Sunteți pe pagina 1din 2

VESDA Model Comparison Chart

All photography, images & design strictly copyright © FlameStop Australia

Page 66 — FlameStop ALARMS

All models available at FlameStop.


VESDA-E VESDA Industrial Products
VEP VLC VLC VLF Industrial
Features VEU VEA VLP VLS Relays Only VFT-15 VLC-EX
VEP-1 VEP-4
VESDAnet (VN)
(RO) 250/500 VESDA VLI

UL, ULC, FM, UL, ULC, FM, UL, ULC, FM, UL, ULC, FM, UL, FM, ATEX,
ActivFire, VdS, ActiveFire, VdS, UL, ULC, CSFM UL, ULC, FM, ActivFire, LPCB, VdS, AFNOR, UL268A (in-duct application), NY-MEA, AFNOR, VdS, ActivFire, CPR,
Worldwide Certificates CSFM, CCCF, CPR, VNIIPO IECEx, CPR
CPR CE, EN VNIIPO, CPR LPCB, VdS

Hazardous Area
Approval (FM Class 1, Pending No Pending N/A Yes No Yes Yes Yes No Yes Yes
Div 2, Groups A, B, C, D)
0.001% obs/m 0.01% obs/m 1.63% obs/m 0.015% obs/m 0.025% obs/m 0.01% obs/m 0.15%/m (0.046%/ 0.015% obs/m
Min Fire 1 Threshold (0.0003% obs/ft) (0.0031% obs/ft) (0.5% obs/ft) (0.0046% obs/ft) (0.008% obs/ft) (0.0031% obs/ft) (0.0046% obs/ft)
ft)
0.001 - 20.0% 0.020 - 16% 0.025 - 20% 0.001 - 20% 0.005 - 20.0% 0.005 - 20%
0.005 - 20% obs/m
Detection Range obs/m obs/m 0.005 - 20% obs/m (0.0016 obs/m obs/m obs/m obs/m
(0.0003 - 6.25% (0.0016% - 6.25% (0.0063 - 5% (0.008 - 6.25% (0.0003 - 6.25% (0.0016 - 6.25%
- 6.25% obs/ft) (0.0016 - 6.25%
obs/ft) obs/ft) obs/ft) obs/ft) obs/ft) obs/ft)
obs/ft)

Patented
Intelligent Filter
Two Stage Filtration Yes Yes Yes Yes Yes Yes Yes Yes Yes Secondary Yes
Foam Filter
Sub-sampling
Probe

40 (expandable to
No. of Pipe Inlets 4 1 4
120 tubes)
4 1 1 15 4 1

1,500 m2
1,000 m2 2,000 m2 2,000 m2 (21,520 2,000 m2 (21,520 250/500 m2
6,500 m2* 2,000 m2 800 m2 (8,610 (16,140 sq. ft) 2,000 m2 (21,520 800 m2
Area Coverage (10,760 (21,520 sq. ft) across 40 sq. ft) across 4 (2,690/5,380
(69,965 sq.ft) (21,520 sq. ft) sq. ft) across 15 sq. ft) (8,610 sq.ft)
sq. ft) sq. ft) -120 sample holes sectors sq. ft) sectors

100 m 280 m 40 x 100 m (130 25/50 m 15 x 50 m (45


Pipe Length (Linear) 400 m (1,312 ft)
(328 ft) (919 ft) x 328 ft)
200 m (656 ft) 200 m (656 ft) 80 m (262 ft)
(82/164 ft) x 164 ft)
360 m (1,181 ft) 80 m (262 ft)

130 m 560 m 30/60 m


Pipe Length (Branched) 800 m (2,625 ft) N/A 400 m (1,312 ft) 400 m (1,312 ft) 100 m (328 ft) N/A 445 m (1,460 ft) 100 m (328 ft)
(427 ft) (1,837 ft) (98/197 ft)
Multiple Pipe Up to 4 Up to 15 No No
No No Up to 120 No No No No
Addressability
Total Number of Alarm 4 4 4 4 16 4 60 4 3
(Day/Night) (Day/Night) (Day/Night) (Day/Night) (Day/Night) 3 3 (Day/Night) (Day/Night) (Day/Night)
Thresholds

7 7 (Expandable to 5 (Expandable
Relay Outputs 7 7 7 or 12 relays 3 3 3 (Expandable to 6) 5 3
127) to 21)
On-board Memory
(Max. Events) 20,000 20,000 20,000 18,000 18,000 12,000 12,000 18,000 Up to 20,000 18,000 12,000

IP Rating IP40 IP40 IP40 IP30 IP30 IP30 IP30 IP30 IP30 IP66 IP54

* System design and regulatory requirements may restrict the monitoring area to a lesser amount
VESDA-E VESDA Industrial Products
Features VEP VLC VLC VLF Industrial
VEU VEA VLP VLS Relays Only VFT-15 VLC-EX
VEP-1 VEP-4
VESDAnet (VN)
(RO) 250/500 VESDA VLI

AutoLearn AutoLearn AutoLearn


AutoLearn™ Smoke™ AutoLearn Smoke™ Yes Yes Yes Yes Smoke™ Smoke™ Yes
(Smoke/Flow) AutoLearn AutoLearn Flow™ No (Smoke) (Smoke) (Smoke) (Smoke) AutoLearn No AutoLearn (Smoke)
Flow™ Flow™ Flow™

VLF 250
EN54-20 Max. no of 30 / 40 / 40 / 80 / 12 / 12 / 12;
80 / 80 / 100 45 100 40-120 (B & C) 30 / 60 / 100 40 / 40 / 60 30 / 36 / 40 30 / 36 / 40 VLF 500 15 / 15 / 15 24 / 28 / 60 30 / 36 / 40
Holes (Class A / B / C)
30 / 30 / 30

Local
LEDs Local (7 on-board LEDs Local
LEDs or 3.5” or 3.5” Local or Remote Local or Remote (5 on-board 10 Segment (5 on-board
LEDs or 3.5” Local As per
Bar Graph/Indicator LED Color Touch LEDs Color Color Touch (20 segment (20 segment LEDs). Remote Circular Display) Yes LEDs) Remote
bargraph bargraph (5 on-board Remote display VLC (VN) &
Screen Touch Screen (20 segment display for
display) display) bargraph LEDs) when fitted with VLC (RO)
Screen VLI-885
display) VESDAnet card

Local USB
Programming Tools Programmed via configuration
-On-board Programmed via Programmed via Programmed via Programmed via RS232 direct On-board port
USB/Ethernet/WiFi connection to PC programmer As per
Programming module USB/Ethernet/WiFi USB/Ethernet/WiFi RS232 direct Connection to VLC (VN) &
- Handheld Programmer connection to PC connection to PC connection to PC Yes Yes Yes connection to PC using VSC™ or and PC Software PC using VSC/
using VSC/VSM4 Programmer (VSC/VSM4) VLC (RO)
- PC Software (VSC, VSM) using VSC/VSM4 using VSC/VSM4 using VSC™ VSM4
when VN card is Programmer for
fitted VLI-885

StaX Expandability Yes Yes Yes No No No No No No No No


Analytics Yes Yes No No No No No No No No No
VESDAnet™
All photography, images & design strictly copyright © FlameStop Australia

Max. No. of devices/ 200 / 100 (with 200 / 100 200 / 100 (VN
detectors per loop 200 / 100 200 / 100 200 / 100 200 / 100 200 / 100 200 / 100 N/A VN Card) N/A (VLI-885) version)

Max. Distance between 1,300 m 1,300 m 1,300 m 1,300 m 1,300 m 1,300 m 1,300 m 1,300 m 1,300 m
Devices (4,265 ft) (4,265 ft) (4,265 ft) (4,265 ft) (4,265 ft) (4,265 ft) N/A (4,265 ft) N/A (4,265 ft) (4,265 ft)
(with VN Card) (VLI-885) (VN version)

Computer-based Yes Yes Yes Yes Yes Yes No Yes Yes


Yes (VN
Management via VSM Yes version)

Remote Relay Modules


- 7 relay version VRT-500 VRT-500 VRT-500 VRT-500 VRT-E00 VRT-500 VRT-500 VRT-500 VRT-500 (VN
N/A N/A N/A N/A VRT-900 N/A N/A N/A N/A N/A version)
- 12 relay version

Compatible Remote
Bargraph Displays - VRT-V00 VRT-Q00
FlameStop ALARMS — Page 67

Display, 7 relays VRT-200 VRT-200 VRT-200 VRT-200 VRT-400 VRT-J00 N/A N/A As per
- Display, 12 relays N/A N/A N/A N/A VRT-800 N/A N/A VRT-W00 (with N/A VRT-T00 VLC (VN) &
VRT-600 VRT-600 VRT-600 VRT-600 VRT-700 VRT-K00 VN Card) (VLI-885) VLC (RO)
- Display, no relays