Documente Academic
Documente Profesional
Documente Cultură
AL
AL
TU
TU
EP
ONC
E
INE
P
NC
C
L
IDE
GU CO
Ministry of Health Malaysia SIG
N
Engineering Services Division DE
Level 3-7, Block E3, Parcel E, Precinct 1
Federal Government Administrative Centre
62590 Putrajaya
Tel: 603-8000 8000 | Fax: 603-8892 4855/4872 E E
LIN LIN
Website: http://engineering.moh.gov.my IDE UIDE
GU G
AL
TU
EP
ONC
C
N
SIG
DE
TS
EN
E
LIN
IDE M
GU ENTS
IRE
QU
M
IRE
RE
QU
RE
ING
ING
ER E
EN
GI
NE
E LIN IGN E ER
ID ES IN
AL
GU CEPTUAL D ENG
PTU DESIG N
N
CE CO
N
CO
TS
M EN
IRE
EQU
R
ING
E ER
G IN
EN
GUIDELINE
ON CONCEPTUAL DESIGN AND
ENGINEERING REQUIREMENTS FOR
CENTRAL STERILE SUPPLY UNIT
(CSSU)
MINISTRY OF HEALTH
MALAYSIA
MOH/ESD/2017-02
Disclaimer: Any pictures of equipment, brand and model of equipment depicted in this guideline shall
not be considered as an acceptance or approval from the Ministry of Health Malaysia. It shall only serve
as an example or illustration for the relevant issues and matter of interest.
3
TABLE OF CONTENTS
1.0 Introduction 15
9.0 References 72
GUIDELINE ON CONCEPTUAL DESIGN AND ENGINEERING
6 REQUIREMENTS FOR CENTRAL STERILE SUPPLY UNIT (CSSU)
MESSAGE
THE DIRECTOR GENERAL OF HEALTH
The Central Sterile Supply Unit (CSSU) is the hub where contaminated re-usable med-
ical devices are decontaminated, cleaned, disinfected, washed, packed, sterilized and
stored before being delivered to the respective departments in a hospital to be used
onto the next patient.
In view of the emergence of many new viruses, the sterility of those medical devices
must be assured at the highest level. To achieve this, the CSSU is designed and op-
erated with the principle of stringent infection control measures in handling those
medical devices from the receiving to the operation table.
This guideline, hopefully, can be benefited by various interested parties within or out-
side the Ministry of Health to further enhance the sustainability of CSSU in continu-
ously producing the highest sterility of re-usable medical devices.
PREFACE
THE DIRECTOR OF ENGINEERING SERVICES DIVISION
Central Sterile Supply Unit (CSSU) is an integral part of the hospital and plays the
role of processing re-usable medical devices and consumables that are used in op-
erating theatres, emergency department and wards where surgical and non-surgical
procedures are carried out.
Properly designed, installed, operated and maintained CSSU facility and equipment
will ensure that reprocessed medical devices and other sterilized products achieve
high assurance levels of sterility, and eliminate any source of contaminant/infection
for the personnel and patient.
These guidelines are developed to ensure that CSSU at the hospitals comply to inter-
national requirements with a greater emphasize put on the engineering aspects as
to address the issues and concerns raised during the construction and operation
phases.
These guidelines are intended for Ministry of Health personnel (the owners), the
hospital administrators, health care workers, designers, maintenance personnel, and
others concerning the CSSU in the healthcare facilities.
ACKNOWLEDGEMENTS
The guidelines were prepared by the Engineering Services Division of the Ministry
of Health Malaysia (MOH) and assisted by Healthcare Facilities Consultant, Sistem
Hospital Awasan Taraf Sdn Bhd (SIHAT), who was appointed by the Government of
Malaysia.
We thank and acknowledge the following personnel who contributed to the prepara-
tion of this document, by taking part in discussions, reviews, providing feedbacks and
being members in the committee meetings.
LIST OF ABBREVIATIONS
ORGANIZATIONS
ASHRAE American Society of Heating, Refrigerating and Air-Conditioning
Engineers
JKKP Jabatan Keselamatan dan Kesihatan Pekerjaan (Department of
Occupational Safety and Health)
MOH Ministry of Health, Malaysia
TERMS
ACMV Air Conditioning and Mechanical Ventilation
AHU Air Handling Unit
CSSU Central Sterile Supply Unit
ICU Intensive Care Unit
MD Medical Device
UPS Uninterruptible Power Supply
11
GLOSSARY
Air- A form of air treatment whereby temperature humidity and air
Conditioning cleanliness are all controlled within limits determined by the
requirements of the air-conditioned enclosure.
Air Handling AHU is a device that is used to filter, condition and circulate the air as
Unit (AHU) part of a heating, ventilating, and air-conditioning (HVAC) system.
Carrier A device that carries or transports the load through the decontamination
process.
ISO Maximum concentration limits (particles/m3 of air) for particles equal to and
Classification larger than the considered sizes shown below
number
= 0.1μm =0.2 μm = 0.3 μm = 0.5 μm = 1 μm = 5.0 μm
ISO Class 1 10 2
ISO Class 2 100 24 10 4
ISO Class 3 1000 237 102 35 8
ISO Class 4 10,000 2370 1020 352 83
ISO Class 5 100,000 23,700 10,200 3520 832 29
ISO Class 6 1,000,000 237,000 102,000 35,200 8320 293
ISO Class 7 352,000 83,200 2930
ISO Class 8 3,520,000 832,000 29,300
ISO Class 9 35,200,000 8,320,000 293,000
HEPA filter High Efficiency Particulate Air filters capable of removing 99.97%
of particles 0.3 µm in diameter and may assist in controlling the
transmission of airborne disease agents.
LAeq, Leq It is the Total Sound Energy measured over a given period of time with
an A weight-age measurement.
Load Collectively, all the goods, equipment and materials that are put into
a sterilizer or washer-disinfector at any one time for the purpose of
processing it.
GUIDELINE ON CONCEPTUAL DESIGN AND ENGINEERING
12 REQUIREMENTS FOR CENTRAL STERILE SUPPLY UNIT (CSSU)
Medical device Any instrument, apparatus, appliance, material or other article, whether
used alone or in combination, including the software necessary for
its proper application intended by the manufacturer, to be used for
human beings for the purpose of: diagnosis, prevention, monitoring,
treatment or alleviation of disease; diagnosis, monitoring, treatment,
alleviation of or compensation for an injury or handicap; investigation,
replacement or modification of the anatomy or of a physiological
process; and control of conception: and which does not achieve its
principal intended action in or on the human body by pharmacological,
immunological or metabolic means, but which may be assisted in its
function by such means.
Pressure The difference in air pressure of the room with respect to the
Differential surrounding. The surrounding here refers to the corridor or adjacent
area where applicable.
Room Units Room units here refer to the local air conditioning units that are used
primarily for the cooling of air, and not disinfection of air.
Spore A small, usually single cell that is dormant and resistant to adverse
environmental conditions, chemical and enzymes.
Tray A container, usually with a flat base and upturned edges, used for
containing an assembly of surgical instruments for packing to be used
in an aseptic procedure.
Ultrasonic A mechanical cleaner that generates sound waves that creates cavitation
cleaner and is used to clean instruments.
Uninterrupt- UPS is a battery back power supply that provides emergency power for
ible Power a specified duration during a power failure.
Supply (UPS)
User User is the person who uses the equipment or services e.g. nursing
staff.
Washer- Machine intended to clean and disinfect medical devices and other
disinfector articles used in the context of medical, dental, pharmaceutical and
veterinary practices.
GUIDELINE ON CONCEPTUAL DESIGN AND ENGINEERING
14 REQUIREMENTS FOR CENTRAL STERILE SUPPLY UNIT (CSSU)
EXECUTIVE SUMMARY
The guidelines were prepared by the Engineering Services Division, Ministry of Health
Malaysia and have eight (8) sections.
Section 1 : Introduction
This section explains the importance of CSSU in the hospital and the need for proper
planning in design, build and maintain of the department.
1. Introduction
Centralized Sterile Supply Unit (CSSU) in hospitals play an important role in providing sterile
products to the various end users e.g. the operation theatres, emergency department,
maternity, wards etc. through a series of strictly monitored cleaning, disinfecting, packing
and sterilizing processes.
Building the CSSU requires an in-depth knowledge of the operational of the department,
relationship between the supplying and receiving departments in the hospital, compliance
to the infection control protocol, cross contamination containment, the necessity of
major processing and supporting working equipment, and the ability of the department
to sustain the current and near future demands.
As the design of the department becomes more complicated to address all the above
mentioned requirements within the allowable space, the engineering systems installed in
this department shall be relooked. Based on the experience from the construction of new
or upgrading the existing of such department in hospitals as well as the operation and
maintenance of the facility, there is the need to establish a quick reference on the various
engineering issues concerning this department.
This document is developed based on numerous established guidelines plus the input from
the local CSSU practitioner and medical planners with the noble intention of reducing any
operational and maintenance problems with regards to engineering systems and design.
It covers the basic planning of the department, space and equipment requirements, and
utilities requirements to support the equipment and department.
Last but not least, the document also provides the basic roles of the hospital and
instructions to be followed in planning and upgrading the process of existing facility and
major equipment replacement in the department. Coupled with the inclusion of the
latest construction and new policy requirements, this document shall be handy for all
relevant parties.
GUIDELINE ON CONCEPTUAL DESIGN AND ENGINEERING
16 REQUIREMENTS FOR CENTRAL STERILE SUPPLY UNIT (CSSU)
Central Sterile Supply Unit (CSSU) is the center for processing reused medical devices and
supplying sterilized products to various departments such as operation theatres, critical
care departments, emergency department and wards.
2.2 Location
The location of the CSSU is dependent on the primary function i.e. to sterilize
consumables and contaminated re-usable MDs.
1) CSSU shall be located near the main source of generation i.e. the operation
theaters. It shall preferably be adjacent to and on the same floor of the
operation theatres. CSSU shall also be close to critical care units and the
emergency department.
2) The potential risk of contamination of the sterile products shall be minimized
by the shorter distance and travel time possible.
3) There shall be a direct and easy access from the medical supplies store to
the CSSU or from the CSSU to other users of departments via designated
route(s).
4) The routes for transporting dirty and sterile products shall, in any way or
point, not be crossing each other. A designated route for maintenance
activities shall be preferable.
5) The CSSU shall not be placed in the inner part of the building to avoid
complexity in the engineering system design and maintenance.
6) Proper accessibility to the department and supporting engineering facilities
shall be considered for maintenance and future equipment replacement
activities.
17
Operation Theatres/
Critical Care
Units/Wards/ ED
Receiving
Distribution
Decontamination
Storing
CSSU
Washing
Cooling
Inspection
Sterilization
Packing
Raw Material/
Linen/ MDs
2.3 Sterilization
2.3.1 Classification
Reusable medical devices1 are classified based on device usage and their
contact with body i.e. non-critical, semi-critical and critical. The classification
is shown in the table below;
Table 1
Spaulding Contact Level Disinfection/ Sterilization
Classification
Non-Critical Skin, non-secretion membranes (e.g. Low or Intermediate Level
bed pans, cuffs etc.) Disinfectant
Semi-Critical Mucous membrane or non-intact High Level Disinfectant
skin (some endoscopes, medical
instrument blades etc.)
Critical Tissue or the vascular system (e.g. Sterilization
implants, invasive catheter etc.)
Medical devices that have contact with sterile body tissues or fluids are
considered critical items. These items shall be sterile when used because
any microbial contamination could result in disease transmission.
1 Chemical disinfection of medical and surgical materials, Spaulding E.H. (Guideline for Disinfection and
Sterilization in Healthcare Facilities, 2008, Page 10)
2 Guideline for Disinfection and Sterilization in Healthcare Facilities, 2008, Page 8
19
There are mainly two types of sterilization i.e. steam sterilization and low
temperature sterilization used in hospitals.
The steam sterilization process shall be applied for heat resistant medical
devices because it has the largest margin of safety due to its reliability,
consistency and lethality.
There are two types of steam sterilizers i.e. gravity displacement type and pre-
vacuum (dynamic-air-removal) type. The gravity displacement autoclaves
are primarily used to process laboratory media, water, pharmaceutical
products, regulated medical waste, and nonporous articles whose surfaces
have direct steam contact.
The high-speed pre-vacuum sterilizers, on the other hand, are fitted with a
vacuum pump (or ejector) to ensure air removal from the sterilizing chamber
and load before the steam is admitted. The advantage of using a vacuum
pump is that there is a nearly instantaneous steam penetration, even into
porous loads.
The typical operating temperature and exposure times for the category of
items sterilized in a gravity displacement and pre dynamic air removal (pre-
vacuum) sterilizers are based on acceptable international standards.
The Bowie-Dick test shall be used to detect air leaks and inadequate air
removal and consists of folded 100% cotton surgical towels that are clean
and preconditioned. A commercially available Bowie-Dick-type test sheet
shall be placed in the center of the pack.
GUIDELINE ON CONCEPTUAL DESIGN AND ENGINEERING
20 REQUIREMENTS FOR CENTRAL STERILE SUPPLY UNIT (CSSU)
There are a few types of low temperature sterilization i.e. Hydrogen Peroxide
Gas Plasma, Ethylene Oxide Gas and Peracetic Acid. These low temperature
sterilizers are used for MDs that are susceptible to heat and moisture e.g.
plastic and electrical devices.
Some of the common types are briefly described in the following paragraphs.
Since EtO poses a potential health hazard to the staff and patient, a
proper installation to prevent exposure and personnel monitoring
mechanisms shall be applied. Local exhaust ventilation system shall
be installed at this sterilizer.
3) Peracetic Acid
The general function of the department shall be addressed by specifying the right flow of
materials and personnel, proper areas zoning, sufficiently sized equipment, and provision
for future expansion.
The details of the departmental layout such as type of rooms, size, orientation, and
location shall be strictly adhered to the guideline produced by the Planning Division,
Ministry of Health.
The actual details of rooms, size and orientation shall be finalized prior to the construction
of the department involving all relevant parties subjected to the actual project area and
complying with the requirements of standard.
The use of newly advanced washing and sterilizing equipment utilizing energy/water
efficient mechanisms shall be encouraged. Based on the available space area, the double
doors version of equipment shall be preferable.
Proper intra route and adequate space between equipment or nearby installation/wall
for maintenance access or activities shall be provided.
The basic layout shall be designed to meet the principle function of CSSU and be
equipped with the proper supporting facilities in resulting infection-free sterilized
medical devices.
The design shall allow flexibility and creativity in space utilization and equipment
sizing without compromising the principle of infection control and cross
contamination prevention.
A CSSU shall be made up of three clearly indicated zones namely the soiled zone,
clean zone and sterile zone.
23
For the double doors equipment arrangement, the washer disinfectors and
sterilizers shall act as the primary and secondary physical barriers.
For the single door equipment set up, the soiled area shall be clearly separated
from the clean or sterile area.
The movement of personnel and material within the CSSU shall be properly
designed to ensure no or minimum contamination of the sterile products.
The layout and proposed workflow in CSSU shall comply with the latest safety
requirements by Fire Department. Dedicated escape route for staff shall be
established to accommodate safe evacuation in the event of fire or any other
emergency incidents.
The layout shall preferably allow adequate space for the future expansion of
services by the department.
The following chart shall serve as a basic guide for area distribution in the new CSSU.
The actual percentage may differ at the site based on the specific requirement at
a particular hospital.
GUIDELINE ON CONCEPTUAL DESIGN AND ENGINEERING
24 REQUIREMENTS FOR CENTRAL STERILE SUPPLY UNIT (CSSU)
15% 20%
15%
20%
30%
Auxilliary zone
Cleaning area
Preparation zone
Steriled products storage
Storage room
Figure 3: Proposed Area Distribution in CSSU
Staff safety and wellbeing is crucial as they constantly come in contact with
contaminated re-usable medical devices. The safety aspects involve administrative
controls i.e. controlling the staff movement and the donning of personnel protective
gears.
The staff movement shall be restricted within zones so as to minimize any cross
contamination within the zones. The staff movement shall abide to the CSSU
operational policies and/or by use of dedicated security passes.
Staff entering the soiled zone shall go through a dedicated change room where
they wear the appropriate clothing and Personnel Protective Equipment (PPE) e.g.
gloves, face mask, wet boots etc.
Staff working in clean zone shall enter the clean zone through a dedicated change
room where they wear appropriate clothing and PPE, while staffs working in the
sterile zone shall then proceed through a door between the clean and sterile zones.
25
There are various types of material moving within the CSSU i.e. contaminated re-
usable medical devices, clean medical devices, linen and consumables.
The Soiled Zone is where soiled items are received from the user locations.
Here, the items are decontaminated, cleaned and disinfected.
1) Receiving Area
Stainless steel tables counter
2) Cleaning Area
a. Decontaminating Area
b. Manual Washing
c. Ultrasonic cleaning area
3) Disinfection
a. Automated Washing Area
b. Automated Cart Washer
4) Hand washing facilities
5) Bins or other containers for the disposal of waste
6) Detergent Room
- Stainless cabinet
- Exhaust fan
7) Cleaning equipment room / area
The Clean Zone is where items that have been cleaned are inspected,
assembled and packed before they are sent for sterilization. Clean Zone is
made up of the following areas;
GUIDELINE ON CONCEPTUAL DESIGN AND ENGINEERING
26 REQUIREMENTS FOR CENTRAL STERILE SUPPLY UNIT (CSSU)
The Sterile Zone is where the loads are sterilized, cooled, stored and
prepared for dispatch to the end-user. The Sterile Zone is made up of the
following areas;
1) Sterilizer
2) Cooling Area
3) Sterilized Products Storage Area and
4) Sterile Item Issuing Area
27
A. Function
1) This area is where contaminated re-usable medical devices
from various user locations are deposited for processing.
2) All items received shall be recorded.
C. Requirements
1) It shall be at the entrance to the CSSU.
2) The entrances shall be secured to prevent access by
unauthorized people.
3) A “red-line” is to be drawn out on the floor to designate the
beginning of the area, where soiled trolleys and materials are
to enter.
GUIDELINE ON CONCEPTUAL DESIGN AND ENGINEERING
28 REQUIREMENTS FOR CENTRAL STERILE SUPPLY UNIT (CSSU)
Cleaning of MDs is the first step towards sterilizing re-usable MDs. The
purpose is to clean and rinse the MDs so as to remove all visible debris
and reduce the number of particulates, micro-organisms and potential
pathogens. Thorough cleaning and rinsing are vital for the effectiveness
of subsequent processes used for decontamination, disinfection and / or
sterilization.
Ineffective cleaning and rinsing of the MDs may result in foreign material on
the device to interfere with the effectiveness of subsequent disinfection and
/ or sterilization.
A. Function
1) Some of the soiled MDs that are deemed unsafe to
handle shall be decontaminated before they are further
cleaned and processed.
2) Decontamination is carried out by immersing the soiled
MDs in chemicals that will inactivate or destroy blood-
borne pathogens on a surface or difficult to access
locations on the MDs e.g. the joints; so that they are
no longer capable of transmitting infections and are
rendered safe for handling.
29
Stainless steel table tops with deep sink Signage identify the area
C. Requirements
1) Area is identified and labeled as “BIOHAZARD
INSTRUMENTS”.
2) There shall be space for foot operated clinical waste bins.
A. Function
1) Soiled MDs that are deemed unsuitable for automated
cleaning are manually cleaned. Manual cleaning is
recommended for MDs that are delicate or complex,
such as micro-surgical devices, instruments having lenses
(scopes) and air-powered drills.
C. Requirements
1) Adjacent to the decontamination area.
A. Function
1) Ultrasonic cleaner is the most effective and efficient
way to clean instruments with small crevices, cavities,
lumens, and between tightly spaced parts, where it is
hard to reach during manual cleaning. It is able to remove
debris from challenging areas of the instrument e.g. the
box lock, jaw, ratchets, hinges, serrations, reamers and
drills. To maximize its effectiveness, the instruments shall
first be cleaned of all visible debris.
31
C. Requirements
1) The ultrasonic cleaner shall have an interlocking lid and
thermostatically controlled heaters/ hot water boiler.
A. Function
1) The WD’s primary function is to wash, disinfect and
lubricate the instruments.
2) A typical wash cycle in a WD is pre-rinsing, cleaning
(with detergent), post rinsing (with lubrication), thermal
disinfectant, final rinse and the drying phase.
3) The whole cycle is automatically validated.
GUIDELINE ON CONCEPTUAL DESIGN AND ENGINEERING
32 REQUIREMENTS FOR CENTRAL STERILE SUPPLY UNIT (CSSU)
C. Requirements
1) Dedicated floor mounted conveyor line (to suit WDs).
2) The WDs shall be sufficiently ventilated to remove heat
and smell from disinfecting agents.
A. Function
1) The main functions of the washer are to wash, disinfect
and dry the soiled carts (trolleys).
2) The wash cycle may consist of pre-rinsing, cleaning
(with detergent), post rinsing (with lubrication), thermal
disinfectant, final rinse and the drying phase. The whole
process of the washing cycle is automatic.
Cart Washer
C. Requirements
1) There shall be a dedicated room adjoining the cart
washer to accommodate the boiler and air compressor.
This room can either come as part of the cart washer
package or is dedicated to the facility.
2) There shall be sufficient space provided around the
equipment for inspection and repairs, while the access
doors shall be sized appropriately to allow a complete
replacement of the equipment.
3) There shall be a water jet facility to be used to clean the
washer disinfector.
A. Function
1) The transfer hatch is used to transfer large, manually
cleaned and disinfected MDs and none-MDs to the next
Zone (IAP Zone). The none-MDs that are transferred are
baskets and instrument trays.
2) This hatch forms a part of the primary physical barrier
between the Soiled Zone and the Clean Zone.
3) The transfer hatch door facing the Soiled Zoned and the
one facing the IAP Zone shall be interlocked, allowing
only one door to be opened at one time.
35
Transfer hatch
C. Requirements
1) The hatches shall be able to close so as to create an airlock
to minimize the air movement between the Soiled Zone
and the Clean Zone.
2) Dedicated floor mounted conveyor lines shall be placed
at the Transfer Hatch.
A. Function
1) This cabinet generates hot air that is used to dry MDs
such as anesthetic hoses, breathing bags, hollow ware
and tubing.
GUIDELINE ON CONCEPTUAL DESIGN AND ENGINEERING
36 REQUIREMENTS FOR CENTRAL STERILE SUPPLY UNIT (CSSU)
Drying cabinets with utensils on rack Drying cabinets with tube rack
C. Requirements
1) There shall be sufficient space at the back of the dryer for
proper air circulation.
A. Function
1) In this area, MDs are Inspected, Assembled and Packed prior to
sending them for sterilization.
37
C. Requirements
1) IAP area shall be sufficiently sized and suitably arranged.
2) Minimum distance from the machine & working table shall be
allowed for material and staff maneuverability.
3) Windows to the outside shall be encouraged; however, when
installing, the windows need to be sealed.
4) Internal walls and doors shall have vision panels.
5) The area shall be under positive pressure differential with
respect to adjacent areas.
A. Function
1) In this area, all the different packing checklists are printed so
that the nursing staff can use this checklist to assemble the
MDs sets based on the operation requirement.
2) Bar code labels are also printed and scanned to capture all
relevant information.
C. Requirements
1) Propriety software for CSSU management
There are basically four different types of clean stores i.e. “Stor Pukal (bulk
store), “Stor Peralatan” (instrument store), “Stor Kain Kasa” (soft goods
store) and “Stor Kain” (linen store).
A. Function
1) The bulk store is used to store items purchased in bulk, especially
the bulky items e.g. sterilization wrapping paper, pouches and
autoclave tape, etc.
The instrument store is used to store medical devices to stock
up on any deficiency in the packing or faulty device.
The swab/gauze store is where gauze is repackaged into the
desired packing e.g. gauze pad, gauze bandages, gauze sponge,
swabs etc.
The linen store is where clean linen is stored and packed as a
part of the procedural accessories e.g. surgical towel, mayo
stand cover, drape sheet etc.
2) These stores are used to store clean items (consumables)
before there are sent to the packing area or directly to the
sterile loading area for sterilization.
C. Requirements
1) The swab/gauze cutting table in the store shall have a Local
Exhaust Ventilation system.
2) Linen packing area shall be properly lit so that the user can
clearly see and pick any frayed linen (loose thread).
A. Function
1) Packed sets shall flow from the IAP area to the Sterilizer Loading
Area.
2) Sterilizer Loading Area is where packed sets and trays are placed
in baskets and mounted on trolleys, parked and awaiting to be
loaded into sterilizers.
3) The loads entering this area are sorted based on the type of
sterilization e.g. high pressure steam sterilization or those
requiring low heat (plasma) sterilization. (Plasma sterilization is
discussed as a separate topic).
4) In case of high pressure single-door sterilizers, this area is used
to load and un-load packed items into and out of the sterilizers.
GUIDELINE ON CONCEPTUAL DESIGN AND ENGINEERING
42 REQUIREMENTS FOR CENTRAL STERILE SUPPLY UNIT (CSSU)
C. Requirements
1) Space requirement shall be based on the three elements i.e.
number of trolleys used, the space required for the trolleys
to move around and space for loading and unloading.
Space requirements shall comply with the manufacturer’s
requirements. A minimum of 2m3 space is required in front the
sterilizers. This area shall be demarcated by a colored line.
2) The area shall be under positive differential pressure with
respect to adjacent areas.
3 IUSS Health Facility Guides, Central Sterile Service Department (Proposal V.1) 21st March 2014, Page 60
43
A. Function
1) This room is used to accommodate sterilizers and its associated
plant and equipment e.g. steam generator (boilers), compressor,
water pump, test points for water etc.
Steam generator
C. Requirements
1) There shall be sufficient space within the plant room to
accommodate the sterilizers, its associated plants and
equipment. Space requirement shall be based on the number
of sterilizer and associated equipment.
2) Sufficient space shall also be provided to allow the maintenance
personnel to carry out their maintenance works.
3) Manufacturer’s requirement shall be adopted.
4) The plant room shall be ventilated to remove heat released
during the sterilization process and discharge from safety
valves. An exhaust system shall be installed.
4.3.1 Sterilizers
A. Function
1) These steam sterilizers are also known as free standing
autoclaves and are used to sterilize items that are able to
withstand high temperature.
2) These sterilizers form the secondary physical barrier
between the clean and sterilized zones.
C. Requirements
1) There shall be sufficient numbers of sterilizers to meet
the demand of the hospital.
2) There shall be sufficient space for future expansions
(additional sterilizers).
A. Function
1) Heat sensitive loads are sterilized in these low
temperature sterilizers.
C. Requirements
1) There shall be sufficient numbers of sterilizers to meet
the demand of the hospital.
2) There shall be sufficient space for future expansions
(additional sterilizers).
A. Function
1) Heat sensitive loads are sterilized in these low
temperature sterilizers.
C. Requirements
1) There shall be sufficient numbers of sterilizers to meet
the demand of the hospital.
2) There shall be sufficient space for future expansions
(additional sterilizers).
A. Function
1) This area is located on the unloading side of the double-door
sterilizer. Here, items that have been sterilized are removed
from the autoclaves and placed onto trolleys, where they are
allowed to cool to room temperature.
C. Requirements
Not Applicable.
A. Function
1) Once the items have been sterilized and cooled in the Cooling
Area, they are transferred to the sterile store. The sterile store
is the cleanest area in the CSSU.
2) Items are stored on open shelf stainless steel racks.
C. Requirements
1) There shall be no source of contamination e.g. wash areas,
trash bins.
2) The store shall be in an area with minimum traffic flow.
A. Function
1) Sterilized items are issued from this sterile issue area to the
users.
C. Requirements
Not Applicable
4 Guideline Storage Design for Sterile and Non-Sterile Stock for New and Refurbished Healthcare Facilities,
Centre for Healthcare Related Infection Surveillance and Prevention & Tuberculosis Control, Queensland
Government
GUIDELINE ON CONCEPTUAL DESIGN AND ENGINEERING
50 REQUIREMENTS FOR CENTRAL STERILE SUPPLY UNIT (CSSU)
A. Function
1) This office is to be used by the person in-charge of the CSSU.
The setup shall be consistent with the setup of any office in the
hospital.
C. Requirements
1) The office shall be located in the clean zone so as to allow the
person in-charge to observe the various activities at this area.
2) The internal walls and doors shall have vision panels.
A. Function
1) The meeting room can either be used specifically for the purpose
of conducting a meeting or can also be used as a training room.
The meeting room can also be used for departmental activities.
C. Requirements
1) The meeting room shall be located in the clean zone and away
from the all the work areas.
2) The internal walls and doors shall have vision panels.
Change Rooms shall be made available for staff to change their clothing to
hospital gowns and wear Personnel Protective Equipment. There shall be
a set of male and female change rooms with wash room facilities. These
change rooms shall be located at the soiled zone and clean zone.
A. Function
1) This facility is for staff to change into or out of the protective
clothing or gowning.
GUIDELINE ON CONCEPTUAL DESIGN AND ENGINEERING
52 REQUIREMENTS FOR CENTRAL STERILE SUPPLY UNIT (CSSU)
C. Requirements
1) There shall be separate change rooms for male and for female
staff.
2) The facility shall have washrooms preferably with shower
facilities.
3) There shall be a step-over-barrier to demarcate the clean and
dirty areas within the change room.
4) There shall be sufficient lockers for the staff and spares for
visitors.
5) There shall be shelves for clean gowns and PPE storage.
6) There shall be space for soiled linen bins and foot operated
clinical waste bins.
A. Function
1) The rest room is used specifically by the staff to have a break,
refreshing oneself, rest or have a meal
C. Requirements
1) Shall be away from processing area
A. Function
1) The prayer room is a room where staff can perform their
religious obligations
C. Requirements
1) There shall be separate prayer rooms for male and female staff
with ablution facilities
A. Function
1) Personnel Protective Equipment store is a store where safety
attires such as gowns, boots, face masks etc. are stored
C. Requirements
1) The PPE store shall be located in the clean zone.
2) This store shall be secured and only assigned staff shall have
access to it.
A. Function
1) The store is used to store detergents and disinfectants used for
decontamination, cleaning and washer disinfector processes
2) Housekeeping cleaning chemicals shall not be stored in this
area
C. Requirements
Not Applicable
A. Function
1) This room is used to hold clinical and non-clinical waste for
collection and disposal
C. Requirements
Not Applicable
A. Function
1) It is a room where all clean consumables and new MDs are
received for further processing
2) Bulk items are also received here and unpacked before sending
them to the clean rooms
C. Requirements
1) The store shall be secured and only assigned staff shall have
access to this store
2) Dedicated CSSU module
5. General Information
The size of the CSSU shall be based on the maximum simultaneous demand.
5.2 Information required in determining the number and size of major equipment
(sterilizers and washers)
Sterilizers and washer disinfector are amongst the costly equipment in the CSSU.
Due to the high initial capital cost, a proper decision making needs to be made
during the purchase of this equipment.
It is better to have two smaller sized equipment than having one large equipment
to accommodate the services during maintenance and breakdown.
The number of equipment shall be calculated on the basis of running and standby
arrangement. All equipment shall be designed to be operated alternately at any
times.
Due to space utilization, the recommended size of sterilizer shall be 20cu.ft for
district hospitals and 30cu.ft for general hospitals. For the general hospital,
the designer shall consider the additional depth of the sterilizer in view of the
maintenance area behind the equipment and the width of physical barrier for the
double door type.
The usable volume for washer disinfector shall be in the range of 280-300L
for general hospitals and 180-200L for district hospitals. No gap between the
equipment and the floor shall be permitted in the double door washer disinfector
arrangement.
6.1.1 Wall
1) Full heighted fire wall shall be provided for the washer and sterilizer
room.
2) Walls shall be of solid construction so as to eliminate the risk of
infestation.
3) Walls shall be washable, scrub-able, smooth, water resistant and not
easily damaged by chemical and disinfectants e.g. tiled, epoxy painted
or spray painted. Tiled walls shall be encouraged to be installed in
soiled zone as they are easier to clean.
4) Walls shall be free of fissures, open joints, or crevices that may retain
or permit the passage of dirt particles.
5) Walls penetrated by pipes, ducts and conduits shall be tightly sealed.
6) Joints shall be avoided as they can hold moisture, encouraging the
growth of organisms. Joints of structural elements shall be sealed if
necessary.
7) In processing areas, finishes shall be suitable for frequent cleaning
and tolerant to surface-cleaning agents.
8) Proper insulation material shall be installed for areas served by the air
conditioning system. The thickness of insulation shall be specified to
meet the requirement of the 24 hours or 8 hours operation.
9) Walls shall be protected against accidental damage from wheeled
traffic by buffer rails and corner guards, which shall be appropriately
sited to reflect the specifications of trolleys in use.
6.1.2 Ceiling
1) Ceiling shall be monolithic from wall to wall without fissures; i.e. there
shall be no open joints that may retain or permit the passage of dirt
particles or supporting microbial growth. This type of ceiling is to be
implemented at the IAP area and sterile store.
2) Proper insulation material shall be installed for areas served by the air
conditioning system. The thickness of insulation shall be specified to
meet the requirement of the 24 hours or 8 hours operation.
3) Seamless ceiling for packing and sterile store. Lighting casing in the
ceiling shall match the ceiling for ease of cleaning and maintenance.
4) Ceiling shall be cleanable, impervious and of durable finishes. The
ceiling shall be able to withstand disinfecting and cleaning agents
without deterioration.
GUIDELINE ON CONCEPTUAL DESIGN AND ENGINEERING
60 REQUIREMENTS FOR CENTRAL STERILE SUPPLY UNIT (CSSU)
6.1.3 Flooring
1) The finish, the screed and sub-flooring in the CSSU shall be suitable for
heavy trolley traffic.
2) The finishes shall be seamless, non-slip, easy to clean, resistant to
the disinfection procedure and not physically affected by germicidal
cleaning solution.
3) In processing areas, finishes shall be suitable for frequent cleaning
and tolerant to surface-cleaning agents.
4) Joints shall be avoided as they can hold moisture, encouraging the
growth of organisms. Joints of structural elements shall be sealed if
necessary.
5) Proper insulation material shall be installed for areas served by the air
conditioning system. The thickness of insulation shall be specified to
meet the requirement of the 24 hours or 8 hours operation
6) The heavy duty, anti-slip, anti-septic vinyl sheet flooring shall be used
in the IAP area, sterile area and stores. It shall be laid with all joints to
be hot welded, and the skirting shall be backed by a coving and bent
up to a height of 100mm high to prevent dust from collecting.
7) Skirting, floor and wall joints shall be made integral with the floor,
tightly sealed against the wall, and constructed without voids.
8) Damp proof membrane shall be provided for the department if located
at the ground level.
9) The washing and soiled areas shall be provided with seamless tiles.
10) The vinyl flooring can be of different colors to distinguish one area
from another.
11) IAP area shall not be having any structural expansion joints.
12) The sterilizer room flooring shall fall naturally to a drain to facilitate
cleaning.
6.1.4 Door
1) There shall be separate doors for staff and goods.
2) Doors shall be adequately sized to allow clear access for staff and
trolleys to pass through.
3) The main door and exit door shall be the fire rated type.
4) All doors except in the change rooms shall have doors closer to reduce
air movement.
61
5) Doors shall open towards the higher pressure side where possible.
6) Visible panels shall be provided at doors that are open to walkways
and where privacy is not required and shall be of the double glazed
type.
7) Doors shall be provided with a kick-plate and push-plate
8) All emergency exit doors shall have electro-mechanical locking
mechanism to enable disengagement in the event of fire
9) The doors shall be lockable.
6.1.5 Windows
1) The room shall have ample daylight. Distribution and location of
windows shall take into account the need to prevent glare and excess
solar gain.
2) To avoid loss of control of air movement by the ventilation system, all
windows shall be fixed, non-openable, sealed and flush type.
3) Open-able windows may be considered for offices and staff rooms;
provided that they are secured.
4) The windows shall be easily accessible for cleaning both internally and
externally.
6.1.7 Painting
1) The paint shall be of anti-fungal and of the chemical resistant type.
2) Epoxy paint shall be applied.
3) The surface shall be pre-treated and smoothed for a better paint
finish.
4) The first layer of paint shall be completely dried before applying the
epoxy on any surfaces.
GUIDELINE ON CONCEPTUAL DESIGN AND ENGINEERING
62 REQUIREMENTS FOR CENTRAL STERILE SUPPLY UNIT (CSSU)
12) The air handling or fan coil unit shall be placed or installed at a suitable
location to facilitate service and maintenance activities.
13) The subsequent table below provides the various parameters for
comfort and safe work environment.
6.2.3 Noise
1) The noise within the ventilation plant rooms shall not be greater than
85 dBA6.
2) The noise level within the department shall not be more than
the values stipulated in the current version of the FACTORY AND
MACHINERY ACT (NOISE EXPOSURE), REGULATIONS by the Malaysian
Department of Health and Safety.
3) Proper acoustic ceiling tiles, soft floor (vinyl) and engineering controls
shall be implemented to reduce the sound levels.
6.2.4 Water
The detailed water requirements e.g. the pressure, flow rate and quality
shall be determined to allow a smooth operation of the major washer and
sterilizing equipment. There are three types of water used in CSSU.
c) The RO water system shall include storage tank & carbon filter.
The system shall have a by-pass route to normal water for
maintenance.
d) The recommended flow rate shall be 20 L/min for washer & 50
L/min for the sterilizer.
6.2.5 Steam
Saturated steam for the sterilizer can either come from the in-house central
steam reticulation system or dedicated steam generators. There shall be
sufficient and clean saturated steam supplied to the sterilizer.
The recommended steam dryness shall not be below than 97% and the
quantity of steam for the equipment shall strictly follow the manufacturer’s
requirement.
In case the steam supply is from dedicated steam generators, the water
supplied to the steam generator shall be treated as discussed in the section
on Treated Water.
6.2.7 Drainage
1) Effluents from the clinical sinks, ultrasonic cleaners, washer disinfectors
and steam sterilizers shall be considered as potentially contaminated
with chemical and microorganism; and shall be discharged to the
sewerage treatment plant.
2) The drain shall be properly sized to accommodate simultaneous
operation of the equipment.
3) Special drain pipe or drainage system shall be provided for the
discharge of effluents from washer and sterilizer.
4) Exposed drains shall be avoided, especially in the clean zones.
GUIDELINE ON CONCEPTUAL DESIGN AND ENGINEERING
66 REQUIREMENTS FOR CENTRAL STERILE SUPPLY UNIT (CSSU)
6.3.2 Lighting
1) The lighting intensity requirement for the various areas in the CSSU
shall have the following values.
Area Luminance (lux)7
Soiled Zone 300
Clean Zone 300
Stores 150
Sterilizer and cart washer plant 200
room
Task lighting (IAP workstation) 500
7 Chartered Institute of Building Services Engineers (CIBSE) Lighting Guide LG2, Hospitals and healthcare
buildings, Page 60
8 Chartered Institute of Building Services Engineers (CIBSE) Lighting Guide LG2, Hospitals and healthcare
buildings, Page 71
67
6.4 Communication
6.5 IT link
Data points shall also be provided if the CSSU has its own IT module to track its
inventory. Where available and required, the CSSU module can be integrated with
the Hospital Management System.
6.6 Security
All entrances and exits shall be secured to prevent unauthorized persons entering
the CSSU.
Basic security features e.g. intercom shall be installed at the entrances for
unauthorized persons to seek access to CSSU.
Card access facilities shall be installed at the CSSU for its authorized staff.
7.1.9 Warranty
Manufacturers do provide warranty. However, the type and period of
warranty shall be established during the specification requirements.
7.2 Roles and responsibilities of user during planning, installation, testing and
commissioning of upgraded facilities or equipment replacement.
The following are some of the roles and responsibilities of the users during the
upgrading of existing facilities or replacement of equipment. It shall serve as a
guidance to ensure proper execution of the project.
Some common reasons for upgrading are increase in demands, compliance to new
requirement and poor existing facilities. To meet the above requirements, there
is a need to make a decision to either build a new facility or upgrade an existing
facility or premise.
An earlier engagement with the nearest health facility shall be organized and the
mode of transporting the dirty and clean products shall be fully established to
avoid interruption to the service.
GUIDELINE ON CONCEPTUAL DESIGN AND ENGINEERING
72 REQUIREMENTS FOR CENTRAL STERILE SUPPLY UNIT (CSSU)
9. References