L and trip delay time
700ms delay.
1. Line Impedance:
2. Zone 1 Reach :
3. Zone 2 Reach :
Zone 2 is set to 100% of protected line impedance + 50% impedance of the adjacent shortest transmission
line.
Z2 = (0.6253+j4.0864) + 0.5 {10.422 x (0.06+j0.3921)} = 0.9379+j6.1296
Z2 = 6.2<81.3º
4. Zone 3 Reach :
Backup Zone 3 is set to 100% of the protected line impedance + 120% impedance of the adjacent longest
transmission line.
Z3 = (0.6253+j4.0864) + 1.2 {36 x (0.1583+j0.4004)} = 7.4638+j21.3837
Z3 = 22.65<70.7º
Therefore:
kZ0 Res. Comp = 0.061 (Set for kZ1, kZ2, kZ3)
The P442 relay have quadrilateral distance elements, thus the resistive reach (RPh) is set independent of
the impedance reach along the protected line.
In general, RPh must be set greater than the maximum fault arc resistance for a phase-phase fault,
calculated from van Warrington formula as follows:
1.4 1.4
Ra = (28710 x L) / If = (28710 x 5) / (7100) = 0.58 = 0.6
RPh >=Ra
Where:
Ra = Arc resistance
L = Maximum phase conductor separation, is assumed 5m.
If = Minimum expected phase-phase fault current, is taken 7.1kA.
The minimum load impedance can be calculated on the basis of the maximum permitted power flow over the
protected line. The maximum power flow is calculated from the ampacity of the conductor of 884A at nominal
system voltage of 132kV, which is 202MVA. It is assumed, that the maximum power flow is transferred under
worst condition at a minimum system voltage of 80%.
Typically, phase fault distance zones would avoid the minimum load impedance by a margin of >= 40%.This
allows max phase resistive reach = 0.6 x 55 =33
A setting between the calculated minimum and maximum should be applied for all zones.
For best zone reach accuracy, the resistive reach of each zone would not normally be set greater than 10
times the corresponding zone reach.
Therefore:
Typically, Earth fault distance zones would avoid the minimum load impedance by a margin of >= 20%.This
allows max phase resistive reach = 0.8 x 55 = 44
Fault resistance would comprise arc resistance and tower footing resistance.A typical resistive reach
coverage would be 40 on the primary side.
In addition, for best zone reach accuracy, the resistive reach of any zone of the relay would not normally be
greater than 10 times the corresponding earth loop reach.
Therefore:
Functions Configuration:
-Setting Group: Select via menu
-Active Settings: Group 1
-Setting Group 1: Enabled
-Setting Group 2: Disabled
-Setting Group 3: Disabled
-Setting Group 4: Disabled
-Distance: Enabled
-Power Swing: Enabled
-Back-up I>: Disabled
-Neg. Sequence O/C: Disabled
-Broken Conductor: Disabled (This setting is disabled similar to settings of Line Bay E02 and E04 which was
disabled as per wapda advise during commissioning at site)
-Earth Fault O/C: Disabled
-Aided DEF: Disabled
-Volt Protection: Disabled
-CB Fail & I<: Disabled.
-Supervision: Enabled
-System Checks: Enabled
-Internal A/R: Enabled
-Setting values: Secondary
CT and VT Ratios:
-Main VT Primary: 132kV
-Main VT Secondary: 110V
-C/S VT Primary: 132kV
-C/S VT Secondary: 110V
-Phase CT Primary: 1200A
-Phase CT Secondary: 1A
-MComp CT Primary: 1200A
-MComp CT Secondary: 1A
-C/S Input: A-B
-Main VT Location: Line
-CT Polarity: Standard or Inverse (To be set at site)
CB Control:
-CB Control by: Disabled
-A/R Single Pole: Disabled
-A/R Three Pole: Enabled
OPTO Configuration:
-Global Nominal Voltage: 110/125V
-Opto Filter Cntl: Select All
Distance Element:
Line Setting:
-Line Length: 10.42 km
-Line Impedance: 4.134
-Line Angle: 81.3º
Zone Setting:
-Zone Status: 01010
-kZ1 Res Comp: 0.061
-kZ1 Angle: -5.5º
-Z1: 3.514
-R1G:30
-R1Ph:15
-tZ1:0.0s
-kZ2 Res Comp: 0.061
-kZ2: Angle: -5.5º
-Z2: 6.2
-R2G: 35
-R2Ph: 20
-tZ2:350ms
-kZ3/4 Res Comp: 0.061
-kZ3/4 Angle: -5.5º
-Z3: 22.65
-R3G-R4G: 40
-R3Ph-R4Ph: 30
-tZ3:700ms
Fault Locator:
-kZm Mutual Comp: 0
-KZm Angle:0º
Distance Schemes:
-Program Mode: Standard Scheme
-Standard Mode: PUP Z2
-Fault Type: Both Enabled.
-Trip Mode: Force 3 poles
Power Swing:
-Delta R: 6
-Delta X: 6
-IN> status: Enabled
-IN> (% Imax.): 40%
-I2> status: Enabled
-I2> (% Imax.): 30%
-ImaxLine> status: Enabled
-ImaxLine>: 4.0 x In (A)
-Unblocking delay: 30 sec
-Blocking zones: Select all
Broken Conductor:
-Broken Conductor: Disabled (This setting is disabled similar to settings of Line Bay E02 and E04 which was
disabled as per wapda advise during commissioning at site)
-I2/I1: 0.2 (N/A)
-I2/I1 Time Delay: 60 s (N/A)
-I2/I1 Trip: Enabled (N/A)
Supervision:
-VTS Time Delay: 5sec
-VTS I2 & I0 Inhibit: 0.05 x In
-Detect 3Pole: Enabled
-Threshold 3Pole: 30V
-Delta I>: 0.1 x In
-CTS Status: Disabled
-CVTS Status: Disabled
Systemchecks:
-Check Scheme for A/R: Select all
-Check Scheme for ManCB: None
-V<Dead Line: 13V
-V>Live Line: 32V
-V<Dead Bus: 13V
-V>Live Bus: 32V
-Diff Voltage: 5V
-Diff Frequency: 0.05Hz
-Diff Phase: 20º
-Bus-Line Delay: 0.2 sec
Autoreclose:
-3P Trip Mode:3/3
-3P Dead Time1: 0.5sec
-Reclaim Time: 180 sec
-Close Pulse Time: 0.1sec
-A/R Inhibit Wind: 5 sec
-C/S 3P Rcl DT1: Enabled
-Block A/R: Select all
Location:
132kV Line Relay Panels: =E07+R1 and =E09+R1
CT Ratio For Backup O/C Protection (Similar For Both Line Bays):
1200/1
The time delayed overcurrent protection relay MiCOM P122 serves as backup protection and is delayed
against the distance zone timers.
Overcurrent operation time should be greater than zone-3 operation time (i.e. 700ms) of distance protection
relay. For definite time o/c, the proposed setting is 800msec. (i.e 100ms is added to backup o/c time to co-
ordinate with zone-3 operating time of 700ms).
Location:
132kV Line Relay Panels: =E07+R1 and E09+R1
CB FAIL EARTH:YES
Description: Enable/Disable the Circuit Breaker Failure protection on earth.
Location:
132kV Line Relay Panel: =E07+R1, and =E09+R1
Location:
132kV Relay Panel: = E02+R1
System Data:
Transmission Line: 132kV Badomali BDL-1
CT Ratio: 1200/1
VT Ratio: (132kV/1.732)/(110V/1.732)
Shortest Line: 21Km, Lynx conductor (132kV Badho Mali to 132kV Narang)
Longest Line: 21Km, Lynx conductor (132kV Badho Mali to 132kV Narang)
Lynx conductor:
Rail conductor:
-Zone 1: 85% of impedance of protected line and trips independently with 0s delay.
-Zone 2: Impedance of protected line + 50% of impedance of adjacent shortest T/L and trip delay time
350ms delay.
-Zone 3: Impedance of protected line + 120% of impedance of adjacent longest T/L and trip delay time
700ms delay.
1. Line Impedance:
2. Zone 1 Reach :
3. Zone 2 Reach :
Zone 2 is set to 100% of protected line impedance + 50% impedance of the adjacent shortest transmission
line.
Z2 = (1.8521+j4.6847)+0.5{21(0.1583+j0.4004)} =3.5142+j8.8889
Z2 = 9.558<68.4º
4. Zone 3 Reach :
Backup Zone 3 is set to 100% of the protected line impedance + 120% impedance of the adjacent longest
transmission line.
Z3 = (1.8521+j4.6847)+1.2{21(0.1583+j0.4004)}=5.8412+j14.7747
Z3 = 15.887<68.4º
Therefore:
kZ0 Res. Comp = 0.056 (Set for kZ1, kZ2, kZ3)
The P442 relay have quadrilateral distance elements, thus the resistive reach (RPh) is set independent of
the impedance reach along the protected line.
In general, RPh must be set greater than the maximum fault arc resistance for a phase-phase fault,
calculated from van Warrington formula as follows:
1.4 1.4
Ra = (28710 x L) / If = (28710 x 5) / (7100) = 0.58 = 0.6
RPh >=Ra
Where:
Ra = Arc resistance
L = Maximum phase conductor separation, is assumed 5m.
If = Minimum expected phase-phase fault current, is taken 7.1kA.
The minimum load impedance can be calculated on the basis of the maximum permitted power flow over the
protected line. The maximum power flow is calculated from the ampacity of the conductor of 488A at nominal
system voltage of 132kV, which is 111.57 MVA. It is assumed, that the maximum power flow is transferred
under worst condition at a minimum system voltage of 80%.
Typically, phase fault distance zones would avoid the minimum load impedance by a margin of >= 40%.This
allows max phase resistive reach = 0.6 x 100 =60
A setting between the calculated minimum and maximum should be applied for all zones.
For best zone reach accuracy, the resistive reach of each zone would not normally be set greater than 10
times the corresponding zone reach.
Therefore:
Typically, Earth fault distance zones would avoid the minimum load impedance by a margin of >= 20%.This
allows max phase resistive reach = 0.8 x 100 = 80
Fault resistance would comprise arc resistance and tower footing resistance.A typical resistive reach
coverage would be 40 on the primary side.
In addition, for best zone reach accuracy, the resistive reach of any zone of the relay would not normally be
greater than 10 times the corresponding earth loop reach.
Therefore:
Relay Settings:
Functions Configuration:
-Setting Group: Select via menu
-Active Settings: Group 1
-Setting Group 1: Enabled
-Setting Group 2: Disabled
-Setting Group 3: Disabled
-Setting Group 4: Disabled
-Distance: Enabled
-Power Swing: Enabled
-Back-up I>: Disabled
-Neg. Sequence O/C: Disabled
-Broken Conductor: Disabled (This setting is disabled as per wapda advise during commissioning at site )
-Earth Fault O/C: Disabled
-Aided DEF: Disabled
-Volt Protection: Disabled
-CB Fail & I<: Disabled.
-Supervision: Enabled
-System Checks: Enabled
-Internal A/R: Enabled
-Setting values: Secondary
CT and VT Ratios:
-Main VT Primary: 132kV
-Main VT Secondary: 110V
-C/S VT Primary: 132kV
-C/S VT Secondary: 110V
-Phase CT Primary: 1200A
-Phase CT Secondary: 1A
-MComp CT Primary: 1200A
-MComp CT Secondary: 1A
-C/S Input: A-B
-Main VT Location: Line
-CT Polarity: Standard or Inverse (To be set at site)
CB Control:
-CB Control by: Disabled
-A/R Single Pole: Disabled
-A/R Three Pole: Enabled
OPTO Configuration:
-Global Nominal Voltage: 110/125V
-Opto Filter Cntl: Select All
Distance Element:
Line Setting:
-Line Length: 11.7 km
-Line Impedance: 5.037
-Line Angle: 68.4º
Zone Setting:
-Zone Status: 01010
-kZ1 Res Comp: 0.056
-kZ1 Angle: 10.2º
-Z1: 4.282
-R1G:30
-R1Ph:20
-tZ1:0.0s
-kZ2 Res Comp: 0.056
-kZ2: Angle: 10.2º
-Z2: 9.558
-R2G: 40
-R2Ph: 30
-tZ2:350ms
-kZ3/4 Res Comp: 0.056
-kZ3/4 Angle: 10.2º
-Z3: 15.89
-R3G-R4G: 60
-R3Ph-R4Ph: 45
-tZ3:700ms
Fault Locator:
-kZm Mutual Comp: 0
-KZm Angle:0º
Distance Schemes:
-Program Mode: Standard Scheme
-Standard Mode: PUP Z2
-Fault Type: Both Enabled.
-Trip Mode: Force 3 poles
Power Swing:
-Delta R: 9
-Delta X: 9
-IN> status: Enabled
-IN> (% Imax.): 40%
-I2> status: Enabled
-I2> (% Imax.): 30%
-ImaxLine> status: Enabled
-ImaxLine>: 4x In (A)
-Unblocking delay: 30 sec
-Blocking zones: Select all
Broken Conductor:
-Broken Conductor: Disabled (This setting is disabled as per wapda advise during commissioning at site )
-I2/I1: 0.2 (N/A)
-I2/I1 Time Delay: 60 s (N/A)
-I2/I1 Trip: Enabled (N/A)
Supervision:
-VTS Time Delay: 5sec
-VTS I2 & I0 Inhibit: 0.05 x In
-Detect 3Pole: Enabled
-Threshold 3Pole: 30V
-Delta I>: 0.1 x In
-CTS Status: Disabled
-CVTS Status: Disabled
Systemchecks:
-Check Scheme for A/R: Select all
-Check Scheme for ManCB: None
-V<Dead Line: 13V
-V>Live Line: 32V
-V<Dead Bus: 13V
-V>Live Bus: 32V
-Diff Voltage: 5V
-Diff Frequency: 0.05Hz
-Diff Phase: 20º
-Bus-Line Delay: 0.2 sec
Autoreclose:
-3P Trip Mode:3/3
-3P Dead Time1: 0.5sec
-Reclaim Time: 180 sec
-Close Pulse Time: 0.1sec
-A/R Inhibit Wind: 5 sec
-C/S 3P Rcl DT1: Enabled
-Block A/R: Select all
Location:
132kV Line Relay Panel: = E02+R1
Relay Settings:
The time delayed overcurrent protection relay MiCOM P122 serves as backup protection and is delayed
against the distance zone timers.
Overcurrent operation time should be greater than zone-3 operation time (i.e. 700ms) of distance protection
relay. For definite time o/c, the proposed setting is 800msec. (i.e 100ms is added to backup o/c time to co-
ordinate with zone-3 operating time of 700ms).
Location:
132kV Line Relay Panel: = E02+R1
CT Ratio:
1200/1
Relay Settings:
CB FAIL EARTH:YES
Description: Enable/Disable the Circuit Breaker Failure protection on earth.
Location:
132kV Line Relay Panel: = E02+R1
System Data:
System Voltage: 132kV, 50Hz
Relay Settings:
Location:
132kV Relay Panel: = E04+R1
System Data:
Transmission Line: 132kV Narowal NRW-1
CT Ratio: 1200/1
VT Ratio: (132kV/1.732)/(110V/1.732)
Lynx conductor:
Rail conductor:
-Zone 1: 85% of impedance of protected line and trips independently with 0s delay.
-Zone 2: Impedance of protected line + 50% of impedance of adjacent shortest T/L and trip delay time
350ms delay.
-Zone 3: Impedance of protected line + 120% of impedance of adjacent longest T/L and trip delay time
700ms delay.
1. Line Impedance:
2. Zone 1 Reach :
3. Zone 2 Reach :
Zone 2 is set to 100% of protected line impedance + 50% impedance of the adjacent shortest transmission
line.
Z2 = (1.6621+j4.2042)+0.5{10.422(0.06+j0.3921)} = 1.9747+j6.2474
Z2 = 6.55<72.46º
4. Zone 3 Reach :
Backup Zone 3 is set to 100% of the protected line impedance + 120% impedance of the adjacent longest
transmission line.
Z3 = (1.6621+j4.2042)+1.2{36(0.1583+j0.4004)} = 8.5006+j21.5014
Z3 = 23.12<68.43º
Therefore:
kZ0 Res. Comp = 0.062 (Set for kZ1, kZ2, kZ3)
The P442 relay have quadrilateral distance elements, thus the resistive reach (RPh) is set independent of
the impedance reach along the protected line.
In general, RPh must be set greater than the maximum fault arc resistance for a phase-phase fault,
calculated from van Warrington formula as follows:
The minimum load impedance can be calculated on the basis of the maximum permitted power flow over the
protected line. The maximum power flow is calculated from the ampacity of the conductor of 488A at nominal
system voltage of 132kV, which is 111.57 MVA. It is assumed, that the maximum power flow is transferred
under worst condition at a minimum system voltage of 80%.
Typically, phase fault distance zones would avoid the minimum load impedance by a margin of >= 40%.This
allows max phase resistive reach = 0.6 x 100 =60
A setting between the calculated minimum and maximum should be applied for all zones.
For best zone reach accuracy, the resistive reach of each zone would not normally be set greater than 10
times the corresponding zone reach.
Therefore:
Minimum Maximum Zone-1 Zone-2 Zone-3
Phase (RPh) 0.6 60 20 30 45
Typically, Earth fault distance zones would avoid the minimum load impedance by a margin of >= 20%.This
allows max phase resistive reach = 0.8 x 100 = 80
Fault resistance would comprise arc resistance and tower footing resistance.A typical resistive reach
coverage would be 40 on the primary side.
In addition, for best zone reach accuracy, the resistive reach of any zone of the relay would not normally be
greater than 10 times the corresponding earth loop reach.
Therefore:
Minimum Maximum Zone-1 Zone-2 Zone-3
Earth (RG) 40 80 30 40 60
Relay Settings:
Functions Configuration:
-Setting Group: Select via menu
-Active Settings: Group 1
-Setting Group 1: Enabled
-Setting Group 2: Disabled
-Setting Group 3: Disabled
-Setting Group 4: Disabled
-Distance: Enabled
-Power Swing: Enabled
-Back-up I>: Disabled
-Neg. Sequence O/C: Disabled
-Broken Conductor: Disabled (This setting is disabled by wapda during commissioning )
-Earth Fault O/C: Disabled
-Aided DEF: Disabled
-Volt Protection: Disabled
-CB Fail & I<: Disabled.
-Supervision: Enabled
-System Checks: Enabled
-Internal A/R: Enabled
-Setting values: Secondary
CT and VT Ratios:
-Main VT Primary: 132kV
-Main VT Secondary: 110V
-C/S VT Primary: 132kV
-C/S VT Secondary: 110V
-Phase CT Primary: 1200A
-Phase CT Secondary: 1A
-MComp CT Primary: 1200A
-MComp CT Secondary: 1A
-C/S Input: A-B
-Main VT Location: Line
-CT Polarity: Standard or Inverse (To be set at site)
CB Control:
-CB Control by: Disabled
-A/R Single Pole: Disabled
-A/R Three Pole: Enabled
OPTO Configuration:
-Global Nominal Voltage: 110/125V
-Opto Filter Cntl: Select All
Distance Element:
Line Setting:
-Line Length: 10.50 km
-Line Impedance: 4.521
-Line Angle: 68.4º
Zone Setting:
-Zone Status: 01010
-kZ1 Res Comp: 0.062
-kZ1 Angle: 10.2º
-Z1: 3.843
-R1G:30
-R1Ph:20
-tZ1:0.0s
-kZ2 Res Comp: 0.062
-kZ2: Angle: 10.2º
-Z2: 6.55
-R2G: 40
-R2Ph: 30
-tZ2:350ms
-kZ3/4 Res Comp: 0.062
-kZ3/4 Angle: 10.2º
-Z3: 23.12
-R3G-R4G: 60
-R3Ph-R4Ph: 45
-tZ3:700ms
Fault Locator:
-kZm Mutual Comp: 0
-KZm Angle:0º
Distance Schemes:
-Program Mode: Standard Scheme
-Standard Mode: PUP Z2
-Fault Type: Both Enabled.
-Trip Mode: Force 3 poles
Power Swing:
-Delta R: 9
-Delta X: 9
-IN> status: Enabled
-IN> (% Imax.): 40%
-I2> status: Enabled
-I2> (% Imax.): 30%
-ImaxLine> status: Enabled
-ImaxLine>: 4.0 x In (A)
-Unblocking delay: 30 sec
-Blocking zones: Select all
Broken Conductor:
-Broken Conductor: Disabled (This setting is disabled by wapda during commissioning )
-I2/I1: 0.2 (N/A)
-I2/I1 Time Delay: 60 s (N/A)
-I2/I1 Trip: Enabled (N/A)
Supervision:
-VTS Time Delay: 5sec
-VTS I2 & I0 Inhibit: 0.05 x In
-Detect 3Pole: Enabled
-Threshold 3Pole: 30V
-Delta I>: 0.1 x In
-CTS Status: Disabled
-CVTS Status: Disabled
Systemchecks:
-Check Scheme for A/R: Select all
-Check Scheme for ManCB: None
-V<Dead Line: 13V
-V>Live Line: 32V
-V<Dead Bus: 13V
-V>Live Bus: 32V
-Diff Voltage: 5V
-Diff Frequency: 0.05Hz
-Diff Phase: 20º
-Bus-Line Delay: 0.2 sec
Autoreclose:
-3P Trip Mode:3/3
-3P Dead Time1: 0.5sec
-Reclaim Time: 180 sec
-Close Pulse Time: 0.1sec
-A/R Inhibit Wind: 5 sec
-C/S 3P Rcl DT1: Enabled
-Block A/R: Select all
Location:
132kV Line Relay Panel: = E04+R1
Relay Settings:
The time delayed overcurrent protection relay MiCOM P122 serves as backup protection and is delayed
against the distance zone timers.
Overcurrent operation time should be greater than zone-3 operation time (i.e. 700ms) of distance protection
relay. For definite time o/c, the proposed setting is 800msec. (i.e 100ms is added to backup o/c time to co-
ordinate with zone-3 operating time of 700ms).
Location:
132kV Line Relay Panel: = E04+R1
CT Ratio:
1200/1
Relay Settings:
CB FAIL EARTH:YES
Description: Enable/Disable the Circuit Breaker Failure protection on earth.
Location:
132kV Line Relay Panel: = E04+R1
System Data:
System Voltage: 132kV, 50Hz
Relay Settings:
Location:
132kV Buscoupler Relay Panel: = E05+R1
System Data:
System Voltage: 132kV, 50Hz
Relay Settings:
(Applicable For Discriminating Zone-1, Zone-2 and Check Zone Relay):
MFAC34 is a voltage operated relay having seven equally spaced settings which may be selected by means
of a plug bridge.
The relay may be used for any type of high impedance circulating current protection.
As per scheme, there are 2-discriminating zones for bus-1 and bus-2 and a check zone.
Discriminating Feature:
The relay plug setting voltage VR must be set to the nearest tap above this value.
Therefore:
VR= 75 volts
Knee point voltage of the current transformers should not be less than twice the relay setting voltage.
VK 2 VR
VK 2 x 75
VK 150 volts
Ip = CT Ratio (IRelay + n IE )
Therefore:
It is desirable that the primary effective setting should not exceed 30% of the minimum fault current i.e. 30%
of 7.1KA= 2130Amps.
Where 30% of the minimum fault current is more than the full load current of the largest circuit, the primary
operating current should be made more than the full load current i.e 130% of the full load current.
Since the resultant value of ‘Ip=110 Amps’ is too low, it may be increased by the addition of a shunt resistor
RSH to give a current of
Taking:
RSH = 625
Each MFAC relay is applied with an external metrosil which must be wired across the relay circuit. This
provides a shunt circuit for high internal fault currents and prevents a high voltage being developed across
the CT and relay circuits.
Check Feature:
VR= 75 volts
No. of ct circuits = 8
As the difference in number of parallel circuit for check and discrimination zone is not significant, therefore
same value of RSH = 625 is taken for increased operating value of primary current.
RSH = 625
Location:
132kV Buscoupler Relay Panel: = E05+R1
Relay Settings:
(Applicable For Discriminating Zone-1 and Zone-2 ‘MVTP31’ Relays):
The MVTP31 provides continuous supervision of buswires in high impedance type busbar protection
schemes.
Open circuit connections between CT’s and relay circuit result in unbalance currents which may operate the
protection. Supervision is applied by a voltage relay across differential relay circuit.
MVTP relays have setting rang 1-16V, in one volt steps, and a fixed operating time of 3-seconds.
Whenever possible, the supervision primary operating current should not be more than 25Amps primary or
10% of the smallest circuit, whichever is greater.
Assuming I = 25A
At 75 volt, the magnetizing current of ct is approx. = 3mA. Assuming one ct is open circuit out of 9, the
magnetizing impedance will be:
Hence,
VSP= I x {(R x Zm)/(R + Zm)}
= (25/2400) x {(3947 x 3125)/(3947+3125)}
= 18 volt
As the maximum available setting is 16volt, therefore:
Location:
132kV Buscoupler Relay Panel: = E05+R1
CT Ratio:
1200/1
Relay Settings:
A 150ms delay at maximum current should be allowed for an instantaneous line protective relay to actuate
and a line circuit breaker to trip and to allow margin for uncertainty. Therefore the proposed setting for time
delay is:
Location:
132kV Buscoupler Relay Control Panel: =E05+R1
CT Ratio:
1200/1
Relay Settings:
CB FAIL EARTH:YES
Description: Enable/Disable the Circuit Breaker Failure protection on earth.
Location:
132kV Buscoupler Relay Control Panel: = E05+R1
System Data:
System Voltage: 132kV, 50Hz
Relay Settings: