Produced on 03/07/2017 with Xpress Selection V7.5.4 - database DIL 11.9.

Project name Laboratorios tabasco


Project address Mexico
Reference proyecto T
Client name CIATEQ
Revision A

Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.

1. Material List
The use of VAM devices has no influence on the selection of outdoor units or its piping diagram. It only affects the
wiring diagram and the centralized controller diagram.

Model Qty Description


RHXYQ14ATL 1 Heat pump VRV IV 220V(TL)
RHXYQ22ATL 2 Heat pump VRV IV 220V(TL)
FXFQ112AVE 2 VRV FA - Ceiling Mounted Cassette(Round Flow)
FXFQ125AVE 1 VRV FA - Ceiling Mounted Cassette(Round Flow)
FXFQ40AVE 1 VRV FA - Ceiling Mounted Cassette(Round Flow)
FXFQ63AVE 5 VRV FA - Ceiling Mounted Cassette(Round Flow)
FXFQ71AVE 3 VRV FA - Ceiling Mounted Cassette(Round Flow)
FXFQ80AVE 3 VRV FA - Ceiling Mounted Cassette(Round Flow)
FXFQ90AVE 1 VRV FA - Ceiling Mounted Cassette(Round Flow)
FXMQ100AVE 1 VRV M-A - Ceiling Mounted Duct
FXMQ63AVE 1 VRV M-A - Ceiling Mounted Duct
VAM350GJVE 2 VAM device
KHRP26A22T 6 Refnet branch piping kit
KHRP26A33T 3 Refnet branch piping kit
KHRP26A72T 5 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 3 Refnet branch piping kit
BRC1C62 2 Wired remote controller
BRC1E62 16 Wired Remote Controller (Navigation Remote Controller)
BYCP125K-W1 16 Decoration panel
KDAJ25K140A 1 Air discharge adaptor
KDAJ25K71A 1 Air discharge adaptor
BHFP22P151 1 Outdoor unit multi connection piping kit
BRC301B61 2 HRV Remote Controller
R410A 27.7kg Extra refrigerant charge
Piping 6.4 2.0m
Piping 9.5 96.8m
Piping 12.7 14.5m
Piping 15.9 77.8m
Piping 19.1 36.0m
Piping 22.2 12.0m
Piping 28.6 21.0m
Piping 31.8 15.0m
Piping 41.3 5.5m
2.
3. Indoor Unit Details
3.1. Table of Abbreviations
Name Logical name of the device
FCU Device model name
Tmp C Indoor conditions in cooling (dry bulb temp. / RH)
Rq TC Required total cooling capacity
Rv TC Revised total cooling capacity (asked from outdoor)
Max TC Available total cooling capacity
Rq SC Required sensible cooling capacity
Max SC Available sensible cooling capacity
Tevap Evaporating temperature of indoor unit coil
Tmp H Indoor temperature in heating
Rq HC Required heating capacity
Max HC Available heating capacity
Airflow Supplied airflow
Sound Sound pressure low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device
Max RH Maximum relative humidity
Min TA Minimum ambient temperature
Max TA Maximum ambient temperature
Min Afl Minimum airflow
Max Afl Maximum airflow
Nom Afl Nominal airflow
Nom Hum Nominal humidity

3.2.
3.3. Out 1 - RHXYQ58ATL
Capacity data at conditions and connection ratio (97%) as entered
Name FCU Tmp C Rq TC Rv TC Max TC Rq SC Max SC Tevap Tmp H Rq HC Max HC Ai
°C kW kW kW kW kW °C °C kW kW c
LER Bioenergía UNO FXFQ80AVE 24.0 / 50% 5.7 7.0 7.8 5.4 5.8 6.0 20.0 n/a 10.0
LAB BIONERGIA DOS FXFQ80AVE 24.0 / 50% 5.7 7.0 7.8 5.4 5.8 6.0 20.0 n/a 10.0
LER Termosolar FXFQ80AVE 24.0 / 50% 6.4 7.4 7.8 5.6 5.8 6.0 20.0 n/a 10.0
Lab. Información FXFQ112AVE 24.0 / 50% 8.1 8.6 10.8 6.8 7.8 6.0 20.0 n/a 14.0
Ingeniería Concurrente PB FXFQ90AVE 24.0 / 50% 8.0 n/a 8.7 5.5 6.4 6.0 20.0 n/a 11.2
Pasillos PB FXMQ63AVE 24.0 / 50% 4.9 5.4 6.1 4.3 4.6 6.0 20.0 n/a 8.0
Vestíbulo FXFQ125AVE 25.0 / 50% 12.8 12.8 12.9 8.7 8.7 6.0 20.0 n/a 16.0
Lab. Virtual FXFQ40AVE 24.0 / 50% 3.8 n/a 3.9 2.8 3.1 6.0 20.0 n/a 5.0
Lab. Automatización FXFQ112AVE 24.0 / 50% 7.6 8.1 10.8 6.6 7.8 6.0 20.0 n/a 14.0
Lab. de Control UNO FXFQ71AVE 24.0 / 50% 5.7 6.2 6.9 5.0 5.3 6.0 20.0 n/a 9.0
LAB CONTROL DOS FXFQ71AVE 24.0 / 50% 5.7 6.2 6.9 5.0 5.3 6.0 20.0 n/a 9.0
Laboratorio 1 FXFQ63AVE 24.0 / 50% 5.1 n/a 6.1 3.6 4.3 6.0 20.0 n/a 8.0
Laboratorio 2 FXFQ71AVE 24.0 / 50% 6.8 6.9 6.9 5.3 5.3 6.0 20.0 n/a 9.0
Laboratorio 3 FXFQ63AVE 24.0 / 50% 5.6 n/a 6.1 3.8 4.3 6.0 20.0 n/a 8.0
Pasillo PA FXMQ100AVE 24.0 / 50% 7.8 8.4 9.7 6.8 7.4 6.0 20.0 n/a 12.5
Ingeniería Concurrente PA 1 FXFQ63AVE 24.0 / 50% 5.3 n/a 6.1 3.1 4.3 6.0 20.0 n/a 8.0
Ingeniería Concurrente PA 2 FXFQ63AVE 24.0 / 50% 5.3 n/a 6.1 3.1 4.3 6.0 20.0 n/a 8.0
Laboratorio 4 FXFQ63AVE 24.0 / 50% 5.2 5.9 6.1 4.2 4.3 6.0 20.0 n/a 8.0

Required cooling capacity towards the outdoor unit: 123.0kW.

Name Sound PS MCA WxHxD Wght


dBA A mm kg

LER Bioenergía UNO 29-38 220V 1ph 0.8 840x246x840 24


LAB BIONERGIA DOS 29-38 220V 1ph 0.8 840x246x840 24
LER Termosolar 29-38 220V 1ph 0.8 840x246x840 24
Lab. Información 34-44 220V 1ph 1.5 840x288x840 26
Ingeniería Concurrente PB 33-41 220V 1ph 1.1 840x246x840 24
Pasillos PB 38-42 220V 1ph 1.8 1000x300x700 35
Vestíbulo 34-44 220V 1ph 1.5 840x288x840 26
Lab. Virtual 25-32 220V 1ph 0.5 840x204x840 20
Lab. Automatización 34-44 220V 1ph 1.5 840x288x840 26
Lab. de Control UNO 29-38 220V 1ph 0.8 840x246x840 24
LAB CONTROL DOS 29-38 220V 1ph 0.8 840x246x840 24
Laboratorio 1 28-34 220V 1ph 0.6 840x204x840 21
Laboratorio 2 29-38 220V 1ph 0.8 840x246x840 24
Laboratorio 3 28-34 220V 1ph 0.6 840x204x840 21
Pasillo PA 39-43 220V 1ph 2.9 1400x300x700 45
Ingeniería Concurrente PA 1 28-34 220V 1ph 0.6 840x204x840 21
Ingeniería Concurrente PA 2 28-34 220V 1ph 0.6 840x204x840 21
Laboratorio 4 28-34 220V 1ph 0.6 840x204x840 21

Outdoor unit placed 6.0m above the indoor units.


The minimum connection ratio for this height difference is 50%.

VAM/VKM devices
Name Model WxHxD Wght Max RH Min TA Max TA Min Afl Max Afl Nom Afl Nom Hum
mm kg % °C °C cfm cfm cfm kg/h
VENTILACION PA VAM350GJVE 879x306x800 32 80 -15.0 50.0 59 294
VENTILACION PB VAM350GJVE 879x306x800 32 80 -15.0 50.0 59 294

4.
5. Outdoor Unit Details
5.1. Table of Abbreviations
Name Logical name of the device
Model Device model name
Tmp C Outdoor temperature in cooling
CC Available cooling capacity
Rq CC Required cooling capacity
Tmp H Outdoor conditions in heating (dry bulb temp. / RH)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (5m actual piping length)
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
Ex Refr Extra refrigerant charge
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

5.2.
5.3. Outdoor Details
Name Model Comb Tmp C CC Rq CC Tmp H HC Rq HC
% °C kW kW °C kW kW
Out 1 RHXYQ58ATL 97 37.0 123.5 123.0 0.0 / 50% 125.7

Name Model Piping Refrigerant


m Type Bse Refr Ex Refr
kg kg
Out 1 RHXYQ58ATL 47.6 R410A 24.1 27.7

Name Model PS MCA WxHxD Wght


A mm kg
Out 1 RHXYQ58ATL 220V 3ph
* RHXYQ22ATL 76 1240x1657x765 317
* RHXYQ22ATL 76 1240x1657x765 317
* RHXYQ14ATL 55 1240x1657x765 285

Sufficient distance should be respected between the modules according to the service & operation space rules as
mentioned in the databook.

6.
7. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.

7.1. Piping Out 1


Out 1
RHXYQ58ATL
RHXYQ22ATL RHXYQ22ATL RHXYQ14ATL

15.9×28.6 15.9×28.6 12.7×25.4


19.1x38.1
BHFP22P151

5.5m [2] 2.0m 13.0m 1.0m 5.5m [1]


19.1×41.3 19.1×31.8 19.1×31.8 9.5×22.2 9.5×15.9
KHRP26A73T + KHRP26A73T + KHRP26A73T + KHRP26A33T
KHRP26M73TP KHRP26M73TP KHRP26M73TP
Pasillo PA
FXMQ100AVE
2.5m 2.0m [1]
9.5×19.1 9.5×15.9
KHRP26A22T

Ingeniería Concurrente PA 2
FXFQ63AVE
6.0m 2.0m [1]
9.5×15.9 9.5×15.9
KHRP26A22T

Ingeniería Concurrente PA 1
FXFQ63AVE
7.0m [1]
9.5×15.9

Laboratorio 4
FXFQ63AVE
5.0m [1] 3.0m [1]
12.7×28.6 9.5×15.9
KHRP26A72T

Pasillos PB
FXMQ63AVE
2.5m 2.0m [1]
12.7×28.6 6.4×12.7
KHRP26A72T

Lab. Virtual
FXFQ40AVE
5.0m 2.0m [1]
9.5×22.2 9.5×15.9
KHRP26A33T

Lab. Automatización
FXFQ112AVE
5.6m 1.2m [1]
9.5×15.9 9.5×15.9
KHRP26A22T

Lab. de Control UNO


FXFQ71AVE
3.3m [1]
9.5×15.9

LAB CONTROL DOS


FXFQ71AVE
7.5m 2.5m [1]
9.5×19.1 9.5×15.9
KHRP26A22T

Laboratorio 3
FXFQ63AVE
6.0m 2.5m [1]
9.5×15.9 9.5×15.9
KHRP26A22T

Laboratorio 2
FXFQ71AVE
7.0m [1]
9.5×15.9

Laboratorio 1
FXFQ63AVE
6.0m [1] 4.0m [1]
15.9×28.6 9.5×15.9
KHRP26A72T

Vestíbulo
FXFQ125AVE
2.5m [1] 1.0m [1]
15.9×28.6 9.5×15.9
KHRP26A72T

Ingeniería Concurrente PB
FXFQ90AVE
5.0m 2.0m [1]
12.7×28.6 9.5×15.9
KHRP26A72T

Lab. Información
FXFQ112AVE
6.0m 2.0m [1]
9.5×22.2 9.5×15.9
KHRP26A33T

LER Termosolar
FXFQ80AVE
5.5m 1.2m [1]
9.5×19.1 9.5×15.9
KHRP26A22T

LER Bioenergía UNO


FXFQ80AVE
3.5m [1]
9.5×15.9

LAB BIONERGIA DOS


FXFQ80AVE
8. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.

8.1. Wiring Out 1


P1,P2
Out 1 VENTILACION PA BRC301B61
RHXYQ58ATL VAM350GJVE
IN F1,F2 F1,F2 L, N 1.35A 1ph
RHXYQ22ATL
Q1,Q2 L1,L2,L3 P1,P2
VENTILACION PB BRC301B61
76A 3ph
VAM350GJVE
RHXYQ22ATL F1,F2 L, N 1.35A 1ph
Q1,Q2 L1,L2,L3
76A 3ph P1,P2
Pasillo PA BRC1C62
RHXYQ14ATL FXMQ100AVE
Q1,Q2 L1,L2,L3 F1,F2 L, N 2.9A 1ph
55A 3ph
P1,P2
Ingeniería Concurrente PA 2 BRC1E62
FXFQ63AVE
F1,F2 L, N 0.6A 1ph

P1,P2
Ingeniería Concurrente PA 1 BRC1E62
FXFQ63AVE
F1,F2 L, N 0.6A 1ph

P1,P2
Laboratorio 4 BRC1E62
FXFQ63AVE
F1,F2 L, N 0.6A 1ph

P1,P2
Pasillos PB BRC1C62
FXMQ63AVE
F1,F2 L, N 1.8A 1ph

P1,P2
Lab. Virtual BRC1E62
FXFQ40AVE
F1,F2 L, N 0.5A 1ph

P1,P2
Lab. Automatización BRC1E62
FXFQ112AVE
F1,F2 L, N 1.5A 1ph

P1,P2
Lab. de Control UNO BRC1E62
FXFQ71AVE
F1,F2 L, N 0.8A 1ph

P1,P2
LAB CONTROL DOS BRC1E62
FXFQ71AVE
F1,F2 L, N 0.8A 1ph

P1,P2
Laboratorio 3 BRC1E62
FXFQ63AVE
F1,F2 L, N 0.6A 1ph

P1,P2
Laboratorio 2 BRC1E62
FXFQ71AVE
F1,F2 L, N 0.8A 1ph

P1,P2
Laboratorio 1 BRC1E62
FXFQ63AVE
F1,F2 L, N 0.6A 1ph

P1,P2
Vestíbulo BRC1E62
FXFQ125AVE
F1,F2 L, N 1.5A 1ph

P1,P2
Ingeniería Concurrente PB BRC1E62
FXFQ90AVE
F1,F2 L, N 1.1A 1ph

P1,P2
Lab. Información BRC1E62
FXFQ112AVE
F1,F2 L, N 1.5A 1ph

P1,P2
LER Termosolar BRC1E62
FXFQ80AVE
F1,F2 L, N 0.8A 1ph

P1,P2
LER Bioenergía UNO BRC1E62
FXFQ80AVE
F1,F2 L, N 0.8A 1ph

P1,P2
LAB BIONERGIA DOS BRC1E62
FXFQ80AVE
F1,F2 L, N 0.8A 1ph
9. Device Options
9.1. Outdoor Unit Options
Model Description Used by
BHFP22P151 Outdoor unit multi connection piping kit Out 1 [RHXYQ58ATL]

9.2. Indoor Unit Options


Model Description Used by
KDAJ25K140A Air discharge adaptor Pasillo PA [FXMQ100AVE]
BYCP125K-W1 Decoration panel Ingeniería Concurrente PA 2 [FXFQ63AVE] Lab. Automatización [FXFQ112AVE] Laboratorio 3 [FXFQ63AVE]
Laboratorio 2 [FXFQ71AVE] LAB BIONERGIA DOS [FXFQ80AVE] Ingeniería Concurrente PA 1
Lab. Información [FXFQ112AVE] LER Bioenergía UNO [FXFQ80AVE] Vestíbulo [FXFQ125AVE]
LAB CONTROL DOS [FXFQ71AVE] LER Termosolar [FXFQ80AVE] Laboratorio 4 [FXFQ63AVE]
Laboratorio 1 [FXFQ63AVE] Lab. de Control UNO [FXFQ71AVE] Lab. Virtual [FXFQ40AVE]
Ingeniería Concurrente PB [FXFQ90AVE]
KDAJ25K71A Air discharge adaptor Pasillos PB [FXMQ63AVE]