[Reference Design 64]

2000 kW, Tier 3, Chilled Water,


Prefabricated, 23700 sq. ft.

DESIGN OVERVIEW INTRODUCTION


The planning process of most projects can be iterative and thereby
Data Center IT Capacity
expensive. Data center projects are burdened with these challenges and can
2000 kW
benefit greatly from simplification and time savings. Schneider Electric’s data
center reference designs help optimize the planning process by providing
Target Availability validated, proven, and documented data center physical infrastructure
Tier 3 designs. The use of these designs has a positive impact on not just the
project itself, but also on the performance, reliability, and efficiency of the
Annualized PUE at 100% Load data center over its lifetime.
1.64 in Miami, FL USA
1.41 in Montreal, Canada
Reference Design 64 includes design information for three spaces: facility
1.48 in St. Louis, MO USA
power, facility cooling, and IT space. This data center combines
prefabricated modules with traditional building architecture, comprising the
Total Racks and Average Density
integrated power, cooling and structural systems required to meet the
400 racks at 5 kW/rack design’s specifications published in this overview document.

Data Center Overall Space


2
Min. 23700 ft

Regional Voltage and Frequency


480V, 60Hz

ABOUT THIS DESIGN

 Traditional IT Space with


prefabricated power and
cooling

 Perimeter-based air distribution

 Highly scalable and adaptable


with Prefabricated Power Skids
and Hydronics Modules

 Chilled water system using air-


cooled packaged chillers with
water-side economizer to save
energy during favorable
outdoor conditions

 Highly redundant design for


increased availability and
concurrent maintenance
[Reference Design 64] 2

Facility Power
FACILITY POWER BLOCK DIAGRAM The facility power system supplies energy to the critical and non-critical
components within the data center. In this Tier 3 design, power is supplied by
Shown 1 of 2
Utility A G Utility B G
two electrical architectures in parallel, each composed of two 1200kW power
skids located inside the building’s electrical rooms. The skids provide 2N UPS
3000A, 480V, 65kA 3000A, 480V, 65kA
power to the IT space, backed up by a 2N generator configuration. A 3000 amp
primary bus on each skid feeds a QED-2 electrical switchboard, two 600kW
600kW 600kW 600kW 600kW
SYMW SYMW
4x
CRAHs SYMW SYMW Symmetra MW UPS with 5 minutes of runtime and an I-Line panelboard, which
provides energy to the cooling system. Within each hydronics module, pumps
1600A, 480V, 65kA 1600A, 480V, 65kA
are supplied with protected power through an N+1 configuration of Smart-UPS
VTs. The 2N power distribution architecture from the electrical room to the IT
space utilizes a combination of LV panels and power distribution units (PDUs).
The facility power system is designed to support integrated peripheral devices
PDU 11x PDU feeds PDU
175kW in IT Space 175kW like fire panels, access control systems, and environmental monitoring and
control devices. Additional low-voltage transformers are included in the design
1200A, 480V, 65kA 1200A, 480V, 65kA to support lighting and other building loads. Power meters in the electrical path
1200A, 480V, 65kA monitor power quality and allow for predictive maintenance & diagnostics of the
system. These meters also integrate with StruxureWare Power Monitoring
UPS
3x DX
UPS UPS Expert.
Cooler

VFD VFD VFD Every component in this design is built and tested to the applicable ANSI,
P P P NEMA, UL or IEEE standards.

Chiller Chiller Chiller Further design details and schematics are available in the engineering package.

DESIGN OPTIONS FACILITY POWER ATTRIBUTES


This reference design can be modified as
follows without a significant effect on the Name Value Unit
design’s performance attributes: Total amps (main bus) 3000 A
Input voltage (main bus) 480 V
 Add StruxureWare Power Monitoring Switchboard kAIC 65 kA
Expert Power path Dual
 Provision for load bank
Generator redundancy 2N
 Change UPS batteries
IT space UPS capacity 2400 kW
 Add/change standby generator options:
IT space UPS redundancy 2N
 Location
IT space UPS runtime @ rated load 5 minutes

© 2014 Schneider Electric. All rights reserved.
Tank size
 Fuel type IT space UPS output voltage 480 V
Facility cooling UPS capacity 32 kW
Facility cooling UPS redundancy N+1

Facility cooling UPS runtime @ rated load 5 minutes

Schneider Electric www.schneider-electric.com


Document Number RD64DS Revision 1
[Reference Design 64] 3

Facility Cooling
FACILITY COOLING BLOCK DIAGRAM Two identical chilled water systems in parallel comprise the facility cooling
design. Each system is composed of a single hydronics module and three
Hydronics module (1 of 2) packaged chillers that deliver chilled water to the electrical and IT rooms. The
Supply
IT1&ER1 hydronics module includes the pumps, valves, controls, and instrumentation
Chiller required to provide cooling in a Tier 3 architecture.
700 kW VFD
Return
IT1&ER1 Three air-cooled chillers with free-cooling arranged in an N+1 configuration
Exp. Tank accompany each of the hydronics modules. The chillers are equipped with dry
VFD
Chiller coolers that can be used during times of favorable outdoor conditions to save
700 kW energy via economizer mode. A thermal storage system is offered as an option
Exp. Tank
VFD to provide 5 minutes of continuous cooling after a power outage or chiller restart.
Return
Dirt/Air IT1&ER1 The piping architecture of the mechanical system feeds perimeter Uniflair
Chiller
700 kW
Sep. Chilled Water units in the IT and electrical rooms. More information on the
Glycol feeder
Supply coolers’ configuration is provided in the IT Space section of this document.
IT1&ER1
This design is instrumented to work with StruxureWare Cooling Monitoring
Thermal Storage Expert.
Tank
Further design details such as dimensions, equipment placement, temperature
set points, pipe sizing, flow rates, and pressure drops are available in the
Piping inside electrical and IT rooms engineering package.
(1 of 2)

HM 1
CRAH
CRAH

Supply CRAH CRAH CRAH CRAH


FACILITY COOLING ATTRIBUTES
CRAH
CRAH

HM 1
Return IT1
CRAH
CRAH

HM 1
Return
Name Value Unit
CRAH

CRAH

CRAH CRAH CRAH CRAH


HM 1 ER1A ER1B Total cooling capacity 2800 kW
Supply
Input voltage 480 V
Heat rejection medium Chilled water
Mechanical redundancy N+1
DESIGN OPTIONS
Packaged chiller
Outdoor heat exchange
with free-cooling
This reference design can be modified as
follows without a significant effect on the Coolant supply temperature 59 F
design’s performance attributes: Coolant return temperature 69 F
Storage tank size 10000 gallons
 Thermal storage tank
 Add StruxureWare Cooling Ride-through time 5 minutes

Monitoring Expert Economizer type Water-side © 2014 Schneider Electric. All rights reserved.

Schneider Electric www.schneider-electric.com


Document Number RD64DS Revision 1
[Reference Design 64] 4

IT Space
IT Room (1 of 2) 20 IT pods and 16 CRAHs distributed between two rooms make up the IT space
of this design. Each IT pod houses 20 NetShelter racks capable of 5 kW for a
P
R R R R R R R R R R D
P
R R R R R R R R R R D total of 100kW. All together this provides 2000 kW worth of IT capacity.
U U
HOT HOT
P
R R R R R R R R R R D
P
R R R R R R R R R R D
The design is highly scalable and adaptable by means of a step and repeat

CRAH
U U
approach to increase IT capacity in 1000kW blocks. A smaller starting load of
CRAH

P
R R R R R R R R R R D
U
P
R R R R R R R R R R D
U
1000kW can also be supported by reducing power and cooling systems to half
HOT
P
HOT
P
of its specified capacity. This flexibility drives efficiency and defers capital
R R R R R R R R R R D R R R R R R R R R R D
expenditure until needed.
CRAH
U U
CRAH

P
R R R R R R R R R R D
U
P
R R R R R R R R R R D
U
Each IT pod is powered by 2N floor mount modular power distribution units
HOT
P
HOT
P
(PDUs) with isolation transformers. Each rack is configured with redundant
R R R R R R R R R R D R R R R R R R R R R D
metered rack-mount PDU to enable remote monitoring of the units for efficiency
CRAH

U U
CRAH

P
R R R R R R R R R R D
P
R R R R R R R R R R D
and capacity management.
U U
HOT HOT
P P
EcoAisle hot air containment system is included with each IT Pod to increase
R R R R R R R R R R D R R R R R R R R R R D
U U
the cooling efficiency of the N+1 perimeter Uniflair Chilled Water CRAHs, which
CRAH
CRAH

P
R R R R R R R R R R D
P
R R R R R R R R R R D
use redundant valves and piping to ensure Tier 3 reliability.
U U
HOT HOT
P P
The security of the room is maintained at multiple points. At the rack level,
R R R R R R R R R R D R R R R R R R R R R D
U U
access is controlled by a door lock and sensor. At the room level, security
cameras are utilized for monitoring.

DESIGN OPTIONS
This reference design can be modified as
follows without a significant effect on the
design’s performance attributes:

 Add environmental and security


management
 Change rack options (tall, wide, IT ROOM ATTRIBUTES
deep)
 Change power distribution options Name Value Unit
(rack PDU type: basic, switched) IT load 2000 kW
 Add StruxureWare Data Center Input voltage 480 V
Expert
Supply voltage to IT 240 V
Average density 5 kW/rack
Number of racks 400 racks
2
IT floor space 12464 ft © 2014 Schneider Electric. All rights reserved.

Single or dual cord Dual


Heat rejection medium Chilled water
CRAC/CRAH type Perimeter CRAH
CRAC/CRAH redundancy N+1

Containment type Hot Aisle

Schneider Electric www.schneider-electric.com


Document Number RD64DS Revision 1
[Reference Design 64] 5

Design Attributes
OVERVIEW Value Unit
Target availability Tier 3 Tier
Annualized PUE at 100% load 1.64 / 1.41 / 1.48
Data center IT capacity 2000 kW
2
Data center overall space 23700 ft
Average density 5 kW/rack
FACILITY POWER Value Unit
Total amps (main bus) 3000 A
Input voltage (main bus) 480 V
Switchboard kAIC 65 kA
Power path Dual
Generator redundancy 2N
IT space UPS capacity 2400 kW
IT space UPS redundancy 2N
IT space UPS runtime @ rated load 5 minutes
IT space UPS output voltage 480 V
Facility cooling UPS capacity 96 kW
Facility cooling UPS redundancy N+1
Facility cooling UPS runtime @ rated load 5 minutes
FACILITY COOLING Value Unit
Total cooling capacity 2800 kW
Input voltage 480 V
Heat rejection medium Chilled water
Mechanical redundancy N+1
Outdoor heat exchange Packaged chiller with free-cooling
Coolant supply temperature 59 F
Coolant return temperature 69 F
Storage tank size 10000 gallons
Ride-through time 5 minutes
Economizer type Water-side

IT SPACE Value Unit


IT load 2000 kW
Input voltage 480 V
Supply voltage to IT 208 V © 2014 Schneider Electric. All rights reserved.

Average density 9 kW/rack


Number of racks 400 Racks
2
IT floor space 12464 ft
Single or dual cord Dual
Heat rejection medium Chilled water
CRAC/CRAH type Perimeter CRAH
CRAC/CRAH redundancy N+1
Containment type Hot Aisle

Schneider Electric www.schneider-electric.com


Document Number RD64DS Revision 1
[Reference Design 64] 6

Data Center Infrastructure


Management (DCIM) System
Good design and quality construction alone do not ensure a highly available &
efficient data center. DCIM provides on-going monitoring and control to ensure the
facility lives up to its design intent. StruxureWare for Data Centers is a software
management suite designed to collect and manage data about a data center’s
assets, resource use, and operational status throughout the life cycle of the facility.
This information is then distributed, integrated, and applied in ways that help
managers optimize the data center’s performance and meet IT, business, and
service-oriented goals. From IT assets to racks, rows, rooms and buildings,
StruxureWare for Data Centers delivers the right information to the right users at the
right time.

Control level: Experts, on site or remotely, can control process performance and
ensure business continuity in real time, while tracking energy consumption in a highly
critical and secure environment.

Operations level: Functional managers can optimize operations, energy, and assets
through smart analytical tools, often spanning multiple sites.

Enterprise level: C-level executives can drive their sustainability strategy efficiently,
choosing the best scenario that meets their business objective to conserve
enterprise-wide resources.

StruxureWare for Data Centers allows for flexibility when requirements and
implementation strategies change over time. StruxureWare software applications
and suites simplify integration time, improve reliability, enhance visibility to energy
information, and streamline operational efficiency.

© 2014 Schneider Electric. All rights reserved.

> Demo:
Visit www.apc.com/software to learn more about StruxureWare for Data Centers!

Schneider Electric www.schneider-electric.com


Document Number RD64DS Revision 1
[Reference Design 64] 7

Schneider Electric Life-Cycle Services


Team of over 7,000 trained specialists covering
every phase and system in the data center

Standardized, documented, and validated


methodology leveraging automation tools and
repeatable processes developed over 45 years

Complete portfolio of services to solve your


technical or business challenge, simplify your
life, and reduce costs

Get more information for this design:


Engineering Package

Every reference design is built with technical documentation


for engineers and project managers. This includes
engineering schematics (CAD, PDF), floor layouts,
equipment lists containing all the components used in the
design and 3D images showing real world illustrations of our
Floor layouts
reference designs.
3D spatial views
Documentation is available in multiple formats to suit the
needs of both engineers and managers working on data
center projects.

© 2014 Schneider Electric. All rights reserved.