Mechanical Smoke Ventilation Calculations

For …………………………………

Mechanical Ventilation system for ………………………

Q g L2 1/3 Z +2
Mf = 0.58 p 2 + 1+ 0,22
p Cp T0 L

WHERE :-

Q = Heat Flux = 5000 KW FOR Shoping Araes


p = Density of smoke
= 1.2 Kg/m3
Cp = Specific Heat
= 1.01 Kj/KgK
g = Gravity Accel.
= 9.81m/sec2
T0 = Abs.Temp - Amb.Temp.
= 303 K
L = Length of void edge past which gases spill
= Width of void
= 3m
Z = Hight of rise of thermal plume above void edge
= H - d2 = 4.0 - 0.8
= 3,2 m
= Emprical hight of virtual source below void edge
= 0.3 H = 0.3 x 4
= 1,2 m

THEN :-

Q g L2 1/3 Z + 2 1,2
Mf = 0.58 p 2 + 1,2 1+ 0,22
p Cp T0 3

Mf =
5193,05