Documente Academic
Documente Profesional
Documente Cultură
V.M.RAJAN,M.E.(Struct),FIE,
Former CE/Civil/TANGEDCO
******
(i) Normally the positions of the columns are shown by Architect in his
plans .
(iv) While fixing the columns orientation care should be taken that it does
not
change architectural elevation. This can be achieved by keeping the
column
orientations and side restrictions as proposed in plans by the Architect
.
(v) As far as possible, column projection/s outside the walls should be
avoided,
unless Architect’s plans show contrary or same is required as
structural
requirement.
(vi) Columns should not obstruct door and window position/s shown in the
Architect’s plans.
(viii) When the locations of two columns are near to each other (for e.g.
the corner
of the building and intersection of the walls), then as for as possible
only one
column should be provided .
(ix) As far as possible, column should not be closer than 2.5m.c/c to avoid
stripped/
combined /continuous footings. Generally the maximum distance
between two
column should not be more than 10.0 m.c/c. Spans of 4 to 6.0m give
normal
sizes of beams. Forr Residential Building Maximum Columns spacing
shall be
between 3m to 4.0m only.
(x) Columns should be normally provided around staircases and lift wells.
(xi) Preferably overhead water tank should rest on the columns as shown
in the
Architect’s plan. The height of water tank should be up to 2.0m.
(xii) Twin columns of equal size are desirable at expansion joints from
aesthetic
point of view .
(xv) When columns along with connecting beams from a frame, the
columns
should be so orientated that as far as possible the larger dimension
of the
column is perpendicular to the major axis of bending. By this
arrangement
column section and the reinforcement are utilized to the best
structural
advantage.
3. Alignment of columns
Thumb rule no.1
Size of the columns
The size of the columns depends on the total load on the columns. There
are axial loads and lateral loads. Large beam spans induce bending
moment not only in the beams, but also in columns which are pulled by
the stresses in the beams. It is highly recommend every structural
designer learn some softwares like STAAD Pro or ETABS for design of high
rise Buildings. The thumb rules are for general designing in very small
projects.
Minimum size of an RCC column should not be less than 9”x 9” (230mm x
230mm) with 4 bars of 12 MM Fe500 Steel.
This setup of 9″ x 12″ RCC columns is safe for G+1 Floors. There are a lot
of other considerations, but this is just a thumb rule.
Practical column sizes used for centering point of view are 9” x 9” (230
x230mm),
If larger barrier free distances are required then going for larger column
size is to be used.
Alignment of Columns
mistakes and placing in columns can be done in the right way. Placing of
columns
depend completely on the plan. A planner has a very important role. A grid
column
placement is always preferred in order to reduce point loads and
unnecessary
required for construction. Beams which have continuity with other simply
supported
beams have reduced bending moments, and thus require less steel and
concrete depth
An experienced planner will keep such things in mind when planning the
structure.
design. It should be remembered that when columns are erected, beams are
laid
ar d r d ar d
Max.
span in 6.0 10.0 8.0 12.0 3.0 5.0
‘m’
13. Beams which are required to give a planer look from the underside
shall be
provided as inverted beams, e.g. canopies. Alternatively hidden beams
inside the slab having the same depth as thickness of slab may be
adopted.
Such hidden beams can be provided in toilet blocks, under partition wall
One-way or two way slab details can be obtained from aspect ratio
L/B=2
Aspect Ratio =
1. For one way slab design, there could be serious of long beams with
spacing approximately between 3m to 5m.
2. For two way slabs, cross beams shall be provided so that the smaller
span of two way panel lies between 4m to 6m.
4. Two way slab can be adopted for shorter spans above 3.0m.
6. As two way slabs are not economical for short spans, in practice,
even though a slab may be supported on all four sides, still it is
designed as one ways slab transferring load only in one direction. Care
should be taken to provide minimum steel at top across the short edge
support to avoid the cracks to be developed at top along short edge
support.
Live Load = 5 KN / m2
Maximum span in
1.50 2.0 3.50 4.50 4.50 6.0
meters
9.Types of slabs:-
Slabs are classified based on whether the slab is supported on four edges
or not. If the slab is supported on four edges, check the aspect ratio ly/lx.
If ly/lx is < 2 it is Two way slab. If ly/lx is >2, it is one way slab. For two
way slab, there are 9 edge conditions. In two way slab, the main
reinforcement is provided in two directions. In one way slab, the main
reinforcement is provided in one direction only. For slab not supported on
four edges, they are classified as follows:-
(i) If the slab is supported on 3 edges all around, the slab is designed as
one way
designed as one
(iii) If the slab is supported on two adjacent edges, the slab may be
designed as
floor level for Indian type water closet. Slabs for toilet block and Nahani
11. Stair case waist slab shall be generally one way slab.
12. Loft slabs over toilets are generally supported on partition walls of
toilet and
W.C. Loft load should be considered while designing the beams
supporting these
walls.
13. Flat slabs may be found economical for spans of 6.0 to 9.0m
standardized/established method.
In this scheme of marking, starting from the column at the bottom left
corner, series of imaginary horizontal grid lines passing through each
column are marked as A-A, B-B, C-C etc., and vertical grid lines passing
through each column are marked as 1-1, .2-2, 3-3 are shown in figure.
The columns are designated as Cij in which suffix i and j refer to
horizontal (ith) and vertical (jth) grid lines intersecting at the column.
Thus, the column at x is marked as C D3. Beams are marked as BM1,BM2
etc., serially starting from the top left corner and proceeding downwards
and then rightwards (bay wise) sequentially. Slabs are designated serially
as Sb1, Sb2 starting from panel in top left corner, proceeding vertically
downwards bay wise and rightwards. This scheme is partially followed in
practice. Scheme of marking columns in this way is very common, but
that for beams and slabs is not very much favoured (especially writing
suffixes m and b to mark beam and slab respectively, is considered to be
superfluous).
2. Estimation of Loads:
Before we design any structure, it is very necessary to understand the
complete structural system of the structure. How the load act on them,
how are they transmitted from one element to the other, etc., must be
easy to design it, however, the first part of the problem, i.e. finding out
system and the way in which the load transfer takes place.
The buildings are designed to carry some live loads, functional loads and
many other loads during its life span. To carry the loads, we provide the
structural systems like slabs, beams, columns etc., which also have dead
loads. The functional loads may be dead loads like tiles, walls, partitions
The loads are usually first carried by the slabs although the beams may
be subjected to direct loads. The slabs will transfer the loads on the
will resist loading by axial compression with bending and will transfer
them to the foundations. Foundations will also resist the loads by bending
1.Slab:
Thumb rule: ½” per foot run Or 1 cm per 1 foot run (Convert 1 m multiply
by 3 to get feet). Example for 5.0m span i.e 15’, the slab thickness
required is 15x1=15cm.
Oneway slab:
Width:
Width of beam= width of wall or 1/3 to 2/3 depth of beam for all beams
Depth:
Dp/Dt =1.67 Ly/Lx but not less than 2.5 where Dp=Depth of beam
Dt=Depth of slab
Size of column shall be chosen on the higher side and richer mixes and
age factor
concrete and Fe 500 TMT bars for Multistoreyed building design. For
achieving
economy in shuttering, column size can be kept the same throughout the
height of building(or in steps of a few storeys at the least) for carrying the
subjected to bending also in addition to axial load the longitudinal bars are
arranged
at the faces in the plane of bending. Generally in top storey the axial load
is less but
building is designed for higher floors and construction is limit to less than
designed
floors, design should be checked for top most floor and accordingly the
column
at different floor levels. Loads are transferred slabs to beams and then to
columns.
Hence, slabs and beams are normally designed prior to the design of
columns. This
method enables one to asses the loads on columns more accurately and
design of
column becomes realistic and economical.
columns and footings to be given to the client prior to the design of slabs
and beams.
column. These loads are normally calculated on the higher side so that
they are not
less than the actual loads transferred from slabs/ beams. This method of
design of
of giving the design of column and footings prior to the design of beams,
the
Office/commercial
Column Position Residential building
building
Residential Flats 16
Education/Medical hospitals
18
building
Library/Godowns/printing press
22
building
Industrial Building 20
Staircase/ Escalators 18
1. Extra load for sitout & Balcony: This can be separately computed
and
apportioned to the column concerned.
2. For Lift & Machine room: extra loads can be arrived from the lift &
Machine
room data.
3. Overhead Tank: extra load can be easily calculated Dead wt. of
OHT+weight of water to be stored and apportioned to the column
concerned. For example
10,000 litres capacity of OHT the dead weight of tank may be taken
as 100%
weight of water i.e 10m3 or 10tonnes. Total weight is 10t+10t =20t.
Load on
each column assuming supporting water tank column as 4,
=20t/4=5t.
Moment factors to be considered for calculating loads on columns as
per
Total Load intensity=load intensity for silt Floor+ load intensity for
residential
= (8 +3x16+10)=66KN/m2
b=width of column.
For 1.5 x 1452= 2178 KN ultimate load, area required= 80x 2178
=174240 mm2
Ast required= 2/100 x(230 x750) =3450mm2 . Provide 8 Nos. 25 dia steel.
=1851KN. >1452KN .
For example for (Silt +4Floors) residential building interior column with
M20 concrete with 5m by 4m grid
For Seismic areas : Assume Pu/fck bD=0.35 for side column and 0.30 for
corner column. In case of non seismic areas, the ratio will be 0.40 for side
column and 0.35 for corner column.
For example if Pu= 2178KN, fck=20, column area for non seismic zone for
side column=2178x1000/0.40x20=272250mm2 . The size of column is
300 x 900mm. Assume 0.8% of C.S area=2160mm2. Provide 8 Nos. 20mm
dia bars. (2512mm2.2160mm2)
(ii) If the line of action of the eccentric Load is inside (within the section)
Assume that line of action of axial load is inside the section and check this
later.
100
Method 6:
b = Breadth of Column in mm
The first step is to find out the Influence Area of the Column to be
Designed. In this plan the tributary area for internal column= (2.85 x
2.35) =6.70m2
STEP 2:- Calculation of the Loads Coming on Column from the
Influence Area :
In this step the Load Calculation is being done. This is done by calculating
all the loads acting within the influence area.
The Loads acting are broadly classified as Dead Load (DL) and Live Load
(LL). Dead Loads are the load of objects which cannot be moved from on
place to another like the loads of Brick Work, Beams, Slabs etc. and the
Live Loads are the loads coming from movable objects such as Humans,
Chair, Table etc.
Thus We Need to Calculate the Dead Loads as well as Live Loads within
the Influence Area, these are as follows in the general case of a Building :-
A) Dead Loads :
B) Live Load :
It depends upon the Nature of the Structure, and it values for different
structural nature are given in the concerned Code of Practice, like in India
these are given in I.S.: 875-Part II.
Dead load
Now after correct calculation of above loads the Total Load is Calculated
by,
Now this the actual load which will be acting on column for each floor, now
if the building say 5 storied, then just multiply the value with the nos. of
floors, like for five storied building multiply the Total Load on each story
with 5.
Now thus the Total load acting on column at Column Base is obtained and
it is denoted with ‘P’.
Hence P= Total Load on each Floor X Nos. of Stories = (Dead Load + Live
Load) X Nos. of Stories.
The Modern Practice is to use Limit State Method for all types of
Designing, Hence we discuss here the Limit State Method Of Design Of
Column.
This is the one of the most important and main step of the Design of
Column.
First in the Limit State Method of Design we must increase the load acting
on the column with a Load Factor so that if there will be any accidental
increase of loads the column will be still safe to resist the load without a
failure. The Factor of Safety for Dead Load + Live Load Combination is 1.5,
hence we must multiply the load action on column (P) with the 1.5 to
obtain the Ultimate Load that is the Factored Load of the Column that is Pu.
Now before going on we here to say that we will design according to the
Code Of Practice of I.S.: 456-2000
Now the column consists of Concrete and as well as Steel in the form of
Reinforcements hence the Total Cross-Sectional Area of Column is made of
Area of Concrete and Area of Steel.
Therefore, Ag = Ac + Asc
Now putting the above obtained value in the original equation (Equation I)
we get,
The higher will be the percentage of steel used the lower will be Ag and
thus lesser will be the cross-sectional dimension of the column. But the as
the Price of Steel is very high as compared to the Concrete hence it is
desirable to use as less as steel possible to make the structure
economical, again if the percentage of steel is lowered then the Ag will
increase at higher rate, about 30% with decrease of just 1% of steel and
so each lateral dimension of the column will increase and will cause a
gigantic section to be provided to resist the load. Therefore both the
factors are to be considered depending upon the amount of loadings.
Now input the value of the Asc in the form of Ag in the Equation I. For
example suppose 1% Steel is used then the equation will be like the one
below :-
Pu = 0.4.fck.(Ag-0.01Ag) + 0.67.fy.0.01Ag
Now as the Ag is obtained thus the Lateral Dimensions of the Column that
are the sides of the column can be easily determined.
For making a Square Section just Determine the Root Value of the Ag. Like
if the Value of Ag is 62500 mm2 Then considering square section of a
column we can get each side
Most of the times after calculating the sides of a column it will give results
such as 196.51mm or 323.62 etc. values, which practically cannot be
provided at field, hence we must increase those values to the nearest
greater multiple of 25mm (i.e. 1 inch). For examples a value of 196.51mm
may be increased to 200mm or 225mm or 250 mm even, and a value of
323.62mm may be increased to 350mm. more it will be increased the
more it will be safer, but it is uneconomical to increase by a very high
amount, it should not be increased more than by 75mm to consider the
economical factor.
Eccentricity means deviating from the true axis. Thus an Eccentric Load
refers to a load which is not acting through the line of the axis of the
column in case of column design. The eccentric load cause the column to
bend towards the eccentricity of the loading and hence generates a
bending moment in the column. In case of eccentric loading we have to
design the column for both the Direct Compression and also for the
bending moment also. Practically all columns are eccentric to some extent
which may vary from few millimetres to few centimetres. In practical field
it is almost impossible to make a perfectly axially loaded column, as a
reason we have to consider a certain value of eccentricity for safety even
though if we are designing for a axially loaded column. The conditions of
considering eccentricity and its value may differ from code to code
according to the country. Here I will tell you what I.S. : 456-2000 says.
According to it the eccentricity which we have to consider for design must
be taken as the greater of the followings :-
i) 20mm.
Where,
Now the Area of Steel Required Asc is to be calculated from the Ag as the
predetermined percentage of Ag. For example if the Gross-Sectional Area
of the Column is 78600 mm2 and at the starting of calculation of Ag it was
assumed that 1% Steel is used then we get,
Hence in the above case we shall Provide 4 Nos. of 16mm Diameter Bars
Hence the Area of Steel Provided is Greater than Area Of Steel Required,
Hence the Structure will be Safe.
In this step we will Determine the Diameter and the Spacing of the Lateral
Ties or Transverse Links or Binders.
The Diameter of the Ties shall not be lesser than the Greatest of the
following two values
1. 6mm
For an example if a Column has 16mm and 20mm both types of bar as
Longitudinal Bars or main Reinforcement then 1/4th of 20mm = 5mm
Hence we shall provide 6mm diameter Ties. But in practice we use 8 dia
RTS only.
The Spacing of Ties shall not exceed the least of the followings three
values
3. 300 mm
[In this case our objective is to minimize the value to reduce the spacing
and to make the structure more stable, hence we shall take least value
and suitably in a multiple of 25mm]
4. Foundation:
But in practice, the foundation depth is kept at 0.90m or even more. The
depth of
foundation depends not only on the nature of soil strata but also on the
height of
minimum depth of 1.50 m from ground level or at least 1.50 times the
width of
12 storeys) 2.0m to 3.0m foundation depth will be adequate. For still taller
buildings
foundation shall be adopted to suit the super structure of load and nature
of soil
condition. For tall isolated Structures, like water towers, the foundation
depth may
be at 3.0m also.
Where the moisture content may vary and cause shrinkage, the depth
must be
considered with the minimum moisture content variation(1.50m to
2.0m).In case of
3.0m to 3.50m. This is why ,the under reamed piles in expansive clays are
taken to
PRACTICAL DIMENSIONS:
mm.
(b) Thumb rule based on side of the footing for Fe 415 / Fe 500 steel.
5 1/7
10 1/5.5
15 1/5.0
20 1 /4.5
25 1 /4.0
30 1 /3.50
Note :
456-2000)
(iv) Reinforcement:
Preferable : 10 Φ RTS
Thumb rule:
Not less than 0.15% of c.s area for mild steel &