Sunteți pe pagina 1din 62

A Case Study of 24 VDC System

1. Introduction to Thermal Power Plants

The electricity has become an essential commodity rather

than luxury now a days. In a state or region thermal power stations will

become important, as hydro resource are inadequate. The concept of a

modern thermal station is that it should be situated at such a place that

the basic requirements of fuel, water and land should be satisfied.

Basically thermal stations are of two types.

1. Pit Head stations.

2. Load demand stations.

Pithead stations are those, which are nearer to the source of

fuel and demand station, are those, which are nearer to the load center.

The basic requirements of thermal power station are:

a. Supply of raw material at competitive cost.

b. Access to the markets for its products.

c. Labour force of the size and quantity required.

d. Means of disposal for any trade effluents that are by

products.

1
A Case Study of 24 VDC System

The other factors to be considered for selecting the site are:

1. Load demand.

2. Land.

3. Site requirements.

4. Access for construction.

5. Transmission lines.

6. Clearances.

7. Environmental factors.

Generally 1000 MW plant requires 90 to 200 acre land. The

water requirements for thermal power stations come under main groups.

The first requirement is for steam generation and the second requirement

is for cooling purposes. Water for steam generation is low of the order of

3 to 4 tones per hour per megawatt, and make up quantity is 2 to 3% of the

same whereas amount of water required for condensation is quite high.

Coal for thermal power stations in India, the principle source of

commercial energy is amounting to 95% of the total primary energy

resources of the country. The coal resources existing in the country are of

the order of 1,30,000 million tons.

Principle of operation;

The fundamental forms of energy with which thermal stations

are principally concerned are heat and work. Heat produces work and this

work is further converted into electrical energy through a medium i.e.

2
A Case Study of 24 VDC System

electrical generator. For the purpose of understanding of thermal plants,

the phenomenon of the thermodynamics vapour cycles explained below.

1. Rankine cycle.

2. Reheat cycle.

3. Regenerative cycle.

Rankine Cycle:

This is the simplest theoretical vapor cycle, which is the basis

for operation of a steam plant. Super heated steam from the boiler is fed

into the prime mover and is expanded there. After which it enters the

condenser emerging as condensate. With the help of a pump this

condensate is again fed into the boiler.

The main purpose of superheating steam and supplying it to

the prime movers is to avoid too much wetness at the end of expansion.

Moisture content of steam would result in undue blade erosion. The

maximum wetness in the final stage of steam that may be tolerated

without any appreciable harm to the turbine blades is about 12%. Also the

use of super heater in a boiler helps in reducing the stack temperature by

extracting heat from the flue gases before these are passed out of

chimney.

3
A Case Study of 24 VDC System

Reheat cycle:

In its simplest form the cycle involve with drawing the steam

from the turbine at some intermediate stage, returning it to the steam

generator where a separate super heater is provided in the gas path for re

super heating the steam after which it is reintroduced into the turbine at

the following stage. It reduces the wetness of the steam at final stage and

improves the efficiency of the cycle.

Regenerative Cycle:

This cycle is an attempt to induce reversibility in the ordinary

Rankine cycle and thus to increase its efficiency. The mixing of cold

condensate with the saturated steam and water mixture in the boiler

constitute the principle irreversible process of the cycle and regeneration

aims at reducing this irreversibility by heating the fed water near to the

saturation temperature through the utilization of the heat of steam, which

is partially expanded in the prime mover. Since the purposes are the

thermal regeneration of condensate the cycle is known as regenerative.

Thermal power plant overview:

The Thermal power Plant consists of the following systems,

which comprise the whole setup as, listed below:

I. Air and gas flow system.

4
A Case Study of 24 VDC System

II. Regenerative feed heating system.

III. Condensate system.

IV. Feed water system.

V. Water and steam circuits.

VI. Steam Turbine.

VII. Turbo Alternators.

VIII. Electrical Power Systems.

5
A Case Study of 24 VDC System

6
A Case Study of 24 VDC System

I. AIR AND GAS FLOW SYSTEM

Two numbers axial reaction forced draught fans and two

numbers axial reaction primary air fans handle the total airflow through

the unit. The flue gases produced in the furnace due to combustion of fuel

is evaluated by two numbers radial double Induced Draught Fans.

a) Secondary Air System (Combustion Air):

The forced draught fans supply the required secondary air

for combustion. This air is pre heated by two in number rotary

regenerative tri sector type air heaters. The air heater out lets ducts are

inter connected to provide a balanced air flow to the furnace and also to

make it possible to operate the unit at reduced rating with one fan in

service. Control of secondary airflow is done by FD fan blade pitch control.

“Secondary air dampers” control the distribution of hot secondary air to

the wind box compartments. The “Furnace safe guard and supervisory

system” normally position these.

The two numbers of steam coil air pre heaters are located in

the by pass duct at FD fan outlet and are used to maintain the average

cold end temperature of the regenerative air heater elements to prevent

cold end erosion. During start up and low bred operation when all burners

are in service.

7
A Case Study of 24 VDC System

The airfoil located in the hot secondary air duct measures the

airflow to wind box.

b) Primary Air system:

The cold primary air fans supply the air required for drying the coal

in the tube mills / mixing box and for transporting the pulverized fuel from

both ends of the tube mill to the coal burners. The primary air is heated in

the primary sectors of the rotary regenerative tri sector air heaters.

The primary air is transported as hot primary air and cold tampering

air in order to achieve the required hot air temperature at the mill inlet to

maintain the coal / air mixture temperature at the mill outlet. The control

for the primary air is achieved through PA fan inlet dampers. Control

dampers in the cold and hot air ducts are regulated to maintain the

required total primary airflow to each mill as well as the mill outlet

temperature. The total primary air through each mill end is further divided

as primary air through mill and by pass air.

The by pass airflows through the mixing box where pre drying

of raw coal takes place. The by pass air maintains the velocity of

pulverized coal / air mixture in the fuel pipes at all loads. The by pass air

quantity increases with decrease in load and vice versa. Airfoils are

provided for measuring mill air and annular venturies are provided for

measuring mill by pass airflow.

c) flue gas system.

8
A Case Study of 24 VDC System

The flue gases produced in the furnace as a result of

combustion travels upward in the furnace, across the horizontal pass and

downward through the second pass of the boiler to the air pre heaters.

In the air heaters, the residual heat of the flue gas is utilized

to pre heat the secondary and primary air. The dust laden flue gases then

pass through the electrolytic precipitator for dust removal.

Two numbers of ID fans are provided to evacuate flue gases

to chimney. The ID fans are provided with variable frequency drive and

inlet damper control.

Inter connecting duct is provided at the outlet of ESP so that

the unit can be operated at reduced rating even with one ID fan in service.

The FD and ID fans are capable of maintaining balanced draft conditions in

the furnace over the entire load range of boiler.

II. REGENERATIVE FEED HEATING SYSTEM:

Description: Feed heating system consists of three low-

pressure heaters, gland steam condenser, drain cooler, deaerator and two

high pressure heaters. The condensate extraction pumps take suction from

condenser hot well and pump the condensate to deaerator through the

tube systems of gland steam condenser, drain coolers and low-pressure

heaters. Boiler feed pumps take suction from deaerator and pump the feed

water to boiler through high pressure heaters. The condensate / feed

9
A Case Study of 24 VDC System

water gets heated up progressively by bled steam from turbine

extractions together with gland leak off steam.

The number of extraction from Turbine as follows:

i. From LP Cylinder: There are three extractions from LP Turbine

termed extraction numbers 1, 2 and 3.

ii. From IP Exhaust: There is one extraction from IP turbine termed

extraction number 4 and its connected to Deaerator.

iii. From IP Cylinder: There is one extraction IP turbine termed

extraction number 5 and it is connected to HP heater 5.

iv. From cold reheat: There is one extraction from CRH line termed

extraction number 6 and it is connected to HP heater 6.

LP Heaters 1,2 and 3 get heating steam from LP Turbine.

Hydraulic operated non-return valves are provided in extraction lines of LP

heaters 2 and 3 to prevent back flow of steam into the turbine during a

trip. Motorized block valves are provided in extraction lines for LPH 1, 2

and 3.

HP Heater 5 gets heating steam from IP turbine and HP

heater 6 from cold reheat line. Hydraulically operated non-return valve is

provided in extraction line to HPH-5. Motorized block valves are provided

for HPH-5 and 6.

Deaerator is designed to operate under variable pressure

between 50% to 100% load on turbine and during this range steam is drawn

10
A Case Study of 24 VDC System

from turbine extraction i.e. , IP exhaust. During startup of turbine,

deaerator is provided with steam supply from cold reheat line as well as

external supply source i.e., auxiliary steam header.

III. CONDENSATE SYSTEM:

For extracting the condensate from condenser hot well and

feeding it into the cycle. Condensate pumps have been provided. Normally

two condensate extraction pumps are working while third pump is stand by.

Following systems are supplied condensate from condensate

pump discharge.

i. LP Bypass spray.

ii. Turbine Exhaust head spray.

iii. Turbine Flash Tank Spray.

iv. Chemical Dilution.

v. Condensate Pump sealing.

vi. Vacuum Breaker sealing.

vii. Valve Gland Sealing.

viii. Spray for wet steam washing.

ix. Auxiliary PRDS Spray.

Condensate from pumps passes through gland steam

condenser, drain cooler, low-pressure heaters 1,2 and 3 and finally to

deaerator.

11
A Case Study of 24 VDC System

Normal cycle make up is added to condenser hot well through

make up control valve DM-2/DM-5 from hot well make up pumps. The

smaller valve (DM-2) shall cater for up to 5% make up supply and large

valve DM-5 shall be sized to provide 10% make up flow.

IV. FEED WATER SYSTEM:

For extracting the feed water from deaerator and feeding to

boiler variable speed boiler feed pumps have been provided. Normally two

pumps are working and third pump is stand by.

Following systems are supply feed water from boiler feed discharge

i. HP Bypass valve spray.

ii. Super heater and deaerator and reheater attemperation spray

feed water passes through HP Heaters 5 and 6, feed water

control station and finally to boiler economizer.

Feed control station is provided to regulate the feed flow

through boiler depending upon steam requirement and to maintain normal

water level in boiler drum at all loads.

1 x 30% low load feed control station (FCS) and 2x100% full

load feed control steam valves have been envisaged for the unit.

V. WATER AND STEAM CIRCUITS:

12
A Case Study of 24 VDC System

Feed water is supplied to the steam drum form the

Economizer, through the economizer outlet links.

a. ECONOMISER:

The purpose of the Economizer is to pre heat the boiler feed

water before it is introduced into steam drum, and to recover some of the

heat from the flue gases leaving the boiler.

Feed water is supplied to the economizer inlet header via the

feed stock and check valves. The feed water flow is upward to the

economizer that is in counter flow to the hot flue gases. Most efficient

heat transfer is here by accomplished. Any difficulty with steam

generation within the economizer is eliminated by the up ward water flow.

From the outlet header the feed water is led to the drum via the

economizer outlet links.

The front and rear wall bottom headers feed the front and

rear furnace wall tubes. The furnace sidewalls are supplied by the two-

sidewall bottom headers. All the bottom headers are connected together

in the form of a ring. Some tubes of the furnace rear wall from the supply

of the extended sidewall inlet headers.

The external sidewall tubes terminate in the rear section of

the sidewall top headers. The water in the furnace walls. Front and rear

water walls and the extended sidewalls absorb heat. The resulting mixture

of water and steam is collected in the outlet headers and discharged into

13
A Case Study of 24 VDC System

the steam drum through a series of riser tubes. In the steam drum

separation of water and steam takes place the drum internals reduce the

dissolved solid content of the steam to below accepted level. The boiler

water mixes with the incoming water. The saturated steam is led to the

super heater connecting tubes.

b. SUPER HEATER:

The super heater is composed of four basis stages or

sections: A pendent spaced section, a plates section, a rear horizontal

section, and the steam cooled wall and roof sections.

Passing through the various stages of super heaters, the

steam is super heated to the designed temperatures, from the super

heater outlet heater, the super heated steam is led to the turbine via the

main steam lines.

c. STEAM DRUM AND REHEATER:

The function of the steam drum is to separate water and

steam from the mixture generated in the furnace walls. The steam

purification primarily depends on the extent of the moisture removal, since

the moisture associated with it carries solids in steam.

After assign through the high-pressure stages of the turbine,

steam is returned to the reheater via the cold reheat lines. The reheat

lines de super heaters are located in the cold reheat lines.

14
A Case Study of 24 VDC System

Reheat flow through the limit is as follows:

front pendant reheater –rear pendant reheater – After being

reheated to the designed temperature, the reheated steam is returned to

the low pressure section of the turbine via the hot reheats line.

VI. STEAM TURBINE:

The turbine is a compound, critical machine with HP, IP and LP

parts. The HP and IP parts are single flow cylinders and LP part is a double

flow cylinder. The individual turbine rotors and the generator rotor are

connected by rigid couplings.

The HP Turbine has been constructed for throttle control

governing. The steam is admitted before the backing by two combined main

steam stop and control valves. The line leading from the HP exhaust going

to the reheater is provided with swing check valve which prevent hot

steam from the reheater flowing back into the LP Turbine.

The steam coming from the reheater is passed to the IP

Turbine via two combined reheat stop and control valves. Coils around pipes

connect the IP and LP cylinders. Bleeds are arranged at several points of

the turbine.

a) HP TURBINE:

The outer casing of the HP turbine is of the barrel type and

has neither an axial nor a radial flange. This prevents mass accumulations

15
A Case Study of 24 VDC System

with high thermal stresses. The almost perfect rational symmetry permits

moderate wall thickness of nearly equal strength at all sections. The inner

casing axially split and kinematically supported. As the pressure difference

across the wall of inner casing is low the horizontal flange and connection

bolts can be kept small. The barrel type casing permits flexibility of

operation in the form of short startup times and a high rate of change of

load even at high initial steam conditions.

b) IP TURBINE:

The IP turbine is a single flow construction attached in the

axially split outer casing in an inner casing supported kinematically and

taking the guide blades. The reheated staem admitted to the inner casing

through the top and bottom of the casing. The arrangement of the inner

casing confines the high steam inlet conditions to the admission branch of

the casing, while the joint of outer casing is subjected to the lower

pressure and lower temperature at the exhaust of inner casing.

c) LP TURBINE:

The casing of the double flow LP turbine is of three-shell

design. The shells are axially split and of rigid holded construction. The

inner shell taking the first rows of guide blades is attached kinematically

in the middle shell, independent of the outer shell. The middle shell is

supported at four points on longitudinal beams. Three rings carrying the

last guide blade rows are also attached to the middle shell.

16
A Case Study of 24 VDC System

VII. TURBO ALTERNATORS:

Basic principle of electrical power generation is from

Faraday’s laws. It says that when a conductor rotates in a magnetic field,

the e.m.f will be induced in a conductor and is proportional to the rate of

change of flux line cut by the conductor and capacity of the magnetic

filed. For higher capacities of the generation vice versa principle used. I.e.,

the conductors of the place constantly (stator) and the magnetic field will

be rotating (rotor). Magnetic field obtained from a separate system called

an excitation system.

Excitation system is classified into two type i.e., static

excitation and brush less excitation. Magnetic field will be generated in

rotor circuit and to obtain the rate of change of flux lines, the rotor will

be rotated by a steam turbine constant speed.

The speed of the turbine is determined by the frequency of

the system used in the country i.e., 50 Hz, proportional to the speed of the

turbine is 3000 rpm, and at this speed a two pole generator must be driven

to generate alternating current at a frequency of 50 cycles per second.

VIII. ELECTRICAL POWER SYSTEMS:

Electrical power is usually produces in the stator windings of

large, modern generators at about 15.75 KV and is fed through terminal

connections to one side of a generator transformer step up the voltage to

220 Kv and transmitted. Now a days transmission is carried out even with a

high voltage of 400 Kv. Increasing of the transmission voltage reduces the

line losses and increases the efficiency of the over all system

17
A Case Study of 24 VDC System

2. Necessity of DC Supply in Thermal Power Plants

1. 24 VDC System:

Digital Distribution Control (DDC-Pro Control system) is an

integrated overall control and monitoring system and is capable to perform

all tasks, which are required to control the power plant process manually or

automatically.

Distributed Digital control is the decentralized supervision &

controlling of thermal Power Plant equipments and various parts. This DDC

system is working on 24V DC supply, which is supplying by 24V charges.

Without 24V DC supply, the plant equipment mainly Boiler,

Turbine and Generator cannot be controlled, operated or safety shutdown.

Two numbers of charges namely float cum boost chargers. i.e.

I and II work in parallel and provide for hot redundancy. The battery

banks 2165Ah & 1640Ah are also connected in parallel with these chargers.

The above combination is connected to 24 V DCDB.

Each digitally distributed process control panel gets two 24v

DC supply – feeders – from DCDB namely USA & USB. These two supplies

18
A Case Study of 24 VDC System

work in redundancy. On failure of one supply, the load will be shared by

other supply. The healthiness of 24v DC supply for over voltage and under

voltage is supervised by on XT - 377 electronic modules in DDC panel.

The following sequence of events occurred when 24V supply fails:

1. No LED indication on BTG Desk including TSE and no alarm either

persists or will come.

2. Boiler Trips on loss of 24VDC supply.

3. Turbine also trips on loss of 24 VDC supply.

4. Generator Breaker trips on Reverse Power Relay.

5. Turbine lub oil pumps will not start on quote.

6. Field devices viz. Transmitters, pressure switches, temp. Switches

and solenoid valves etc will not work.

19
A Case Study of 24 VDC System

4. Introduction to Batteries

What is Battery?

A Battery is a device that converts the chemical energy

contained in its active materials directly into electric energy by means of

an electro chemical oxidation-reduction (redox) reaction. While the term

“Battery” is often used, the basic electrochemical unit being referred to is

the “cell”.

A battery consists of one or more electrochemical cells.

Although the term battery and cells are often used interchangeably, cells

are the building blocks of which batteries are constructed. Batteries

consist of one or more cells that are electrically connected.

Components of a Battery Cell:

A cell normally consists of four principal components, these are:

 A positive electrode that receives electrons from the external

circuit when the cell is discharged.

20
A Case Study of 24 VDC System

 A negative electrode that donates electrons to the external

circuit as the cell discharges.

 Electrolyte, which provides a mechanism for charge to flow

between positive and negative electrodes.

 A separator, which electrically isolates the positive and

negative electrodes.

Voltage and Capacity of A battery cell:

a) Cell voltage: -

The voltage of battery / cell is determined by the materials

used in it. The reduction and oxidation reactions mentioned earlier each

produce a fixed potential. The sum of the reduction and oxidation

potentials is the voltage of the cell. For example, the discharge reaction at

the positive electrode for a Nickel – Cadmium cell is NiOOH  Ni (OH) 2

which has potential of 0.5 volts. The reaction at the negative electrode is

Cd  cd (OH) 2, which has a potential 0.8 volts. This means that the overall

voltage of Nickel-Cadmium cell is 1.3 Volts. In fact losses within the cell

make the actual voltage of a Nickel-Cadmium cell more like 1.2 Volts.

Thus the voltage of any battery / cell is established

depending on the cell chemistry. Nickel-cadmium cells are about 1.2 volt,

Lead acid cells are about 2.0 Volts, and Lithium cells may be as high as

nearly 4.0 volts. Cells can be connected together so that their voltage

21
A Case Study of 24 VDC System

adds. This means Nickel-Cadmium batteries of 2.4, 3.6, 4.8 volts are

possible, but batteries of 2,3, or 4 volt are not.

While the voltage of a cell is fixed by its cell chemistry, the

capacity is variable depending on the quantity of active materials it

contains. Individual cells may range in capacity from fractions of an

ampere-hour to many thousands of ampere-hours.

The capacity of a cell is essentially the number of electrons

that can be obtained from it. Since current is the number of electrons per

unit time, cell capacity is the current supplied by a cell over time and is

normally measured in ampere-hours.

How a cell Works? (Electrochemical Operation of a cell): -

When a battery or a cell is inserted into a circuit, it

completes a loop, which allows charge to flow uniformly around the circuit.

In the external part of the circuit, the charge flows in the form of ions

that are transported from one electrode to the other. As mentioned

above, the positive electrode receives electrons from the external circuit

on discharge. These electrons then react with the active materials of the

positive electrode in reduction reactions that continue the flow of charge

through the electrolyte to the negative electrode. At the negative

electrode, oxidation reactions between the active materials of the

negative electrode and the charge flowing thorough the electrolyte result

in surplus electrons that can be donated to the external circuit.

22
A Case Study of 24 VDC System

It is important to note that the system is closed. For every

electron generated in an oxidation reaction at the negative electrode,

there is an electron consumed in a reduction at the positive.

As the process continues, the active materials become

depleted and the reactions slow down until the battery is no longer capable

of supplying electrons. At this point the battery is discharged.

electrical Connections in a Battery:

Batteries normally consist of multiple cells that are

electrically connected. The way that the electrical connections are made

determines the voltage and capacity of the battery. If the positive

terminal of one cell is connected to the negative terminal of the next and

so on through the battery, the result is called a series connected battery.

The other way to connect cells within a battery is to connect

the negative terminal from one cell to the negative of the next cell and to

connect the positive terminals to the positive terminal. When this is done

throughout the battery, the result is the parallel-connected battery.

Here the capacities of the individual cells add to make the

battery capacity, but the battery voltage remains as the voltage of the

individual cell.

23
A Case Study of 24 VDC System

5. SMF-VRLA Battery

The development of the Sealed Maintenance Free Valve

Regulated lead Acid battery design is based on the finding that the

positive electrode accepts the charge less efficiency than the negative.

Under typical charging conditions, Oxygen evolution at the positive plates

peaks at charge AH to Discharge AH ratio of approximately 0.94, whereas

the rate of hydrogen evolution at the negative reaches a maximum at the

value of 1.0.

Considering this fact, if the oxygen evolved at the positive

plate is made to diffuse through the electrolyte and made to reduce at the

negative electrode, the hydrogen evolution can be suppressed. In this way,

oxygen evolved during charging recombines at the negative that

consequently never becomes fully charged, there by eliminating gassing.

24
A Case Study of 24 VDC System

forcing the oxygen gas to diffuse to the negative instead of

bubbling to the top, as in flooded cells, is achieved by immobilizing the

electrode. The electrolyte can be immobilized either as a Gel or in an

Absorbent Glass Mat (AGM). In both cases oxygen transportation occurs in

the gas phase. The gelled electrolyte develops a fissured structure

permitting the horizontal movement of oxygen whereas in the AGM design

the separator is not saturated with electrolyte and there are voids to

allow the passage for oxygen.

The separator is highly absorbent glass man type with

porosity designed to have pore volume in excess of electrolyte volume

(starved electrolyte design) due to which the oxygen gas finds an

unimpeded path to the negative plate turning a part of it in to a partially

designed condition. There by effectively suppressing the hydrogen gas

evolution at the negative plate. This is what is known as the “Oxygen

recombination Principle”

The part of negative plate which was partially discharged is

then reverted to original spongy lead by subsequent charging, thus a

negative plate keeps equilibrium between the amount which turns into

sponge lead by charging and the amount of spongy lead which turns into

Lead Sulphate by observing the oxygen gas generated at the positive plate.

The oxygen recombination principle can be shown by the following reaction

mechanism.

1) Reaction at positive plat:

25
A Case Study of 24 VDC System

H2O -------- ½ O2 + 2H

2) Reaction at negative plate:

Pb +1/2 O2 --------------- PbO

PbO +H2SO4--------------------PbSO4 + H2O

PbSO4---------------------2H+ 2e - +Pb + H2SO4

From the above equation it can be seen that the reaction is

reversible and based on which the lead acid battery is classified as

secondary battery which can give number of discharge and charge cycles.

During discharge the lead dioxide in positive plate and spongy

lead in negative plate react with the sulfuric acid in the electrolyte to

form lead sulphate both in positive and negative plates and water in the

electrolyte.

So during discharge the lead dioxide and spongy lead react

with sulfuric avid in the electrolyte and gradually transform into lead

sulphate the sulphuric acid concentration decreases in the electrolyte due

to the depletion of sulphate ions to the positive and negative plates.

Conversely, when the battery is charged the positive and

negative materials. Which have been turned into lead sulphate, gradually

revert to lead dioxide and spongy lead respectively. Releasing sulphuric

acid engulfed in the active materials during which the sulphuric acid

concentration increase.

26
A Case Study of 24 VDC System

When the battery charging approaches its final stages the

charging current is consumed solely for electrolyte decomposition of water

in the electrolyte resulting in generation of oxygen gas from positive plate

and hydrogen gas from negate vive plate. The generated gas released our

said the battery causing a decrease of the electrolyte quantity in the

battery. Hence the battery needs to be replenished with the water. This is

the common phenomenon observed in all the conventional flooded type lead

acid batteries requiring constant monitoring and maintenance of the

battery. In order to overcome this phenomenon of replenishment with

water the maintenance free valve regulated lead acid battery (VRLA) has

bee developed. Which needs no replenishments with water at all during its

entire life period of operation and has got several other advantages both

constructional and performance wise.

2.25V PER CELL AT FLOAT CHARGE:

During float mode the potential is to be maintained at 2.25V

per cell at 270C at the current limited to 0.2 C. This voltage and the

resultant current will construct the self-discharge and the battery will be

maintained in a fully charged condition. This made of charging is used in

float application that has very infrequent discharges and has sufficient

time for recharge before the next discharge.

Boost Charge:

At boost mode, the potential in maintained at 2.30 V per cell

with current limited to 0.2 C. This is given only for short durations to avoid

over charge. This mode of charging is used in cyclic application where fast

charging is to be done. A boost charge is recommended when the individual

27
A Case Study of 24 VDC System

cell voltages of a battery differ by more than 0.05V in the open circuit

condition. The boost charge will stabilize and equalize their voltages

MOUNTING LAY OUT OF MAINTENANCE FREE VALVE

REGULATED LEAD ACID BATTERY BANK

28
A Case Study of 24 VDC System

29
A Case Study of 24 VDC System

DEFINITIONS

Cell : The minimum unit of which a battery is composed,

consisting of positive and negative plates,

separators, electrolytes, etc. In valve regulated had

acid batteries, normal, voltage is 2 volts per cell.

Battery : one or more cells connected to form one – unit and

having provision for external connections.

MF – Battery: A battery, which during its specified working life

needs, no maintenance other than charging, provided

normal operating conditions are experienced.

Float Charge: A parallel connection of charger, battery and load

where the charger generally supplies the de load and

maintain the battery is a charged state.

Boost Charge: A charge, generally at high rate for a short period.

Ampere Hour: Current multiplied by time. Used to indicate the

capacity of a battery.

Ampere hour efficiency: The ratio of the number of ampere hours

delivered during the discharge of a cell or battery

to the number of ampere hours necessary to restore

the initial state of charge under specified conditions

of temperature, current and final voltage.

30
A Case Study of 24 VDC System

Anode: The electrode by which electrons leave a cell and on

which electrochemical oxidation takes place.

7. 24 VDC System at KTPS-V Stage

24 VDC Power system is designed to cater the need of 100%

redundant no break DC supply to the load. Further system caters the need

of battery charging & trickle charging. Redundancy is achieved by

designing the system in such a way that even if anyone of the charger or

any two of four sections of Auxiliary Cubicle any two of the "battery fails,

it is possible to isolate the faulty one from the main system for

maintenance' and still feed the DC supply to the load.

The Charger is designed to float charge SMF cells at the

terminal voltage of 2.25V I cell i.e. at 27 V and simultaneously supply the

DC load. In charge mode the charger can charge the battery sets each of

12 V SMF cells of capacity 1640AH & 2165AH up to the terminal voltage of

2.35V I cell i.e. 28.2 volts. The charging current limit in battery paths is

adjustable between 100A to 4OOA.

The Charger unit derives power from 3 -Phase 415V, 50Hz,

AC supply, for 24 Volts DC system. Both chargers gives a continues DC

regulated supply of 27 Volts. The charger output voltage can be adjusted

by means of potentiometer. In both float as well as charge mode, range of

adjustment of output voltage is given in the technical specification.

The out put of each charger is controlled by an respective

electronic circuit and then the smooth DC out put goes to the Auxiliary

31
A Case Study of 24 VDC System

cubical through MCCB 1000A & 800A (which is fitted in Aux. Cubicle). All

out going DC terminations & distribution to the respective dual DCDB (600

& 800A) and Cattery (1640AH &. 2165 AH) from respective charger are

provided in the Auxiliary cubicle.

The 800Amps output of both Charger 1 & Charger 2 is given

to the section 1 & section2 respectively of Dual DCDB 8O0Amps through

Auxiliary cubicle. Foe each section 800A MCCB is provided at input side.

Bus coupler MCCB of 800A is also provided between two sections for

achieving the redundancy in the 24 Vdc supply on load side.

The 600Amps output of both Charger 1 & Charger 2 is given

to the section 1 & section 2 respectively of Dual DCDB 6O0Amps through

Auxiliary cubicle. Foe each section 600A MCCB is provided at input side.

Bus coupler MCCB of 600A is also provided between two sections for

achieving the redundancy in the 24 Vdc supply on load side.

32
A Case Study of 24 VDC System

TECHNICAL SPECIFICATION

33
A Case Study of 24 VDC System

1 Type of Charger : Float Cum boost Charger


2 Rated AC Input : 415V, +/- 10 %, 50Hz +/- 5 %, 3 Wire.
3. Rated DC Output :
Float Mode : 27V (Adjustable from 24 to 28V)
Charge mode : 28.2V (Adjustable from 24 to 30V)
4. Rated Output current : 1785 Amps
5. Rating Class : " A " (100% Continues)

(As per IS 4540)


6. Current limit : 110 %
a) Current limit at : From 80% to 110 %
b) Continuously adjustable :
7. Class of Insulation :
employed for
a) Rectifier Transformer : Class – “B”
b) Smoothing Reactors : Class – “B”
c) Rectifier Assembly : Class – “B”
8. Maximum permissible

temperature
a) Rectifier Transformer : 700C
b) Smoothing Reactors : 700C
c) Rectifier Assembly : SCR - 50 °C & Diode - 70 °C
9. Transformer Details :
a) Input (Primary) : 1) For T1: Delta
2) For T2: Star
b) Output (Secondary) : 1) For T1. Double Star
2) For T2. Double Star
c) Rated KVA : 69 KVA equally distributed In T1 & T2

each of 34.5 KVA


d) Impedance : 5%
e) Over load Capacity & : 10 %

rating
f) 1 Min. Power freq. : 2.5 KV

withstand voltage
g) Whether Single I Double : Double wound

wound
h) Method of cooling : Forced Air Cooling

34
A Case Study of 24 VDC System

10. Whether Automatic Yes

Voltage. Regulation is

6ffered
11. Method of voltage control Potentiometric Control
12. Whether any safety device Soft start feature prevents the

provided output voltage to rise during starting.

The feedback control system keeps

the output voltage within limits.

Bleeder resistance is also provided.


13. Guaranteed efficiency at : Better than 8%

rated load
14. P.F. at rated current : 0.8 at 415V AC Input Voltage
15. Equipment reactance Approx. 5 %
16. a) Type of rectifier cell : Silicon
b) Cooling method : Force Cooling
17. Whether smoothening : Yes

filter provided
18. Ripple Current at rated : a) With Battery: - 1 % RMS

load b) Without battery: - 1 % RMS

19. Battery Charger control :

panel
a) Sheet thickness : 14 Swg. (2 mm)
b) Approx. weight : 1650 Kgs.
c) Dimensions :
i) Height : 2430 mm
ii) Depth : 1200 mm
iii) Width : 1500 mm
20 Instruments provided on : AC /DC Voltmeter, DC Ammeter

charger panel current & Voltage transducers, Timer


21. Class of accuracy : Class 1 (1 %) for meters & 0.5 % for

transducers

22. Audio alarms with indication in charger panel

35
A Case Study of 24 VDC System

LH.S. Of the panel

a) AC Input Fuse Fail

b) Input Mains Fail

c) Input Phase Fail

d) Rectifier Fuse Fail

e) Free Wheeling Diode Fuse Fail

f) Smoothening Condenser Fuse Fail

RH.S. Of the panel

g) Charger Fail! System on Battery Operation

h) Charger Over Loaded

I) Inside Cubicle Temperature High

j) Redundant Fan Fail

k) Receive Attention

I) Spare

m) Spare

23. Indications provided in charger panel

a) Input AC ON

b) Input Contactor ON

c) Float mode

d) Charge mode

e) Receive Attention

36
A Case Study of 24 VDC System

24 Whether-output-MCCBs : Yes 3 pole MCCBs are provided in

are provided" for charger Auxiliary cubicle

25. Audio alarm with indication provided in Auxiliary cubicle for each

charger.

L.H.S. of the panel for Charger

a) System on Battery'1 (1640 AH)

b) System on Battery 1 (2165 AH)

c) High: Output DC Voltage DCDB1 (6ODA)

d) Low DC Output Voltage DCDB1 (600A)

e) High DC Output Voltage DCDB1 (800A)

f) Low' DC Output Voltage DCDB 1 (800A)

g) Earth Leakage in + Ve path of Batt.1 (1640 AH)

h) Earth Leakage in - Ve path of Batt. 1 (1640 AH)

I) Earth Leakage in + Ve path of Batt. 1 (2165 AH)

j) Earth Leakage in - Ve path of .Batt. 1 (2165 AH)

k) Output MCCB1 Trip ( 800 A )

I) Output MCCB2 Trip (1000A)

m) Receive Attention

RH.S. of the panel Charger II

a) System on Battery 2 (1640 AH)

b) System on Battery 2 (2165 AH)

c) High Output DC Voltage DCDB2 (600A)

d) Low DC Output Voltage DCDB2 (GOOA)

e) High- -DC- -Output Voltage DCDB2 (800A)

f) Low DC Output Voltage OCDB2 (800A)

37
A Case Study of 24 VDC System

g) Earth Leakage in + Ve path of Batt. 2 (1640 AH)

h) Earth leakage in - Ve path of Batt. 2 (1640 AH)

I) Earth Leakage in + Ve path of Batt. 2 (2165 AH)

j) Earth Leakage in - Ve path of Batt. 2 (2165 AH)

k) Output MCCB1 Trip (800 A)

I) Output MCCB2 Trip (1000A)

m) Receive Attention

26 Indications provided in : Receive Attention in both chargers

Auxiliary cubicle section

27. Instruments provided in : Charge / Discharge Ammeter in each

Auxiliary cubicle battery path

Auxiliary cubicle
28. Class of Accuracy : Class 1 (1 %)

38
A Case Study of 24 VDC System

BRIEF DESCRIPTION OF CIRCUIT

Circuit diagram of each identical Charger 24 V /1785 Amps is

divided in to three parts as follows.

1. Power circuit (XE 2440 A2)

2. Control circuit (XE 2441 A1)

3. Alarm and Annunciation circuit. (XE 2442 A2)

I. POWER CIRCUIT (XE 2440A21)

The charger derives power from the 415 Volts, 3- Phase, 50 Hz

AC mains. Isolation switch SW 3 with fuses F1, F2, F3 are provided at input

side for protection. AC voltmeter with voltmeter selector switch is provided

for measurement of voltages between different phases.

The incoming 3- Phase, 415 V AC supply is stepped down by means

of two double wound transformers T1 (  - Y Y) and T2 (Y - Y Y) and six

phase output of each transformers secondary is rectified by Thyrister

controlled bridge & IPTs. Free wheeling diode is provided in out .put circuit.

Further each thyrister is protected for short circuit and hole storage

transient effects by means of fuses & metal oxide variators (M0Vs).

Transient coming from the AC supply are suppressed by MOVs at the primary

and secondary side of the transformers T1 & T2.

Filter choke (L) & Capacitor banks (C1 & C2) are provided to

39
A Case Study of 24 VDC System

filter rectified DC out put of the charger to get smooth DC out put .

Capacitor banks are protected from fault current by filter capacitor fuses

(F23 & F24). Bleeder resistor (RB) is included in circuit to ensure proper

triggering of the thyrister at light load. Shunt I ammeter and voltmeter are

provided at the out put side to measure current and voltage respectively.

Voltage & current transducers are provided at the out put side of each

charger for feeding voltage & current signals to the DAS system.

The output of each charger is controlled by an respective

electronic circuit and then the smooth DC out put goes to the Auxiliary

cubical. All out going DC termination's & distribution to the respective Dual

DCDB ( 600A & 800A) and Battery ( 1640AH & 2165 AH ) from respective

charger are provided in the Auxiliary cubicle.

II. CONTROL CIRCUIT (XE 2441 A1)

DC out put of the each charger is controlled by AC phase control

technique with the help of SCR and voltage & current feedback, Voltage

feedback comes from the voltage divider network This divider continuously

monitoring the DC out put voltage & feeds voltage signal to the amplifier card.

Transformer T6 is a power supply transformer for the control

circuit. Secondary of this transformer is, rectified by two separate diode

bridge then rectified out put is supplied to power supply. to supply 15 V DC

out put to various control circuits like current limit card and amplifier card.

40
A Case Study of 24 VDC System

Transformer T3, T4, T5 and T7, T8, T9 are used to generate

synchronized triggering pulses for firing. Card II & I respectively for

triggering scraps. A 12-pulse drive unit with 12 single pulse control is used for

12 thyristors.

The control circuit consists of following cards.

a) Power supply card (XA 760 C)

This circuit provided j: 15 V DC supply to various control circuits.

Its output is 200 mA. & It is protected from over load by current limit

circuit. The feedback system used in the equipment gives rise to overshoots

and undershoots for step changes in either the input voltages or load .It has

been observed that if overshoot is limited to' about 5% of the voltage

without floating battery, satisfactory results are obtained.

b) Firing card (XA 526/ 2)

Two firing cards I & II are used in this circuit to trigger 12

SCRs in bridge. Each firing card triggers 6 SCRs. Synchronizing transformers

T3, T4, T5 and T7, T8, T9 used for synchronization of AC voltage with

respective firing cards.

Working of PCB XA 526 C:

The drive unit is constructed with three ICs (IC2, IC3, and IC4)

41
A Case Study of 24 VDC System

in each control unit. A 15 Volts DC supply is required to operate the drive

units.

The synchronized AC voltage for R phase is connected to pin no.

5 of IC TCA 785 (IC2) through resistor R5 & to ground potential via two

back-to-back diodes 08 & 09. Pin no. 1 is the common ground point. Similarly

for Y & B phases’ synchronized voltage is taken to pin no. 5 of IC3 & IC4

through resistors R10 & R15 respectively.

A saw tooth amplitude of 8Volts Is determined by ramp

capacitor C5 & ramp resistor R6 & potentiometer PR 1. The RC combination C5

& R6 thus determines the slope of the voltage rise- of the ramp voltage at pin

10 of IC2. Every ramp begins a zero crossing of the synchronization voltage &

ends at the next with the discharge of the ramp capacitor C5 caused by an

Internal circuit in the IC.

The controlled DC voltage at pin no. 11 of IC2 can be varied-

between 0.8 to 8 volts. The control voltage is compared with 1he ramp voltage

and the respective output- pulses of the trigger angles are started.

Two outputs from pin no. 15 & 14 of IC2 are taken to transistor

TR3 & TR4 "pulse transformers PCB XA 527. Pin no. 15 of IC2 delivers pulse

only in the +ve half waves and pin no. 14 of1C2 delivers pulse in -ve half waves.

Output pulses taken from pin no. 15 and 14. of each of the three TCA 785 IC

at 1200 interval and fed to- the primary of the pulse transformer; Respective

42
A Case Study of 24 VDC System

thyristors gate receive the bigger pulse from the secondary winding of the

pulse transformer. For three phases’ les IC2, IC3 & IC4 are used.

The control voltage can be adjusted between 0 to 8 volts. When

the +ve going saw tooth voltage reaches the control voltage value (at pin no.

11) a trigger pulse is enabled at IC2 output at pin 15. The more +ve the control

voltage, longer the saw tooth voltage takes to reach the point at which the

thyrister is triggered. Thus the pulse can be shifted in time by control

voltage and the conduction angle is adjustable at the load.

c) Amplifier card ( XA 375 0 )

Negative reference voltage from zener OZ1 and the voltage-

sensing signal from the voltage divider R21, R22, RV3, RV4, R14.R15 is given to

the inverting input of the error detector amplifier IC1. Output of IC2 is fed

to IC1 through an OR gate formed by diode 02 & 046 by the voltage divider

network.

If the inverting input of IC1 tends to rise due to an increase in

the output voltage or charging current or total current during charging I the

output of IC, which is given to the pin no. 1 of firing card decreases. The

charging current of C1 reduces, leading to an increase in the value of the

firing angle of the SCR1. The C9 - R36 combination forms a soft start ckt. So

that, the output voltage builds up slowly when the unit is switched ON.

d) Current limit & over load card (XA 243 D)

43
A Case Study of 24 VDC System

This card contains OPAMP, which senses the milli volt drop

across the shunt SH1 which measures total out put current of the charger.

This milli volt drop is directly proportional to the total current" The bleeder

cut helps in the reduction of power consumption and also in reducing inside

ambient temperature of the unit.

The circuit works as follows

The output of the IC1 is given through DZ1 to the transistor TR3

in the current limit card. When the output of the OPAMP IC1 is small, the

transistor TR3 is in full conducting state. When the output voltage of the

OPAMP IC1 increases, the emitter voltage of TR3 also increases & it switch

ON the sensing circuit, which operates a relay BC1 is connected in series with

the bleeder cut contractor coil 2CON/ 1. When the contact BC/1 operates 2

CO /1 de -energizes the bleeder resistor RB gets disconnected from the unit.

A small hysterics of about 10% is provided for relay BC/ 1 to minimize

contactor chattering. This card also consists of overload alarm circuit. Relay 1

DCOL /3 & 2DCOL 13 will operate when total current exceeds 110% of the fun

load capacity of the equipment.

e) Charger fail card (XA 225 D)

This card senses out put current in terms of voltage from

current limit section of the amplifier card. When charger out put voltage is

less than battery voltages then this circuit operates to give charger fail

44
A Case Study of 24 VDC System

indication. in this case charger is in condition the charger is ON but not

taking the load.

III. ALARM AND ANNUNCIATION CIRCUIT:. (XE 2442 A2)

All indications & alarms for the faulty condition of the charger

as per the specification are provided in this circuit. Two sets of the potential

free contacts are also provided on the 2.5 Sq.mm terminal block for DAS &

owners annunciation system.

Following audiovisual alarms with indication are provided in each charger.

LH.S of the panel:

a) AC Input Fuse Fail

b) Input Mains Fail

c) Input phase Fail

d) Rectifier Fuse Fail

e) Free Wheeling Diode Fuse Fail

f) Smoothening Condenser Fuse Fail

RH.S of the panel:

a. Charger Fail/ System on Battery Operation

b. Charger Over Loaded

45
A Case Study of 24 VDC System

c. Inside Cubicle Temperature High

d. Redundant Fan Fail

e. Receive Attention

f. Spare

g. Spare

Indications provided in charger panel

a) Input AC ON

b) Input Contactor ON

c) Float mode

d) Charge mode

e) Receive Attention

The annunciation system has acknowledged and tests push

buttons; buzzer for audio indication and facia window for visual indication- On

fault tubular bulb in respective window glows and buzzer starts ringing. When

fault is cleared respective audio & visual indication goes OFF.

The alarm & annunciation circuit works as follows:

1. AC Input fuse fail:

When Input fuses F1, F2, F3 blows, respective trip indicating

46
A Case Study of 24 VDC System

fuses FT1, FT2, FT3 also blows and its plunger operates micro switch MS4.lt

energizes Relay ACFF/3 and its contact ACFF /1 closes hence lamp 4. AC

Input fuse fail" indicator will glow. For buzzer gets supply through relay 1

RA /1 NC contact & audible alarm comes. After pressing alarm accept push

button PB3" 1 RA / 2 operates and buzzer stops ringing and lamp 10" Receive,

Attention" glows.

The fault lamp and receive attention lamp goes OFF once the

fault is rectified. Similar operation takes place for any fault listed above.

PRECAUTION: Before rectifying any fault (replacing component) the Charger

should be isolated from incoming AC mains supply.

2. INPUT MAINS FAIL:

Relay MF/3 is connected across the output of the bridge

rectifier consisting of D39 through 042. Relay MF/3 remains operated due to

presence of incoming supply voltage. Contact MF1 is NC, when mains failure,

relay MF/3 gets de-energized and closes contact MF1 to get audio visual

indication of " Mains Fail”.

3. Input Phase fail:

The phase fail is sensed by the resistance R1, R2 & R3 &

capacitor C17 & rectifier bridge D8 under normal conditions when all three

-phases are available in the correct phase, sequence voltages across the diode

47
A Case Study of 24 VDC System

bridge is all most zero. On failure of any phase or reversal of phase sequence

disturbs the bridge ckt. Balancing and voltage drops across the diodes. Relay 1

PF/2 operates and its contact 1 PF/1 closes to operate relay 2PF/3. Which

glows lamp 5 to get audiovisual indication of “Input Phase fail ".

4. RECTIFIER FUSE FAIL:

Trip fuses through FT11 to FT22 are in parallel to rectifier fuses

F11 to F22 respectively. Whenever rectifier fuse blows, the trigger fuse also

blows to operate respective micro switch MS2, MS7, MS9 or MS10. These

operate relay 1RE/3. Which glows lamp2 to get audiovisual alarm of" Rectifier

Fuse fail".

5. FREE WHEELING DIODE FUSE FAIL :

F37 is free wheeling diode fuse & FT25 is its respective trigger

fuse connected in parallel. If F37 blows F25 also blows & its plunger operates

micro switch MS8. MS8 extends supply to the relay FWD/3. Contact FWD/1

closes to glow tamp 1 to get audio visual alarm of" Free Wheeling Diode fuse

fail

6. SMOOTHENING CONDENSER FUSE FAIL:

F23 & F24 are filter capacitor protection fuses, trigger fuses

FT23 & FT24 connected in parallel to them respectively. Whenever F23 & /or

F24 blows its respective trigger fuse FT23 &/or FT24 also blows to operate

48
A Case Study of 24 VDC System

micro switch MS3. MS3 extends supply to relay SFF/3, Contact SFF/1

operates to glow lamp13 to get audio visual indication of II Smoothening

Condenser fuse fail II

7. CHARGER FAIL I SYSTEM ON BATTERY OPERATION:

When charger out put voltage is less than battery voltages, load

is operating from, battery I charger fail circuit operates it senses out put

current in terms of voltage from current limit section of the amplifier to

operate relay CF/3. Contact CF/1 closes to glow lamp 6 to get audio visual

alarm of Charger fail I System on Battery Operation". In this case the

charger is ON but not taking the load.

8. CHARGER OVER LOAD:

Relay DCOU3 operates at 110% of the charger capacity, contact

DCOU1 closes and lamp 9. Glows to get audiovisual alarm of Charger Over Load

8. Inside Cubicle Temp. High:


9.

If inside temperature in charger goes above' ambient temp +

10°C (this value sated in thermostat) then thermostat provided in toe charger

senses it & energize' relay ITH/2 Contact ITH/1 closes to glow lamp 7 to get

audio visual alarm of “inside Cubicle Temp High”.

1 O. REDUNDANT FAN FAIL:

49
A Case Study of 24 VDC System

The micro switches MS5 & 6 are fitted above exhaust fan in

such a manner that they are normally closed when fans are in ON when any

fan fails then MS5 & I or MS6 opens which closes contact NO contact of

relay RFF/3 . Contact RFF/1 operates to glow lamp 8 to get audiovisual alarm

of "Redundant Fan Failure.

50
A Case Study of 24 VDC System

DC Distribution Board feeder details (USA and UCB Power supplies of DDC Pro control
Panels)

DDC Panel NAME Panel Description

CRA 01 Mill AB Panel

CRA 02 Mill CD Panel

CRA 03 Mill EF Panel

CRA04 Forced Draught (FD) Fans Panel

CRA 05 Induced Draught (ID) Fans Panel

CRA 06 Deaerator / Hot well level control

panel

CRA 07 Feed control station / Drum level

control Panel

CRA 08 Super Heater Spray Panel

CRA 09 RH Spray and HP heaters 5 and

Panel.

CRA 10 Bearing cooling water / LP Heaters

panel

CRA 11 CMC / PA Fans Panel.

CRB 01 Air Heaters A and B Panel

8. Brief Description of the Main Components in the Charger

51
A Case Study of 24 VDC System

(A) Transformer

WORKING PRINCIPLE OF A TRANSFORMER

A transformer is a static (or stationary) piece of apparatus by

means of which electric power is one circuit is transformed into electric

power of the same frequency in another circuit it can raise or lower the

voltage is a circuit but with a corresponding decrease or increase in current.

The physical basis of a transformer is mutual induction between – two circuit

linked by a common magnetic flux. In the simplest form of consist of two

inductive coils which are electrically separated but magnetically linked

through a part of low reluctance as shown in figure. The two coils posses high

mutual inductance. If one coil is connected to a source of alternating voltage,

an alternating voltage, an alternating flux is setup in the laminated core, most

of which is linked with the other coil in which it produces mutually induced

emf. According to faraday’s laws of electro magnetic induction e = mdi/dt) if

the second coil circuit is closed a current flows in it and so electric energy is

transformed (entirely magnetically) from the first coil to the second coil. The

first coil in which electrical energy is fed from the AC supply mains, is called

primary winding and the other from which energy is drawn out is called

secondary winding. In brief transformer is a device that

1. Transforms electric power from one circuit to another.

2. It does so without a change of frequency.

3. It accomplishes this by electro magnetic induction.

52
A Case Study of 24 VDC System

4. Where the two electric circuits are in mutually inductive influence of each

other.

B. SCR:

A Silicon controlled rectifier is a semiconductor device that acts

as a electronic switch. It is one of the prominent member of the thyrister

family. It is a four layer PNPN or NPNP. Basically it is a rectified with a

control element. It can change alternating current into direct current and

direct current into alternating current etc., It consist of three diodes

connected back to back with a gate connection. It can control the amount of

power feed to the load. It can control loads by switching current OFF and ON

up to many thousand times a second It can switch ON for variable length of

time, there by delivering selected amount of power to the load. Thus, SCR

combines the features of a rectifier and a transistor and posers the

advantage of a rheostat and a switch with none of their disadvantages.

ANODE A

P S1 G
N
GATE S2
P

N S3 C

CATHODE

53
A Case Study of 24 VDC System

When a PN junction is added to the junction transistor the

resulting three PN junction device is called a Silicon controlled rectifier.

Thus, the structure of the silicon controlled rectifier (SCR) consist of four

alternate P and N – type layers, as in the four layer diode below figure 11(a)

shows its construction. The circuit symbol for the SCR is shown in fig (b).

In the SCR, connections are made available to the inner layer,

which are not accessible in the diode. The three junctions are marked J1, J2

and J3 where as the three terminals are: Anode (A), Cathode (C) and Gate

(G), which in connected to the inner P type layer. The function of the Gate is

to control the firing of SCR. In the normal operating conditions of SCR, anode

is held at high positive potential w.r.t to cathode. Since they conduct large

currents, junction areas of SCR are very large.

TWO TRANSISTOR REPRESENTATION OF SCR:

The operation of the SCR may be explained by considering it to

be divided in to two parts each being a transistor T 1 and another NPN

transistor T2 as shown in fig (1) fig (2) shows its electrical equalant circuit.

Thus, the equipment circuit of SC is composed of PNP transistor

and NPN transistor connected as shown in fig (3). It is clear that thereby

making a positive feedback loop. It is also clear that collector current of T 1 is

54
A Case Study of 24 VDC System

also the base current of T2 and the base current of T1 is also the collector

current of T2.

It is obvious from the figure that if gate terminal ‘G’ is not

connected anywhere, the gate current Ig is zero. A voltage supply VSS is

connected in series with a protecting resistor R between the anode and the

cathode as shown in fig (3). Under this condition junction J 2 is reverse biased

while junction J1 and J3 and forward biased, the whole unit behaves as an open

circuit between anode and a cathode. But when by inserting a current pulse at

the gate G, the junction J2 is forward biased, then the unit acts as a short

circuit and the current is limited only by load resistance.

When a positive voltage is applied at A with respect to cathode,

each of the emitter junction is forward biased while J 2 remains reverse

biased. Then the two currents IC1 and IC2 are very small and are given by

IC1 = 1I + IC1  (1)

IC2 = 2I + IC2  (2)

Where  and IC0 are the current gain and collector reverse saturation

current, respectively. Then the total current at the anode terminal is given by

I= IC1 + IC1 = (1 +1 )I + ICO1 + ICO2

ICo  IC0
1 2
(or) I = 1  (   )  (3)
1 2

55
A Case Study of 24 VDC System

Since the currents IC1 and IC2 are very small there are the

leakage currents only. The leakage current is silicon is very small and at low

emitter currents the value of  in a Silicon transistor is also small. Because of

these conditions, the current given by equation (3) is low. For ordinary

transistor the value of  is rapidly as the emitter current of a junction is

increased, and Equ – (3) shows that as the sum of 1 and 2 approaches unity,

the current – I will become very large. It is the characteristic property of

silicon junction that the value of  in quite small at very small current levels

and it increases as the current level is increased. Such property is not

exhibited by germanium and hence the controlled rectifiers are always made

of silicon.

VOLT – AMPERE CHARACTERISTICS OF SCR:

The voltage current characterization of SC is shown in fig © in

fig (a) current flow is blocked due to reverse – biased junction J 2. However

when anode voltage is increased, A certain critical value called forward break

over voltage VBO is reached when J2 break down and SCR switches suddenly

to a high conducting stage.

56
A Case Study of 24 VDC System

When a reverse voltage is applied between A and C small leakage

current flows. Similarly a small leakage current also flows when it is forward

biased. When forward voltage is increased a breakdown condition in reached

which fires SCR. The firing of SCR can be also be made by applying a short

positive pulse current at the gate. This is denoted by dotted line Ob. SC

remains conducting as long as the above current in maintained greater than

holding current**. IH if anode current becomes less than IH, SCR turns off.

With supply connection as in fig (b), the current through the SCR

is blocked by the two reverse biased junctions J 1 and J3 when V in occurs

which may destroy the SCR. Hence it is seen that SCR is a unidirectional

device unlike triac, which is bi-directional.

57
A Case Study of 24 VDC System

The Volt- Ampere characteristics can be explained on the basis

of factor . Referring to the SCR characteristics shown in fig region loop

corresponds to low currents (+2)<1, with junction J2 being reverse biased.

Here the sum (1+2), which increases in the region PA, in equal to 1 at point

A. the point A Corresponds to break over or triggering voltage VBO and

including and holding current IH. As the value of (1+2) increases with

current, the junction J2 will be forward biased and the region AB will

correspond to high current and two-voltage drop. Since the region AB is

associated with a negative resistance, conduction in the device will stop only if

the current value is reduced below the value of IH, when the operating point

will go from B to O.

A current IG, applied to gate region P and driven across junction

J3, can effectively increase the vale of 2 due to increase in base current of

Junction J3. This is the principle of silicon control rectifier (SCR). Thus the

condition 1+2= 1, can be attained at lower values of break over voltage even

through, IG may be small. The higher the value of triggering gate current IG,

the lower is the value of the applied voltage V at which break over occurs, as

shown in fig (a).

Thus, with a relatively high value of Ig, the device turns on at

very small values of applied voltage. Also when the current values fall below

IH, conditions cases and the device appear to be very strongly reversed

biased.

58
A Case Study of 24 VDC System

Once the SCR has fired the gate loses its controlling action and

the SCR cannot be turned OFF by gate signals. The only way to bring the SCR

back to its normal OFF condition is to reduce the anode voltage sufficiently

for anode current to drop blow holding current IH. A typical Sn 050 Silicon

controlled rectifier has a peak reverse voltage of 30V, typical gate trigger

currant of 1.0 MA and typical holding current of 50 MA. Its turn on time

approximates one – Sec and turn of is accomplished in 5 to 10 – Sec,

thereby exceeding the capabilities of usual thyratrons is switching speeds.

59
A Case Study of 24 VDC System

9.General DC Applications in Thermal


Power Stations

1. 24 V DC System for DDC System:

To give a supply to DDC Pro control system – DDC is a

microprocessor based, programmable and distributed control and monitoring

system. Which is capable to perform all the function which are required to

maintain Thermal power Plant in auto / manual.

1. Signal conversion (For Signal E.g. are Temperature, Pressure, Flow,

ON/OFF Etc.,)

2. Signal Transmission.

3. Monitoring.

4. Binary (on-off, sequential) control.

5. Analog (modulating) control.

6. Protection.

7. Communication.

Digital Distribution Control represents the latest state of the

art in power plant control system design. It is a high-grade control system

and will meet the ever-increasing demands, which are made on the operational

reliability and availability of power stations.

60
A Case Study of 24 VDC System

10. Conclusion

Distributed Digital control is the decentralized supervision &

controlling of thermal Power Plant equipments and various parts. This DDC

system is working on 24V DC supply, which is supplying by 24V charges.

Hence, it is understood from the project that without 24V DC supply

the plant equipment mainly Boiler, Turbine and Generator cannot be

controlled, operated or safety shutdown.

The 24V charger – I & II and its battery banks are continuously

monitoring and taking parameters are very important for trouble free

operation of thermal power plant equipment.

Power situation in the country is worsening day by day, with liberal

policies now in force, more and more high tech machinery equipment would be

pouring from outside putting very exacting demands on owner, procurement of

high quality stand by power sources like UPS would become inescapable.

61
A Case Study of 24 VDC System

11. Bibliography

1. PRINCIPLES OF ELECTRONICS – V.K. MEHTA

2. Power Electronics By Kanchandani.

3. POWER ELECTRONICS – P.S. BHIMBRA.

4. Power Electronics By. Md. Rashid.

5. Operation and Maintenance Manual of M/s Amararaja

Batteries Limited for MF-VRLA Batteries.

6. Operation and Maintenance Manual of M/s AFCO SET 24

Volts DC Chargers.

7. Electrical Technology By B.L. Tereja.

62

S-ar putea să vă placă și