Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.
1. Material List
The use of VAM devices has no influence on the selection of outdoor units or its piping diagram. It only affects the
wiring diagram and the centralized controller diagram.
3.2.
3.3. Out 1 - RHXYQ58ATL
Capacity data at conditions and connection ratio (97%) as entered
Name FCU Tmp C Rq TC Rv TC Max TC Rq SC Max SC Tevap Tmp H Rq HC Max HC Ai
°C kW kW kW kW kW °C °C kW kW c
LER Bioenergía UNO FXFQ80AVE 24.0 / 50% 5.7 7.0 7.8 5.4 5.8 6.0 20.0 n/a 10.0
LAB BIONERGIA DOS FXFQ80AVE 24.0 / 50% 5.7 7.0 7.8 5.4 5.8 6.0 20.0 n/a 10.0
LER Termosolar FXFQ80AVE 24.0 / 50% 6.4 7.4 7.8 5.6 5.8 6.0 20.0 n/a 10.0
Lab. Información FXFQ112AVE 24.0 / 50% 8.1 8.6 10.8 6.8 7.8 6.0 20.0 n/a 14.0
Ingeniería Concurrente PB FXFQ90AVE 24.0 / 50% 8.0 n/a 8.7 5.5 6.4 6.0 20.0 n/a 11.2
Pasillos PB FXMQ63AVE 24.0 / 50% 4.9 5.4 6.1 4.3 4.6 6.0 20.0 n/a 8.0
Vestíbulo FXFQ125AVE 25.0 / 50% 12.8 12.8 12.9 8.7 8.7 6.0 20.0 n/a 16.0
Lab. Virtual FXFQ40AVE 24.0 / 50% 3.8 n/a 3.9 2.8 3.1 6.0 20.0 n/a 5.0
Lab. Automatización FXFQ112AVE 24.0 / 50% 7.6 8.1 10.8 6.6 7.8 6.0 20.0 n/a 14.0
Lab. de Control UNO FXFQ71AVE 24.0 / 50% 5.7 6.2 6.9 5.0 5.3 6.0 20.0 n/a 9.0
LAB CONTROL DOS FXFQ71AVE 24.0 / 50% 5.7 6.2 6.9 5.0 5.3 6.0 20.0 n/a 9.0
Laboratorio 1 FXFQ63AVE 24.0 / 50% 5.1 n/a 6.1 3.6 4.3 6.0 20.0 n/a 8.0
Laboratorio 2 FXFQ71AVE 24.0 / 50% 6.8 6.9 6.9 5.3 5.3 6.0 20.0 n/a 9.0
Laboratorio 3 FXFQ63AVE 24.0 / 50% 5.6 n/a 6.1 3.8 4.3 6.0 20.0 n/a 8.0
Pasillo PA FXMQ100AVE 24.0 / 50% 7.8 8.4 9.7 6.8 7.4 6.0 20.0 n/a 12.5
Ingeniería Concurrente PA 1 FXFQ63AVE 24.0 / 50% 5.3 n/a 6.1 3.1 4.3 6.0 20.0 n/a 8.0
Ingeniería Concurrente PA 2 FXFQ63AVE 24.0 / 50% 5.3 n/a 6.1 3.1 4.3 6.0 20.0 n/a 8.0
Laboratorio 4 FXFQ63AVE 24.0 / 50% 5.2 5.9 6.1 4.2 4.3 6.0 20.0 n/a 8.0
VAM/VKM devices
Name Model WxHxD Wght Max RH Min TA Max TA Min Afl Max Afl Nom Afl Nom Hum
mm kg % °C °C cfm cfm cfm kg/h
VENTILACION PA VAM350GJVE 879x306x800 32 80 -15.0 50.0 59 294
VENTILACION PB VAM350GJVE 879x306x800 32 80 -15.0 50.0 59 294
4.
5. Outdoor Unit Details
5.1. Table of Abbreviations
Name Logical name of the device
Model Device model name
Tmp C Outdoor temperature in cooling
CC Available cooling capacity
Rq CC Required cooling capacity
Tmp H Outdoor conditions in heating (dry bulb temp. / RH)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (5m actual piping length)
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
Ex Refr Extra refrigerant charge
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device
5.2.
5.3. Outdoor Details
Name Model Comb Tmp C CC Rq CC Tmp H HC Rq HC
% °C kW kW °C kW kW
Out 1 RHXYQ58ATL 97 37.0 123.5 123.0 0.0 / 50% 125.7
Sufficient distance should be respected between the modules according to the service & operation space rules as
mentioned in the databook.
6.
7. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.
Ingeniería Concurrente PA 2
FXFQ63AVE
6.0m 2.0m [1]
9.5×15.9 9.5×15.9
KHRP26A22T
Ingeniería Concurrente PA 1
FXFQ63AVE
7.0m [1]
9.5×15.9
Laboratorio 4
FXFQ63AVE
5.0m [1] 3.0m [1]
12.7×28.6 9.5×15.9
KHRP26A72T
Pasillos PB
FXMQ63AVE
2.5m 2.0m [1]
12.7×28.6 6.4×12.7
KHRP26A72T
Lab. Virtual
FXFQ40AVE
5.0m 2.0m [1]
9.5×22.2 9.5×15.9
KHRP26A33T
Lab. Automatización
FXFQ112AVE
5.6m 1.2m [1]
9.5×15.9 9.5×15.9
KHRP26A22T
Laboratorio 3
FXFQ63AVE
6.0m 2.5m [1]
9.5×15.9 9.5×15.9
KHRP26A22T
Laboratorio 2
FXFQ71AVE
7.0m [1]
9.5×15.9
Laboratorio 1
FXFQ63AVE
6.0m [1] 4.0m [1]
15.9×28.6 9.5×15.9
KHRP26A72T
Vestíbulo
FXFQ125AVE
2.5m [1] 1.0m [1]
15.9×28.6 9.5×15.9
KHRP26A72T
Ingeniería Concurrente PB
FXFQ90AVE
5.0m 2.0m [1]
12.7×28.6 9.5×15.9
KHRP26A72T
Lab. Información
FXFQ112AVE
6.0m 2.0m [1]
9.5×22.2 9.5×15.9
KHRP26A33T
LER Termosolar
FXFQ80AVE
5.5m 1.2m [1]
9.5×19.1 9.5×15.9
KHRP26A22T
P1,P2
Ingeniería Concurrente PA 1 BRC1E62
FXFQ63AVE
F1,F2 L, N 0.6A 1ph
P1,P2
Laboratorio 4 BRC1E62
FXFQ63AVE
F1,F2 L, N 0.6A 1ph
P1,P2
Pasillos PB BRC1C62
FXMQ63AVE
F1,F2 L, N 1.8A 1ph
P1,P2
Lab. Virtual BRC1E62
FXFQ40AVE
F1,F2 L, N 0.5A 1ph
P1,P2
Lab. Automatización BRC1E62
FXFQ112AVE
F1,F2 L, N 1.5A 1ph
P1,P2
Lab. de Control UNO BRC1E62
FXFQ71AVE
F1,F2 L, N 0.8A 1ph
P1,P2
LAB CONTROL DOS BRC1E62
FXFQ71AVE
F1,F2 L, N 0.8A 1ph
P1,P2
Laboratorio 3 BRC1E62
FXFQ63AVE
F1,F2 L, N 0.6A 1ph
P1,P2
Laboratorio 2 BRC1E62
FXFQ71AVE
F1,F2 L, N 0.8A 1ph
P1,P2
Laboratorio 1 BRC1E62
FXFQ63AVE
F1,F2 L, N 0.6A 1ph
P1,P2
Vestíbulo BRC1E62
FXFQ125AVE
F1,F2 L, N 1.5A 1ph
P1,P2
Ingeniería Concurrente PB BRC1E62
FXFQ90AVE
F1,F2 L, N 1.1A 1ph
P1,P2
Lab. Información BRC1E62
FXFQ112AVE
F1,F2 L, N 1.5A 1ph
P1,P2
LER Termosolar BRC1E62
FXFQ80AVE
F1,F2 L, N 0.8A 1ph
P1,P2
LER Bioenergía UNO BRC1E62
FXFQ80AVE
F1,F2 L, N 0.8A 1ph
P1,P2
LAB BIONERGIA DOS BRC1E62
FXFQ80AVE
F1,F2 L, N 0.8A 1ph
9. Device Options
9.1. Outdoor Unit Options
Model Description Used by
BHFP22P151 Outdoor unit multi connection piping kit Out 1 [RHXYQ58ATL]