Documente Academic
Documente Profesional
Documente Cultură
Applications Handbook
AMCA International
• System Pressure • Fan Testing and Rating • System Checklist • Acceptance Tests
Losses
• The Fan “Laws” • Fan Manufacturer’s • Test Methods and
• Fan Performance Analysis Instruments
Characteristics • Air Systems
• Master Troubleshooting • Precautions
• System Effect • Fan and System Appendices
Interaction • Limitations and
• System Design Expected Accuracies
Tolerances • System Effect Factors
• Calculations
Review Committee
These members contributed to the final review of the publications contained in this
Fan Application Manual.
or
Publication 200
Air Systems
1 Introduction
3 Symbols and Subscripts
4 Properties of Air
5 Airflow
13 The Flow System
34 System Design and Tolerances
40 Annex A — SI / I-P Conversion Table
41 Annex B — Standard Atmospheric Data Versus Altitude Charts
43 Annex C — Psychrometric Density Tables
47 Annex D — Friction Charts
49 Annex E — Air Density Correction Factor Charts
Publication 201
Fans and Systems
51 Introduction
51 Symbols and Subscripts
51 Fan Testing
54 Fan Ratings
63 Catalog Performance Tables
66 Air Systems
74 System Effect Factor (SEF)
79 Outlet System Effect Factors
88 Inlet System Effect Factors
99 Effects of Factory Supplied Accessories 49
102 Annex A. — SI / I-P Conversion Table (Informative)
103 Annex B. — Dual Fan Systems - Series and Parallel
106 Annex C. — Definitions and Terminology
113 Annex D. — Examples of the Convertibility of Energy from Velocity Pressure
to Static Pressure
120 Annex E. — References
Table of Contents (continued)
Publication 202
Troubleshooting
122 Introduction
122 Procedure for Troubleshooting
122 Safety Precautions
122 System Checklist
128 Fan Manufacturer’s Analysis
130 Conclusion
131 Annex A. Noise
134 Annex B. Insufficient Airflow
136 Annex C. Airflow High
137 Annex D. Static Pressure Wrong
139 Annex E — Power High
140 Annex F — Fan Does Not Operate
141 Annex G — Premature Failure
142 Annex H — Vibration
Publication 203
Field Performance Measurement of Fan Systems
145 Introduction
145 Scope
145 Types of Field Tests
146 Alternatives to Conducting Field Tests
146 System Effect Factors
146 Fan Performance
146 Referenced Planes
147 Symbols and Subscripts
147 Fan Flow Rate
152 Fan Static Pressure
156 Fan Power Input
158 Fan Speed
158 Densities
Table of Contents (continued)
SYSTEM
INLET
COIL BRANCH
DUCT
FILTER
LOUVER
DAMPER
DIFFUSER
2 | Air Systems
2. Symbols and Subscripts
A Area m2 (ft2)
Ae Area-Orifice Equivalent to System m2 (ft2)
Ao Area-Nozzle with no loss m2 (ft2)
ah Absolute Humidity kg/m3 (lb/ft3)
C Dynamic Loss Coefficient Dimensionless
Cd Coefficient of Discharge Dimensionless
Cn Coefficient of Nozzle Discharge Dimensionless
c Speed of Sound m/s (ft/s)
D Duct Diameter and Equivalent Diameter m (ft)
E System Resistance Curve Dimensionless
ε Absolute Surface Roughness Height m (ft)
f Friction Coefficient Dimensionless
g Gravity m/s2 (ft/s2)
γ Ratio of Specific Heats Dimensionless
K System Effect Factor (System) Dimensionless
L Length m (ft)
μ Air Viscosity, Absolute N-s/m2 (lbm/ft-s)
∆P Pressure Differential Pa (in. wg)
P Pressure Pa (in. wg)
Ps Static Pressure Pa (in. wg)
Psx Static Pressure at Plane x Pa (in. wg)
Pt Total Pressure Pa (in. wg)
Ptx Total Pressure at Plane x Pa (in. wg)
Pv Velocity Pressure Pa (in. wg)
p Atmospheric Pressure Pa (in. Hg)
Q Airflow Rate m3/s (cfm)
Qx Airflow Rate at Plane x m3/s (cfm)
R Gas Constant J/kg-K (ft-lb/lbm-°R)
Re Reynolds Number Dimensionless
rh Relative Humidity % (%)
ρ Air Density kg/m3 (lbm/ft3)
ρx Air Density at Plane x kg/m3 (lbm/ft3)
SEF System Effect Factor (Fan) Pa (in. wg)
SR System Resistance Factor m-4 (ft-4)
sh Specific Humidity (_/_ dry air) kg/kg dry air (lb/lb) dry air
t Temperature °C (°F)
td Dry-Bulb Temperature °C (°F)
tw Wet-Bulb Temperature °C (°F)
V Average Velocity m/s (ft/min)
v Velocity - At any Point m/s (ft/min)
Y Expansion Factor Dimensionless
Z Altitude m (ft)
~ Is Proportional to Dimensionless
2.2 Subscripts
4 | Air Systems
In the design of most air systems, it is acceptable to mixture is defined as the ratio of the vapor pressure
assume that the gas is incompressible, therefore, the existing compared to the vapor pressure at saturation
air density may be considered constant, and for the same dry-bulb temperature. This is also equal
therefore, the absolute pressure and absolute to the ratio of the mole fractions under the same
temperature are directly proportional. condition. Relative humidity is always expressed as a
percent.
3.1.3.2 Dry-bulb, wet-bulb and dew point
temperature. Unless otherwise specified, the Specific humidity (sh) is the actual mass (weight) of
temperature of an air-water vapor mixture is that the water vapor existing per unit mass (unit weight) of
temperature which is indicated by an ordinary or dry- dry air or gas. Absolute humidity (ah) may be
bulb thermometer. This dry-bulb temperature is the expressed in kilograms (pounds) of water vapor per
temperature of both the air and the water vapor in the cubic meter (cubic foot) of mixture. The humidity of
mixture. The wet-bulb temperature may be an air-water vapor mixture is often expressed by
determined by exposing a wetted bulb in a moving giving either relative humidity or a wet-bulb
air-water vapor mixture until equilibrium is obtained. depression.
The wet-bulb temperature will be lower than the dry-
bulb temperature as long as evaporation continues. If 4. Airflow
no evaporation is possible, the mixture is saturated
and the wet and dry-bulb temperatures for this The flow of any fluid between two points is caused by
condition will be identical. The dew point temperature the existence of a pressure differential between the
of an air-water vapor mixture is the saturation two points. It is the purpose of this section to explain
temperature corresponding to the absolute humidity the parameters that may affect the flow of a gas
of the mixture. The dew point temperature may also between two points.
be considered as that temperature at which
condensation begins when the mixture is gradually 4.1 Flow conditions
cooled.
Most air systems are designed in the incompressible
3.1.4 Viscosity. A non-perfect gas, such as air, is range. Where compressibility is a factor, Mach
capable of exerting a force parallel to the surface of a number and Reynolds number must be considered.
body which is moving with respect to the gas. The
magnitude of the force parallel to the surface is used The magnitude of these parameters gives an
to define an important property of non-perfect gases indication of the effects which can be expected from
- viscosity. The effects of viscosity on the behavior of the deviations in the non-perfect gas behavior from
real gases cause resistance to flow; the resistance is that of a perfect gas.
proportional to the velocity gradients which exist in
the gas. The absolute viscosity (µ) is defined as the 4.1.1 Mach number. Mach number, for our purposes
shearing stress for a unit rate of change of velocity. here, is the ratio of the velocity of an airstream to the
The absolute viscosity has units of newton-sec per speed of sound in that airstream.
meter squared (N-s/m2) in the SI system and pound
mass per foot-second (lbm/ft-s) using I-P units. Mach number = V/c
Air Systems | 5
4.1.2 Reynolds number. The ratio of the inertia force friction drag, and, for streamlined bodies closely
to the viscous force caused by changes in velocity aligned with the flow, represents the entire drag force.
within the fluid element is known as the Reynolds For blunt bodies, which may be streamlined bodies at
number. large angles to the flow, profile drag exists. Profile
drag is caused by the inability of the flow, due to its
viscous effects, to follow the body shape. The
⎛ρ⎞
Re = DV ⎜ ⎟ Eq. 4.1-1A SI inability to follow the body shape creates a wake of
⎝μ⎠ very turbulent flow which in effect creates the profile
⎛ ρ ⎞ drag force. These wake effects are the predominant
Re = DV ⎜ ⎟ Eq. 4.1-1A I-P cause of flow losses in systems.
⎝ 60 μ ⎠
⎛ DV ⎞
=⎜ ⎟
⎝ γ ⎠
Where:
6 | Air Systems
the duct to the low velocity section near the duct wall In addition to the losses in total pressure in a system
causes a marked resistance to the flow. This caused by friction losses and dynamic losses, there
resistance varies linearly with the length of the duct are losses due to System Effects.
and approximately with the square of the average
velocity in the duct. The resistance is also a function System Effects occur because of the differences
of the Reynolds number of the flow, which is between the fan inlet and outlet connections to the
calculated using the average velocity in the duct, the installed system and the standardized connections
duct diameter, and the surface roughness of the duct used in laboratory tests to obtain fan performance
wall. ratings. AMCA Publication 201, Fans and Systems,
gives specific details on System Effects related to
The velocity profiles in a duct system for fully fans. System Effects related to series system
developed flow will vary depending on whether the elements are covered further in Section 4.5 of this
flow is laminar or turbulent and the degree of duct publication.
roughness. Velocity profiles of various flow conditions
are shown in Figure 4C. 4.4.1 Duct friction losses. In the normal range of air
systems for HVAC and industrial applications, the
The absolute velocity of the air stream will vary flow falls into the transition region between laminar
substantially over the cross-sectional duct area, but flow and complete turbulent flow. In this region the
for duct systems the velocity used for determining the losses due to friction are a function of Reynolds
velocity pressure is always the average velocity given number and the relative roughness of the duct wall.
by: The pressure loss in the transition region will vary at
slightly less than the square of the velocity. The
V average = Q/A Eq. 4.3-1 pressure loss due to friction for flow in ducts may be
calculated from the Darcy-Weisbach equation:
Where:
∆Pt = f(L/D) Pv Eq. 4.4-1
V = Velocity, m/s (ft/min)
Q = Flow rate, m3/s (cfm) Where:
A = Area of the cross-section where the flow occurs,
m2 (ft2) ∆Pt = Total pressure loss due to friction, Pa (in. wg)
f = Friction factor, dimensionless
The duct velocity profiles shown in Figure 4C are L = Length of duct, m (ft)
uniform along the length of the duct and symmetrical D = Diameter of pipe, m (ft)
around the center line. Where there are disturbances Pv = Velocity pressure, Pa (in. wg)
in the ducts, such as turns, expansion or contraction,
etc., the velocity profile across the duct can become In the transition flow range, the value of the friction
very asymmetrical as shown in Figure 4D. factor cannot be calculated directly. It can be
obtained from the Moody diagram or by iterative
The flow will return to a normal velocity profile after a solution of the Colebrook equation. See the ASHRAE
disturbance if there is sufficient length of straight duct Handbook: Fundamentals, chapter on Duct Design,
to allow the velocity distribution to regain uniformity. A for a more complete discussion of duct friction losses.
minimum of 2½ equivalent duct diameters of straight
duct is required to attain a normal velocity profile for The Moody diagram, Figure 4E, shows the
velocities of 12.7 m/s (2500 ft/min) or less. Add one relationship of the friction factor, Reynolds number
duct diameter for each additional 5.08 m/s (1000 and duct roughness (ε) in meters (feet). Most
ft/min). See AMCA Publication 201-90, Fans and applications are in the transition region between
Systems. laminar and full turbulent flow conditions.
4.4 System losses Using duct friction charts (see Annex D) is the most
common method of determining friction losses.
The losses in total pressure for flow through a system These charts are based on ducts having average
are caused by two factors: friction losses due to roughness and standard air density. Correction
viscosity as the air flows along the surface of ducts factors must be applied for ducts having different
and other system elements, and dynamic losses roughness, and for variations in air density and
due to the turbulent wake caused by changes in viscosity.
direction and separation of the flow around obstructions.
Air Systems | 7
r LAMINAR
TURBULENT
SMOOTH Re = 107
SMOOTH Re = 105
ε = 0.03D ROUGH
ε = 0.008D ROUGH
0 0.5 1.0 1.5 2.0
v
V
D = Duct Diameter
ε = Duct Roughness
Re = Reynolds Number
v = Velocity at any Point
V = Average Velocity
r = Radius
0.09
0.08
0.05
0.07
0.04
0.06
0.03
0.05
0.02
0.015
FULLY ROUGH (EQ 18)
0.04 Eq. (29a)
0.006
RO
0.03
UG
0.004
H
W
IT Eq.
H (2
Re 9a
DE )
0.002
PE
N
DE
NC
0.02
E
0.0010
0.0008
Eq. (27) 0.0006
0.0002
TRANSITION
LAMINAR TURBULENT
REGION
0.00010
0.00005
0.010
0.009
0.008 0.00001
103 2 3 5 104 2 3 5 105 2 3 5 106 2 3 5 107 2 3 5 108
REYNOLDS NUMBER, Re
Reprinted by permission of the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, Georgia, from the 1993
ASHRAE Handbook-Fundamentals. (Moody 1944). Values on the chart are the same for both the SI and I-P systems. Equation numbers refer
to equations in the source document.
Air Systems | 9
Loeffler1 has developed simplified equations for the Correction factors for density and viscosity variations
friction factor in the normal range of flow conditions need to be applied for conditions other than standard
found in industrial and HVAC air systems. The air. See Annexes B and E.
equations provide for direct calculation of duct friction
total pressure losses. These equations yield results 4.4.2 Dynamic losses. Dynamic losses occur where
that are accurate within ±5% and are conservative there are changes in velocity or direction in the air
over most of the range of flow. system and are due primarily to the profile drag.
Dynamic losses are proportional to the square of
For aluminum ducts, medium smooth: velocity, and therefore, are proportional to the
velocity pressure.
ε = 0.0000457 m (0.00015 ft)
∆Pt ~ V 2 ~ Pv
⎛ LQ ⎞
1.863
Pt loss = a ⎜ 4.93 ⎟ Dynamic pressure loss data are given in a number of
⎝ D ⎠ forms such as pressure loss for given volume or
Where: velocity, equivalent length of duct, or velocity
pressure multiplier, and is available from
a = 1.764 × 10-2 Eq. 4.4-2 SI manufacturers' data and handbooks such as:
ASHRAE, the Industrial Ventilation Guide and
a = 4.816 × 10-9 Eq. 4.4-2 I-P SMACNA.
For galvanized steel ducts, average: Except at duct exits, dynamic losses occur along
some length and cannot be separated from friction
ε = 0.0001524 m (0.0005 ft) losses. For practical purposes the dynamic losses
are assumed to be concentrated at one point and the
friction losses are included as part of the duct friction.
⎛ LQ1.921 ⎞ Dynamic loss coefficients for duct fittings are based
Pt loss = a ⎜ 5.066 ⎟
⎝ D ⎠ on zero length. For friction loss calculations, the
Where: centerline length of the duct fitting is taken as the
length of the fitting.
a = 1.717 × 10-2 Eq. 4.4-3 SI
4.4.3 Dynamic loss coefficient. There are two
common methods of expressing dynamic losses.
a = 3.534 × 10-9 Eq. 4.4-3 I-P
These are: 1) The equivalent length of duct method,
and 2) the loss coefficient method. The equivalent
For fiberglass ducts or lined ducts, fabric and wire
length of duct method replaces the dynamic loss of
flexible ducts (wire covered with fabric), medium
fittings (elbows, tees, branches, etc.) with a length of
rough,
duct that will have an equivalent loss. The equivalent
length of duct for all of the dynamic losses are added
ε = 0.00091443 m (0.003 ft)
to the straight duct length. A friction chart showing the
loss is then used to determine the total loss in the
⎛ LQ1.965 ⎞ system.
Pt loss = a ⎜ 5.208 ⎟
⎝ D ⎠
The dynamic loss coefficient method is based on the
Where: fact that all losses in a system are functions of the
velocity pressure and can be calculated by a
a = 2.093 × 10-2 Eq. 4.4-4 SI corresponding dynamic loss factor multiplied by the
velocity pressure. These losses are added to the
a = 3.64 × 10-9 Eq. 4.4-4 I-P straight duct friction loss to determine the total loss in
the system.
Where:
The dynamic loss coefficient method is preferred
Pt loss = Total pressure loss, Pa (in. wg) because it is usually quicker and offers the
Q = Flow rate, m3/s (cfm) advantage of faster recalculation when other branch
D = Duct diameter, m (ft) (or equivalent diameter duct sizes are tried.
of rectangular ducts) D equivalent = (4ab/ )0.5
where a and b are the sides in m (ft) Dynamic losses are proportional to the velocity
L = Duct length in m (ft) pressure occurring in the system element and,
10 | Air Systems
therefore, the pressure loss in the fitting can be 4.5.2 Element System Effects in series. System
related to the velocity pressure by use of a dynamic Effects for other air system elements occur when two
loss coefficient. or more elements are in close proximity to one
another. Loss coefficients for duct fittings, coils,
The dynamic loss coefficient Co is defined as: filters, dampers, etc., are determined with a sufficient
length of straight duct (normally 10 diameters) ahead
Co = ∆Pt/Pvo Eq. 4.4-5 of the element to allow for a normally distributed
velocity profile entering the element, and a sufficient
Where: length of straight duct (normally 10 diameters)
downstream from the element to allow a normally
Co = Dynamic loss coefficient, reference to section distributed velocity profile to be re-established. When
o, dimensionless two elements, such as elbows, or an elbow and a
∆Pt = Dynamic pressure loss, Pa (in. wg) damper, are placed close together the air entering
Pvo = Velocity pressure at section o, Pa (in. wg) the second element will be highly turbulent and
asymmetrical in profile, causing a higher loss than
expected. In addition, any static regain occurring
The coefficient relates the pressure loss in the
downstream of the first element would also be lost
element to the velocity pressure at a given cross-
when sufficient length of straight duct is not present.
sectioned area of the element.
To illustrate System Effects for duct elements, the
The pressure loss of duct system elements with
loss coefficients for a single 90° elbow and two
known dynamic loss coeffients can be calculated by:
elbows in series are shown in Figure 4F.
∆Pt = Co Pvo Eq. 4.4-6
In the case of the two elbows in series, the difference
between twice the loss of the single elbow and the
Where there are changes in area or divided flow in
actual combined loss is the System Effect. The
the fitting, the designer must be careful to use the
System Effect varies substantially depending on how
proper area as noted in the loss tables for the
close the two elbows are to each other.
determination of the velocity pressure to be used with
the dynamic loss coefficient. The ASHRAE
Similar effects can be expected when any system
Handbook: Fundamentals, Chapter on Duct Design,
elements are in close proximity. The amount of the
provides a detailed discussion of the dynamic loss
System Effect will vary over a rather wide range
coefficient and tables for coefficients of many
depending upon the physical characteristics of each
common duct elements.
element and their relationship to each other in the
system.
4.5 System Effects
Very little actual data is available on System Effects
Additional losses can occur in air systems because of of various combinations of system elements, and the
the physical relationship of various elements in the system designer must, of necessity, estimate the
system. These System Effect losses occur because System Effects. The following tables for estimating
of the difference between the way the performance of System Effects, and Equation 4.5-1, are given as a
the element was determined by testing and the way guide to the designer. Actual data should be used
the element is actually installed in the system. whenever it is available.
4.5.1 Fan System Effects. Fan System Effects occur Cc = (Ca + Cb) K Eq. 4.5-1
because of the difference in inlet and outlet
conditions under laboratory test conditions and the
Where:
inlet and outlet conditions as the fan is installed in the
system. Detailed information on Fan System Effects
Cc = Loss coefficient of combined elements,
is contained in AMCA Publication 201, Fans and
dimensionless
Systems. The System Effect is accounted for as a
Ca = Loss coefficient of element a, dimensionless
pressure loss which must be included with the other
system losses. The sum of the pressure losses is Cb = Loss coefficient of element b, dimensionless
then used as the basis for selecting the fan. K = System Effect Factor, dimensionless
1. Loeffler, J. J., Simplified Equations for HVAC Duct Friction Factors, ASHRAE Journal, January, 1980
Air Systems | 11
ONE ELBOW Figure 4G should be used for elements in series
where the flow is straight through, while Figure 4H
should be used when a turning element (elbow, etc.)
C1 = 1.15* is involved. These tables have been developed on
FLOW the basis of limited data and are intended only as a
guide. Actual System Effects may vary from the
values shown. See sample calculation in Section 5.8
2 C1 Two
times the
loss
2.30 a
coefficient
of a single
elbow
System b
+0.33 +81.7% +33.98% +6.5%
Effect
14.3% 1.88 0.78 0.15
(Difference)
L
12 | Air Systems
5. The Flow System ρ is equal to the air density in kg/m3 (lbm/ft3), and
standard air density equals 1.2 kg/m3 (0.075 lbm/ft3).
5.1 Concepts of pressure Pv is always positive and this pressure is always
exerted in the direction of airflow. Air confined within
The flow of air between two zones (or spaces) is due a duct or a tank, whether in motion or not, creates
to a pressure difference between the two zones. This another kind of pressure which exerts itself in all
pressure difference forces the air to flow from the directions at once, including perpendicular to the
high pressure zone to the low pressure zone. walls of the enclosure. This is known as static
Ductwork is used in most air systems to convey the pressure Ps. Static pressure is negative when it is
air from one zone to another. The quantity of air Q in below atmospheric pressure, and positive when
m3/s (cfm) that will flow is equal to the cross-sectional above atmospheric pressure. Total pressure Pt at any
area A of the duct in m2(ft2) times the air velocity V in point in an air system is equal to the algebraic sum of
m/s (ft/min). the static pressure Ps and velocity pressure Pv. Pt can
be either positive or negative, depending on its
Q = AV Eq. 5.1-1 components.
Air Systems | 13
In Figure 5A, the sealed length of duct has a static pressure of 345 Pa (1.39 in. wg) above atmospheric pressure.
Since there is no airflow, velocity pressure is equal to zero. The total pressure Pt can then be calculated according
to equation 5.1-3.
SI I-P
Pt = Ps + Pv Pt = Ps + Pv
= 345 + 0 = 1.39 + 0
= 345 Pa = 1.39 in. wg
14 | Air Systems
In Figure 5B, with the duct open and a fan placed at one end blowing air through the duct, we find both static
pressure and velocity pressure as illustrated by the water gauge. The total pressure is the sum of velocity pressure
and static pressure.
20.3 m/s
AIRFLOW
(4005 FPM)
In this illustration, the static pressure will be above atmospheric pressure and the total pressure is numerically
greater than either static or velocity pressure.
Air Systems | 15
In Figure 5C, a fan is placed at the end of the duct and draws air through the duct. In this case, the static pressure
is below atmospheric pressure. In both Figures 5B and 5C, the total pressure rise across the fan is 345 Pa (1.39
in. wg); therefore, the energy used in both systems is equal.
20.3 m/s
AIRFLOW
(4005 FPM)
16 | Air Systems
5.3 Conservation of energy Therefore, to simplify Bernoulli's Theorem:
The well known Bernoulli Theorem, frequently used Ps1 + Pv1 = Ps2 + Pv2 + losses1,2 Eq. 5.3-1
in the flow of fluids, states the law of conservation of
energy for fluid systems. In its simpler form for Simply stated, the sum of static pressure and velocity
airflow: pressure at any point in a flow system is equal to the
sum of static pressure and velocity pressure at any
(V12/2g) + (P1/ρg) + Z1 = (V22/2g) + (P2/ρg) other point in the system, plus any losses in pressure
+ Z2 + losses1,2 occurring between the two points.
Where:
Although it is very important to recognize that the
Vx2/2g= Kinetic energy or velocity pressure (Pv) sum of static and velocity pressure remains constant
at any point in the system when disregarding losses,
Px/ρg = Potential energy or static pressure (Ps)
it is the losses that are of real importance in the
Zx = The elevation (normally ignored in fan
design and function of air moving systems.
systems with minimal changes in
elevation) may need to be evaluated when To illustrate Bernoulli's Theorem, Figure 5D shows a
the system elevation change causes a typical venturi system commonly used to measure
noticeable change in air density. fluid flow.
Pt PS PV Pt PS PV Pt PS PV
Pt Pt
PS
PRESSURE PS
Pa (INCHES W.G.) PV
PV
Air Systems | 17
For the purposes of illustration, assume this is a If the plenum is very large relative to the nozzle
perfect device with no losses. The velocity pressure, diameter, the velocity in the plenum will approach
static pressure, and total pressure at each point in the zero, so the total pressure at point 1 (Pt1) will be equal
system are shown on the gauges as well as on the to the static pressure (Ps1). Assuming a perfect fluid
lower portion of the illustration. Part of the static at and no losses occurring in the nozzle, the static
point 1 is converted to velocity pressure as the fluid pressure in the plenum (point 1) is totally converted
is accelerated in the contracted flow area in the neck to velocity pressure at the discharge of the nozzle
of the venturi. At point 2, in the neck of the venturi, (point 2).
the velocity pressure reaches its maximum and the
static pressure is reduced, but the total pressure At point 2, just beyond the discharge end of the
remains constant. As the flow area is gradually nozzle, the static pressure (Ps2) will be zero (at
increased to point 3, the velocity is slowed down to atmospheric pressure) and the total pressure (Pt2) will
the original velocity and the velocity pressure is be equal to the velocity pressure of the air stream.
reduced to its original value. The static pressure Applying Bernoulli's Equation for points 1 and 2
increases back to its original value also, while the gives:
total pressure remains constant.
Ps1 + Pv1 = Ps2 + Pv2
In this illustration, part of the static pressure at point
1 is converted to increased velocity pressure at point
Since Pv1 is equal to 0 and Ps2 is equal to 0, the
2 and the velocity pressure is then converted back
equation reduces to:
into static pressure at point 3.
Ps1 = Pv2
The conversion of the velocity pressure into static
pressure by reducing the velocity is known as static
regain and it is very important to understand this In this case, the energy of the static pressure in the
phenomenon in the design of flow systems. plenum is totally converted to the velocity energy at
the discharge of the nozzle. It should also be noted
In air systems, changes in velocity often occur as the that the velocity pressure is totally lost as the
air flows through the various elements comprising the airstream discharges to atmosphere.
system. Some total pressure loss will occur any time
the velocity in the system is increased or decreased. Using Equation 5.1-2A (as reduced above) the
The magnitude of these losses is dependent on the relationship between static pressure and the throat
physical characteristics of the system element in velocity can be established in the above example.
which the velocity change takes place. Decreases in Using this in Equation 5.1-2A gives:
velocity occurring at abrupt enlargements in area
result in total pressure losses approaching one V2 = (2Ps1/ρ2)0.5 Eq. 5.3-2A SI
velocity pressure.
V2 = 1096(Ps1/ρ2)0.5 Eq. 5.3-2A I-P
Figure 5E illustrates air flowing from a large plenum
through a long radius flow nozzle and discharging to Or where: Ps1 = Pv2
atmosphere.
Then for standard air, the equations would be:
Where:
Ps1 = Pv2
18 | Air Systems
Then, for standard air, the equation would be: In practical system design both Cn and Y approach
unity and can normally be neglected. However, these
Pv2 = 0.6V 2 Eq. 5.3-3B SI factors are important when measuring fan
performance in accordance with ANSI/AMCA
Pv2 = (V2/4005)2 Eq. 5.3-3B I-P Standard 210.
In the above example, the quantity of flow would be In Figure 5F, the nozzle is replaced by a sharp edged
dependent on the area of the nozzle discharge and orifice. The flow through the orifice tends to neck
the velocity in the throat as given by the equation: down to a flow area smaller than the orifice diameter.
The point at which the flow area reaches its minimum
Q2 = V2A2 is called the vena contracta. The flow through the
orifice is given by the equation:
Where:
Q = Cd(2Ps/ρ)0.5A Eq. 5.3-6 SI
Q = Airflow rate, m3/s(cfm)
V = Velocity, m/s (ft/min) Q = Cd1096(Ps/ρ)0.5A Eq. 5.3-6 I-P
A = Area, m2 (ft2)
Where:
Substituting for V2 from Equation 5.3-2A and 5.3-2B
gives: A = Area of orifice, m2 (ft2)
Cd = Coefficient of discharge, dimensionless
Q = (2Ps1/ρ2)0.5A2 Eq. 5.3-4A SI
VENA CONTRACTA
Q = 1096(Ps1/ρ2 )0.5A
2 Eq. 5.3-4A I-P
Air Systems | 19
If we plot the flow through these elements versus Resistance Curve (see Figure 5H) the point of
static pressure as shown in Figure 5G, we obtain a operation is at the intersection of the fan performance
squared curve which is typical of flow versus curve and the System Resistance curve.
pressure for any constant system.
SYSTEM
RESISTANCE
PRESSURE
PRESSURE
POINT OF
OPERATION
P = KQ2
FAN PRESSURE
CURVE
FLOW FLOW
These curves are called System Resistance curves, 5.4 Fan total and static pressure
and define the relationship of flow versus pressure
for any system with constant resistance. System The flow of a gas through a system of ducts and
Resistance curves are defined by the following various system elements requires energy:
equations:
a) To accelerate the air from ambient conditions at
Q = (2Ps/ρ)0.5Ae Eq. 5.3-7A SI the entry to the system
Q = 1096(Ps/ρ)0.5Ae Eq. 5.3-7A I-P b) To overcome the losses in the system from
friction and system element shock losses
Then for standard air:
c) For the loss of energy dissipated as velocity at
Q = 1.29(Ps )0.5A Eq. 5.3-7B SI the system outlet
e
The System Resistance concept is very useful in PtF = Pt2 - Pt1 Eq. 5.4-1
understanding flow in complete systems or elements
of flow systems. If we add a fan curve to the System Or:
20 | Air Systems
The velocity pressure of a fan is defined as: Both static pressure and total pressure curves of the
fan and system resistance are shown. Either set of
PvF = Pv2 Eq. 5.4-3 curves can be used for the flow rate because the
point of operation is the same. The difference in
The static pressure of a fan is defined as: pressure at the point of operation between the total
pressure curve and the static pressure curve is the
PsF = PtF - PvF Eq. 5.4-4 velocity pressure at the fan discharge (plane 2).
Fan static pressure, as defined, is a term that is Most fans are rated in terms of static pressure and
peculiar to fans and is not consistent with the normal flow, however, fans having high discharge velocities
meaning of static pressure rise. Fan static pressure is such as vaneaxial fans are quite often rated in terms
derived from the method of testing fans where the fan of total pressure. Be aware of these different
static pressure is equal to gauge static pressure at methods of rating and be certain whether fan static
the fan discharge when the fan draws air from pressure or fan total pressure was used to determine
surrounding atmosphere through a well shaped inlet. the fan selection.
Special care must be used when using fan static 5.4.2 Fan system pressure relationships. Figure
pressure for purposes of matching the required fan 5K shows the relationship of total pressure, static
performance against system total pressure losses. pressure and velocity pressure for a fan with free inlet
The relationship of these pressures is covered in conditions and discharging through a duct against
detail for various systems further on in this section. some system. In this example the fan is shown as
being equipped with a short inlet duct and an inlet
The static pressure of a fan can also be stated in bell. For simplicity's sake it is assumed that there are
several other forms. Substituting Equation 5.4-2 for no losses at the inlet to the fan.
the total pressure of the fan in Equation 5.4-4 gives:
The total pressure prior to the entry of the fan in
PsF = Ps2 + Pv2 - Ps1 - Pv1 - Pv2 Eq. 5.4-5 Figure 5K is zero and since it was assumed that there
are no entry losses, the total pressure remains zero
Simplifying: until the flow is acted upon by the fan. As air enters
the fan, its velocity and the pressure due to that
PsF = Ps2 - Ps1 - Pv1 Eq. 5.4-6 velocity (velocity pressure) increases while static
pressure decreases in direct proportion. (In actual
Since: conditions there will be some entry losses which will
be accounted for in the fan performance rating.)
Ps1 + Pv1 = Pt1 Referring to Figure 5K, the fan total pressure is equal
to the total pressure at plane 2 minus the total
pressure at plane 1.
The equation can be restated as:
PtF = Pt2 - Pt1 Eq. 5.4-8
PsF = Ps2 - Pt1 Eq. 5.4-7
The fan static pressure is equal to the total pressure
5.4.1 Fan performance specification. The system
at plane 2 minus the velocity pressure at plane 2.
designer should be aware of the effect of the velocity
pressure at the outlet of the system and the velocity
PsF = Pt2 - Pv2 Eq. 5.4-9
pressure of the fan discharge (plane 2) on the
determination of fan total or static pressure for the
system. The net result of the fan total or static The static pressure of the fan can also be stated as
pressure requirements at a given flow rate for the the static pressure at plane 2 minus the static
system is the fan performance specification, which is pressure at plane 1 minus the velocity pressure at
normally stated as flow at a specific static, or total plane 1.
pressure. This statement of required fan performance
is, in reality, a statement of one point on a system PsF = Ps2 - Ps1 - Pv1 Eq. 5.4-10
resistance or equivalent orifice curve, which then
defines the flow and pressure relationship of the Or, as the static pressure at plane 2 minus the total
system being designed. pressure at plane 1.
The actual point of operation of the combined fan and PsF = Ps2 - Pt1 Eq. 5.4-11
system will be the intersection of the fan performance
curve and the system curve as shown in Figure 5J.
Air Systems | 21
The actual static pressure rise across the fan from 5.5 The total system
plane 1 to plane 2 will be greater than the fan static
pressure by the amount of the velocity pressure at A fan provides the total pressure to move the air
the fan inlet, plane 1. The difference in the actual through a system and the flow rate will reach a point
static pressure rise across the fan and the fan static of equilibrium (point of operation) when the total
pressure represents the energy required to pressure provided by the fan equals the total
accelerate the air to its entry velocity. This kinetic pressure losses in the system at that flow rate. A
energy is retained by the moving air stream until typical system with inlet and discharge resistance is
there is a change in velocity in the system or it is illustrated in Figure 5L.
dissipated at the point of discharge, and as such
does not represent a loss in total pressure until it is Applying Bernoulli's Equation at the point of entry and
discharged. the outlet:
The equipment arrangement shown in Figure 5K is PtE = PtO + Pt loss E,O - PtF Eq. 5.5-1
typical of the test conditions for fans in ANSI/AMCA
Standard 210, and is the basis for fan performance Rearranging:
ratings. When fans are tested in accordance with
ANSI/AMCA Standard 210, the inlet and discharge PtF = Pt loss, E,O + PtO - PtE Eq. 5.5-2
conditions are rigidly specified for each test method.
Restating in terms of Ps and Pv:
When a fan is installed in an air system where the
actual entry and exit conditions are different than the PtF = Pt loss E,O + PsO + PvO - PsE - PvE
test conditions, the performance of the fan may be
altered and System Effect factors must be used to
PtF = Pt loss E,O + PvO + (PsO - PsE - PvE) Eq. 5.5-3
account for the altered performance. AMCA
Publication 201, Fans and Systems describes
Substituting from Equation 5.4-4 for PtF :
various System Effects and provides quantitative
data for calculating System Effect losses.
PvF
PRESSURE
SYSTEM RESISTANCE
(TOTAL PRESSURE) PtF
PsF
SYSTEM RESISTANCE
(STATIC PRESSURE)
Equations 5.5-3 and 5.5-4 are the general statements System total pressure loss = total pressure loss
of fan total pressure or fan static pressure required internal to the system, plus the velocity pressure loss
for flow through a system. The Pt loss term is the loss at the outlet(s) of the system.
internal to the system from friction and shock losses.
The PvO term represents the energy loss to the The term (PsO - PsE - PvE) represents the change in fan
system contained in the velocity at the outlet of the total pressure or fan static pressure requirements
system. because of the static pressure conditions existing at
the system entry or outlet and any velocity pressure
In Equation 5.5-4, the items enclosed in large present at the system entry. Velocity and velocity
brackets represent the fan total pressure. pressure generated by external sources, such as
wind, at the system entry are seldom encountered,
In the normal method of calculating system total so the PvE term can generally be disregarded.
pressure losses, the velocity pressure at the outlet(s)
0
FAN
PtF = Pt2 - Pt1
PsF = PtF - Pv2
Pt
+ Pv Pt2 = PtF
Ps2 = PsF
Pv1 Pv2
PtE= 0 0
Ps1
_ Ps ABSOLUTE
PRESSURE
PtF Pv2
ATMOSPHERIC
PRESSURE
Pv Pt2
PvO = PtO
+ Ps2
PtE = 0 0
_
Pt PsF
ABSOLUTE
Ps PRESSURE
Ps1
PLANE 1 PLANE 2
E O
ENTRY OUTLET
FLOW
FAN
ATMOSPHERIC
PRESSURE Pt FAN PtO = Pv2
Pv
+ Pt
PtE = 0
_
Ps
Ps
Pt1 ABSOLUTE
FAN
PRESSURE
Pv Ps1
PtF = Pt LOSS + PvO
Where:
PsF = Pt LOSS + PvO - Pv2
Pv1
since PvO = Pv2
PsF = Pt LOSS
(Pressure Loss Internal to System)
Air Systems | 25
5.6 Types of fan system PsF = Pt loss + PvO - Pv2 Eq. 5.6-2
There are four basic system Installation Types: In the special case where the velocity pressure at the
outlet is equal to the velocity pressure at the fan
AMCA INSTALLATION TYPE A: discharge, the fan static pressure will equal the total
Free Inlet, Free Outlet pressure loss. If these velocity pressures are different
the fan total pressure and fan static pressure must be
increased or decreased by the amount of the
difference in these velocity pressures.
AMCA INSTALLATION TYPE D: Fans designed for use at the end of a system, such
Ducted Inlet, Ducted Outlet as power roof ventilators, include the loss at the
discharge in the fan ratings and no system effect loss
is needed.
26 | Air Systems
pressure loss in the evasé section. Losses will be CoPvo
quite small for a long evasé outlet of good design SR = Eq. 5.7-4 SI
(Q / 1.29)2
(optimum included angle is about 10 degrees). The
change in fan static pressure, because of the change
in the outlet velocity, is accounted for in the terms CoPvo
"PvO - PvF" in Equation 5.5-4. SR = Eq. 5.7-4 I-P
(Q / 4005)2
Air Systems | 27
RESISTANCE RESISTANCE
ELEMENT PLANE 1 PLANE 2 ELEMENT
E 0
Pvt
Figure 5Q - Fan with Inlet and Discharge Resistance - Evasé Outlet Added
RESISTANCE 1 Q1
QT
RESISTANCE 2 Q2
Where: = QT (0.4495)
C = 1.29 (for SI units)
= 4005 (for I-P units) If:
Air Systems | 29
and total the losses. In systems that include parallel ITEM DUCT,
branches it is customary to determine the loss of the 6.096 m (20 ft.) of 0.4064 m (16 in.) diameter.
branch path that has the highest resistance to Airflow = 0.94 m3/s (2000 cfm)
establish the fan requirements. Other branch paths Pt Loss = 8.94 Pa (0.036 in. wg)
that have lower losses must have resistance added
to them to balance the system since the total ITEM D - DIVIDED FLOW FITTING,
pressure loss of each path must be equal. 0.4572 m (18 in.) to 0.4064 m (16 in.) and 0.3048 m
(12 in.) diameter, with a main branch dynamic loss
5.8.1 Example: System loss calculations for coefficient of 0.
branch 1 (dynamic loss coefficient method) Airflow = 1.416 m3/s (3000 cfm)
Pv = 44.70 Pa (0.18 in. wg)
ITEM K - DISCHARGE DIFFUSER Pt Loss = 44.70 × 0 (0.18 × 0)
0.3048 m (12 in.) diameter with a dynamic loss
= 0 Pa (0 in. wg)
coefficient of 0.50.
NOTE: The net loss in the main branch of this fitting
Airflow = 0.47 m3/s (1000 cfm) is zero (0), since there is static regain to offset the loss.
Pv = 25.08 Pa (0.101 in. wg)
Pt Loss = 0.50 × 25.08 (0.50 × 0.101) ITEM DUCT,
= 12.54 Pa (0.051 in. wg) 12.192 m (40 ft.), 0.4572 m (18 in.) diameter.
NOTE: Loss coefficient includes velocity lost at Airflow = 1.42 m3/s (3000 cfm)
discharge and static regained by diffusion. Pt Loss = 21.36 Pa (0.086 in. wg)
30 | Air Systems
ITEM H - INTAKE LOUVER resistance will need to be added by adjusting its
Airflow = 1.42 m3/s (3000 cfm) damper to balance the system.
Pt Loss = 19.87 Pa (0.08 in. wg)
(from manufacturer's data) 5.8.3 Fan selection for the example system. The
total system pressure loss of the branch with the
SYSTEM TOTAL PRESSURE LOSS BRANCH 1 = highest resistance must be used to determine the fan
336.4 Pa (1.355 in. wg). pressure requirements. The fan will need to provide a
total pressure of 336.2 Pa (1.354 in. wg) at 1.42 m3/s
5.8.2 Example: System loss calculations for (3000 cfm). The fan static pressure PsF is equal to the
branch 2: fan total pressure PtF minus the calculated fan
discharge velocity pressure Pv2.
ITEM K - DIFFUSER
Pt Loss = 12.42 Pa (0.050 in. wg) PsF = PtF - Pv2
NOTE: Loss coefficient includes velocity lost at = 336.2 - 25.58
discharge and static regained by diffusion. = 310.62 Pa or (1.354 - 0.103 = 1.251 in. wg)
Air Systems | 31
12.2m 6.1m 6.1m
FAN
D C A
1.42m3/s
0.94m3/s 0.472m3/s
0.46m DIA.
E B B
COIL
F 0.30m DIA. 0.30m DIA.
FILTER 0.472m3/s 0.472m3/s
G
LOUVER
H J J DAMPER J
DIFFUSER K K K
3 2 1
SI
18” DIA.
E B B
COIL
F 12” DIA. 12” DIA.
FILTER 1000 CFM 1000 CFM
G
LOUVER
H J J DAMPER J
DIFFUSER K K K
3 2 1
I-P
300
PT vs FLOW
PT vs FLOW
0 1 2 3 4
CFM × 1000
SI (Volume flow rate) I-P (Power required at 68°F and 3000 ft)
226.8 kg/min ÷ (60 s/min × 0.800 kg/m3) = 4.725 m3/s 14.5 BHP × (0.067 lbm/ft3 ÷ 0.075 lbm/ft3) = 12.95 BHP
I-P (Volume flow rate) In normal HVAC applications the effects of density
500 lbm/min ÷ 0.5 lbm/ft3 = 10000 cfm changes other than for operation at higher altitudes,
are quite often ignored and the system design is
The pressure loss in the system would be calculated based on handling standard air. The system designer
based on 4.725 m3/s (10000 cfm) at standard air should, however, be aware of the effects of density
density of 1.2 kg/m3 (.075 lbm/ft3). If in this example change and take them into consideration when
the pressure loss at standard air is 1490.16 Pa (6 in. making field measurements of system performance
wg) the pressure loss at actual conditions would be or balancing the system.
this value multiplied by the density ratio:
Use Annex C to determine the density of air over a
SI (Pressure loss - actual conditions) range of barometric pressures, temperatures, and
1490.15 Pa × (0.8 kg/m3 ÷ 1.2 kg/m3) = 993.44 Pa relative humidities. Annex E gives the density ratios
for a wide range of temperatures and altitudes. The
I-P (Pressure loss - actual conditions) air density at the various conditions is obtained by
6 in. wg × (.05 lbm/ft3 ÷ .075 lbm/ft3) = 4 in. wg multiplying standard air density of 1.2 kg/m3 (0.075
lbm/ft3) by the factors shown in the table.
A fan for this system must be selected based on its
performance at standard conditions. For this example 6. System Design and Tolerances
select the fan for a performance of 4.725 m3/s (10000
cfm) at 1490.16 Pa (6 in. wg) static pressure. Before making a final determination of the fan
Determine the fan power required at standard density selection there are several factors in the design of a
from the fan performance data. The power required system and the selection of a fan that need to be
at actual conditions would then be calculated by understood and evaluated:
multiplying the catalog fan power by the density ratio.
In this example the fan power required at standard a) The effect of variation in the resistance of the
conditions is 10.82 kW (14.5 BHP). At the actual actual installed system versus the resistance of
operating conditions of 121.1°C (250°F) air at 914.4 the designed system, i.e.; point of operation
m (3000 ft) altitude, the fan power required would be
the power for standard air multiplied by the density b) The fan performance characteristics and
ratio: system/performance tolerances
34 | Air Systems
a) The installed system is different from the These curves are only shown to make the system
designed system, such as the addition of elbows designer aware of the effect of the slope of the fan
and offsets to meet field conditions, failure to curve on the expected system performance with
provide turning vanes in elbows, or the change in variations in system resistance. Many other factors
position of various system elements with respect enter into the determination of the best fan type and
to each other; size for a given application.
b) Excessive leakage or increased resistance due 6.2.2 Fan performance tolerance. The fan
to poor quality workmanship at the installation; performance also has a tolerance which must be
considered. The AMCA Check Test Tolerances are
c) Loss coefficients of the various system elements described in AMCA Publication 211, Certified Ratings
such as coils, filters, dampers, diffusers, elbows, Program -Air Performance, Product Rating
etc., improperly accounted for; Requirement Subsection B. The AMCA Check Test
Tolerance is shown on Figure 6B. This tolerance is to
d) System Effects: be applied along a parabolic system line. The power
• not properly accounted for required by the AMCA Check Test Tolerances shall
• ignored in the original system design not exceed the rated data at the measured volume by
• not accounted for because of on-site more than 5% or 37 watts, whichever is greater. The
installation changes. fan curve in Figure 6B has dashed lines indicating the
tolerance range of fan performance, and when
The degree to which all of the various tolerances and combined with the system resistance tolerance
the field changes affect the actual system resistance curves, an area of probable system performance is
varies quite widely. Experience indicates that the indicated by the tolerance limits shown for the system
difference to be expected between the calculated and resistance and the tolerance limits shown for the fan
actual system resistance can be as much as ±10%. flow-pressure. As can be seen, the probable flow
In extreme cases, greater system resistance range could be from 3.15 m3/s (6674 cfm) to 3.39
differentials have been experienced. Not accounting m3/s (7185 cfm) which is -4.7 to +2.6%. An installed
for system effects in the design will result in a higher system tolerance range approaching ± 5.0% of flow
system resistance and reduced flow. could be expected.
6.2 Fan performance 6.2.3 Performance safety factor. Evaluate the fan
performance tolerance and system resistance
There is a wide variety of basic fan designs in axial, tolerances to determine if the lower or upper limits of
centrifugal and mixed flow variations. Curves of the probable flow in the system are acceptable. The
several typical basic fans, all selected for a point of combination of these tolerances should also be
operation of 3.30 m3/s (7000 cfm) at a static pressure evaluated to ensure that the high side system
of 1490.16 Pa (6 in. wg), are shown on Figure 6A. All resistance curve does not fall into the unstable
of these fans pass through the design point of portion of the fan curve. With a few exceptions, all
operation, but with different slopes. The point of fans have an unstable range of performance.
highest efficiency will typically occur somewhat to the Operation in this area of the curve should be avoided
right of the peak pressure point. and precautions taken to ensure operation outside of
the unstable area at the highest expected system
6.2.1 System resistance effect on performance. resistance.
The system resistance curves for the point of
operation and curves for ±10% and ±25% of the 6.2.3.1 Static pressure safety factor. It has been
design pressure are also shown in Figure 6A. The common practice among system designers to apply a
intersection of these system lines with the various fan performance safety factor to the calculated system
curves show what range of volume performance can requirements. This is often accomplished by adding a
be expected for each fan over this range of system nominal percentage of pressure to the system
resistance. The amount of variation in flow rate with pressure requirements. Some system designers will
changes in the system resistance will be dependent size the system for a higher flow rate than is required.
on the slope of the fan performance curve in the
range of operation. The use of safety factors is discouraged when all
system components and system effects are
properly accounted for. The use of safety factors
is not required when system effect factors and all
known losses are accounted for.
Air Systems | 35
6.3 Effects of system changes Figure 6D shows a typical fan curve with system
resistance curves for a variable system where the
Some air systems are designed to operate at more system pressure is allowed to vary as the system
than one system condition, such as an exhaust demand for airflow changes. The system may be
system serving multiple inlets where some of the varied by volume control, dampers, or other control
inlets can be closed off, or supply systems where devices to provide a varying flow rate as demanded
some of the outlets can be closed off or dampered for by the system.
reduced flow. The effect of these changes in the
system need to be evaluated in the system design The tolerance ranges are shown for both the fan and
and the selection of a fan for this service. The main the system resistance. The most critical point in the
concern would be that the fan is not forced to operate design of this type of system will be at the low flow-
in the unstable range. Also, the fan performance high pressure condition. The fan selection and
should be such that the system performance is system limits should be such that the fan will operate
acceptable over the range of operating conditions in the stable portion of the fan curve at the maximum
desired. The motor must be selected to cover this resistance condition. Make sure the fan power
range of operating conditions. The system resistance requirements over the tolerance range can be met by
and system performance, for the example used in the motor selected.
Section 5.8, were calculated for the design condition
and also for two other system conditions. [Figure 6C Figure 6E shows a typical set of fan curves for a
illustrates the effect of system changes.] The system centrifugal fan with inlet vane control with system
resistance and flow were calculated for the condition resistance curves for a variable resistance system. In
where all the dampers were open and for the this system, both the pressure and flow
condition where one of the dampers was closed. characteristics of the fan are varied by changing the
Each of these conditions has a different system inlet vanes position to meet the flow rate demand of
resistance curve resulting in a different operating the system. Similar systems employ axial fans with
point on the fan curve and a different total flow for the variable pitch control, or fans with variable speed
system. The flow in each branch of the system will capability.
also change. This leads to an important conclusion:
The critical area of fan selection is near the peak of
IN A FIXED SYSTEM, A CHANGE IN RESISTANCE the pressure curve. Almost all fans exhibit some
IN ANY ELEMENT WILL CHANGE THE TOTAL degree of instability to the left of the peak pressure
SYSTEM RESISTANCE, AND AS A RESULT, point. It is wise to avoid operation in this range
CHANGE THE POINT OF OPERATION ON THE without the expressed approval of the fan
FAN CURVE AND THE FLOW RATE THROUGH ALL manufacturer.
OTHER ELEMENTS OF THE SYSTEM.
There are many system variations to meet various
It is because of this interaction of the total system design criteria that the designer may encounter. Not
with changes in any part of the system that the job of all of the possibilities can be covered in the scope of
balancing a system is very difficult. this publication. If fan users apply the principles
outlined in this publication to the specific system,
6.4 Variable systems they can expect to design a good, functional system
and avoid many of the pitfalls often encountered in air
Where systems are designed to be variable over systems.
some range of operation, or where both the fan and
system are variable, the point of operation needs to
be evaluated at the upper and lower limits of
operation, relative to the tolerance of the fan and
system.
36 | Air Systems
+25%
+10%
PRESSURE
BACKWARD -10%
1490.16 Pa
INCLINED FAN -25%
(6.0 in. wg)
RADIAL
BLADE FAN
3.3m/s VANEAXIAL
(7000 cfm) FAN
VOLUME FLOWRATE
+10%
DESIGN POINT
OF OPERATION
-10%
PRESSURE
FAN CURVE
POTENTIAL SYSTEM
FLOW RANGE
3.15 m3/s 3.39 m3/s
(6701 cfm) (7210 cfm)
3.3 m3/s AMCA CERTIFIED RATING
(7000 cfm) TOLERANCE
VOLUME FLOWRATE
Air Systems | 37
DWDI FAN
DESIGN
SYSTEM
TOTAL PRESSURE
Pt vs FLOW
VOLUME FLOWRATE
+10%
-10%
HIGH PRESSURE
DESIGN POINT
FAN CURVE
+10%
PRESSURE
VOLUME FLOWRATE
38 | Air Systems
+10%
-10% MAXIMUM FLOW
DESIGN POINT
PRESSURE
VARIABLE VOLUME
SYSTEM RESISTANCE
STATIC PRESSURE
CONTROL POINT
VOLUME FLOWRATE
Air Systems | 39
Annex A. SI / I-P Conversion Table
Viscosity:
Absolute (lbm/ft-s) 1.4882 = Pa s (Pa s) 0.6719 = (lbm/ft-s)
Kinematic (ft2/s) 0.0929 = m2/s (m2/s) 10.7639 = ft2/s
Gas Constant (ft lb/lbm-°R) 5.3803 = J-kg/K (j-kg/K) 0.1858 = (ft lb/lbm-°R)
40 | Air Systems
Annex B. Standard Atmospheric Data Versus Altitude Charts
Z t p ρ μ v c
Altitude Temperature Atmospheric Gas Absolute Kinematic Speed of
Pressure Density Viscosity Viscosity Sound
Air Systems | 41
Chart B.2 - I-P Standard Atmospheric Data Versus Altitude
Z t p ρ μ ν c
Altitude Temperature Atmospheric Air Dynamic Kinematic Speed of
Pressure Density Viscosity Viscosity Sound
42 | Air Systems
Annex C. Psychrometric Density Tables
Air Systems | 43
Chart C.1 - Psychrometric Density Table (SI) (Continued)
44 | Air Systems
Chart C.2 - Psychrometric Density Table (I-P)
Air Systems | 45
Chart C.2 - Psychrometric Density Table (I-P)
46 | Air Systems
100 VE 100
LO
CI
TY
70 90 m/ 70
s
30
80
50 50
40 25 70 40
50
30 60 30
63
20
ASHRAE Handbook-Fundamentals.
80
18 50
20 20
0
Annex D. Friction Charts
16 45
10
5
14 40
12
35
0
10 12 10
16
30
0
10
20
7 7
0
9
25
5 8 5
5
31
4 7 4
0
40
3 6 3
0
50
0
2 5 2
63
Chart D.1 - SI
0
80
4
00
20
3
12
0.7 0.7
00
16
2.5
00
0.5 0.5
20
0.4 0.4
mm
00
2.0
R,
25
E
31
1.6
IAM
00
0.2 0.2
D
1.4
40
CT
1.2
DU
9
0.1
20 50 100 200 500 1,000 2,000 5,000 10,000 20,000 50,000 200,000 400,000
Air Systems | 47
Reprinted by permission of the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, Georgia, from the 1993
10 10
80
7 00 7
48 | Air Systems
70
5 65 00 5
0
60 0 VE
4 0 LO 4
55 0 CI
0 TY
3 50 0 , fp 3
00 m
45
ASHRAE Handbook-Fundamentals.
00
2 40 12 2
3
00 00
36 0
00
32 10
4
00
00 0
90
1 28 00 1
5
00 80
00
6
0.8 24 0.8
00
7
8
20
0.5 0 0.5
9
18 0
10
0.4 00 0.4
16 40
12
00 00
0.3 0.3
14
14
00
16
18
0.2 12 0.2
00
20
22
Chart D.2 - I-P
10
24
00
26
90
0 30
32
0.1 80 0.1
0
36
0.08 0.08
40
70 18
60
55
0.05 0 0.05
60
in.
70
0.04 50
0 0.04
R,
80
E
0.03 0.03
90
0
ET
40
0
10
IAMD
0.02 0.02
CT
30
0
DU
0.01 0.01
50 100 200 500 1,000 2,000 5,000 10,000 20,000 50,000 100,000 200,000 400,000
AIR QUANTITY, cfm at 0.075 lb/ft3 (ε = 0.0003 ft)
Reprinted by permission of the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, Georgia, from the 1993
Annex E. Air Density Correction Factor Charts
Air Systems | 49
Chart E.2 - Air Density Correction Factor (I-P)
(Multiply Standard Air Density, 0.075 lbm/ft3 × the Factor to obtain Density at Condition B.)
Altitude, ft. -1000 Sea Level 1000 2000 3000 4000
Barometer, in. Hg 31.02 29.92 28.86 27.82 26.82 25.84
in wg. 422.2 407.5 392.81 378.6 365.0 351.7
Air Temp. °F -40 1.31 1.26 1.22 1.17 1.13 1.09
0 1.19 1.15 1.11 1.07 1.03 0.99
40 1.10 1.06 1.02 0.99 0.95 0.92
70 1.04 1.00 0.96 0.93 0.89 0.86
100 0.98 0.95 0.92 0.88 0.85 0.81
150 0.90 0.87 0.84 0.81 0.78 0.75
200 0.83 0.80 0.77 0.74 0.71 0.69
250 0.77 0.75 0.72 0.70 0.67 0.64
300 0.72 0.70 0.67 0.65 0.62 0.60
350 0.68 0.65 0.62 0.60 0.58 0.56
400 0.64 0.62 0.60 0.57 0.55 0.53
450 0.60 0.58 0.56 0.54 0.52 0.50
500 0.57 0.55 0.53 0.51 0.49 0.47
550 0.54 0.53 0.51 0.49 0.47 0.45
600 0.52 0.50 0.48 0.46 0.45 0.43
700 0.47 0.46 0.44 0.43 0.41 0.39
800 0.44 0.42 0.40 0.39 0.37 0.36
900 0.40 0.39 0.37 0.36 0.35 0.33
1000 0.37 0.36 0.35 0.33 0.32 0.31
50 | Air Systems
Fans and Systems 201
ANSI/AMCA 210 Laboratory Methods of Testing Fans 2. Symbols and Subscripts
For Aerodynamic Performance Rating, offers the
system design engineer guidance as to how the fan For symbols and subscripted symbols, see Table 2.1.
was tested and rated. AMCA Publication 201 Fans For subscripts, see Table 2.2.
and Systems, helps provide guidance as to what
effect the system and its connections to the fan have 3. Fan Testing
on fan performance.
Fans are tested in setups that simulate installations.
Recognizing and accounting for losses that affect the The four standard installation types are as shown in
fan’s performance, in the design stage, will allow the Figure 3.1.
designer to predict with reasonable accuracy, the
installed performance of the fan.
AMCA INSTALLATION TYPE A:
Free Inlet, Free Outlet
1.1 Purpose
UNITS OF MEASURE
SYMBOL DESCRIPTION SI I-P
SUBSCRIPT DESCRIPTION
a Atmospheric conditions
c Converted Value
x Plane 0, 1, 2, ...as appropriate
1 Fan Inlet Plane
2 Fan Outlet Plane
3 Pitot Traverse Plane
5 Plane 5 (nozzle inlet station in chamber)
6 Plane 6 (nozzle discharge station in chamber)
8 Plane 8 (inlet chamber measurement station)
1 2
Transition Straightener
Piece
Since changes in performance will be different for ηtc = (Qc × Ptc × Kp) / (6362 • Hc) (I-P)
various product designs, it will be necessary to make
suitable allowances based on data obtained from the ηsc = ηtc × (Psc/Ptc)
applicable fan catalog or directly from the
manufacturer. These equations have their origin in the classical
theories of fluid mechanics, and the accuracy of the
Most single width centrifugal fans are tested using results obtained is sufficient for most applications.
Arrangement 1 fans. Some allowance for the effect Better accuracy would require consideration of
of bearings and bearing supports in the inlet may be Reynolds number, Mach number, kinematic viscosity,
necessary when using Arrangement 3 or dynamic viscosity, surface roughness, impeller blade
Arrangement 7. The various AMCA standard thickness and relative clearances, etc.
arrangements are shown on Figures 3.5, 3.6, and
3.7. 4.2 Limitations
CENTRIFUGAL FAN
PL 2 PL X
AXIAL FAN
38mm ±6mm
(1.5in. ±0.25 in.)
PL.5 PL.6 PL.8 PL.1 PL.2
0.5 M MIN.
0.2M 0.5M 0.2 M MIN.
MIN. MIN. 0.3 M MIN.
t d2
AIRFLOW M FAN
VARIABLE
SUPPLY t d3
SYSTEM 0.1 M MIN.
SETTLING SETTLING
MEANS MEANS
(See note 4)
Ps5 ΔP Pt8
ISO 13349
AMCA Drive Alternative Fan
Drive Description Fan Configuration
Arrangement Configuration
Arrangement
AMCA International, Inc. | 30 W. University Dr. | Arlington Heights, IL, 60004-1893 | U.S.A
ISO 13349
AMCA Drive Alternative Fan
Drive Description Fan Configuration
Arrangement Configuration
Arrangement
AMCA International, Inc. | 30 W. University Dr. | Arlington Heights, IL, 60004-1893 | U.S.A
ISO 13349
AMCA Drive Alternative Fan
Drive Description Fan Configuration
Arrangement Configuration
Arrangement
integrally mounted.
AMCA International, Inc. | 30 W. University Dr. | Arlington Heights, IL, 60004-1893 | U.S.A
c. Compressibility. Compressibility is the characteristic Air density (ρ), fan size (D), and fan rotational speed
of a gas to change its volume as a function of (N) are usually constant for the entire curve and must
pressure, temperature and composition. The be stated.
compressibility coefficient (Kp) expresses the ratio of
the fan total pressure developed with an A typical fan performance curve is shown in Figure
incompressible fluid to the fan total pressure 4.1. Figure 4.2 illustrates examples of performance
developed with a compressible fluid (See curves for a variety of fan types.
ANSI/AMCA 210). Differences in the compressibility
coefficient between two similar fans must be
Pt
100
Ps
90
80
PRESSURE, P
POWER, H
ηt
EFFICIENCY, η PERCENT
70
60
50
ηs
40
H
30
20
OPERATION AT 10
STANDARD DENSITY
0
AIRFLOW, Q
• Highest efficiency of all centrifugal fan designs. • Scroll-type design for efficient conversion of velocity
• Ten to 16 blades of airfoil contour curved away from pressure to static pressure.
AIRFOIL
direction of rotation. Deep blades allow for efficient • Maximum efficiency requires close clearance and
expansion within blade passages alignment between wheel and inlet
• Air leaves impeller at velocity less than tip speed.
• For given duty, has highest speed of centrifugal
fan designs
• Efficiency only slightly less than airfoil fan. • Uses same housing configuration as airfoil design.
BACKWARD-
BACKWARD-
• Higher pressure characteristics than airfoil, • Scroll. Usually narrowest of all centrifugal designs.
backward-curved, and backward-inclined fans. • Because wheel design is less efficient, housing
RADIAL
• Curve may have a break to left of peak pressure dimensions are not as critical as for airfoil and
R R
and fan should not be operated in this area. backward-inclined fans.
• Power rises continually to free delivery.
M
M
• Flatter pressure curve and lower efficiency than the • Scroll similar to and often identical to other centrifugal
FORWARD-
• Do not rate fan in the pressure curve dip to the left • Fit between wheel and inlet not as critical as for airfoil
of peak pressure. and backward-inclined fans.
• Power rises continually toward free delivery. Motor
selection must take this into account.
• Limited to low-pressure applications. • Optimum design is close to blade tips and forms
• Usually low cost impellers have two or more blades of smooth airfoil into wheel.
single thickness attached to relatively small hub.
• Primary energy transfer by velocity pressure.
• Somewhat more efficient and capable of developing • Cylindrical tube with close clearance to blade tips.
AXIAL FANS
TUBEAXIAL
• Good blade design gives medium- to high-pressure • Cylindrical tube with close clearance to blade tips.
VANEAXIAL
• Performance similar to backward-curved fan except • Cylindrical tube similar to vaneaxial fan, except
CENTRIFUGAL
• Lower efficiency than backward-curved fan. • Air discharges radially from wheel and turns 90° to
• Performance curve may have a dip to the left of flow through guide vanes.
peak pressure.
SPECIAL DESIGNS
A
• Low-pressure exhaust systems such as general • Normal housing not used, since air discharges from
CENTRIFUGAL
• Low-pressure exhaust systems such as general • Essentially a propeller fan mounted in a supporting
factory, kitchen, warehouse, and some commercial structure
installations.
AXIAL
EFFICIENCY
ηt
4 ηs 6 • Power reaches maximum near peak efficiency and low-, medium-, or high-pressure applications.
wo 4 becomes lower, or self-limiting, toward free delivery. • Applied to large, clean-air industrial operations for
2
VOLUME FLOW RATE, Q 2 significant energy savings.
0 0
0 2 4 6 8 10
10
• Similar to airfoil fan, except peak efficiency slightly lower. • Same heating, ventilating, and air-conditioning
PRESSURE-POWER
8
10 applications as airfoil fan.
6 8 • Used in some industrial applications where airfoil
EFFICIENCY
4
6 blade may corrode or erode due to environment.
4
2
VOLUME FLOW RATE, Q 2
0 0
0 2 4 6 8 10
10
• Higher pressure characteristics than airfoil and backward- • Primarily for materials handling in industrial plants.
PRESSURE-POWER
8
10 curved fans. Also for some high-pressure industrial requirements.
6 8 • Pressure may drop suddenly at left of peak pressure, but • Rugged wheel is simple to repair in the field. Wheel
EFFICIENCY
4
6 this usually causes no problems. sometimes coated with special material.
4 • Power rises continually to free delivery. • Not common for HVAC applications.
2
2
VOLUME FLOW RATE, Q
0 0
0 2 4 6 8 10
10
• Pressure curve less steep than that of backward-curved • Primarily for low-pressure HVAC applications, such as
PRESSURE-POWER
8
10 fans. Curve dips to left of peak pressure. residential furnaces, central station units, and
6 8 • Highest efficiency to right of peak pressure at 40 to 50% packaged air conditioners.
EFFICIENCY
4
6 of wide open volume.
4 • Rate fan to right of peak pressure.
2
VOLUME FLOW RATE, Q 2 • Account for power curve, which rises continually toward
0 0
0 2 4 6 8 10 free delivery, when selecting motor.
10
• High flow rate, but very low-pressure capabilities. • For low-pressure, high-volume air moving applications,
PRESSURE-POWER
8
10 • Maximum efficiency reached near free delivery. such as air circulation in a space or ventilation through
6 8 • Discharge pattern circular and airstream swirls. a wall without ductwork.
EFFICIENCY
10
• High flow rate, medium-pressure capabilities. • Low- and medium-pressure ducted HVAC applications
PRESSURE-POWER
8
10 • Performance curve dips to left of peak pressure. Avoid where air distribution downstream is not critical.
6 8 operating fan in this region. • Used in some industrial applications, such as drying
EFFICIENCY
4
6 • Discharge pattern circular and airstream rotates or swirls. ovens, paint spray booths, and fume exhausts.
4
2
2
VOLUME FLOW RATE, Q
0 0
0 2 4 6 8 10
10
• High-pressure characteristics with medium-volume flow • General HVAC systems in low-, medium-, and high-pressure
PRESSURE-POWER
8
10 capabilities. applications where straight-through flow and compact
6 8 • Performance curve dips to left of peak pressure due to installation are required.
EFFICIENCY
4
6 aerodynamic stall. Avoid operating fan in this region. • Has good downstream air distribution
4 • Guide vanes correct circular motion imprated by wheel and • Used in industrial applications in place of tubeaxial fans.
2
2 improve pressure characteristics and efficiency of fan. • More compact than centrifugal fans for same duty.
VOLUME FLOW RATE, Q
0 0
0 2 4 6 8 10
10
• Performance similar to backward-curved fan, except • Primarily for low-pressure, return air systems in HVAC
PRESSURE-POWER
8
10 capacity and pressure is lower. applications.
6 8 • Lower efficiency than backward-curved fan because air • Has straight-through flow.
EFFICIENCY
4
6 turns 90°.
4 • Performance curve of some designs is similar to axial flow
2
VOLUME FLOW RATE, Q 2 fan and dips to left of peak pressure.
0 0
0 2 4 6 8 10
10
• Usually operated without ductwork; therefore, operates at • Low-pressure exhaust systems, such as general factory,
PRESSURE-POWER
8
10 very low pressure and high volume. kitchen, warehouse, and some commercial installations.
6 8 • Only static pressure and static efficiency are shown for • Low first cost and low operating cost give an advantage over
EFFICIENCY
4
6 this fan. gravity flow exhaust systems.
4 • Centrifugal units are somewhat quieter than axial flow units.
2
2
VOLUME FLOW RATE, Q 0
0
0 2 4 6 8 10
10
• Usually operated without ductwork; therefore, operates at • Low-pressure exhaust systems, such as general factory,
PRESSURE-POWER
8
10 very low pressure and high volume. kitchen, warehouse, and some commercial installations.
6 8 • Only static pressure and static efficiency are shown for • Low first cost and low operating cost give an advantage
EFFICIENCY
a: These performance curves reflect general characteristics of various fans as commonly applied. They are not intended to provide complete selection criteria, since other parameters,
such as diameter and speed, are not defined.
Fans designed for use other than with duct systems The performance of fans intended for use with duct
are usually rated over a lower range of pressures. systems is usually published in the form of a "multi-
They are commonly cataloged and sold as a rating" table. A typical multi-rating table, as illustrated
complete unit with suitable drive and motor. in Figure 5.2 shows:
Typical fans in this group are propeller fans and a) the speed (N) in rpm
power roof ventilators. They are usually available in b) the power (H) in kw (hp)
direct or belt-drive arrangements and performance c) the fan static pressure (Ps) in Pa (in. wg)
ratings are published in a modified form of the multi- d) the outlet velocity (V) in m/s, (fpm)
rating table. Figure 5.1 illustrates such a table for part e) the airflow (Q) in m3/s (cfm)
of a line of belt-drive propeller fans.
Figure 5.3 shows constant speed characteristic
5.2 Ducted fans curves superimposed on a section of the multi-rating
table for the same fan. A brief study of this figure will
There are three types of ducted fans, as described in assist in understanding the relationship between
Section 3: curves and the multi-rating tables.
SIZE No. of Motor Peak AIRFLOW (ft3/min) @ STATIC PRESSURE (in. wg)
rpm
(in.) Blades hp bhp 0 1/8 1/4 3/8 1/2 5/8 3/4 7/8 1
1/4 862 0.18 4,283 3,350 1,230
1/4 960 0.27 4,770 3,960 2,050
24 3
1/3 1071 0.36 5,321 4,620 3,730 1,600
1/2 1220 0.54 6,062 5,450 4,750 3,600 1,710
1/4 806 0.27 6,123 4,990 2,230
1/3 883 0.36 6,708 5,675 4,100 1,620
27 3
1/2 1035 0.57 7,862 7,000 6,035 3,315 2,020
3/4 1165 0.83 8,850 8,110 7,290 6,385 3,400 2,330
1/2 825 0.56 9,240 7,970 6,430 2,700
3/4 945 0.83 10,580 9,500 8,300 5,040 3,010
33 3 1 1045 1.1 11,710 10,755 9,685 8,490 4,890 3,215
1½ 1190 1.6 13,335 12,490 11,580 10,610 9,500 5,905 4,100
2 1306 2.2 14,630 13,845 13,030 12,185 11,280 10,200 6,470 4,740 3,900
TYPICAL RATING TABLE FOR A SERIES OF BELT-DRIVEN PROPELLER FANS
Figure 5.1 - Propeller Fan Performance Table
Fans and Systems | 63
IMPELLER DIAMETER: 927 mm OUTLET AREA: .71 SQ METERS
TIP SPEED IN m/s: .0485 × RPM MAXIMUM kW: 13.65 × (RPM/1000)3
Outlet 62 Pa 93 Pa 124 Pa 155 Pa 186 Pa 217 Pa 246 Pa 310 Pa 373 Pa
Volume
Vel.
m3/s rpm kW rpm kW rpm kW rpm kW rpm kW rpm kW rpm kW rpm kW rpm kW
(m/s)
1.81 2.55 222 0.14
2.17 3.06 236 0.17 270 0.25
2.53 3.56 253 0.22 284 0.30 313 0.39
2.89 4.07 272 0.27 300 0.36 327 0.45 352 0.55
3.25 4.58 292 0.34 317 0.43 343 0.53 366 0.64 389 0.75 411 0.87
3.61 5.08 314 0.42 337 0.52 360 0.63 382 0.74 403 0.86 424 0.98 443 1.10
3.97 5.59 338 0.51 358 0.62 378 0.73 399 0.85 419 0.98 438 1.10 458 1.19 494 1.52
4.33 6.10 361 0.62 379 0.74 398 0.86 417 0.98 436 1.11 455 1.25 472 1.39 507 1.68 540 1.99
4.69 6.61 385 0.74 402 0.87 419 1.00 437 1.13 454 1.26 472 1.41 489 1.56 522 1.86 554 2.18
5.06 7.13 409 0.88 426 1.01 441 1.16 457 1.30 473 1.44 489 1.58 506 1.74 538 2.06 568 2.39
5.42 7.63 434 1.03 449 1.18 464 1.33 479 1.49 494 1.63 509 1.79 524 1.95 555 2.28 584 2.62
5.78 8.14 458 1.21 473 1.37 488 1.53 501 1.69 515 1.86 529 2.01 543 2.18 572 2.53 600 2.89
6.14 8.65 483 1.41 498 1.58 511 1.75 525 1.92 537 2.09 550 2.26 564 2.43 590 2.78 617 3.16
6.50 9.15 508 1.63 522 1.81 535 1.99 538 2.16 560 2.35 572 2.54 585 2.71 610 3.07 635 3.45
6.86 9.66 547 2.06 559 2.25 571 2.44 584 2.62 595 2.82 606 3.01 630 3.39 654 3.78
7.22 10.17 571 2.34 585 2.54 595 2.74 607 2.93 616 3.14 629 3.34 651 3.74 674 4.15
7.94 11.18 621 2.99 633 3.20 644 3.41 654 3.63 665 3.85 675 4.07 695 4.52 715 4.96
8.67 12.21 682 3.98 693 4.20 703 4.44 712 4.68 721 4.93 741 5.40 759 5.89
9.39 13.23 742 5.13 752 5.38 761 5.64 769 5.90 788 6.41 805 6.94
10.11 14.24 791 6.20 801 6.47 810 6.73 818 7.01 834 7.57 852 8.11
10.83 15.25 850 7.70 859 7.99 867 8.27 883 8.87 898 9.47
11.55 16.27 908 9.40 916 9.70 932 10.32 946 10.96
12.28 17.30 965 11.30 981 11.95 995 12.62
13.00 18.31 1015 13.06 1030 13.77 1044 14.46
13.72 19.32 1072 15.78 1093 16.50
14.44 20.34 1129 17.98 1142 18.76
TYPICAL MULTISPEED RATING TABLE FOR A SINGLE WIDTH, SINGLE INLET CENTRIFUGAL FAN
TYPICAL MULTISPEED RATING TABLE FOR A SINGLE WIDTH, SINGLE INLET CENTRIFUGAL FAN
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
VOLUME OUTLET
390 RPM
490 RPM
CFM VELOCITY
6885 900 292 .450 317 .579 343 .716 366 .856 389 1.01 411 1.17
7650 1000 314 .560 337 .695 360 .840 332 .992 403 1.15 424 1.31 443 1.48
8415 1100 338 .682 358 .822 378 .981 399 1.144 419 1.31 438 1.48 458 1.60 494 2.04
9180 1200 361 .826 379 .988 398 1.149 417 1.314 436 1.49 455 1.58 472 1.86 507 2.25 540 2.67
9945 1300 335 .988 482 1.163 419 1.340 437 1.514 454 1.69 472 1.89 489 2.09 522 2.49 554 2.92 584 3.37
10710 1400 409 1.175 426 1.360 441 1.553 457 1.741 473 1.93 489 2.12 506 2.34 538 2.76 568 3.28 598 3.66
11475 1500 434 1.387 449 1.587 464 1.78 479 1.995 494 2.19 509 2.40 524 2.61 555 3.06 584 3.52 612 3.99
12240 1600 456 1.626 473 1.837 488 2.048 501 2.269 515 2.49 529 2.70 543 2.92 572 3.49 600 3.87 627 4.36
13005 1700 482 493 2.115 511 2.346 525 2.570 537 2.80 550 3.03 564 3.26 590 3.73 617 4.24 643 4.76
CFM
13770 1800 508 2.19 522 2.424 535 2.665 538 2.901 560 3.15 572 3.40 585 3.84 610 4.12 635 4.63 661 5.18
14535 1900 547 2.767 559 3.017 571 3.276 584 3.52 595 606 4.04 630 4.55 654 5.07 678 5.63
15300 2000 571 3.744 584 3.403 596 607 3.93 618 4.21 629 4.48 651 5.02 674 5.56 696 6.11
16830 2200 629 4.003 633 4.289 644 4.577 654 4.87 665 5.16 675 5.46 695 6.06 715 6.65 736 7.24
18360 2400 682 5.335 693 5.632 703 5.76 712 6.28 721 6.81 741 7.24 759 7.90 778
19890 2600 742 6.885 752 7.22 761 7.56 769 7.91 788 8.60 9.30 822 10.02
21420 2800 791 8.308 801 8.67 810 9.03 818 8.48 834 10.15 852 10.88 867 11.65
22950 3000 850 10.32 859 10.71 867 11.09 883 11.89 898 12.70 914 13.48
24480 3200 908 12.60 916 13.01 932 13.84 946 14.70 960 15.56
26010 3400 965 15.16 981 16.03 995 16.92 1009 17.83
27540 3600 1015 17.52 1030 18.47 1044 19.39 1057 20.35
29070 3800 1079 21.16 1093 22.13 1106 23.12
30600 4000 1129 24.11 1142 25.16 1155 26.18
RECOMMENDED
SELECTION RANGE
PR
ES
SU
RE
PRESSURE
E
RV
CU
SELECTION
NOT USUALLY
EM
RECOMMENDED
ST
SY
IN THIS RANGE
E
RV
CT
CU
DU
EM
ST
T SY
DUC
AIRFLOW
A more through discussion of duct system pressure Notice that on a percentage basis, the same
losses can be found in AMCA Publication 200 Air relationships also hold for System Curves B and C.
Systems. These relationships are characteristic of typical fixed
systems.
200
180
PERCENT OF SYSTEM RESISTANCE
160
C
E M
140
ST
SY
120
100
SYSTEM
80 A DESIGN
M
B
TE POINT
EM
S
SY
ST
60
SY
40
20
0
0 20 40 60 80 100 120 140 160 180 200
Figure 6.2 shows the airflow may be reduced from The greater airflow moved by the fan against the
design Q by increasing the resistance to airflow, i.e., resulting higher system resistance to airflow is a
changing the system curve from System A to System measure of the increased work done. In the same
B. The new operating point is now at Point 2 (the system, the fan efficiency remains the same at all
intersection of the fan curve and the new System B) points on the same system curve.
with the airflow at approximately 80% of Q. Similarly,
the airflow can be increased by decreasing the This is due to the fact that airflow, system resistance,
resistance to airflow, i.e., changing the system curve and required power are varied by the appropriate
from System A to System C. The new operating point ratio of the fan rotational speed.
200
PERCENT OF SYSTEM RESISTANCE
180
EM
C
M
ST
160 E
ST
SY
SY
140
FAN CURVE
120 2
SYSTEM
100 1 DESIGN
POINT
80
3
60 B
T EM
40 SYS
20
0
0 20 40 60 80 100 120 140 160 180 200
Psc = Ps × (Nc/N)2 Qc = Q
Psc = Ps × (ρc/ρ)
Hc = H × (Nc/N)3
Pvc = Pv × (ρc/ρ)
6.6 Effect of density on system resistance
Hc = H × (ρc/ρ)
The resistance of a duct system is dependent upon
the density of the air flowing through the system. An
A
EM
ST
SY
PERCENT OF SYSTEM RESISTANCE
CT
DU
H (AT 1.1N)
160 S (AT 1.1N)
PRESSURE
133
PERCENT OF POWER
140
S (AT N)
PRESSURE
120 2
H (AT N)
100 1
100
80
60
40 50
20
110%
0
0 20 40 60 80 100 120 140 160 180 200
100
SYSTEM A
PERCENT OF SYSTEM
60
40
20
100
PERCENT OF POWER
POWER @ DENSITY ρ
80
60
40
0
0 20 40 60 80 100 120 140 160 180 200
1
FAN PRESSURE
CURVE
DESIGN RESISTANCE
DESIGN AIRFLOW
CURVE B:
ACTUAL SYSTEM
5
CURVE C
ACTUAL SYSTEM
PEAK FAN
PRESSURE 2
ACTUAL SYSTEM
LESS THAN
3 DESIGN
DESIGN RESISTANCE
FAN PRESSURE
CURVE
DESIGN AIRFLOW
72 | Fans and Systems Figure 6.6 - Fan/System Curve Not at Design Point
6.10 Deficient fan/system performance • Include adequate allowance for the effect of all
accessories and appurtenances on the
The most common causes of deficient fan/system performance of the system and the fan. If
performance are improper fan inlet duct design, fan possible, obtain from the fan manufacturer
outlet duct design, and fan installation into the duct data on the effect of installed appurtenances
system. Any one or a combination of these conditions on the fan's performance (See Section 10).
that alter the aerodynamic characteristics of the air
flowing through the fan such that the fan’s full airflow • Use field measurement techniques that can be
potential, as tested in the laboratory and cataloged, is applied effectively on the particular system.
not likely to be realized. Be aware of the probable accuracy of
measurement and conditions that affect this.
Other major causes of deficient performance are: Refer to AMCA Publication 203 Field
Performance Measurement of Fan Systems;
• The air performance characteristics of the for more precise measurement see AMCA
installed system are significantly different from Standard 803 Industrial Process/Power
the system designer's intent (See Figure 6.6). Generation Fans: Site Performance Test
This may be due to a change in the system by Standard. Also, refer to AABC National
others or unexpected behavior of the system Standards, Chapter 8, Volume Measurements,
during operation. Associated Air Balance Council, 5th Edition,
1989.
• The system design calculations did not include
adequate allowances for the effect of accessories 6.12 System Effect
and appurtenances (See Section 10).
Figure 6.7 illustrates deficient fan/system
• The fan selection was made without allowing performance resulting from one or more of the
for the effect of appurtenances on the fan's undesirable airflow conditions listed in Section 6.10.
performance (See Section 10). It is assumed that the system pressure losses, shown
in system curve A, have been accurately determined,
• Dirty filters, dirty ducts, dirty coils, etc., will and a suitable fan selected for operation at Point 1.
increase the system resistance, and However, no allowance has been made for the effect
consequently, reduce the airflow - often of the system connections on the fan's performance.
significantly. To account for this System Effect it will be necessary
to add a System Effect Factor (SEF) to the calculated
• The "performance" of the system has been system pressure losses to determine the actual
determined by field measurement techniques system curve. The SEF for any given configuration is
that have a high degree of uncertainty. velocity dependent and will vary across a range of
airflow. This will be discussed in more detail in
Other "on-site" problems are listed in AMCA Section 7. (See Figure 7.1).
Publication 202 Troubleshooting, which includes
detailed checklists and recommendations for the In Figure 6.7 the point of intersection between the fan
correction of problems with the performance of air performance curve and the actual system curve B is
systems. Point 4. The actual airflow will be deficient by the
difference 1-4. To achieve design airflow, a SEF
6.11 Precautions to prevent deficient equal to the pressure difference between Point 1 and
performance 2 should have been added to the calculated system
pressure losses and the fan selected to operate at
• Use appropriate allowances in the design Point 2. Note that because the System Effect is
calculations when space or other factors velocity related, the difference represented between
dictate the use of less than optimum Points 1 and 2 is greater than the difference between
arrangement of the fan outlet and inlet Points 3 and 4.
connections (See Sections 8 and 9).
The System Effect includes only the effect of the
• Design the connections between the fan and system configuration on the fan's performance.
the system to provide, as nearly as possible,
uniform airflow conditions at the fan outlet and
inlet connections (See Sections 8 and 9).
A System Effect Factor is a value that accounts for Figure 7.1 shows a series of 19 System Effect
the effect of conditions adversely influencing fan Curves. By entering the chart at the appropriate air
performance when installed in the air system. velocity (on the abscissa), it is possible to read
across from any curve (to the ordinate) to find the
SEF for a particular configuration.
CURVE B
ACTUAL SYSTEM
WITH SYSTEM EFFECT
CURVE A
CALCULATED SYSTEM
WITH NO ALLOWANCE
FOR SYSTEM EFFECT
2
AIRFLOW
DEFICIENCY
DESIGN AIRFLOW
500
400 S
SYSTEM EFFECT FACTOR PRESSURE, Pa
300
T
U
200
100
90 W
80
70
60
X
50
40
30
20
2.5 3 4 5 6 7 8 9 10 20 30
3.0
2.5 R
SYSTEM EFFECT FACTOR - PRESSURE, in. wg
2.0
S
1.5
1.0
0.9 U
0.8
0.7
0.6
V
0.5
0.4 W
0.3
0.25
X
0.2
0.15
0.1
5 6 7 8 9 10 15 20 25 30 40 50 60
F 16.00
G 14.20
H 12.70
I 11.40
J 9.50
K 7.90
L 6.40
M 4.50
N 3.20
O 2.50
P 1.90
Q 1.50
R 1.20
S 0.75
T 0.50
U 0.40
V 0.25
W 0.17
X 0.10
2
⎛ V ⎞
SEF = C ⎜ ⎟ ρ
⎝ 1.414 ⎠ SI
2
⎛ V ⎞
SEF = C ⎜ ⎟ ρ
⎝ 1097 ⎠ I-P
In Sections 8 and 9, typical inlet and outlet Alternatively, the SEF may be calculated by the
configurations are illustrated and the appropriate method shown in Table 7.1. Determine the
System Effect Curve is listed for each configuration. configuration being evaluated and use the
If more than one configuration is included in a appropriate loss coefficient, Cp, and application
system, the SEF for each must be determined velocity, V. The SEF can then be calculated using the
separately and the total of these System Effects must equations shown in Table 7.1.
be added to the total pressure losses.
FAN POWER
CALCULATED
ACTUAL SYSTEM RESISTANCE
FAN PRESSURE
DESIGN AIRFLOW
As previously discussed, fans intended primarily for Figure 8.1 shows changes in velocity profiles at
use with duct systems are usually tested with an various distances from centrifugal and axial flow fan
outlet duct in place (See Figure 3.2). In most cases outlets. By definition, 100% "effective duct length" is
it is not practical for the fan manufacturer to supply a minimum of two and one half (2½) equivalent duct
this duct as part of the fan, but rated performance will diameters. For velocities greater than 13 m/s (2500
not be achieved unless a comparable duct is included fpm), add 1 duct diameter for each additional 5 m/s
in the system design. The system design engineer (1000 fpm).
BLAST AREA
DISCHARGE DUCT
OUTLET AREA
CUTOFF
25%
50%
75%
CENTRIFUGAL FAN
100% EFFECTIVE DUCT LENGTH
AXIAL FAN
To calculate 100% duct length, assume a minimum of 2½ duct diameters for 12.7 m/s (2500 fpm) or less. Add 1
duct diameter for each additional 5.08 m/s (1000 fpm).
EXAMPLE: 25.4 m/s (5000 fpm) = 5 equivalent duct diameters. If the duct is rectangular with side dimensions a
and b, the equivalent duct diameter is equal to (4ab/π)0.5.
To determine the applicable SEF, calculate the To effectively transition from a smaller duct size to a
average velocity in the outlet duct and enter the larger duct size it is necessary to use a connection
System Effect Curve (Figure 7.1) at this velocity, piece between the duct sections that allows the
utilizing the appropriate System Effect Curve airstream to expand gradually. This piece is called a
selected from Figure 8.2, then read over horizontally diffuser, or evasé. These terms are used
to the System Effect Factor, Pascals (in. wg) on the interchangeably in the industry. A properly designed
ordinate. evasé has a smooth and gradual transition between
the duct sizes so that airflow is relatively undisturbed.
8.1.2 Centrifugal flow fan - outlet ducts.
Centrifugal fans are sometimes installed with a less An evasé operates on a very simple principle: air
than optimum outlet duct. If it is not possible to use a flowing from the smaller area to the larger area loses
AXIAL FAN
To calculate 100% duct length, assume a minimum of 2½ duct diameters for 12.7 m/s (2500 fpm) or less. Add 1
duct diameter for each additional 5.08 m/s (1000 fpm).
Figure 8.2 - System Effect Curves for Outlet Ducts - Axial Fans
80 | Fans and Systems
velocity as it approaches the larger area, and a See AMCA Publication 200 Air Systems, for an
portion of the change (reduction) in velocity pressure example showing the effect of a diffuser on a duct
is converted into static pressure. This process is exit.
called “static regain”, and is simply defined as the
conversion of velocity pressure to static pressure. 8.3 Outlet duct elbows
The efficiency of conversion (or loss of total pressure)
will depend upon the angle of expansion, the length Values for pressure losses through elbows, which are
of the evasé section, and the blast area/outlet area published in handbooks and textbooks, are based
ratio of the fan. upon a uniform velocity profile at entry into the elbow.
Any non-uniformity in the velocity profile ahead of the
The fan manufacturer will, in most cases, be able to elbow will result in a pressure loss greater than the
provide design information for an efficient diffuser. industry-accepted value.
BLAST AREA
DISCHARGE DUCT
OUTLET AREA
CUTOFF
CENTRIFUGAL FAN
To calculate 100% duct length, assume a minimum of 2½ duct diameters for 2500 fpm or less. Add 1 duct diameter
for each additional 1000 fpm.
EXAMPLE: 5000 fpm = 5 equivalent duct diameters. If the duct is rectangular with side dimensions a and b, the
equivalent duct diameter is equal to (4ab/π)0.5.
Pressure
0% 50% 80% 90% 100%
Recovery
Blast Area
System Effect Curve
Outlet Area
0.4 P R-S U W —
0.5 P R-S U W —
0.6 R-S S-T U-V W-X —
0.7 S U W-X — —
0.8 T-U V-W X — —
0.9 V-W W-X — — —
1.0 — — — — —
Figure 8.3 - System Effect Curves for Outlet Ducts - Centrifugal Fans
Fans and Systems | 81
Since the velocity profile at the outlet of a fan is not 8.3.1 Axial fans - outlet duct elbows. Tubeaxial
uniform, an elbow located at or near the fan outlet will fans with two-piece and four-piece mitered elbows at
develop a pressure loss greater than the industry- varying distances from the fan outlet have a
accepted value. negligible SEF (see Figure 8.4).
The amount of this loss will depend upon the location Vaneaxial fans with two and four-piece mitered
and orientation of the elbow relative to the fan outlet. elbows at varying distances from the fan outlet
In some cases, the effect of the elbow will be to resulted in System Effect Curves as shown in Figure
further distort the outlet velocity profile of the fan. 8.4.
This will increase the losses and may result in such
uneven airflow in the duct that branch- takeoffs near 8.3.2 Centrifugal fans - outlet duct elbows. The
the elbow will not deliver their design airflow. (See outlet velocity of centrifugal fans is generally higher
Section 8.6) toward one or adjacent sides of the rectangular duct.
If an elbow must be located near the fan outlet it
Wherever possible, a length of straight duct should should have a minimum radius-to-duct-diameter ratio
be installed at the fan outlet to permit the diffusion of 1.5, and it should be arranged to give the most
and development of a uniform airflow profile before uniform airflow possible. Figure 8.5 gives System
an elbow is inserted in the duct. If an elbow must be Effect Curves that can be used to estimate the effect
located near the fan outlet then it should be a radius of an elbow at the fan outlet. It also shows the
elbow having a minimum radius-to-duct-diameter reduction in losses resulting from the use of a straight
ratio of 1.5. outlet duct.
% EFFECTIVE
DUCT LENGTH
% EFFECTIVE
DUCT LENGTH
Figure 8.4 - System Effect Curves for Outlet Duct Elbows - Axial Fans
POSITION D
POSITION B
E
C TIV TH
FE G
EF LEN
% CT
DU
INL
ET
POSITION A
Note: Fan Inlet and elbow positions must be oriented as shown for the proper application of the table on the facing
page.
A N O P-Q S
B M-N N O-P R-S
0.4
C L-M M N Q
D L-M M N Q
A O-P P-Q R T
B N-O O-P Q S-T
0.5
C M-N N O-P R-S
D M-N N O-P R-S
A Q Q-R S U
B P Q R T
0.6
C N-O O Q S
A R-S S T V
B Q-R R-S S-T U-V
0.7
C P Q R-S T
D P Q R-S T
A S S-T T-U W
B R-S S T V
0.8
C Q-R R S U-V
D Q-R R S U-V
A T T-U U-V W
B S S-T T-U W
0.9
C R S S-T V
D R S S-T V
A T T-U U-V W
B S-T T U W
1.0
C R-S S T V
D R-S S T V
For DWDI fans determine SEF using the curve for SWSI
fans. Then, apply the appropriate multiplier from the
tabulation below
0.4 7.5
0.5 4.8
0.6 3.3
0.7 2.4
0.8 1.9
0.9 1.5
1.0 1.2
Figure 8.7 - Pressure Drop Multipliers for Volume Control Dampers on a Fan Discharge
Note: Avoid location of split or duct branch close to fan discharge. Provide a straight section of duct to allow for air
diffusion.
a. b. c.
IDEAL SMOOTH ENTRY TO BELL MOUTH INLET PRODUCES VENA CONTRACTA AT INLET
DUCT ON A DUCT SYSTEM FULL FLOW INTO FAN REDUCES EFFECTIVE FAN INLET AREA
d. e.
CONVERGING TAPERED ENTRY FLANGED ENTRY INTO
INTO FAN OR DUCT SYSTEM FAN OR DUCT SYTEM
Figure 9.1 Typical Inlet Connections for Centrifugal and Axial Fans
DUCT LENGTH
DUCT LENGTH
H/T 90° Elbow No Duct [1][2] 0.5D [1][2] 1.0D [1][2] 3.0D
Notes:
[1] Instability in fan operation may occur as evidenced by an increase in pressure fluctuations and sound level.
Fan instability, for any reason, may result in serious structural damage to the fan.
[2] The data presented in Figure 9.2 is representative of commercial type tubeaxial and vaneaxial fans, i.e. 60%
to 70% fan static efficiency.
Figure 9.2 - System Effect Curves for Inlet Duct Elbows - Axial Fans
— N P R-S
Figure 9.4A - Two Piece Mitered 90° Round Section Elbow - Not Vaned
R/D NO 2D 5D
DUCT DUCT DUCT
LENGTH 0.5 O Q S
OF DUCT
D
0.75 Q R-S T-U
+
1.0 R S-T U-V
R
3.0 S T-U V
Figure 9.4B - Three Piece Mitered 90° Round Section Elbow - Not Vaned
R/D NO 2D 5D
DUCT DUCT DUCT
Figure 9.4C - Four or More Piece Mitered 90° Round Section Elbow - Not Vaned
Figure 9.4 - System Effect Curves for Various Mitered Elbows without Turing Vanes
R
1.0 R S-T U-V
1.0 S T-U V
R/D NO 2D 5D
LENGTH H DUCT DUCT DUCT
OF DUCT
0.5 S T-U V
+
R
1.0 T U-V W
Figure 9.5B - Square Elbow with Inlet Transition - 3 Long Turning Vanes
R/D NO 2D 5D
H DUCT DUCT DUCT
LENGTH
OF DUCT
R 0.5 S T-U V
+
1.0 T U-V W
Figure 9.5C - Square Elbow with Inlet Transition - Short Turning Vanes
Figure 9.5 - System Effect Curves for Various Square Duct Elbows
IMPELLER
ROTATION
COUNTER-ROTATING SWIRL
IMPELLER IMPELLER
ROTATION ROTATION
TURNING
VANES
TURNING
VANES
TURNING
IMPELLER
IMPELLER VANES
ROTATION
ROTATION
0.075D
DUCT
0.075D
DUCT DUCT
2D
2L
L L
EQUAL
INLET
DIA.
EQUAL
DIAMETER L
OF INLET
Figure 9.11A - Fans and Plenum Figure 9.11B - Axial Fan Near Wall
L L L L
DWDI SWSI
Figure 9.11C - Centrifugal Fan Near Wall(s) Figure 9.11D - DWDI Fan Near Wall on One Side
Figure 9.11 - System Effect Curves for Fans Located in Plenums and Cabinet
Enclosures and for Various Wall-to-inlet Dimensions
SPLITTER SHEET
Figure 9.12A - Enclosure Inlet Not Figure 9.12B - Flow Condition of Figure 9.12A
Symmetrical with Fan Inlet. Pre- Improved with a Splitter Sheet. Substantial
Rotational Vortex Induced Improvement Would Be To Relocate
Enclosure Inlet as Shown in Figure 9.11A
1 DIA.
MIN
INLET PLANE
R
TE
E NT
AM GE
DI N
TA
OF
INLET PLANE
100 - - - - -
95 - - X W V
90 - X V-W U-V T-U
85 X W-X V-W U-V S-T
75 W-X V U S-T R-S
50 V-W U S-T R-S Q
25 U-V T S-T Q-R P
Cone Type
Variable
Inlet Vanes
Arrangement 3 and 7 fans (see Figure 3.5) require With a belt driven axial flow fan it is usually necessary
that the fan shaft be supported by a bearing and that the fan motor be mounted outside the fan
bearing support in the fan inlet or just adjacent to it. housing (see Figure 3.7 Arrangement 9, and Annex B
Figure B.7).
These components may have an effect on the flow of
air into the fan inlet and consequently on the fan To protect the belts from the airstream, and also to
performance, depending upon the size of the prevent any air leakage through the fan housing,
bearings and supports in relation to the fan inlet manufacturers in many cases provide a belt tube.
opening. The location of the bearing and support, that
is, whether it is located in the actual inlet or "spaced Most manufacturers include the effects of an axial fan
out" from the inlet, will also have an effect. belt tube in their rating tables. In cases where the
effect is not included, the appropriate SEF is
In cases where manufacturer's performance ratings approximated by calculating the percentage of
do not include the effect of the bearings and unobstructed area of air passage way and using
supports, it will be necessary to compensate for this Figure 9.14.
inlet restriction. Use the fan manufacturer's
allowance for bearings in the fan inlet if possible. 10.4 Inlet box
If no better data are available, use the procedures When an inlet box configuration is supplied by the fan
described in Section 9.7 as an approximation. manufacturer, the fan performance should include
the effect of the inlet box.
10.2 Drive guards obstructing fan inlet
The System Effect of fan inlet boxes can vary widely
All fans have moving parts that require guarding for depending upon the design. This data should be
safety in the same way as other moving machinery. available from the fan manufacturer. In the absence
Fans located less than 2.1 m (7 ft) above the floor of fan manufacturer's data, a well-designed inlet box
require special consideration as specified in the should approximate System Effect Curves "S" or "T"
United States’ Occupational Safety and Health Act. of Figure 7.1.
National, federal, state and local rules, regulations,
and codes should be carefully considered and 10.5 Inlet box dampers
followed.
Inlet box dampers may be used to control the airflow
Arrangement 3 and 7 fans may require a belt drive through the system. Either parallel or opposed blades
guard in the area of the fan inlet. Depending on the may be used (see Figure 10.1).
design, the guard may be located in the plane of the
inlet, along the casing side sheet, or it may be The parallel blade type is installed with the blades
"spaced out" due to "spaced out" bearing pedestals. parallel to the fan shaft so that, in a partially closed
position, a forced inlet vortex will be generated. The
In any case, depending on the location of the guard, effect on the fan characteristics will be similar to that
and on the inlet velocity, the fan performance may be of a variable inlet vane control.
significantly affected by this obstruction. It is
desirable that a drive guard located in this position be The opposed blade type is used to control airflow by
furnished with as much opening as possible to allow the addition of pressure loss created by the damper
maximum flow of air to the fan inlet. in a partially closed position.
If available, use the fan manufacturer's allowance for If possible, complete data should be obtained from
drive guards obstructing the fan inlet. SEF for drive the fan manufacturer giving the System Effect of the
guard obstructions situated at the inlet of a fan may inlet box and damper pressure drop over the range of
be approximated using Figure 9.14. application. If data are not available, System Effect
Curves "S" or "T" from Figure 7.1 should be applied
Where possible, open construction on guards is for the inlet box and pressure loss from the damper
recommended to allow free air passage to the fan manufacturer for the damper in making the fan
inlet. Guards and sheaves should be designed to selection.
obstruct, as little of the fan inlet as possible and in no
case should the obstruction be more than 1/3 of the
fan inlet area.
FAN PERFORMANCE
W/OUT VARIABLE INLET VANES
120
100 VARIABLE
INLET VANES
PERCENT OF SHUT-OFF PRESSURE
CONE TYPE 80
VARIABLE INLET
VANES 75% OPEN
60
40
75% OPEN
20
CYLINDRICAL TYPE
VARIABLE INLET
VANES 0 20 40 60 80 100 120
PERCENT OF WIDE OPEN VOLUME
Figure 10.2 - Typical Variable Inlet Vanes for a Backward Inclined Fan
Viscosity:
Absolute (lbm/ft-s) 1.4882 = Pa s (Pa s) 0.6719 = (lbm/ft-s)
Kinematic (ft2/s) 0.0929 = m2/s (m2/s) 10.7639 = ft2/s
Gas Constant (ft lb/lbm-°R) 5.3803 = J-kg/K (j-kg/K) 0.1858 = (ft lb/lbm-°R)
200%
SERIES FAN
COMBINED
PRESSURE
CURVE
100%
SINGLE FAN
PRESSURE
CURVE
100%
PERCENT OF FAN AIRFLOW
M
M
TE
TE
YS
YS
ES
ES
BL
BL
STA
PERCENT OF FAN STATIC PRESSURE
STA
UN
100
SINGLE FAN -
PRESSURE
CURVE
200
PERCENT OF FAN AIRFLOW
AILERON
C.1.3 Barometric pressure. Barometric pressure Wet bulb depression is the difference between dry-
(pb) is the absolute pressure exerted by the bulb and wet-bulb temperatures (td - tw) at the same
atmosphere at a location of measurement (per AMCA location.
99-0066).
C.2 The fan
C.1.4 Pressure-static. Static pressure is the portion
of the air pressure that exists by virtue of the degree C.2.1 Blast area. The blast area of a centrifugal fan
of compression only. If expressed as gauge pressure, is the fan outlet area less the projected area of the
it may be negative or positive (per AMCA 99-0066). cutoff; see Figure B.6 (per AMCA 99-0066).
Static pressure at a specific plane (Psx) is the C.2.2 Inlet area. The fan inlet area (A1) is the gross
arithmetic average of the gauge static pressures as inside area of the fan inlet (see Figure 9.14).
measured at specific points in the traverse of the
plane. C.2.3 Outlet area. The fan outlet area (A2) is the
gross inside area of the fan outlet.
C.1.5 Pressure-velocity. Velocity pressure is that
portion of the air pressure which exists by virtue of C.2.4 Fan. (1) A device, which utilizes a power-drive
the rate of motion only. It is always positive (per rotating impeller for moving air or gases. The internal
AMCA 99-0066). energy (enthalpy) increase imparted by a fan to a gas
does not exceed 25 kJ/kg (10.75 BTU/lbm). (2) A
Velocity pressure at a specific plane (Pvx) is the device having a power-driven rotating impeller
square of the arithmetic average of the square roots without a housing for circulating air in a room (per
of the velocity pressures as measured at specific AMCA 99-0066).
points in the traverse plane.
The volume airflow of a fan (Q) is the rate of airflow
C.1.6 Pressure-total. Total pressure is the air in m3/s (cfm) expressed at the fan inlet conditions.
pressure that exists by virtue of the degree of
compression and the rate of motion. It is the C.2.5 Fan impeller diameter. The fan impeller
algebraic sum of the velocity pressure and the static diameter is the maximum diameter measured over
pressure at a point. Thus if the air is at rest, the total the impeller blades.
pressure will equal the static pressure (per AMCA 99-
0066). C.2.6 Fan total pressure. Fan total Pressure (Pt) is
the difference between the total pressure at the fan
Total pressure at a specific plane (Ptx) is the algebraic outlet and the total pressure at the fan inlet. Pt = Pt1 -
sum of the static pressure and the velocity pressure Pt2 (Algebraic).
at that plane.
Ignoring the losses that exist between the planes of
C.1.7 Standard air density. A density of 1.2 kg/m3 measurement and the fan, Figures C.1, C.2 and C.3
(0.075 lbm/ft3) corresponding approximately to air at illustrate fan total pressures for three basic
20°C (68°F), 101.325 kPa (29.92 in. Hg) and 50% arrangements for fans connected to external
relative humidity (per AMCA 99-0066). systems.
PLANE 1 PLANE 2
Pt2
Pt = Pt2
Figure C.1 - Fan Total Pressure for Installation Type B: Free Inlet, Ducted Outlet
Pt1
Pt = Pv2 - Pt1
Figure C.2 - Fan Total Pressure for Installation Type C: Ducted Inlet, Free Outlet
PLANE 1 PLANE 2
Pt1 Pt Pt2
Pt = Pt2 - Pt1
Figure C.3 - Fan Total Pressure for Installation Type D: Ducted Inlet, Ducted Outlet
Where the fan inlet is open to atmospheric air, (free C.3.3 Fan performance curve. Of the many forms of
inlet, ducted outlet), the fan static pressure (Ps) is fan performance curves, generally all convey
equal to the static pressure at the fan outlet. information sufficient to determine fan performance
as defined above. In this manual, ‘fan performance
Ps = Ps2 curve’ refers to the constant speed performance
PLANE 1 PLANE 2
Pv = Pv2
Pv2
Figure C.4 - Fan Velocity Pressure for Installation Type B: Free Inlet, Ducted Outlet
PLANE 1 PLANE 2
Figure C.5 - Fan Static Pressure for Installation Type D: Ducted Inlet, Ducted Outlet
DIVERTER
FF
TO
CU
CENTER PLATE
BLAST AREA
DISCHARGE
OUTLET AREA
SIDE SHEET
BACKPLATE
BLADE FF
TO
CU
INLET
SCROLL
IMPELLER
FRAME
RIM
BEARING
SUPPORT
INLET COLLAR
BACKPLATE
RIM
HUB INLET
MOTOR BLADE
GUIDE VANE
IMPELLER
INLET BELL
Figure C.7A - Tubular Centrifugal Fan-
Direct Drive
CASING
BLADE
DIFFUSER
HUB
MOTOR
IMPELLER
CASING
BLADE
HUB
GUIDE VANE
Figure C.7C - Vaneaxial Fan-Belt Drive
IMPELLER
SI I-P
Select a fan for Q = 1.42 m3/s (3000 cfm) and Ps = 747 Pa (3.0 in. wg).
996 4
747 3
Pt
Pv
498 2
Ps 124 Pa
249 1 (0.5 in.wg)
0 0
A B C D
ATMOSPHERIC PRESSURE
SI I-P
C-D Outlet duct on fan as tested 0.00 Pa (no SEF) 0.0 in. wg
E Ps energy required to
create velocity at E 124.50 Pa (part of duct system) 0.5 in. wg
Solution:
Select a fan for Q = 1.42 m3/s (3000 cfm) and Ps = 921.30 Pa (3.7 in. wg)
Use manufacturer's data for rpm (N) and power (H).
1245 5
922 Pa (3.7 in.wg)
996 4
747 3 922 Pa Pt
(3.7 in.wg) Pv
498 2 124 Pa
747 Pa (3.0 in.wg) Ps (0.5 in.wg)
249 1
0 0
F
A B C D E ATMOSPHERIC PRESSURE
This example is similar to the plenum effect example The SEF for fans without outlet duct was obtained as
except the duct at the fan outlet has been omitted. follows:
The fan discharges directly into the plenum.
GIVEN:
It may seem unreasonable that the System Effect Blast Area
Fan = 0 .6
loss at the fan outlet is greater than the defined fan Outlet Area
outlet velocity. Fans with cutoffs must generate
higher velocities at the cutoff plane (blast area) than
Fan outlet velocity = 14.4 m/s
in the outlet duct (outlet area). This higher velocity (at
(2830 fpm) No outlet duct
cutoff) is partially converted to Ps when outlet ducts
are used as on fan tests. When fans with cutoffs are System Effect Curve = R-S, (from Figure 8.3)
"bulk-headed" into plenums or discharge directly into SEF = 149.4 Pa (0.6 in. wg), (from Figure 7.1) at 14.4
the atmosphere as with exhausters, all the velocity m/s (2830 fpm) velocity and system curve R)
SI I-P
D Ps energy required to
create velocity at D 124.50 Pa (part of duct system) 0.5 in. wg
Solution:
Select a fan for 1.42 m3/s (3000 cfm) Q and 1070.70 Pa (4.3 in. wg) Ps.
Use manufacturer's data for rpm (N) and power (H).
1245 5
872 Pa (3.5 in.wg)
996 4
747 3
Pt
Pv
498 2 124 Pa
747 Pa (3.0 in.wg) Ps (0.5 in.wg)
249 1
0 0
A B C D ATMOSPHERIC PRESSURE E
SI I-P
A-B Duct friction at 1.42 m3/s (3000 cfm) 747.00 Pa (duct design) 3.0 in. wg
Solution:
Select a fan for 1.42 m3/s (3000 cfm) Q and 1195.2 Pa (4.8 in. wg) Ps
Use manufacturer's data for rpm (N) and power (H).
(I-P) in.wg
ELBOW SEF OBSTRUCTION SEF
149 Pa (0.6 in.wg) 50 Pa (0.2 in.wg)
(SI) Pa
+249 +1
ATMOSPHERIC PRESSURE
0 0
100 Pa (0.4 in.wg)
149 Pa (0.6 in.wg)
-249 -1 REQUIRED
Pt
-847 Pa (-3.4 in.wg)
Pv
-498 -2
Ps -996 Pa (4.0 in.wg)
-747 -3
224 Pa (0.9 in.wg)
-996 -4
-1245 -5
-1171 Pa (4.7 in.wg)
-971 Pa (3.9 in.wg)
A B C D E
-1121 Pa (4.5 in.wg)
FAN INLET
1. ANSI/AMCA 210-99, Laboratory Methods of Testing Fans for Aerodynamic Performance Rating, Air Movement
and Control Association International, Inc., 30 West University Drive, Arlington Heights, IL, 60004-1893 U.S.A.,
1999.
2. AMCA Publication 200-95, Air Systems, Air Movement and Control Association International, Inc., 30 West
University Drive, Arlington Heights, IL, 60004-1893 U.S.A., 1995.
3. AMCA Publication 202-98, Troubleshooting, Air Movement and Control Association International, Inc., 30 West
University Drive, Arlington Heights, IL, 60004-1893 U.S.A., 1997.
4. ASHRAE Handbook, HVAC Systems and Equipment, 1996, The American Society of Heating, Refrigerating
and Air Conditioning Engineers, Inc., 1791 Tullie Circle N.E., Atlanta, GA, 30329 U.S.A., 1996, (Chapter 18
Fans).
5. Traver, D. G., System Effects on Centrifugal Fan Performance, ASHRAE Symposium Bulletin, Fan Application,
Testing and Selection, The American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc.,
1791 Tullie Circle N.E., Atlanta, GA, 30329 U.S.A., 1971.
6. Christie, D. H., Fan Performance as Affected By Inlet Conditions, ASHRAE Transactions, Vol. 77, The
American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc., 1791 Tullie Circle N.E.,
Atlanta, GA, 30329 U.S.A., 1971.
7. Zaleski, R. H., System Effect Factors For Axial Flow Fans, AMCA Paper 2011-88, AMCA Engineering
Conference, Air Movement and Control Association International, Inc., 30 West University Drive, Arlington
Heights, IL, 60004-1893 U.S.A., 1988.
8. Roslyng, O., Installation Effect on Axial Flow Fan Caused Swirl and Non-Uniform Velocity Distribution,
Institution of Mechanical Engineers (IMechE), 1 Birdcage Walk, London SW1H 9JJ, England, 1984.
9. Clarke, M. S., Barnhart, J. T., Bubsey, F. J., Neitzel, E., The Effects of System Connections on Fan
Performance, ASHRAE RP-139 Report, The American Society of Heating, Refrigerating and Air Conditioning
Engineers, Inc., 1791 Tullie Circle N.E., Atlanta, GA, 30329 U.S.A., 1978.
10. Madhaven, S., Wright, T., J. DiRe, Centrifugal Fan Performance With Distorted Inflows, The American Society
of Mechanical Engineers, 345 East 47th Street, New, York, NY, 10017 U.S.A., 1983.
11. Cory, W. T. W., Fan System Effects Including Swirl and Yaw, AMCA Paper 1832-84-A5, AMCA Engineering
Conference, Air Movement and Control Association International, Inc., 30 West University Drive, Arlington
Heights, IL, 60004-1893 U.S.A., 1984.
12. Cory, W. T. W., Fan Performance Testing and Effects of the System, AMCA Paper 1228-82-A5, AMCA
Engineering Conference, Air Movement and Control Association International, Inc., 30 West University Drive,
Arlington Heights, IL, 60004-1893 U.S.A., 1984.
14. Industrial Ventilation –23rd Edition, American Conference of Governmental Industrial Hygienists, 1330 Kemper
Meadow Drive, Cincinnati, OH 45240-1634 U.S.A., 1998.
15. Fans and Systems, John E. Thompson and C. Jack Trickler, The New York Blower Company, Chemical
Engineering, March 21, 1983, pp. 48-63
16. AABC National Standards, Chapter 8, Volume Measurements, Associated Air Balance Council, 1518 K Street
NW, Suite 503, Washington, DC 20005 U.S.A.
120 | Fans and Systems
Troubleshooting 202
1. Introduction
After the installation of an air moving system is completed, a system sometimes fails to achieve its designed
performance.
This part of the AMCA Fan Application Manual will help you identify what is wrong and decide how to correct it.
2.1 Look in the "Master Troubleshooting Appendices" for a subject which corresponds with the apparent problem.
2.3 If the cause of the trouble is not found proceed through the "System Checklist" (see Section 4).
2.4 If the problem has still not been solved, it is now advisable to contact the representative of the fan manufacturer.
He should be given the results of the "System Checklist" and the additional information listed in Section 5.1.
2.5 The fan manufacturer or his representative will analyze the information submitted, as outlined in Section 5.2.
With this information and, if necessary, an on-site inspection, he may be able to explain why the system is not
achieving its design performance and may recommend changes in the system or the fan installation which will
overcome the problem.
3. Safety Precautions
Before checking the fan and system it will be necessary to shut down the fan. During inspection the fan must be
electrically isolated and all disconnect switches and other controls LOCKED in the "OFF" position. Where these
are in locations remote from the fan, prominent DO NOT START signs should also be in place.
CAUTION - Even when LOCKED out electrically, fans located outdoors or in a parallel or series fan system may
be subject to "wind-milling." Therefore, as an added precaution, the impeller should be secured to physically restrict
rotational movement.
4. System Checklist
A systematic check of the items listed here should help identify the problem - or problems - and allow suitable
corrective action to be taken.
SYSTEM CHECKLIST
A) While the impeller is coasting to a stop, see if it is rotating in the proper direction (see Figures 4.1, 4.2 and
4.3).
B) Make certain the impeller rotation is correct for the housing (guide vanes of vaneaxial and tubular centrifugal
fans) and not installed backwards (see Figures 4.1, 4.2, and 4.3).
Note: Tubeaxial fan rotation is the same as shown in Figure 4.2 except without the guide vanes.
ROTATION
Note: Fan manufacturers describe the rotation of the fan impeller as being "clockwise" or "counterclockwise”.
• For AXIAL fans when viewing the INLET or OUTLET as specified by the Fan Manufacturer
• For CENTRIFUGAL fans when viewing the DRIVE SIDE (see AMCA Standard 99-2406)
• For TUBULAR CENTRIFUGAL fans when viewing the OUTLET (see AMCA Standard 99-2410).
122 | Troubleshooting
ROTATION ROTATION
INLET
GUIDE VANES
OUTLET
GUIDE VANES
AIRFLOW AIRFLOW
ROTATION
GUIDE
VANES AIRFLOW
Troubleshooting | 123
C) If the fan is belt driven:
1) Are the drive pulley (Motor Sheave) and the driven pulley (Fan Sheave) in alignment? Improper alignment
of the sheaves can cause excessive power consumption (high amperage), squealing belts, shortened belt
and sheave life and high axial vibration.
FAN FAN
MOTOR MOTOR
2) Are the belts loose? Loose belts that flap or slip can cause excessive noise and vibration. Slipping belts
will also affect fan speed and reduce belt and sheave life.
Belts should be tensioned to the belt manufacturer's recommendations. Tension of the drive belts should be
adjusted for stretching after the first 48 hours of operation. Caution! Excessive belt tension will reduce fan
and motor bearing life.
3) Are the belts and/or sheaves worn? If so, an immediate replacement could save down time at a later
date. Where more than one belt is used, replace with a new set of matched belts.
D) Check the flow surfaces (passages between the inlets, impeller blades and inside of housing) for
cleanliness. A 2 mm (0.0625 in.) buildup of dirt on the flow surface could impair fan performance and/or
cause vibration.
E) Are there any gouges, tears, holes, erosion or corrosion in the impeller blades, rims or backplate: inlets
and/or housing? If so, report the approximate size and location to the fan manufacturer and discontinue
operation until repairs are made.
F) Is any foreign matter trapped in the impeller, housing or ductwork (loose insulation, papers, ice, etc.)? If so,
remove.
124 | Troubleshooting
G) Are coils, heaters, filters, ducts, etc. dirt laden? If so, clean or replace. Remove any non-essential
obstructions to airflow in elbows, shutters, transformations, dampers, bird-screens, etc. Verify that all
dampers (control, backdraft, fire, etc.) are adjusted to the proper settings.
H) Have all the parts supplied with the fan been installed?
I) Are there any obstructions to airflow near the fan inlets? Objects such as pipes, airflow measurement
stations, ductwork, columns, belt guards, belt drives, etc. could adversely affect the output of the fan. For
more information, see AMCA Publication 201 Fans and Systems.
J) Are the fan outlet connections correctly designed and installed? Duct takeoffs, or obstructions in the fan
outlet could adversely affect the output of the fan (see AMCA Publication 201).
K) See Figure 4.6A for typical centrifugal fan inlet-impeller relationships and Figure 4.6A for typical axial fan
housing-impeller relationships. A few simple measurements as indicated on these figures can tell the
manufacturer if a problem exists in this area. Note: several measurements should be taken around the
entire inlet/housing circumference to determine the average, maximum and minimum values.
I.S. I.S.
I.S. SHOULD BE SAME BOTH SIDES
FOR DOUBLE WIDTH FAN
R.C. C.
C. = VANE CLEARANCE
Troubleshooting | 125
L) On a double-width fan, is the approach to both inlets identical? Airflow should be symmetrical about the
centerline of the fan housing (see Figure 4.7A). Non-symmetrical airflow can lead to decreased air
performance. Belt drives, belt guards and motors can cause non-symmetrical airflow to the inlets if too
severely restricted (see AMCA Publication 201).
L L
P AIRFLOW
L NOT EQUAL TO M
L M
N NOT EQUAL TO R
N AIRFLOW
M) Are turning vanes installed in elbows that are too close to the fan inlet or discharge (see Figures 4.8A and
4.8B). Published pressure losses through elbows are based on a uniform velocity profile. Turning vanes
help achieve this uniform flow (see AMCA Publication 201).
126 | Troubleshooting
Figure 4.8B - Turning Vanes in Elbow Adjacent to Axial Fan
N) If the fan is equipped with an inlet vane damper, check the operation as follows:
1) Do not rely on the control arm position alone for locating the position of the inlet vane damper blades
without first checking visually to see that the inlet vane damper position agrees with the position of the
control arm.
2) If the unit is a double-width fan equipped with inlet vanes or inlet vane damper control, both inlet vane
dampers must be synchronized (the inlet vane dampers must be in the same relative position with
respect to the impeller on both inlets). If the inlet vane dampers are not synchronized, there will be
unbalanced airflow between inlets resulting in deficient air performance, unbalanced thrust on the
bearings and/or a surge condition in the fan.
3) Make certain that inlet vane dampers are of the proper rotation with respect to the impeller.
As the vanes close they should cause the entering air to spin in the same direction as the impeller.
4) Are the inlet vane dampers correctly positioned for the design operating conditions? If not, the desired
pressure-volume of the fan will not be realized (see Figure 4.9).
100% Open
100
75% Open
Percent of No Delivery Pressure
50% Open
80
60
25% Open
40
20
0 20 40 60 80 100
Figure 4.9 - Typical Pressure-Volume Curve for Operation with Inlet Vane Damper Control
Troubleshooting | 127
O) Inspect any ductwork or plenums approaching the fan inlets for the possibility of inducing swirl of air into the
inlet. Pre-swirl of air entering the fan inlet can reduce the fan performance (see Figures 4.10A and 4.10B).
(See AMCA Publication 201.)
IMPELLER IMPELLER
ROTATION ROTATION
P) After completing the above steps and making sure the fan and system are safe to start, remove all DO NOT
START signs on disconnect switches and override systems and put the unit back into operation.
Q) Inspect the entire system including the fan, fan plenum and all ductwork for significant air leaks.
Air leaks may be detected by sound, smoke, feel, soapy solution, etc. Some common air leak sources are:
access doors, coils, duct seams, fan outlet connection, etc. Significant air leaks must be sealed.
If the cause of the trouble has still not been found after completing the "System Checklist," the fan manufacturer
should be consulted.
The fan manufacturer will review the information provided concerning the system and recommend an appropriate
course of action.
To make a complete analysis of the problem, in addition to the results of the "System Checklist," the manufacturer
will need:
A) Complete plans (drawings) including all ductwork, location, size, model and manufacturer of all fans,
motors, coils, dampers, etc. with all pertinent dimensions for the complete system as actually installed.
B) If the fan/air handling system fails to achieve the design performance, the measured performance and the
design performance figures should be supplied.
128 | Troubleshooting
E) If a separate air performance test has been conducted on the installed fan, a statement of measured fan
performance along with a copy of the test data, the type of test and instrumentation, and the measurement
location of the airflow rate and pressure determinations should be supplied. A statement of fan performance
should contain:
3) Power (H)
A) Assess the probable accuracy of the field performance measurements (see AMCA Publication 203 Field
Performance Measurements of Fan Systems).
B) Examine the system drawings (plans) for any System Effect losses (see AMCA Publication 201) which were
not allowed for in the system design calculations or the original fan selection.
C) Reassess the fan performance, accounting for System Effect losses established in step B to the designed
fan/system performance (see Figure 5.1).
SYSTEM EFFECT
FAN CATALOG
PRESSURE-VOLUME CURVE
DESIGN PRESSURE
DESIGN VOLUME
Figure 5.1
Troubleshooting | 129
The information obtained through the checklists in this manual should help in defining the necessary corrective
action.
In most cases, if the troubleshooting procedure has been followed carefully and impartially it will be apparent
whether the system has been built and installed in accordance with the design drawings, whether the fan was
properly selected and suitable allowances made for the appropriate System Effect Factors, or whether the fan is
not performing up to its published ratings.
6. Conclusion
By intelligent application of the procedures outlined in this manual it should be possible to find the cause of a
performance problem in any air moving system.
Identification of a problem associated directly with the fan may require the assistance of the fan manufacturer.
Recognition of the cause of the trouble will usually be a major step toward curing it. Corrective measures may
include alterations to the system, modifications to the fan outlet or inlet connections, adjustments to the fan, etc.
In many cases an increase in the fan speed may be decided upon but it is extremely important that the fan shall
not be operated above its cataloged maximum speed or the maximum speed recommended by the
manufacturer. Excessive speed may result in catastrophic impeller failure. If a speed increase proves to be
an acceptable alternative, then the motor should also be checked for its capacity to handle the increased fan power.
130 | Troubleshooting
MASTER TROUBLESHOOTING APPENDICES
Annex A. Noise
A-1 IMPELLER HITTING INLET OR HOUSING . . . . . . . . . . . . . a. Impeller not centered in inlet or housing.
b. Inlet or housing damage.
c. Crooked or damaged impeller.
d. Shaft loose in bearing.
e. Impeller loose on shaft.
f. Bearing loose in bearing support.
g. Bent shaft.
h. Misaligned shaft and bearings.
132 | Troubleshooting
e. Inlet vortex surge.
f. Distorted inlet airflow.
Troubleshooting | 133
Annex B. Insufficient Air Flow
134 | Troubleshooting
SPEED, MONITOR MOTOR AMPS SO
AS NOT TO EXCEED MOTOR
NAMEPLATE AMPS.
B-7 NO STRAIGHT DUCT AT FAN OUTLET . . . . . . . . . . . . . . . a. Fans which are normally used in duct
system are tested with a length of
straight duct at the fan outlet. If there is
no straight duct at the fan outlet,
decreased performance may result. If it
is not practical to install a straight
section of duct at the fan outlet, the fan
speed may need to be increased to
overcome this pressure loss (see
System Effects in AMCA Publication
201).
CAUTION! DO NOT INCREASE FAN
SPEED BEYOND THE FAN MANUFA-
CTURER'S RECOMMENDATIONS.
ALSO, WHEN INCREASING FAN
SPEED, MONITOR MOTOR AMPS SO
AS NOT TO EXCEED MOTOR
NAMEPLATE AMPS.
B-8 OBSTRUCTION IN HIGH VELOCITY AIR STREAM . . . . . . a. Obstruction near fan outlet or inlet(s).
b. Sharp elbows near fan outlet or inlet(s).
c. Improperly designed turning vanes.
d. Projections, dampers or other
obstruction in a part of the system
where air velocity is high.
Troubleshooting | 135
Annex C. Airflow High - (Too Much Airflow)
136 | Troubleshooting
Annex D. Static Pressure Wrong
Troubleshooting | 137
D-5 FAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . a. Impeller installed backwards.
b. Impeller running backwards.
c. Improper impeller blade angle.
d. Cutoff missing or improperly installed.
e. Impeller not centered with inlet collar(s).
f. Fan speed too slow.
g. Impeller/inlet dirty or clogged.
h. Improper running clearance.
i. Improper inlet cone to impeller fit.
j. Improperly set inlet vanes or damper.
138 | Troubleshooting
Annex E. Power High
Troubleshooting | 139
Annex F. Fan Does Not Operate
a. Blown fuses.
b. Broken belts.
c. Loose pulleys.
d. Electricity turned off.
e. Impeller touching housing.
f. Wrong voltage.
g. Motor too small and overload protector
has broken circuit.
h. Low voltage, excessive line drop or
inadequate wire size.
i. Load inertia too large for motor.
j. Seized bearing.
140 | Troubleshooting
Annex G. Premature Failure
Troubleshooting | 141
Annex H. Vibration
MECHANICAL VIBRATION
142 | Troubleshooting
H-5 FAN SUPPORT STRUCTURE . . . . . . . . . . . . . . . . . . . . . . . a. Support structure natural frequencies.
b. Insufficient mass or stiffness.
c. Large unsupported mass.
d. Lack of lateral support, particularly with
fans mounted on isolators.
e. Fan skewed (bolted down to uneven
surface).
f. Broken support members.
g. Short-circuited or improperly adjusted
isolators.
h. Fan (mounted on isolators) with rigid
inlet(s) and outlet connections.
Troubleshooting | 143
Field Performance
Measurements of Fan Systems 203
1. Introduction 2. Scope
Performance ratings of fans are developed from The recommendations and examples in this
laboratory tests made according to specified publication may be applied to all types of centrifugal,
procedures on standardized test setups. In North axial, and mixed flow fans in ducted or nonducted
America, the standard is ANSI/AMCA Standard 210 / installations used for heating, ventilating, air
ANSI/ASHRAE 51 Laboratory Methods of Testing conditioning, mechanical draft, industrial process,
Fans for Rating. exhaust, conveying, drying, air cleaning, dust
collection, etc. Although the word air is used when
In actual systems in the field, very few fans are reference is made in the general sense to the
installed in conditions reproducing those specified in medium being handled by the fan, gases other than
the laboratory standard. This means that, in air are included in the scope of this publication.
assessing the performance of the installed fan-
system, consideration must be given to the effect on Measurement of sound, vibration, and stress levels
the fan’s performance of the system connections, are not within the scope of this publication.
including elbows, obstructions in the path of the
airflow, sudden changes of area, etc. The effects of 3. Types of Field Tests
system conditions on fan performance is discussed in
Section 5, and more completely in AMCA Publication There are three general categories of field tests:
201, Fans and Systems.
A) General Fan System Evaluation -
A major problem of testing in the field is the difficulty A measurement of the fan-system’s performance
of finding suitable locations for making accurate to use as the basis of modification or adjustment
measurements of flow rate and pressure. Sections of the system.
9.3 and 10.3 outline the requirements of suitable
measurement sections. B) Acceptance Test -A test specified in the sales
agreement to verify that the fan is achieving the
Because these problems and others will require specified performance.
special consideration on each installation, it is not
practical to write one standard procedure for the C) Proof of Performance Test -A test in response
measurement of the performance of all fan-systems to a complaint to demonstrate that the fan is
in the field. This publication offers guidelines to meeting the specified performance requirement.
making performance measurements in the field
which are practical and flexible enough to be applied As acceptance and proof of performance tests are
to a wide range of fan and system combinations. related to contract provisions, they are usually
subject to more stringent requirements and are
Because of the wide variety of fan types and systems usually more costly than a general evaluation test. In
encountered in the field, Annex A includes examples the case of large fans used in industrial applications
of a number of different field tests. In most cases, and of mechanical draft fans used in the electrical
these examples are based on actual tests which have power generation industry the performance of a field
been conducted in the field. test may be part of the purchase agreement between
the fan manufacturer and the customer. In addition to
Before performing any field test, it is strongly Publication 203, AMCA Standard 803 Site
recommended that the following AMCA publications Performance Test Standard-Power Plant and
be carefully reviewed: Industrial Fans defines the conditions which must be
met to achieve higher accuracy of measurement. In
AMCA Publication 200 - Air Systems new installations of this type, it is desirable to include
AMCA Publication 201 - Fans and Systems a suitable measuring section in the design.
AMCA Publication 202 - Troubleshooting Agreement must be reached on the test method to be
AMCA Standard 210 - Laboratory Methods of Testing used prior to performance of the test.
Fans for Rating
4. Alternatives to Field Tests Examples of the application of SEFs in determining
the results of field tests are included in Annex A.
In some cases, considerations such as cost and
problems of making accurate measurements may In field tests of fan-system installations in which
make the following alternative methods of testing system effects have not been accounted for, it is
worth investigation: important that their sources be recognized and their
magnitudes be established prior to testing.
A) Testing the fan before installation in a laboratory
equipped to perform tests in accordance with The alternative to dealing with a large magnitude
AMCA Standard 210. Limitations in laboratory SEF is to eliminate its source. This requires revisions
test facilities may preclude tests on full size fans. to the system. This alternative course of action is
In this case, the full size fan can be tested at the recommended when swirl exists at the fan inlet (see
installation site in accordance with AMCA Publication 201, Figure 9.8). The effect on fan
Standard 210. This will usually require the performance as a result of swirl at the inlet is
installation of special ductwork. impossible to estimate accurately as the system
effect is dependent upon the degree of swirl. The
B) Testing a reduced scale model of the fan in effect can range from a minor amount to an amount
accordance with AMCA Standard 210 and that results in the fan-system performance being
determining the performance of the full size fan completely unacceptable.
as described in AMCA Publication 802, Power
Plant Fans – Establishing Performance Using 6. Fan Performance
Laboratory Methods.
Fan performance is a statement of fan flow rate, fan
C) Testing a reduced scale model of the complete total or static pressures, and fan power input at stated
fan and system using the test methods outlined fan speed and fan air density. Fan total or static
in this publication. efficiencies may be included. The fan air density is
the density at the fan inlet. The fan flow rate is the
Tests conducted in accordance with AMCA Standard volume flow rate at the fan inlet density.
210 will verify the performance characteristics of the
fan but will not take into account the effect of the 7. Referenced Planes
system connections on the fan’s performance (see
Section 5). Certain locations within a fan-system installation are
significant to field tests. These locations are
5. System Effect Factors designated as follows:
AMCA Publication 201, Fans and Systems, deals in Plane 1: Plane of fan inlet
detail with the effect of system connections on fan Plane 2: Plane of fan outlet
performance. It gives system effect factors for a wide Plane 3: Plane of Pitot-static tube traverse for
variety of obstructions and configurations which may purposes of determining flow rate
affect a fan’s performance. Plane 4: Plane of static pressure measurement
upstream of fan
System Effect Factor (SEF) is a pressure loss which Plane 5: Plane of static pressure measurement
recognizes the effect of fan inlet restrictions, fan downstream of fan
outlet restrictions, or other conditions influencing fan
performance when installed in the system. The use of the numerical designations as subscripts
indicate that the values pertain to those locations.
SYSTEM EFFECT FACTORS (SEFs) ARE
INTENDED TO BE USED IN CONJUNCTION WITH
THE SYSTEM RESISTANCE CHARACTERISTICS
IN THE FAN SELECTION PROCESS. Where SEFs
are not applied in the fan selection process, SEFs
must be applied in the calculations of the results of
field tests. This is done for the purpose of allowing
direct comparison of the test results to the design
static pressure calculation. Thus, for a field test, the
fan static pressure is defined as:
A Area of cross-section ft2 Determine fan flow rate using the area, velocity
D Diameter ft pressure, and density at the traverse plane and the
De Equivalent diameter ft density at the fan inlet. The velocity pressure at the
FLA Full load amps amps traverse plane is the root mean square of the velocity
H Fan power input hp pressure measurements made in a traverse of the
HL Power transmission loss hp plane. The flow rate at the traverse plane is
Hmo Motor power output hp calculated by converting the velocity pressure to its
kW Electrical power kilowatts equivalent velocity and multiplying by the area of the
L Length ft traverse plane.
N Speed of rotation rpm
NLA No load amps amps 9.2 Velocity measuring instruments
NPH Nameplated horsepower hp
NPV Nameplated volts volts Use a Pitot-static tube of the proportions shown in
Ps Fan static pressure in. wg Annex B or a double reverse tube, shown in Annex C,
Psx Static pressure at Plane x in. wg and an inclined manometer to measure velocity
Pt Fan total pressure in. wg pressure. The velocity pressure at a point in a gas
stream is numerically equal to the total pressure
Ptx Total pressure at Plane x in. wg
diminished by the static pressure. The Pitot-static
Pv Fan velocity pressure in. wg
tube is connected to the inclined manometer as
Pvx Velocity pressure at Plane x in. wg shown in Annex F. The double reverse tube is
pb Barometric pressure in. Hg connected to the inclined manometer as shown in
pe Saturated vapor pressure at tw in. Hg Annex C.
pp Partial vapor pressure in. Hg
px Absolute pressure at Plane x in. Hg 9.2.1 Pitot-static tube. The Pitot-static tube is
Q Fan flow rate cfm considered to be a primary instrument and need not
Qi Interpolated flow rate cfm be calibrated if maintained in the specified condition.
Qx Flow rate at Plane x cfm It is suited for use in relatively clean gases. It may be
SEF System effect factor in. wg used in gases that contain moderate levels of
T Torque lb-in. particulate matter such as dust, water, or dirt,
td Dry-bulb temperature °F provided certain precautions are employed (see
tw Wet-bulb temperature °F Section 15).
V Velocity fpm
9.2.2 Double reverse tube. The double reverse tube
∆Px,x’ Pressure loss between
is used when the amount of particulate matter in the
Planes x and x’ in. wg gas stream impairs the function of the Pitot-static
∆Ps Pressure loss across damper in. wg tube. The double reverse tube requires calibration. It
ρ Fan gas density lbm/ft3 is important that the double reverse tube be used in
ρx Gas density at Plane x lbm/ft3 the same orientation as used during calibration. Mark
Σ Summation sign --- the double reverse tube to indicate the direction of
Airflow direction --- the gas flow used in its calibration.
60%
80%
40% 35%
20% 35%
De
MIN.
2
12 in. MIN.
4YZ
WHERE: De =
π INLET BOX DAMPERS
Z
Note: The measurement plane should be located a minimum of ½ De from the inlet cone, but not less than 12 in.
from the leaving edge of the damper blades.
Figure 9.2
STACK
VELOCITY
PROFILE
Note: Spiral vortex may form when fan discharges directly into a stack or similar arrangement.
Figure 9.3
150 | Field Performance Measurement
traverse plane should be situated a sufficient equivalent diameters from the inlet of the duct.
distance downstream from the fan to allow the flow to Where the duct is small, its length may
diffuse to a more uniform velocity distribution and to necessarily be greater than 2 equivalent
allow the conversion of velocity pressure to static diameters in order to ensure that the tip of the
pressure. Annex P provides guidance for the location Pitot-static tube is a minimum of 1½ equivalent
of the traverse plane in these cases. The location of diameters from the duct inlet. This short length of
the traverse plane on the inlet side of the fan should duct should produce no significant addition to the
not be less than ½ equivalent diameter from the fan system resistance, but in some cases it may alter
inlet. Regions immediately downstream from elbows, the pattern of flow into the fan impeller, and
obstructions and abrupt changes in airway area are thereby affect the performance of the fan slightly.
not suitable traverse plane locations. Regions where
unacceptable levels of swirl are usually present, such 9.4 The traverse
as the region downstream from an axial flow fan that
is not equipped with straightening vanes, should be Annex H contains recommendations for the number
avoided. Swirl may form when a fan discharges and distribution of measurement points in the
directly into a stack or similar arrangement (see traverse plane. If the flow conditions at the traverse
Figure 9.2). plane are less than satisfactory, increase the number
of measurement points in the traverse to improve
9.3.1 Inlet box location. When the traverse plane accuracy.
must be located within an inlet box, the plane should
be located a minimum of 12 inches downstream from Since the flow at a traverse plane is never strictly
the leaving edges of the damper blades and not less steady, the velocity pressure measurements
than ½ equivalent diameter upstream from the edge indicated by the manometer will fluctuate. Each
of the inlet cone (see Figure 9.3). Do not locate velocity pressure measurement should be mentally
traverse points in the wake of individual damper averaged on a time-weighted basis. Any velocity
blades. In the case of double inlet fans, traverses pressure measurement that appears as a negative
must be conducted in both inlet boxes in order to reading is to be considered a velocity pressure
determine the total flow rate. measurement of zero and included as such in the
calculation of the average velocity pressure.
9.3.2 Alternative locations. On occasion, an
undesirable traverse plane location is unavoidable, or When it is necessary to locate the traverse plane in a
each of a limited number of prospective locations converging or diverging airway, orient the nose of the
lacks one or more desirable qualities. In such cases, Pitot-static tube such that it coincides with the
the alternatives are: anticipated line of the flow stream. This is particularly
important at measurement points near the walls of
1) Accept the most suitable location and evaluate the airway (see Annex A-1A).
the effects of the undesirable aspects of the
location on the accuracy of the test results. In No appreciable effect on Pitot-static tube readings
some instances, the estimated accuracy may occur until the angle of misalignment between the
indicate that the results of the test would be airflow and the tube exceeds 10 degrees.
meaningless, particularly in acceptance tests and
proof of performance tests. 9.5 Flow rate calculations
2) Provide a suitable location by modifying the 9.5.1 Flow rate at traverse plane. The flow rate at
system. This course of action is recommended the traverse plane is calculated as follows:
for acceptance tests and proof of performance
tests. The modifications may be temporary, Q3 = V3A3
permanent, minor or extensive, depending on the
specific conditions encountered. When the inlet Where:
side of the fan is not ducted but is designed to
accept a duct, consider installing a short length of A3 = the area of the traverse plane
inlet duct to provide a suitable traverse plane V3 = the average velocity at the traverse plane
location. This duct should be of a size and shape
= 1096 (Pv3/ρ3)0.5
to fit the fan inlet, a minimum of 2 equivalent
diameters long and equipped with a bell shaped ρ3 = the density at the traverse plane
or flared fitting at its inlet. The traverse plane Pv3 = the root mean square velocity pressure at the
should be located a minimum of ½ equivalent traverse plane
diameters from the fan inlet and not less than 1½ = [∑(Pv3r)0.5 / number of readings]2
ρ1 = the density at the fan inlet In addition to low range velocities, other conditions
may exist at the traverse plane which can
significantly affect the accuracy of the flow rate
9.5.4 Fan flow rate, multiple traverse planes.
determination. These include nonuniform velocity
When it is necessary to use more than one traverse
distribution, swirl, and other mass turbulence.
plane in order to account for the total flow:
Improve the accuracy of the flow rate determination
by avoiding these conditions in the selection of the
Q = Q1
traverse plane location, or improve the conditions by
= Q3a (ρ3a/ρ1) + Q3b (ρ3b/ρ1) + ... + Q3n (ρ3n/ρ1)
modifying the system.
This section describes only the instruments for use in When a system component is situated between the
measuring static pressure. Instruments for use in the measurement plane and the plane of interest, the
other measurements involved in the determination of pressure loss of the component must be calculated
fan static pressure are described in Section 13. and credited to the fan. The calculation of the
pressure loss is usually based on the component’s
Use a Pitot-static tube of the proportions shown in performance ratings, which may be obtained from the
Annex B, a double reverse tube as shown in Annex manufacturer of the item.
C, or a side wall pressure tap as shown in Annex E,
and a manometer to measure static pressure. If there is a change in area between the
measurement plane and the plane of interest, then
10.2.1 Pitot-static tube. The comments that appear the calculation of the static pressure at the plane of
in Section 9.2 regarding the use and calibration of the interest must account for velocity pressure
Pitot-static tube are applicable to its use in the conversion and include any associated pressure
measurement of static pressures. loss. When the change in area is moderate and
gradual, the conversion of velocity pressure is
10.2.2 Double reverse tube. The double reverse considered to occur without loss and the static
tube cannot be used to measure static pressure pressure is calculated on the basis of no change in
directly. It must be connected to two manometers and total pressure between the measurement plane and
the static pressure for each point of measurement the plane of interest. This assumes that the duct
must be calculated. Both the manometer connections friction loss between the two planes is negligible.
and the method of calculation are shown in Annex C. When the change in area is an abrupt and sizable
enlargement, as in a duct leading into a large
10.2.3 Pressure tap. The pressure tap does not plenum, the loss is considered to be equivalent to the
require calibration. Use no fewer than four taps velocity pressure in the smaller area, and the static
located 90 degrees apart. In rectangular ducts, a pressure at the plane of interest is considered to be
pressure tap should be installed near the center of the same as the static pressure at the measurement
each wall. It is important that the inner surfaces of the plane. This assumes that the velocity pressure in the
duct in the vicinities of the pressure taps be smooth larger area and the duct friction loss are negligible.
and free from irregularities, and that the velocity of
the gas stream does not influence the pressure 10.3.1 Location of the measuring plane. When the
measurements. fan is ducted outlet, the static pressure measurement
plane downstream of the fan should be situated a
10.2.4 Manometers. A manometer with either sufficient distance from the fan outlet to allow the flow
vertical or inclined indicating column may be used to to diffuse to a more uniform velocity distribution and
measure static pressure. Inclined manometers used to allow the conversion of velocity pressure to static
to measure static pressures require calibration and pressure. See Annex P for guidance in locating the
should be selected for the quality, range, slope, scale measurement plane in these cases. In general,
graduations, and indicating fluid necessary to pressure taps should be used if it is necessary to
minimize reading resolution errors. measure static pressure in the immediate vicinity of
the fan outlet. The static pressure at this location is
10.3 Static pressure measurements difficult to measure accurately with a Pitot-static tube
due to the existence of turbulence and localized high
It is important that all static pressure measurements velocities. If the surface conditions or the velocities at
be referred to the same atmospheric pressure, and the duct walls are unsuited for the use of pressure
this atmospheric pressure be that for which the taps, then a Pitot-static tube must be used with
barometric pressure is determined. extreme care, particularly in aligning the nose of the
tube with the lines of the flow streams.
Make static pressure measurements near the fan
inlet and the fan outlet, and where the airway The location of the static pressure measurement
If in any fan-system installation the prospective Pt4 = the total pressure plane of measurement
locations for static pressure measurement planes Pt1 = the total pressure at the fan inlet
lack one or more desirable qualities, the alternatives ∆P4,1 = the sum of the pressure losses between the
are to accept the best qualified locations and two planes
evaluate the effects of the undesirable aspects of the
conditions on the accuracy of the test results or These losses (∆P) include those attributable to duct
provide suitable locations by modifying the system. friction, duct fittings, other system components, and
changes in airway area. Although ∆P represents a
10.3.2 When using a Pitot-static tube or a double loss in all cases, it is considered a positive value as
reverse tube to measure static pressure, a number of used in the equations in this publication. By
measurements must be made throughout the plane. substitution and rearrangement:
Use Annex H to determine the number and
distribution of the measurement points. When using Ps1 = Ps4 + Pv4 - Pv1 - ∆P4,1
pressure taps, a single measurement at each of the
taps located at the plane is sufficient. Similarly, for static pressure at the fan outlet, Ps2:
Static pressure measurements may be positive or Ps2 = Ps5 + Pv5 - Pv2 + ∆P2,5
The velocity pressures at the various planes can be The uncertainty analyses in Annex T indicate that the
determined from the following general equations for uncertainties in fan static pressure determinations
the velocity pressure at a plane of measurement (x): are expected range from 2% to 8%. This range is
based on considerations of the conditions expected
Pvx = Pv3 (A3/Ax)2 (ρ3/ρx) to be encountered in most field test situations.
The phase current method is convenient and watts input × motor efficiency
Hmo =
sufficiently accurate for most field tests. In this 746
method, the closer the actual phase current is to the
motor nameplate value of full load amps, the greater 4) Given the typical motor performance chart of
the accuracy. Since fan motors are normally selected amps versus power factor and motor efficiency at
for operation at or near the full load point, this method a stated voltage.
provides a reasonably accurate estimate of the Use the field test measurements of amps input
power output of the fan motor. Determine fan power and volts, and the typical motor performance
input by using the motor power output and, where data values of power factor (pf) and motor
applicable, the power transmission loss. efficiency, corresponding to the measured amps
input; the motor power output is calculated as:
A calibrated motor provides accurate data to 11.4.1 Estimating belt drive losses. In view of the
determine motor power output. However, the cost of lack of published information available for use in
the calibration is a limiting factor in the use of this calculating belt drive losses, a graph is included in
method in field tests. For low horsepower Annex L for this purpose. As indicated in the graph,
applications, the fan manufacturer may be able to belt drive loss, expressed as a percentage of motor
calibrate a motor. power output, decreases with increasing motor
power output and increases with increasing speed.
11.2.4. Torquemeters. Another method to determine This graph is based on the results of over 400 drive
fan power input involves the use of a torquemeter loss tests provided to AMCA by drive manufacturers.
installed between the fan and the driver. The use of a The graph serves as a reasonable guide in
torquemeter requires some prearrangement with the evaluating belt drive losses. The calculation of belt
purchaser, who would normally have specified such drive loss, using this graph, is included in many of the
equipment, so that site conditions can be altered to examples in Annex A.
Psc = Ps (Nc / N)2 (ρc / ρ) 6) Responsibility for the cost of the test or any fan-
system modifications required as a result of the
Ptc = Pt (Nc / N)2 (ρc / ρ) test should be established.
2) Manometers suitable for measuring static 3) Loop the manometer tubing well above the
pressures. Manometer fluids other than water are manometer so that any fluid which is
acceptable, provided the specific gravity is inadvertently blown from the gauge will drain
known. A spare bottle of manometer fluid is back into the manometer.
advisable.
4) The Pitot-static tube is intended for measuring
3) Inclined manometer suitable for measuring pressures in relatively clean gases. When using
velocity pressures. Pitot-static tubes in dirty, wet, or corrosive
atmospheres, both legs of the Pitot-static tube
4) Flexible tubing of suitable length to enable must be cleaned out frequently during the test.
manometers to be installed at a convenient Since fan pressure readings are never strictly
location. steady, absence of fluctuations is an
indication of a plugged Pitot-static tube.
5) Tubing couplings and “T” type tubing connectors. Consider using a double reverse tube in these
situations.
6) Thermometers to cover the range of anticipated
temperatures. 5) When making measurements in wet gas
streams, continually check for the presence of
7) Sling psychrometer for obtaining dry-bulb and moisture in the tubing. Clear plastic tubing is
wet-bulb temperatures. ideal from this standpoint. If moisture collects in
the tubing, immediately remove the Pitot-static
8) Clip-on ammeter-voltmeter, power analyzer, or tube and clean the inside of the tubing and Pitot-
other suitable electrical measurement static tube before proceeding with the test.
instruments for the determination of fan power
input. 6) Before performing any work inside a fan,
ductwork, or other system components, make
9) Fan speed measurement instrument. certain that the fan motor starter is “locked out.”
13) Complete AMCA Fan Application Manual 9) Measure temperatures on both sides of double
containing Publications 200, 201, 202, and 203. inlet fans as temperature differences may exist
between each side.
16. Precautions
10) When measuring in high temperature, corrosive
The following precautions should be observed when or explosive atmospheres, instruments should be
conducting a field test: selected for suitability for such atmospheres.
1) Connect the Pitot-static tube to the manometers 17. Typical Fan-System Installations
according to anticipated pressures, i.e., whether
the pressures are positive or negative, and the A fan assembly may include any number of
magnitudes of pressures. appurtenances: variable inlet vanes, inlet boxes, inlet
box dampers, outlet dampers, inlet screens, belt
The performance ratings for a fan that includes inlet 1) Make field test measurements sufficient for
box dampers, variable inlet vanes or outlet dampers determining fan static pressure, fan power input,
cover operation of the fan with these items in the full fan speed, and the density of the air at the fan
open positions. In order to be able to compare the inlet. In this method for testing a free inlet, free
field test results to the fan performance ratings, it is outlet fan, the fan static pressure is calculated as
essential that these items be fixed in their full open the static pressure on the outlet side of the fan
positions for the duration of the test. In addition, when less the static pressure on the inlet side of the
the loss through a damper must be calculated, it is fan: Ps = Ps2 - Ps1. The static pressure
essential that the damper blades be fixed in their full measurements involved must be referred to the
open positions during the test since this is the same atmospheric pressure and made at
condition on which the damper pressure loss ratings locations sufficiently distant from the fan inlet and
are based. This consideration arises when a damper, outlet so as to be unaffected by the velocity of the
which is not considered a part of the fan is located air entering and leaving the fan. Using the fan
between a static pressure measurement plane and manufacturer’s certified performance ratings,
the fan. In order to determine the fan static pressure, draw a performance curve for the fan for
the loss through the damper must be calculated. In operation at the test values of fan speed and
these cases, the calculation of the loss is based on entering air density. Determine the fan air flow
the performance ratings for the damper. rate by entering this curve at the test values of
fan static pressure and fan power input (see
17.1 Free inlet, free outlet fans Example 5C in Annex A).
It is difficult to achieve an accurate field test of a free 2) Use the method as described above with the
inlet, free outlet fan. The most obvious problem is the exception that the performance curve is
lack of a suitable location for the velocity pressure established by a laboratory test of the fan,
measurement plane. In addition, in the case of conducted in accordance with AMCA Standard
ventilators that supply or exhaust air from a building- 210. For the laboratory test, the fan must be set
the most commonly encountered applications of free up in a manner that duplicates the field
inlet, free outlet fans-it is extremely difficult to define, installation conditions. That is, all appurtenances
set, and maintain for the duration of the test the must be in place and any restrictions or
“normal” system condition. Items affecting the system obstructions to the free flow of air into the fan
include: inlet and away from the fan outlet must be
accurately duplicated in the laboratory test setup.
This consideration, which is the same as that used in 17.5.1 Packaged units. This type of unit is supplied
the methods for testing fans for performance rating and rated by the manufacturer as an assembly. The
purposes, charges to the fan the losses incurred in static pressures at the inlet and outlet to the
accelerating the air into the fan inlet and eliminates assembly and the velocity pressure at the inlet to the
inaccuracies which may occur in any attempt to assembly are used in calculating the static pressure
measure velocity pressure and static pressure at the generated by this type of air handling unit. See
fan inlet. Since Ps1 + Pv1 = 0, the equation for Examples 4C and 4D in Annex A.
calculating fan static pressure for this configuration
is: 17.5.2 Factory assembled central station units.
The air performance ratings for this type of unit are
Ps = Ps2 + SEF 1 +SEF 2 + ... + SEF n based on the operation of the fan section assembly
only, but include the effects of the air flow conditions
entering and leaving the fan section which are
created by accessory equipment such as plenums,
Field Performance Measurement | 163
coils, filters, mixing boxes, etc. The fan section
assembly includes the fan and the cabinet in which
the fan has been installed. The accessory items are
considered to be included in the system in which the
fan section operates. The static pressure and the
velocity pressure at the inlet of the fan section and
the static pressure at the fan section outlet, which
coincides with the fan outlet, are used in calculating
the static pressure generated by the fan section
assembly. See examples 4B and 4E in Annex A.
This annex contains examples of field tests. The examples are presented in detail and cover several types of fan-
system combinations. Field test procedures are illustrated in a variety of situations. Portions of the procedures are
typical for all fan-system installations. Other portions of the procedures demonstrate methods for dealing with the
more difficult features encountered in some installations. Not all of the possible fan-system combinations are
included in the examples, but it is expected that the examples will provide sufficient guidance for dealing with those
cases not covered.
5A: Free Inlet, Free Outlet Roof Ventilator with temporary duct
5B: Free Inlet, Free Outlet Propeller Fan with temporary duct
5C: Free Inlet, Free Outlet Roof Ventilator as installed
SEF 1
DIFFUSER
3 2
L
A2
VARIABLE
INLET VANES
A3
LOCATIONS OF
PLANES 2 AND 3
ORIENTATION
OF PITOT TUBE
COMMENTS
1. The variable inlet vanes are considered part of the 3. Measure td1 and tw1 in the path of the air flowing into
fan. Performance ratings for fans with inlet vanes the fan inlets. Determine pb for the general vicinity of
cover operation with the inlet vanes in their full open the fan. Measure td3 in Plane 3. All of these
position. In order to be able to compare the test measurements are used in the determination of
results to the fan performance ratings, it is essential densities at the various planes of interest.
that the inlet vanes be fixed in their full open positions
for the duration of the test. 4. Measure the fan speed and the motor amps, volts,
and, if possible, watts. Record all pertinent motor
2. Determine Pv3 by using the root mean square of nameplate data, including volts (NPV) and full load
the velocity pressure measurements made in a amps (FLA). If the motor power output is to be
traverse of Plane 3, located near the end of the fan estimated by using the phase current method
diffuser (evasé). Determine Ps3 by averaging the described in Annex K, it is not necessary to measure
static pressure measurements made in the same motor watts; however, it may be necessary to
traverse. Procedures for the traverse are described in disconnect the drive and measure the no load amps
Section 9.4. These velocity pressure and static (NLA) if the motor is not operating at or near its full
pressure measurements are susceptible to error due load point (refer to Annex K).
to the turbulence existing in the region of the fan
outlet. In addition, it is undesirable to have Plane 3 5. SEF 1 is due to the effect of insufficient length of
located in a diverging airway. However, no other duct at the fan outlet. In order to calculate the value
more suitable location for Plane 3 exists in this of SEF 1, it is necessary to measure the length of the
example. It is recommended that the Pitot-static tube outlet duct, L; the outlet area of the fan, A2; and the
be oriented so that its nose is aligned with the blast area of the fan.
anticipated flow streams, particularly near the walls of
the diffuser, as shown in the diagram. Determine the 6. The sum of the static pressure, Ps1, and velocity
area of the traverse plane, A3, which is located at the pressure, Pv1, at the inlets of a fan with unrestricted
tip of the Pitot-static tube, as shown in the diagram, inlets is considered to be equal to the sum of the
not at the location of the Pitot-static tube access static pressure, Psx, and the velocity pressure, Pvx, at
holes in the diffuser. a point sufficiently distant from the fan inlets as to be
in still air. At this point, the static pressure is zero, and
V2 = (Q2/A2) Qc = Q
= (57223/11.94) = 58121 cfm
= 4793 fpm Psc = Ps
= 14.97 in. wg
Duct diameter equivalent to the diffuser outlet area: Hc = H
= 178 hp
De2 = 4 A2 / π
= ( 4 × 11.94 ) / π
= 3.9 ft.
= De2 (V2/1000)
= 3.9 (4793/1000)
= 18.7 ft
TEMPORARY
DUCT
DIFFUSER
STATIC 3a 3b
PRESSURE TAPS 0.5 De
SILENCERS
A2
SEF 1
COMMENTS
1. This fan, as supplied and rated by the entrances to the inlet boxes (Plane 1). Determine Ps2
manufacturer, includes the variable inlet vanes and by averaging the pressure measurements at each of
inlet boxes, but does not include the silencers. four static pressure taps located near the end of the
Performance ratings for fans with inlet vanes cover fan diffuser (evasé). See Annex E for details of static
operation with the inlet vanes in the full open pressure taps.
positions. In order to be able to compare the test
results to the fan performance ratings, it is essential 4. Measure td3 and tw3 near the inlet ducts. Determine
that the inlet vanes be fixed in their full open positions pb for the general vicinity of the fan. Measure td2 in
for the duration of the test. Plane 2. All of these measurements are used in the
determination of densities at the various planes of
2. Determine Pv3a and Pv3b by using the root mean interest.
square of the velocity pressure measurements made
in traverses of Planes 3a and 3b. A3a and A3b are the 5. Measure the fan speed and the motor amps, volts,
areas traversed. Determine Ps3a and Ps3b by and if possible, watts. Record all pertinent motor
averaging each of the two sets of static pressure nameplate data, including volts (NPV) and amps
measurements made in the same traverses. (FLA). If the motor power output is to be estimated by
Procedures for traverses are described in Section using the phase current method described in Annex
9.4. Ps3a and Ps3b are used in determining the density K, it is not necessary to measure motor watts;
at the traverse plane. A location for Plane 3 however, it may be necessary to disconnect the drive
measurements may be obtained by installing ducts and measure the no load amps (NLA) if the motor is
on each silencer inlet, as shown in the diagram. The not operating at or near its full load point. Refer to
ducts should be a minimum of one equivalent Annex K.
diameter in length, and have flared inlets to reduce
entrance losses and provide more uniform velocity 6. SEF 1 is due to the effect of there being no duct
profiles at the pressure measurement planes. at the fan outlet. In order to calculate the value of
SEF 1, it is necessary to measure the fan outlet area,
3. Measure Ps1a and Ps1b at locations close to the A2, and the blast area of the fan.
entrances to the inlet boxes and in planes which are
substantially equal in area to the planes of the 7. To calculate the fan static pressure:
Where: DENSITIES
VIVs in full open positions. Fan direct connected to V3b = 1096 (Pv3b/ρ3)0.5
motor. The motor manufacturer advises that this = 1096 (0.62/0.0712)0.5
motor type has a peak efficiency of 91% at a power = 3234 cfm
factor of approximately 0.89.
Q3b = V3bA3b
= 3234 × 12.5
= 40425 cfm
170 | Field Performance Measurement
Q3 = Q3a + Q3b SYSTEM EFFECT FACTOR
= 40100 + 40425
= 80525 cfm AMCA Publication 201-90, Figures 7.1 and 8.3
indicate the following calculations:
Q = Q1
= Q3 (ρ3/ρ1) Q3 (ρ3/ρ2) = 80525 (0.0712/0.0721)
= 80525 (0.0712/0.0711) = 79520 cfm
= 80638 cfm
(Q2/A2) = (79520/18)
FAN POWER INPUT = 4418 fpm
Annex K indicates that Equation A will provide a For a blast area ratio of 0.75, and no duct, Figure 8.3
reasonably accurate estimate of motor power output shows System Effect Curve T applies. For 4418 fpm
for a 250 hp motor operating at 90% FLA. velocity and curve T, Figure 7.1 shows SEF 1 = 0.65
in. wg at 0.075 lbm/ft3. At 0.0720 lbm/ft3:
Hmo = 250 (257/285) (460/460)
= 225 hp SEF 1 = 0.65 (0.0721/0.075)
= 0.62 in. wg
As a check of this value, using the motor efficiency
data and the appropriate equation in Section 11.2.2: FAN STATIC PRESSURE
Since the fan is direct-connected to the motor, there Psc = 11.33 (0.075/0.0711)
is no drive loss, and: = 11.95 in. wg
TEMPORARY
PLANE 3
SHORT DUCT
LOCATION
3 STATIC PRESSURE TAPS
SILENCER
TRANSITION
0.5 De 5
DIFFUSER
INLET SECTION 2
BOX INNER
1 CYLINDER
SIDE VIEW L
GUIDE VANES
COMMENTS
1. This is a variable pitch axial flow fan. The fan See Annex E for details of static pressure taps. In this
assembly, as supplied and rated by the manufacturer, example, Ps2 is considered to be equal to Ps5.
includes the inlet box and diffuser section, but does
not include the silencer. It is essential that the blade 4. Measure td3 and tw3 near the entrance to the short
pitch angle be fixed for the duration of the test. This inlet duct. Determine pb for the general vicinity of the
blade angle should be agreed upon by all interested fan. Measure td5 in Plane 5. All of these
parties. measurements are used in the determination of
densities at the various planes of interest.
2. A temporary short duct is installed upstream of the
silencer to establish Plane 3 in which more uniform 5. Measure the fan speed and the motor amps, volts,
pressures can be obtained. The duct should be a and if possible, watts. Record all pertinent motor
minimum of one equivalent diameter in length, and nameplate data, including volts (NPV) and full load
have a flared inlet to reduce entrance losses and amps (FLA). If the motor power output is to be
provide a more uniform velocity profile at the estimated by using the phase current method
pressure measurement plane. Determine Pv3 by described in Annex K, it is not necessary to measure
using the root mean square of the velocity pressure motor watts; however, it may be necessary to
measurements made in a traverse of Plane 3. Ps3 is disconnect the drive and measure the no load amps
determined by averaging the static pressure (NLA) if the motor is not operating at or near its full
measurements made in the same traverse. load point. Motor performance data, supplied by the
Procedures for traverses are described in Section motor manufacturer, are used in the determination of
9.4. Ps3 is used in determining the density at the motor power output for this example.
traverse plane.
6. SEF 1 is due to the effect of insufficient length of
3. Measure Ps1 at a location close to the entrance to duct between the diffuser outlet and the elbow
the inlet box and in a plane which is substantially downstream of the diffuser. In order to calculate the
equal in area to the plane of the entrance to the inlet value of SEF 1, it is necessary to measure the length
box (Plane 1). Determine Ps5 by averaging the of the transition, L, and the outlet area of the diffuser,
pressure measurements at each of four static A2.
pressure taps located near the end of the fan diffuser.
Since the fan is direct connected to the motor, there Ps2 = Ps5
is no drive loss, and: = 20.8 in. wg
OUTLET DAMPER
SEF 1
PLENUM
COMMENTS
1. Each of the fans, as supplied and rated by the between the outlet damper and the plenum. See
manufacturer, includes an outlet damper. Annex E for details of static pressure taps. Measure
Performance ratings for fans with outlet dampers td2 in Plane 2 for each fan.
cover operation with the outlet damper in the full
open position. In order to be able to compare the test 4. For each fan, measure td1 and tw1 in the path of the
results to the fan performance ratings it is essential air flowing into the fan inlet. Determine pb for the
that the outlet dampers be fixed in the full open general vicinity of the fans. Measure td3 in Plane 3. All
positions for the duration of the test. of these measurements are used in the determination
of densities at the various planes of interest.
2. In this example, there are no suitable locations for
traverse planes for use in determining directly the 5. Measure the fan speed and the motor amps, volts,
flow rate for each fan. The alternative is to determine and if possible, watts for each fan. Record all
the total flow rate and since the fans and their pertinent motor nameplate data, including volts
operating speeds are alike, assume that each fan (NPV) and full load amps (FLA). If the motor power
delivers a flow rate proportional to its actual speed. outputs are to be estimated by using the phase
Determine Pv3 by using the root mean square of the current method described in Annex K, it is not
velocity pressure measurements made in a traverse necessary to measure motor watts; however, it may
of Plane 3, located near the end of a straight run of be necessary to disconnect the drives and measure
duct, such as shown in the diagram. Determine Ps3 by the no load amps (NLA) if the motors are not
averaging the static pressure measurements made in operating at or near their full load points. Refer to
the same traverse. Procedures for traverses are Annex K.
described in Section 9.4. Ps3 is used in determining
the density at the traverse plane. Measure the area of 6. SEF 1 is due to the effect of insufficient length of
traverse plane, A3, which is located at the tip of the duct between the outlet of each fan and the plenum.
Pitot-static tube. In this case, the duct length is so short as to be
judged equivalent to there being no duct at all. In
3. Determine Ps2 for each fan by averaging the order to calculate the value of SEF 1, it is necessary
pressure measurements at each of four static to measure the outlet areas of the fans, A2, and their
pressure taps located in the short length of duct blast areas.
RH Fan
td1 = 75°F
tw1 = 57°F
td2 = 79°F
Q = Q1 LH Motor
= Q3 (ρ3/ρ1) HL = 0.05 Hmo
= 20661 (0.0724/0.0718) = 0.05 × 16.66
= 20834 cfm = 0.83 hp
Assume that the air flow rate for each fan is H = Hmo - HL
proportional to its speed. = 16.66 - 0.83
= 15.83 hp
LH Fan
Q = Q1 RH Motor
= 20834 [1910/(1910 + 1890)] HL = 0.05 Hmo
= 10472 cfm = 0.05 × 15.31
= 0.77 hp
RH Fan H = Hmo - HL
Q = Q1 = 15.31 - 0.77
= 20834 [1890/(1910 + 1890)] = 14.54 hp
= 10362 cfm
SYSTEM EFFECT FACTOR
FAN POWER INPUT
AMCA Publication 201-90, Figures 7.1 and 8.3
LH Fan indicate the following calculations:
Measured amps/FLA = (16.7/23)
= 0.73 LH Fan
= 73% Q2 = Q1 (ρ1/ρ2)
= 10472 (0.0718/0.0724)
RH Fan = 10385 cfm
Measured amps/FLA = (15.7/23)
= 0.68 V2 = (Q2/A2)
= 68% = (10385/3.2)
= 3245 fpm
Ps = Ps2 + SEF 1
LH Fan
Ps = 6.4 + 0.48
= 6.88 in. wg
RH Fan
Ps = 6.4 + 0.48
= 6.88 in. wg
PLAN VIEW 2
3-PIECE
ELBOW
R/D = 1
SEF 1
SEF 2
L
SIDE VIEW OUTLET SIDE VIEW
COMMENTS
1. Determine Pv3 by using the root mean square of described in Annex K, it is not necessary to measure
the velocity pressure measurements made in a motor watts; however, it may be necessary to
traverse of Plane 3, located near the end of a straight disconnect the drive and measure the no load amps
run of duct, such as shown in the diagram. Determine (NLA) if the motor is not operating at or near its full
Ps3 by averaging the static pressure measurements load point. Refer to Annex K.
made in the same traverse. Procedures for traverses
are described in Section 9.4. Ps3 is used in 5. SEF 1 is due to the effect of the elbow located at
determining the density at the traverse plane. the fan inlet. SEF 2 is due to the effect of insufficient
Measure the area of the traverse plane, A3, which is length of duct between the fan outlet and the elbow
located at the tip of the Pitot-static tube. downstream of the fan. In order to calculate the
values of the SEFs, it is necessary to measure the
2. Determine Ps1 by averaging the pressure inlet area and the outlet area of the fan, A1 and A2;
measurements at each of four static pressure taps in the length of the outlet duct, L; and the blast area of
the collar connection at the fan inlet. Determine Ps2 the fan.
by averaging the pressure measurements at each of
6. To calculate the Fan Static Pressure:
four static pressure taps located near the fan outlet.
Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2
3. Measure td3 and tw3 in the traverse plane. Assume
td1 is equal to td3. Determine pb for the general vicinity
Where:
of the fan. Measure td2 in Plane 2. All of these
measurements are used in determining densities at
Pv1 = Pv3 (A3/A1)2 (ρ3/ρ1)
the various planes of interest.
7. In order to compare the test results to the quoted
4. Measure the fan speed and the motor amps, volts,
fan curve drawn for operation at 1880 rpm and 0.075
and if possible, watts. Record all pertinent motor
nameplate data, including volts (NPV) and full load lbm/ft3 density, it is necessary to convert the results
amps (FLA). If the motor power output is to be to the specified conditions. The basis for the
estimated by using the phase current method calculations is described in Section 14.
SITE MEASUREMENTS
⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
ρ1 = ρ3 ⎜ s1 ⎟⎜ ⎟
pb = 29.20 in. Hg ⎝ 13.6 p3 ⎠ ⎝ t d1 + 460 ⎠
td2 = 72°F ⎛ −2.18 + 13.6 × 29.20 ⎞ ⎛ 532 ⎞
= 0.0719 ⎜ ⎟ ⎜ 532 ⎟
td3 = 72°F ⎝ 13.6 × 29.06 ⎠⎝ ⎠
tw3 = 66°F = 0.0718 lbm/ft 3
Ps1 = -2.18 in. wg
Ps2 = 0.35 in. wg
The density at Plane 2:
Ps3 = -1.95 in. wg
Pv3 = 0.45 in. wg
N = 1730 rpm ⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
ρ2 = ρ3 ⎜ s2 ⎟⎜ ⎟
A1 = 1.07 ft2 ⎝ 13.6 p3 ⎠ ⎝ t d2 + 460 ⎠
A2 = 1.17 ft2 ⎛ 0.35 + 13.6 × 29.20 ⎞ ⎛ 532 ⎞
= 0.0719 ⎜ ⎟ ⎜ 532 ⎟
A3 = 1.07 ft2 ⎝ 13.6 × 29.06 ⎠⎝ ⎠
Blast Area = 0.7 ft2 = 0.0723 lbm/ft 3
L = 0.83 ft
For Plane 3 conditions of: Annex K indicates that the average of the results of
Equation A and Equation B will provide a reasonably
td3 = 72°F accurate estimate of motor power output for a 5 hp
tw3 = 66°F motor operating at 74% FLA.
De2 = (4A2/π)0.5
= (4 × 1.17/π)0.5
= 1.22 ft
= 2.5 × 1.22
= 3.05 ft
SEF 2 2
1
SEF 1
4-PIECE ELBOW
R/D = 1
L2
L1
COMMENTS
1. Determine Pv3 by using the root mean square of atmospheric pressure as used in all other pressure
the velocity pressure measurements made in a measurements. In this case, the pressure was
traverse of Plane 3, located near the end of a straight measured as 0.1 in. wg.
run of duct, such as shown in the diagram. Determine
Ps3 by averaging the static pressure measurements 3. Measure td3 and tw3 in the traverse plane.
made in the same traverse. Procedures for traverses Determine pb for the general vicinity of the fan.
are described in Section 9.4. Ps3 is used in Measure td1 and td2. All of these measurements are
determining the density at the traverse plane. used in determining densities at the various planes of
Measure the area of the traverse plane, A3, which is interest.
located at the tip of the Pitot-static tube.
4. Measure the fan speed and the motor amps, volts,
2. Determine Ps1 by using a Pitot-static tube or static and if possible, watts. Record all pertinent motor
pressure taps in the duct connection at the fan inlet. nameplate data, including volts (NPV) and full load
If a Pitot-static tube is used, it should not project into amps (FLA). If the motor power output is to be
the upstream elbow but be located well within the estimated by using the phase current method
length of the duct connection as shown in the described in Annex K, it is not necessary to measure
diagram. The friction loss in the short length of outlet motor watts; however, it may be necessary to
duct is assumed to be negligible, and Ps2 is disconnect the drive and measure the no load amps
considered to be equal to the static pressure at the (NLA) if the motor is not operating at or near its full
duct outlet. The static pressure at the outlet of the load point. Refer to Annex K.
duct is zero gauge pressure, referred to the
atmospheric pressure in the region of the duct outlet. 5. SEF 1 is due to the effect of insufficient length of
In situations such as this example, the air may be duct between the fan inlet and the elbow upstream of
discharging from the duct into a region in which the the fan. SEF 2 is due to the effect of insufficient
atmospheric pressure is somewhat different from that length of duct at the fan outlet. In order to calculate
to which all other pressure measurements are the values of the SEFs, it is necessary to measure
referred. When this possibility exists, it is essential the inlet area and the outlet area of the fan, A1 and
that the static pressure in the region of the A2; the lengths of the inlet connection and the outlet
discharging air be measured, referred to the same duct, L1 and L2; and the blast area of the fan.
pb = 29.82 in. Hg
⎛ P + 13.6 pb ⎞ ⎛ t d2 + 460 ⎞
td1 = 86.6°F ρ1 = ρ2 ⎜ s1 ⎟⎜ ⎟
td2 = 91.3°F ⎝ 13.6 p2 ⎠ ⎝ t d1 + 460 ⎠
tw2 = 70.4°F ⎛ −11.4
4 + 13.6 × 29.82 ⎞ ⎛ 551.3 ⎞
= 0.0714 ⎜ ⎟ ⎜ 546.6 ⎟
td3 = 86°F ⎝ 13.6 × 29.83 ⎠⎝ ⎠
Ps1 = -11.4 in. wg = 0.0700 lbm/ft 3
Ps2 = 0.1 in. wg
Ps3 = -8.9 in. wg
The density at Plane 3:
Pv3 = 1.24 in. wg
N = 2120 rpm, fan speed
A1 = 1.40 ft2 ⎛ P + 13.6 pb ⎞ ⎛ t d2 + 460 ⎞
ρ3 = ρ2 ⎜ s3 ⎟⎜ ⎟
A2 = 1.40 ft2 ⎝ 13.6 p3 ⎠ ⎝ t d3 + 460 ⎠
A3 = 1.57 ft2 ⎛ −8.9 + 13.6 × 29.82 ⎞ ⎛ 551.3 ⎞
= 0.0714 ⎜ ⎟ ⎜ 546 ⎟
⎝ 13.6 × 29.83 ⎠⎝ ⎠
Blast Area = 1.26 ft2 = 0.0705 lbm/ft 3
L1 = 1.33 ft
L2 = 3.0 ft
FLOW RATES
MEASURED MOTOR DATA
V3 = 1096 (Pv3/ρ3)0.5
Volts = 460, 460, 459 = 1096 (1.24/0.0705)0.5
= 460 av = 4596 fpm
Amps = 26.5, 25.5, 26
= 26 av Q3 = V3A3
NLA = 11.3 = 4596 × 1.57
= 7216 cfm
MOTOR NAMEPLATE DATA
Q = Q1
30 hp, 3 phase, 60 hertz = Q3 (ρ3/ρ1)
460 volts, 1750 rpm, 36 FLA = 7216 (0.0705/0.0700)
= 7268 cfm
GENERAL
FAN POWER INPUT
Fan connected to motor through belt drive.
Measured amps/FLA = (26/36)
= 0.72
= 72%
Hmo = (21.67 + 17.85)/2 Duct diameter equivalent to the fan outlet area:
= 19.76 hp
De2 = (4A2/π)0.5
Figure L.1 in Annex L indicates estimated belt drive = (4 × 1.40/π)0.5
loss of 4.8%. = 1.34 ft
HL = 0.048 Hmo Figure 8.3 shows that for velocities over 2500 fpm,
= 0.048 × 19.76 100% effective duct length is one duct diameter per
= 0.95 hp 1000 fpm:
H = Hmo - HL = D2 (V2/1000)
= 19.76 - 0.95 = 1.34 (5089/1000)
= 18.81 hp = 6.82 ft
SYSTEM EFFECT FACTORS The length of the outlet duct in % effective duct
length:
To determine the value of SEF 1, calculate the
velocity at the fan inlet: = (L2/6.82) 100
= (3.0/6.82) 100
V1 = (Q1/A1) = 44%
= (7268/1.40)
= 5191 fpm Blast ratio area = Blast Area/A2
= 1.26/1.40
The diameter of the fan inlet: = 0.9
D1 = (4A1/π)0.5 For blast area ratio of 0.9 and 44% effective duct
= (4 × 1.40/π)0.5 length, Figure 8.3 shows no System Effect Curve
= 1.34 ft. applies and SEF 2 = 0.
The length of the duct between the elbow and the fan FAN STATIC PRESSURE
inlet in terms of D1:
Pv1 = Pv3 (A3/A1)2 (ρ3/ρ1)
= (L1/D1) = 1.24 (1.57/1.40)2 (0.0705/0.0700)
= (1.33/1.34) = 1.57 in. wg
= 1.0
Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2
AMCA Publication 201-90, Figure 9.5 indicates that = 0.1 - (-11.4) - 1.57 + 1.2 + 0
for a four piece elbow with a radius to diameter ratio = 11.13 in. wg
of 1, and with a length of duct between the elbow and
the fan inlet equal to 1 equivalent diameter, System CONVERSIONS TO SPECIFIED CONDITIONS
Effect Curve S applies. For 5191 fpm velocity and
curve S, Figure 7.1 shows SEF 1 = 1.3 in. wg at Qc = 7268 (2075/2120)
0.075 lbm/ft3. At 0.0700 lbm/ft3: = 7114 cfm
4 5 STRAIGHTENING VANES
2 3
1
SEF 2 STATIC PRESSURE TAPS
A3
PLAN VIEW
SEF 1
INNER CYLINDER
LOCATION OF PLANE 3
SIDE VIEW
COMMENTS
1. This type of installation is normally classified as located at the tip of the Pitot-static tube, as shown in
one in which a satisfactory test cannot be conducted. the diagram, not at the location of the Pitot-static tube
Due to the configurations of the airways, there are no access holes.
locations at which reasonably accurate pressure
measurements can be made. In addition, the 3. Determine Ps4 by averaging the pressure
judgments required in determining the values of the measurements at each of four static pressure taps
SEFs are susceptible to error. The purpose of located near the fan inlet. In the same manner,
presenting this example is to illustrate the not determine Ps5 at a location near the fan outlet. It is
uncommon instance in which a test must be conducted undesirable to have pressure measurement planes
in order to provide performance information, even located in converging and diverging airways, but
though the results will be innaccurate to a degree there are no other more suitable locations for these
which is not normally acceptable. planes in this installation. Measure A4 and A5, the
cross-sectional areas of the airways at Planes 4 and 5.
2. Determine Pv3 by using the root mean square of
the velocity pressure measurements made in a 4. Measure td3, tw3, and td4. Determine pb for the
traverse of Plane 3, located as shown in the diagram. general vicinity of the fan. These measurements are
Determine Ps3 by averaging the static pressure used in the determination of densities at the various
measurements made in the same traverse. planes of interest.
Procedures for traverses are described in Section
9.4. These velocity pressure and static pressure 5. Measure the fan speed and the motor amps, volts,
measurements are susceptible to error due to the and if possible, watts. Record all pertinent motor
turbulence existing in the region of the fan outlet. In nameplate data, including volts (NPV) and full load
addition, it is undesirable to have Plane 3 located in amps (FLA). If the motor power output is to be
a diverging airway. However, no other more suitable estimated by using the phase current method
location for Plane 3 exists in this example. It is described in Annex K, it is not necessary to measure
recommended that the Pitot-static tube be oriented motor watts; however, it may be necessary to
so that its nose is aligned with the anticipated flow disconnect the drive and measure the no load amps
streams, particularly near the walls of the diffuser. (NLA) if the motor is not operating at or near its full
Determine the area of the traverse plane, A3, which is load point. Refer to Annex K.
Annex K indicates that the average of the results of Pv1 = Pv3 (A3/A1)2 (ρ3/ρ1)
Equation A and Equation B will provide a reasonably
accurate estimate of motor power output for a 25 hp = 0.044 (29.8/8.0)2 (0.0694/0.0691)
motor operating at 80% FLA. = 0.61 in. wg
Figure L.1 in Annex L indicates estimated belt drive Pv2 = Pv3 (A3/A2)2 (ρ3/ρ2)
loss of 4.9%. = 0.044 (29.8/8.0)2 (0.0694/0.0694)
= 0.61 in. wg
HL = 0.049 Hmo
= 0.049 × 18.46 Ps2 + Pv2 = Ps5 + Pv5
= 0.90 hp Ps2 = Ps5 + Pv5 - Pv2
= 1.22 + 0.42 - 0.61
H = Hmo - HL = 1.03 in. wg
= 18.46 - 0.90 Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2
= 17.56 hp = 1.03 - (-1.92) - 0.61 + 0 + 0.24
= 2.58 in. wg
SYSTEM EFFECT FACTORS
Losses between Planes 1 and 4 and between Planes
SEF 1 = 0 See item 6 under COMMENTS. 2 and 5 have been ignored.
To determine the value of SEF 2, AMCA Publication CONVERSION TO SPECIFIED CONDITIONS
201-90, Figure 8.2 indicates that a vaneaxial fan with
no outlet duct will use System Effect Curve U. Qc = 26128 (1580/1590)
= 25964 cfm
Q2 = Q3 (ρ3/ρ2)
= 26015 (0.0694/0.0694)
Psc = 2.58 (1580/1590)2 (0.0690/0.0691)
= 26015 cfm
= 2.54 in. wg
V2 = (Q2/A2)
Hc = 17.56 (1580/1590)3 (0.0690/0.0691)
= (26015/8.0)
= 3252 fpm = 17.21 hp
SEF 1
3
1
L
INLET BOX
DIFFUSER
COMMENTS
1. This fan, as supplied and rated by the 5. Measure the fan speed and the motor amps, volts,
manufacturer, includes the inlet box damper and the and if possible, watts. Record all pertinent motor
inlet box. Performance ratings for fans with inlet box nameplate data, including volts (NPV), and full load
dampers cover operation with the dampers in the full amps (FLA). If the motor power output is to be
open positions. In order to be able to compare the estimated by using the phase current method
test results to the fan performance ratings, it is described in Annex K, it is not necessary to measure
essential that the damper be fixed in the full open motor watts; however, it may be necessary to
position for the duration of the test. disconnect the drive and measure the no load amps
(NLA) if the motor is not operating at or near its full
2. Determine Pv3 by using the root mean square of load point. Refer to Annex K.
the velocity pressure measurements made in a
traverse of Plane 3, located shortly upstream of the 6. SEF 1 is due to the effect of insufficient length of
inlet damper. Determine Ps3 by averaging the static duct at the fan outlet. In order to calculate the value
pressure measurements made in the same traverse. of SEF 1, it is necessary to measure the length of the
Procedures for traverses are described in Section outlet duct, L; the fan outlet area, A2; and the blast
9.4. Measure A3, the area of the traverse plane, area of the fan.
located at the tip of the Pitot-static tube and A1, the
area of the inlet to the damper. 7. To calculate the Fan Static Pressure:
For Plane 3 conditions of: Annex K indicates that the average of the results of
Equation A and Equation B will provide a reasonably
td3 = 63°F accurate estimate of motor power output for a 500 hp
tw3 = 62°F motor operating at 84% FLA.
Figure 8.3 shows that for velocities over 2500 fpm Qc = 23075 (1780/1790)
100% effective duct length is one duct diameter for = 22946 cfm
every 1000 fpm:
Psc = 71.0 (1780/1790)2 (0.059/0.0610)
= De2 (V2/1000) = 67.9 in. wg
= 2.60 (3802/1000)
= 9.89 ft. Hc = 405 (1780/1790)3 (0.059/0.0610)
= 385 hp
L in % effective duct length:
= (L/9.89) 100
= (2.50/9.89) 100
= 25%
INLET BOXES
INLET BOX 1a 1b
DAMPERS 3a 3b
COMMENTS
1. This fan, as supplied and rated by the 4. Measure td3a, td3b, and td5. Since flue gas is being
manufacturer, includes the inlet box dampers and the handled by the fan, the Orsat apparatus is used by
inlet boxes, but does not include the outlet damper. process personnel to determine the density of the
Performance ratings for fans with inlet box dampers gas. Determine pb for the general vicinity of the fan.
cover operation with the dampers in the full open These data are used in the determination of densities
positions. Also, performance ratings for items such as at the various planes of interest.
the outlet damper are for operation in the full open
position. In order to be able to compare the test 5. Measure the fan speed and the motor amps, volts,
results to the fan performance ratings, it is essential and if possible, watts. Record all pertinent motor
that the outlet damper and the inlet dampers be fixed nameplate data, including volts (NPV) and full load
in their full open positions. amps (FLA). If the motor power output is to be
estimated by using the phase current method
2. Determine Pv3a and Pv3b by using the root mean described in Annex K, it is not necessary to measure
square of the velocity pressure measurements made motor watts; however, it may be necessary to
in Planes 3a and 3b. Determine Ps3a and Ps3b by disconnect the drive and measure the no load amps
averaging each of the two sets of static pressure (NLA) if the motor is not operating at or near its full
measurements made in the same traverses. load point. Motor performance data, supplied by the
Procedures for traverses are described in Section motor manufacturer, are used in the determination of
9.4. Measure A3a and A3b, the areas of the traverse motor power output for this example.
planes and A1a and A1b, the areas of the inlets to the
inlet dampers. 6. In this example, the duct downstream of the outlet
damper is of sufficient length, and no SEF applies.
3. Determine Ps5 by averaging the pressure
measurements of each of four static pressure taps 7. To calculate the Fan Static Pressure:
located downstream of the outlet damper.
Ps = Ps2 - Ps1 - Pv1
Pv1 is calculated using the total flow rate and the total CALCULATIONS
area at the inlets to the inlet dampers.
DENSITIES
Pv1 = (Q1/1096A1 )2 ρ1
The densities at Planes 3a and 3b are:
8. In order to compare the test results to the quoted
fan curve drawn for operation at 880 rpm and 0.049 ⎛ P + 13.6 pb ⎞ ⎛ 70 + 460 ⎞
ρ3a = 0.0725 ⎜ s3a ⎟⎜ ⎟
lbm/ft3 density, it is necessary to convert the results ⎝ 13.6 × 29.92 ⎠ ⎝ t d3a + 460 ⎠
to the specified conditions. The basis for calculations ⎛ −18.8 + 13.6 × 30.12 ⎞ ⎛ 530 ⎞
is described in Section 14. = 0.0725 ⎜ ⎟ ⎜ 805 ⎟
⎝ 13.6 × 29.92 ⎠⎝ ⎠
OBSERVATIONS = 0.0458 lbm/ft 3
SITE MEASUREMENTS
⎛ P + 13.6 pb ⎞ ⎛ 70 + 460 ⎞
ρ3b = 0.0725 ⎜ s3b ⎟⎜ ⎟
pb = 30.12 in. Hg ⎝ 13.6 × 29.92 ⎠ ⎝ t d3b + 460 ⎠
td3a= 345°F ⎛ −18.3 + 13.6 × 30.12 ⎞ ⎛ 530 ⎞
td3b= 359°F = 0.0725 ⎜ ⎟ ⎜ 819 ⎟
⎝ 13.6 × 29.92 ⎠⎝ ⎠
td5 = 363°F
= 0.0451 lbm/ft 3
Q = Q1 Ps1 = Ps3
= Q3 (ρ3/ρ1) = (Ps3a + Ps3b)/2
= 891501 (0.0455/0.0455) = (-18.8 - 18.3)/2
= 891501 cfm = -18.55 in. wg
The data supplied by the motor manufacturer indicate Hc = 3174 (880/892)3 (0.049/0.0455)
motor efficiency of 94% at the measured power input = 3282 hp
of 2519 kW. Using this information:
H = Hmo
= 3174 hp
4 5
SEF 1
2-PIECE ELBOW
(TYPICAL)
INNER SEF 2
L1 L2
CYLINDER
1 2
COMMENTS
1. The unusual duct arrangement in this example 4. Measure td3 and tw3 in the traverse plane.
makes it very difficult to obtain accurate pressure Determine pb for the general vicinity of the fan.
measurements, and this fact should be understood Measure td4. These measurements are used in
before testing begins. Also, the use of a diverging determining densities at the various planes of
inlet fitting and a converging outlet fitting with this fan interest.
can pose additional problems. Unless the degrees of
divergence and convergence are moderate, as they 5. Measure the fan speed, motor amps, volts, and if
are in this example, the fan performance will be possible, watts. Record all pertinent motor nameplate
adversely affected. data, including volts (NPV) and full load amps (FLA).
If the motor power output is to be estimated by using
2. Determine Pv3 by using the root mean square of the phase current method described in Annex K, it is
the velocity pressure measurements made in a not necessary to measure motor watts; however, it
traverse of Plane 3, located well downstream in a may be necessary to disconnect the drive and
straight run of duct, such as shown in the diagram. measure the no load amps (NLA) if the motor is not
Determine Ps3 by averaging the static pressure operating at or near its full load point. Motor
measurements made in the same traverse. performance data, supplied by the motor
Procedures for traverses are described in Section manufacturer, are used in the determination of motor
9.4. Ps3 is used in determining the density at the power output for this example.
traverse plane. Measure the area of the traverse
plane, A3. 6. SEF 1 is due to the effect of insufficient length of
duct between the fan inlet and the elbow upstream of
3. Determine Ps5 by averaging the pressure the fan. SEF 2 is due to the effect of insufficient
measurements at each of four static pressure taps length of duct between the fan outlet and the elbow
located near the end of the duct connection at the fan downstream of the fan. In order to calculate the
outlet. Determine Ps4 by using static pressure taps in values of the SEFs, it is necessary to measure the
the duct connection at the fan inlet. Measure A4 and inlet area and the outlet area of the fan, A1 and A2;
A5, the cross-sectional areas of the duct connections and the lengths of the inlet and outlet duct
at the static pressure taps. connections, L1 and L2.
Hmo = (18.0 × 0.875)/0.746 Figure 8.1 shows that for velocities of 2500 fpm or
= 21.1 hp less, the 100% effective duct length is 2.5 diameters:
Since the fan is direct connected to the motor, there = 2.5 × 3.01
is no drive loss, and: = 7.53 ft
AMCA Publication 201-90, Figure 9.2 indicates that Ps2 + Pv2 = Ps5 + Pv5
for a two piece elbow with a length of duct between Ps2 = Ps5 + Pv5 - Pv2
the elbow and the fan inlet equal to 1.00 diameter = 0.82 + 0.783 - 0.37
System Effect Curve S-T applies. For a velocity of = 1.23 in. wg
2482 fpm and curve S-T, Figure 7.1 shows SEF 1 =
0.25 in. wg at 0.075 lbm/ft3. At 0.0729 lbm/ft3: Pv4 = Pv3 (A3/A4)2 (ρ3/ρ4)
SEF 1 = 0.25 (0.0729/0.075) = 0.783 (4.91/6.2)2 (0.0728/0.0729)
= 0.24 in. wg = 0.49 in. wg
For SEF 2, AMCA Publication 201-90, Figures 7.1, Pv1 = Pv3 (A3/A1)2 (ρ3/ρ1)
8.1, and 8.4 indicate the following calculations: = 0.783 (4.91/7.1)2 (0.0728/0.0729)
= 0.37 in. wg
Q2 = Q3 (ρ3/ρ2)
= 17647 (0.0728/0.0728) Ps1 + Pv1 = Ps4 + Pv4
= 17647 cfm Ps1 = Ps4 + Pv4 - Pv1
= -1.1 + 0.49 - 0.37
V2 = Q2/A2 = -0.98 in. wg
= 17647/7.1
= 2485 fpm
Qc = 17623 (1750/1760)
= 17523 cfm
2b
STATIC PRESSURE TAPS
1b
2a FAN B
1a
DAMPER
SIDE VIEW
COMMENTS
1. The two single inlet fans in this example have been measurements are assumed to exist at the
rated by the manufacturer as a two stage assembly. respective plane of interest because of the close
Although rated as an assembly, sufficient proximity and the fact that the two planes are equal in
measurements are made to provide performance area. The static pressure at each plane may be
data for each fan. The damper downstream of the determined by averaging the static pressure
second fan is not included as part of the rated measurements at each of four static pressure taps, or
assembly. In virtually all cases in which an air flow by averaging the static pressure measurements
control damper, such as the one shown in the made in a Pitot-static tube traverse of the plane.
diagram, is included in the system, the point of However, due to the turbulence existing in the
operation of major interest and for which the fan has regions of the outlets of the fans, it is recommended
been selected is at the maximum air flow rate. This that static pressure taps be used at Planes 1b-2a and
example is no exception. Therefore, it is essential 2b.
that the damper be fixed in its full open position for
the duration of the test. 4. Measure td3, tw3, td1b, and td2b; td1a is assumed to be
equal to td3. Determine pb for the general vicinity of
2. Determine Pv3 by using the root mean square of the fan. These measurements are used in
the velocity pressure measurements made in a determining densities at the planes of interest.
traverse of Plane 3. Determine Ps3 by averaging the
static pressure measurements made in the same 5. Measure the fan speed and the motor amps, volts,
traverse. Procedures for traverses are described in and if possible, watts for each fan. Record all
Section 9.4. Ps3 is used in determining the density at pertinent motor nameplate data, including volts
the traverse plane, A3, which is located at the tip of (NPV), and full load amps (FLA). If the motor power
the Pitot-static tube. outputs are to be estimated by using the phase
current method described in Annex K, it is not
3. Determine the static pressures at Planes 1a, 1b- necessary to measure motor watts; however, it may
2a, and 2b. As shown in the diagram, these planes be necessary to disconnect the drives and measure
are located shortly downstream of the inlets and the no load amps (NLA) if the motors are not
outlets of the fans, which are the planes of interest. In operating at or near their full load points. In this
each case, the conditions which exist at the plane of example, a watts input measurement is made for
7. To calculate the static pressure for the two stage Data identical for each stage:
assembly: 350 hp, 3 phase, 60 hertz
4000 volts, 1790 rpm, 44.5 FLA
Ps = Ps2b - Ps1a - Pv1a
GENERAL
Where:
Fans direct connected to motors. Motor efficiency
Pv1a = Pv3 (A3/A1a )2 (ρ3/ρ1a) data supplied by motor manufacturer.
Q2b = Q3 (ρ3/ρ2b)
= 21471 (0.0470/0.0624)
= 16172 cfm
SEF 1
3a
2
3c
3b
COMMENTS
1. This fan, as supplied and rated by the Pitot-static tube is used, it should be positioned well
manufacturer, does not include the backdraft damper. within the inlet collar in which Plane 1 is located.
Measure the area of Plane 1 for use in calculating
2. Normally, velocity pressure measurements would Pv1. The static pressure at the outlet of the backdraft
be made in a single plane, located in a duct common damper is zero gauge pressure, referred to the
to all branches. In this example, a measurement atmospheric pressure in the region of the outlet of the
plane which provides a satisfactory velocity profile backdraft damper. In situations such as this example,
cannot be located within the short length of duct the air may be discharging from the damper into a
between the point of connection of the branch ducts region in which the atmospheric pressure is
and the fan inlet. The alternative, as indicated in the somewhat different from that to which all other
diagram, is to make a velocity pressure pressure measurements are referred. When this
measurement traverse in the longest available duct possibility exists, it is essential that the static
run of each branch. The velocity pressure for each pressure in the region of the discharging air be
branch is determined by using the root mean square measured, referred to the same atmospheric
of the velocity pressure measurements made in the pressure as used in all other pressure
traverse. The static pressure at each traverse plane measurements.
is determined by averaging the static pressure
measurements made in the same traverse. These 4. Measure the dry-bulb and wet-bulb temperatures
static pressure values are used in determining the at each velocity traverse plane and the dry-bulb
densities at the traverse planes. Procedures for temperature at Plane 1. In this example, td2 is
traverses are described in Section 9.4. In order to assumed to be equal to td1. Determine pb for the
determine the air flow rates it is necessary to general vicinity of the fan. These measurements are
measure the area of each traverse point. used in determining densities at the planes of
interest.
3. Ps1, the static pressure at the fan inlet may be
determined by averaging the static pressure 5. Measure the fan speed and the motor amps, volts,
measurements at each of four static pressure taps or and if possible, watts. Record all pertinent motor
by averaging the static pressure measurements nameplate data, including volts (NPV) and full load
made in a Pitot-static tube traverse of Plane 1. If a amps (FLA). If the motor power output is to be
Q1 = Q3a (ρ3a/ρ1) + Q3b (ρ3b/ρ1) + Q3c (ρ3c/ρ1) Fan connected to motor through belt drive. Pressure
loss data supplied by manufacturer of backdraft
Ps2 is the sum of the static pressure in the region of damper.
the damper outlet, which was measured as zero, and
the backdraft damper pressure loss. CALCULATIONS
Qc = 41603 (810/800)
= 42123 cfm
2-PIECE ELBOW
SEF 1
L1
1
STATIC GUIDE VANES
PRESSURE TAPS
INNER CYLINDER
2
SEF 2
L2
5
PLAN VIEW
COMMENTS
1. Determine Pv3 by using the root mean square of motor nameplate data, including volts (NPV), and full
the velocity pressure measurements made in a load amps (FLA). If the motor power output is to be
traverse of Plane 3, located near the end of a straight estimated by using the phase current method
run of duct, as shown in the diagram. Determine Ps3 described in Annex K, it is not necessary to measure
by averaging the static pressure measurements motor watts; however, it may be necessary to
made in the same traverse. Procedures for traverses disconnect the drive and measure the no load amps
are described in Section 9.4. Ps3 is used in (NLA) if the motor is not operating at or near its full
determining the density at the traverse plane. load point. Refer to Annex K.
Measure the area of the traverse plane, A3, which is
located at the tip of the Pitot-static tube. 5. SEF 1 is due to the effect of insufficient length of
duct between the fan inlet and the elbow upstream of
2. Determine Ps5 by averaging the pressure the fan. SEF 2 is due to the effect of insufficient
length of duct between the fan outlet and the elbow
measurements at each of four static pressure taps
downstream of the fan. In order to calculate the
located near the end of the duct connection at the fan
values of the SEFs, it is necessary to measure the
outlet. Determine Ps1 by using a Pitot-static tube or
inlet area and the outlet area of the fan, A1 and A2;
static pressure taps in the duct connection at the fan
and the lengths of the inlet and outlet duct
inlet. If a Pitot-static tube is used, it should not project
connections, L1 and L2.
into the upstream elbow but be located well within the
length of the duct connection.
6. To calculate the Fan Static Pressure:
3. Measure td3 and tw3 in the traverse plane; td1 is
Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2
assumed to be equal to td3. Determine pb for the
general vicinity of the fan. Measure td5. These
Where: Pv1 = Pv3
measurements are used in determining densities at
the planes of interest.
Since:
4. Measure the fan speed and the motors amps,
A1 = A3
volts, and if possible, watts. Record all pertinent
ρ1 = ρ3 DENSITIES
Due to the close proximity of Planes 2 and 5 and the For Plane 3 conditions of:
fact that there is no change in area between the two
planes, all conditions which exist at Plane 5 are td3 = 72°F
assumed to exist at Plane 2. tw3 = 66°F
Therefore: p3 = pb + (Ps3/13.6)
= 29.20 + (-1.92/13.6)
Ps2 = Ps5 = 29.06 in. Hg
7. In order to compare the test results to the quoted Use Figure N.1 in Annex N to obtain ρ3 = 0.0719
fan curve drawn for operation at 1730 rpm and 0.075 lbm/ft3.
lbm/ft3 density, it is necessary to convert the results
to the specified conditions. The basis for the Assume that td1 = td3.
calculations is described in Section 14.
tw3= 66°F
td5= 73°F Assume that td2 = td5 and Ps2 = Ps5.
Ps1= -2.02 in. wg
Ps3= -1.92 in. wg ρ 2 = ρ5
Pv3= 0.35 in. wg
⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
Ps5= 0.10 in. wg = ρ3 ⎜ s5 ⎟⎜ ⎟
N = 1710 rpm ⎝ 13.6 p3 ⎠ ⎝ t d5 + 460 ⎠
A1 = A2 = A3 = A5 ⎛ 0.10 + 13.6 × 29.20 ⎞ ⎛ 532 ⎞
= 0.0719 ⎜ ⎟ ⎜ 533 ⎟
= 2.64 ft2 ⎝ 13.6 × 29.06 ⎠⎝ ⎠
L1 = 1.5 ft, length of inlet duct
= 0.0721 lbm/ft 3
L2 = 2.25 ft, length of the outlet duct
Eqn B = 5 [(12.3 - 7)/(14 - 7)] (228/230) The diameter of the fan outlet:
= 3.75 hp
D2 = (4A2/π)0.5
Hmo = (4.35 + 3.75)/2
= (4 × 2.64/π)0.5
= 4.05 hp = 1.83 ft
Figure L.1 in Annex L indicates estimated belt drive Figure 8.1 shows that for velocities of 2500 fpm or
loss of 6.3%. less, the 100% effective duct length is 2.5 diameters:
HL = 0.063 Hmo = 2.5 × 1.83
= 0.063 × 4.05 = 4.58 ft
= 0.26 hp
The length of the outlet duct in % effective duct
H = Hmo - HL length:
= 4.05 - 0.26
= 3.79 hp = (L2/4.58) 100
= (2.25/4.58) 100
SYSTEM EFFECT FACTORS = 49%
To determine the value of SEF 1, calculate the From Figure 8.4, for a vaneaxial fan with a 49%
velocity at the fan inlet: effective duct length between its discharge and a two
piece elbow, System Effect Curve W applies. From
V1 = (Q1/A1) Figure 7.1, for 2411 fpm velocity and curve W, SEF 2
= (6384/2.64) is less than 0.1 in. wg, and is considered negligible.
= 2418 fpm
SEF 2 = 0.00
Calculate the diameter of the fan inlet:
FAN STATIC PRESSURE
D1 = (4A1/π)0.5
= (4 × 2.64/π)0.5 Since:
= 1.83 ft.
A1 = A3
Calculate the length of duct between the elbow and ρ1 = ρ3
the fan inlet in terms of the fan inlet diameter: Pv1 = Pv3
Qc = 6384 (1730/1710)
= 6459 cfm
3
WET CELL SCRUBBER
1
2
PLAN VIEW
SEF 1
SIDE VIEW
COMMENTS
1. Determine Pv3 by using the root mean square of amps (FLA). If the motor power output is to be
the velocity pressure measurements made in a estimated by using the phase current method
traverse of Plane 3, located in the duct connection at described in Annex K, it is not necessary to measure
the fan inlet, as shown in the diagram. Determine Ps3 motor watts; however, it may be necessary to
by averaging the static pressure measurements disconnect the drive and measure the no load amps
made in the same traverse. Procedures for traverses (NLA) if the motor is not operating at or near its full
are described in Section 9.4. Ps3 is used in load point. Refer to Annex K.
determining the density at the traverse plane.
Measure the area of the traverse plane, A3, which is 5. SEF 1 is due to the effect of there being no duct
located at the tip of the Pitot-static tube. In locating at the fan outlet. In order to calculate the value of
Plane 3 downstream of the scrubber, changes in the SEF 1, it is necessary to measure the outlet area of
composition of the air as a result of the action of the the fan, A2, and the blast area of the fan.
scrubber are properly taken into account in the
determination of fan air flow rate. Due to the close 6. To calculate the Fan Static Pressure:
proximity of Planes 1 and 3, and the fact that there is
no change in area between the two planes, the Ps = Ps2 - Ps1 - Pv1 + SEF 1
conditions which exist at Plane 3 are assumed to
exist at Plane 1. Where:
2. Ps2, the static pressure at the fan outlet, is zero. Pv1 = Pv3
Ps1 = Ps3
3. Measure td3 and tw3 in the traverse plane. Ps2 = 0
Determine pb for the general vicinity of the fan.
Measure td2. These measurements are used in 7. In order to compare the test results to the quoted
determining densities at the planes of interest. fan curve drawn for operation at 1700 rpm and 0.071
lbm/ft3 density, it is necessary to convert the results
4. Measure the fan speed and the motor amps, volts, to the specified conditions. The basis for the
and if possible, watts. Record all pertinent motor calculations is described in Section 14.
nameplate data, including volts (NPV), and full load
210 | Field Performance Measurement
OBSERVATIONS
⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
ρ2 = ρ3 ⎜ s2 ⎟⎜ ⎟
SITE MEASUREMENTS ⎝ 13.6 p3 ⎠ ⎝ t d2 + 460 ⎠
⎛ 0 + 13.6 × 29.80 ⎞ ⎛ 525 ⎞
pb = 29.80 in. Hg = 0.0732 ⎜ ⎟⎜ ⎟
⎝ 13.6 × 29.21 ⎠ ⎝ 530 ⎠
td3= 65°F
= 0.0740 lbm/ft 3
tw3= 64°F
td2= 70°F
Ps3= -8.0 in. wg FLOW RATES
Pv3= 0.337 in. wg
N = 1672 rpm V3 = 1096 (Pv3/ρ3)0.5
A1 = A3 = 1096 (0.337/0.0732)0.5
= 7.06 ft2 = 2352 fpm
A2 = 5.15 ft2
Q3 = V3A3
Blast Area = 3.67 ft2 = 2353 × 7.06
= 16605 cfm
MEASURED MOTOR DATA
Q = Q1
Volts = 450, 458, 462
= Q3 (ρ3/ρ1)
= 457 av
= 16605 (0.0732/0.0732)
Amps = 44, 45, 44.5
= 16605 cfm
= 44.5 av
Q2 = Q3 (ρ3/ρ2)
MOTOR NAMEPLATE DATA
= 16605 (0.0732/0.0740)
40 hp, 3 phase, 60 hertz = 16425 cfm
460 volts, 1780 rpm, 49 FLA
FAN POWER INPUT
GENERAL
Measured amps/FLA = (44.5/49)
Fan connected to motor through belt drive. = 0.91
= 91%
CALCULATIONS
Annex K indicates that Equation A will provide a
DENSITIES reasonably accurate estimate of motor power output
for a 40 hp motor operating at 91% FLA.
For Plane 3 conditions of:
td3 = 65°F Hmo = 40 (44.5/49) (457/460)
tw3 = 64°F = 36.1 hp
Pv1 = Pv3
= 0.337 in. wg
Qc = 16605 (1700/1672)
= 16883 cfm
2
1
BACKDRAFT DAMPER
4
STATIC PRESSURE TAPS
3a SIDE VIEW 3b
COMMENTS
1. This centrifugal roof ventilator, as supplied and 3. Ps4 may be determined by averaging the static
rated by the manufacturer, does not include the pressure measurements at each of four static
backdraft damper. It is essential that the backdraft pressure taps or by averaging the static pressure
damper blades be fixed in their full open positions, measurements made in a Pitot-static tube traverse of
otherwise uneven velocity distribution will occur at Plane 4. If a Pitot-static tube is used, it should be
the inlet to the ventilator, adversely affecting its positioned well within the duct in which Plane 4 is
performance. located, and not project into the upstream elbows.
Measure the area of Plane 1 for use in calculating
2. Normally, velocity pressure measurements would Pv1. In this example, A4 = A1. Ps2, the static pressure
be made in a single plane, located in a duct common at the outlet of the ventilator, is zero gauge pressure,
to all branches. In this example, a measurement referred to the atmospheric pressure in the region of
plane which provides a satisfactory velocity profile the ventilator outlet. In situations such as this
cannot be located within the short length of duct example, the air may be discharging from the
between the point of connection of the branch ducts ventilator into a region in which the atmospheric
and the ventilator inlet. The alternative, as indicated pressure is somewhat different from that to which all
in the diagram, is to make a velocity pressure other pressure measurements are referred. When
measurement traverse in each branch. The velocity this possibility exists, it is essential that the static
pressure for each branch is determined by using the pressure in the region of the discharging air be
root mean square of the velocity pressure measured, referred to the same atmospheric
measurements made in the traverse. The static pressure as used in all other pressure
pressure at each traverse plane is determined by measurements. In this case, Ps2 was measured as
averaging the static pressure measurements made in zero.
the same traverse. These static pressure values are
used in determining the densities at the traverse 4. Measure the dry-bulb and wet-bulb temperatures
planes. Procedures for traverses are described in at each velocity traverse plane. In this example, td1
Section 9.4. In order to determine the air flow rates, it and td4 are assumed to be equal to td3a. Determine pb
is necessary to measure the area of each traverse
for the general vicinity of the fan. These
plane.
measurements are used in determining densities at
the planes of interest.
Figure L.1 in Annex L indicates estimated belt drive Psc = 0.89 (620/625)2 (0.075/0.0721)
loss of 5.8%. = 0.91 in. wg
H = Hmo - HL
= 4.84 - 0.28
= 4.56 hp
4 SEF 1 5
L
+
+ +
COMMENTS
1. This is an air conditioning unit which has been is determined by using the root mean square of the
assembled at the installation site. The subject of the velocity pressure measurements made in the
test is the fan, which is rated by the manufacturer as traverse. the static pressure at each traverse plane is
free-standing, unencumbered by the cabinet in which determined by averaging the static pressure
it has been installed. The fan performance ratings are measurements made in the same traverse. These
based on operation with the fan outlet ducted. Before static pressure values are used in determining the
proceeding with the test, it is essential that all densities at the traverse planes. Procedures for
dampers--outside air, return air, mixing box, traverses are described in Section 9.4. In order to
multizone, face and bypass or volume control--be determine the air flow rates, it is necessary to
fixed in the positions agreed upon by all interested measure the area of each traverse plane.
parties as being applicable for the installation. Also,
the temperatures of the heating coils must be kept 3. Determine Ps4 by averaging the static pressure
constant throughout the test period. It may be measurements made in a traverse of Plane 4.
necessary to lock out, disconnect, or otherwise Determine Ps5 in a similar manner. Pitot-static tube
modify automatic control devices in order to prevent traverses are used in determining these static
the positions of the dampers and temperatures of the pressures because the installation of suitable
coils from changing during the test. Refer to Section pressure taps is usually prevented by the insulating
17.4.3 for additional considerations affecting the test material encountered in this type of equipment. Due
procedure for fans in this type of installation. to the abrupt expansion in area from Plane 2 to Plane
5, it is assumed that there is no conversion of velocity
2. Normally, velocity pressure measurements would pressure at Plane 2 to static pressure at Plane 5.
be made in a single plane, located in a duct common Therefore, it is assumed that Ps2 = Ps5. Measure the
to all branches. In this example, a measurement area of Plane 4 for use in calculating Pv4.
plane which provides a satisfactory velocity profile
cannot be located upstream of the fan or between the 4. Measure the dry-bulb and wet-bulb temperatures
point of connection of the branch ducts and the fan at Plane 4 and the dry-bulb temperatures at Planes
outlet. The alternative, as indicated in the diagram, is 3a, 3b, and 5. Determine pb for the general vicinity of
to make a velocity pressure measurement traverse in
the air conditioning unit. These measurements are
each branch. The velocity pressure for each branch
used in determining densities at the planes of interest.
p4 = pb + (Ps4/13.6)
= 28.72 + (-1.75/13.6)
= 28.59 in. Hg
Since:
ρ4 = ρ1
Q4 = Q1
Qc = 48982 (1170/1160)
= 49404 cfm
L
SEF 1 5
2
OUTSIDE + +
AIR
+ +
FAN SECTION
SIDE VIEW
FILTER SECTION COIL SECTION
COMMENTS
1. This is a factory assembled, draw-through central Section 9.4. In order to determine the air flow rate, it
station unit. The subject of the test is the fan section, is necessary to measure the area of the traverse
which is rated by the manufacturer as an assembly of plane.
the fan and the cabinet in which the fan has been
installed. As a draw-through unit, the performance 3. Determine Ps1 by averaging the static pressure
ratings for the fan section are based on operation measurements made in a traverse of Plane 1. Ps5
with the fan outlet ducted. Before proceeding with the may be determined in a similar manner or by
test, it is essential that all dampers--outside air, return averaging the pressure measurements at each of
air, mixing box, multizone, face and bypass, or four static pressure taps. If it is possible to install
volume control--be fixed in the positions agreed upon suitable pressure taps, their use is preferred in the
by all interested parties as being applicable for the region of the fan outlet. due to the close proximity of
installation. Also, the temperatures of heating and Planes 2 and 5, and the fact that there is no change
cooling coils must be kept constant throughout the in area between the two planes, the conditions which
test period. It may be necessary to lock out, exist at Plane 5 are assumed to exist at Plane 2.
disconnect, or otherwise modify automatic control Measure the area of Plane 1 for use in calculating
devices in order to prevent the positions of the Pv1.
dampers and temperatures of the coils from changing
during the test. Refer to Section 17.4.2 for additional 4. Measure the dry-bulb and wet-bulb temperatures
considerations affecting the test procedure in this at Plane 3 and the dry-bulb temperatures at Planes 1
type of installation. and 5. Determine pb for the general vicinity of the air
conditioning unit. These measurements are used to
2. Determine Pv3 by using the root mean square of determine densities at the planes of interest.
the velocity pressure measurements made in a
traverse of Plane 3, located near the end of a straight 5. Measure the fan speed and the motor amps, volts,
run of duct, as shown in the diagram. Determine Ps3 and if possible, watts. Record all pertinent motor
by averaging the static pressure measurements nameplate data, including volts (NPV), and full load
made in the same traverse. This static pressure value amps (FLA). If the motor power output is to be
is used to determine the density at the traverse estimated by using the phase current method
plane. Procedures for traverses are described in described in Annex K, it is not necessary to measure
Ps = Ps2 - Ps1 - Pv1 + SEF 1 Fan connected to motor through belt drive.
Where: CALCULATIONS
td3 = 49.3°F
The calculation of Pv1 is often ignored in instances
tw3 = 47.3°F
similar to this example on the basis that the
calculated value of Pv1 is relatively small, and it
p3 = pb + (Ps3/13.6)
omission does not affect the test results significantly.
= 29.27 + (1.31/13.6)
8. In order to compare the test results to the quoted = 29.37 in. Hg
fan section curve drawn for operation at 1430 rpm
Use Figure N.1 in Annex N to obtain ρ3 = 0.0762
and 0.075 lbm/ft3 density, it is necessary to convert
the results to the specified conditions. The basis for lbm/ft3.
the calculations is described in Section 14.
⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
OBSERVATIONS ρ1 = ρ3 ⎜ s1 ⎟⎜ ⎟
⎝ 13.6 p3 ⎠ ⎝ t d1 + 460 ⎠
SITE MEASUREMENTS ⎛ −0.847 + 13.6 × 29.27 ⎞ ⎛ 509.3 ⎞
= 0.0762 ⎜ ⎟ ⎜ 507.5 ⎟
⎝ 13.6 × 29.37 ⎠⎝ ⎠
pb = 29.27 in. Hg = 0.0760 lbm/ftt 3
td1 = 47.5°F
td3 = 49.3°F
tw3 = 47.3°F ⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
ρ5 = ρ3 ⎜ s5 ⎟⎜ ⎟
td5 = 49°F ⎝ 13.6 p3 ⎠ ⎝ t d5 + 460 ⎠
Ps1 = -0.847 in. wg
⎛ 1.39 + 13.6 × 29.27 ⎞ ⎛ 509.3 ⎞
Ps3 = 1.31 in. wg = 0.0762 ⎜ ⎟ ⎜ 509 ⎟
⎝ 13.6 × 29.37 ⎠⎝ ⎠
Pv3 = 0.294 in. wg
Ps5 = 1.39 in. wg = 0.0763 lbm/ft 3
N = 1402 rpm
A1 = 147.2 ft2 It is assumed ρ2 = ρ5.
A2 = A3 = A5
= 15.42 ft2 FLOW RATES
Blast Area = 9.4 ft2
L = 2.0 ft, length of outlet duct V3 = 1096 (Pv3/ρ3)0.5
= 1096 (0.294/0.0762)0.5
= 2153 fpm
Q2 = Q5 = (L/11.1) 100
= Q3 (ρ3/ρ5) = (2.0/11.1) 100
= 18%
= 33199 (0.0762/0.0763)
= 33155 cfm
Blast area ratio = Blast Area/A2
FAN POWER INPUT = 9.4/15.42
= 0.61
Measured amps/FLA = (47.7/49.7)
= 0.96 For a blast area ratio of 0.6, 18% effective duct length
= 96% and elbow position A, Figure 8.5 shows System
Effect Curve R applies. For 2150 fpm velocity and
Annex K indicates that Equation A will provide a curve R, Figure 7.1 shows SEF 1 = 0.34 in. wg at
reasonably accurate estimate of motor power output 0.075 lbm/ft3 density. At 0.0762 lbm/ft3:
for a 40 hp motor operating at 96% FLA.
SEF 1 = 0.34 (0.0762/0.075)
Hmo = 40 (47.7/49.7) (442/440) = 0.35 in. wg
= 38.6 hp
FAN SECTION STATIC PRESSURE
Figure L.1 in Annex L indicates estimated belt drive
loss of 4.5%. Pv1 = (Q1/1096 A1)2 ρ1
= (33286/1096 × 147.2)2 0.0760
HL = 0.045 Hmo = 0.003 in. wg
= 0.045 × 38.6
= 1.74 hp It is assumed that Ps2 = Ps5
De2 = (4 A2/π)0.5
= (4 × 15.42/π)0.5
= 4.43 ft
3
2
SEF 1
4 1 PLAN VIEW
INLET PLENUM FILTERS FANS 5
COMMENTS
1. The subject of the test in this example is the air 3. Ps4 may be determined by averaging the pressure
conditioning unit assembly. This assembly does not measurements at each of four static pressure taps or
include the inlet plenum. The performance ratings for by averaging the static pressure measurements
the unit assembly are based on operation with the made in a Pitot-static tube traverse of Plane 4. Ps5 is
outlets of the fans ducted. Before proceeding with the determined in a similar manner. However, if it is
test, it is essential that all system dampers be fixed in possible to install suitable static pressure taps, their
the positions agreed upon by all interested parties as use is preferred in the regions of the outlets of the
being applicable for the installation. Also, the fans. Due to the close proximity of Planes 1 and 4
temperature of the cooling coil must be kept constant and the fact that there is no change in area between
throughout the test period. It may be necessary to the two planes, the conditions which exist at Plane 4
lock out, disconnect or otherwise modify automatic are assumed to exist at Plane 1. Although Plane 5 is
control devices in order to prevent the positions of the greater in area that Plane 2, the degree of divergence
dampers and the temperature of the coil from is relatively small. Therefore, Ps2 will be calculated
changing during the test. Refer to Section 17.4.1 for based on Ps5 and the assumption that there is no
additional considerations affecting the test procedure change in total pressure from Plane 2 to Plane 5.
in this type of installation.
4. Measure the dry-bulb and wet-bulb temperatures
2. Determine Pv3 by using the root mean square of at Plane 4 and the dry-bulb temperatures at Planes 3
the velocity pressure measurements made in a and 5. In this example, the cooling medium, normally
traverse of Plane 3, located near the end of a straight circulated in the coil was shut off in order to maintain
run of duct, as shown in the diagram. Determine Ps3 constant air temperatures during the test. In order to
by averaging the static pressure measurements account for water vapor which may have been added
made in the same traverse. This static pressure value to the air as a result of evaporation of moisture
is used to determine the density at the traverse previously condensed on the coil, the wet-bulb
plane. Procedures for traverses are described in temperature at Plane 3 was measured. Determine pb
Section 9.4. in order to determine the air flow rate, it for the general vicinity of the air conditioning unit.
is necessary to measure the area of the traverse These measurements are used in determining
plane. densities at the planes of interest.
FLOW RATES Duct diameter equivalent to the outlet area of one fan:
Q3 = V3A3 Figure 8.3 shows that for velocities over 2500 fpm,
= 2390 × 16.4 100% effective duct length is one diameter for every
= 39196 cfm 1000 fpm:
Q2 = Q5 = De2 (V2/1000)
= Q3 (ρ3/ρ5) = 2.71 (3404/1000)
= 39196 (0.0736/0.0737) = 9.22 ft
= 39143 cfm
L in % effective duct length:
Q = Q1 = Q4
= Q3 (ρ3/ρ4) = (L/9.22) 100
= (2.0/9.22) 100
= 39196 (0.0736/0.0735)
= 22%
= 39249 cfm
Blast area ratio = Blast area/A2
FAN POWER INPUT
= (2 × 4.0)/11.5
Measured amps/FLA = (38.0/39.5) = 0.70
= 0.96
= 96% For a blast area ratio of 0.7, and 22% effective duct
length Figure 8.3 shows System Effect Curve W
Annex K indicates that Equation A will provide a applies. For 3404 fpm velocity and curve W, Figure
reasonably accurate estimate of motor power output 7.1 shows SEF 1 = 0.13 in. wg at 0.075 lbm/ft3
for a 25 hp motor operating at 96% FLA. density. At 0.0737 lbm/ft3:
Figure L.1 in Annex L indicates estimated belt drive STATIC PRESSURE OF UNIT
loss of 4.8%.
Pv5 = (Q5/1096 A5)2 ρ5
HL = 0.048 Hmo = (39143/1096 × 14.3)2 0.0737
= 0.048 × 24.1 = 0.46 in. wg
= 1.2 hp
Pv2 = (Q2/1096 A2)2 ρ2
H = Hmo - HL = (39143/1096 × 11.5)2 0.0737
= 24.1 - 1.2 = 0.71 in. wg
= 22.9 hp
Qc = 39249 (1050/1025)
= 40206 cfm
3a
3b
PLAN VIEW
5
L
2
FILTER SECTION
SEF 1 1
+ +
SIDE VIEW
COMMENTS
1. The subject of the test in this example is the air pressure at each traverse plane is determined by
conditioning unit assembly. This assembly includes using the root mean square of the velocity
the filter section and the inlet louver. The measurement traverse in each of two branches. The
performance ratings for the unit assembly are based velocity pressure for each branch is determined by
on operation with the outlets of the fans ducted. using the root mean square of the velocity pressure
Before proceeding with the test, it is essential that all measurements made in the traverse. The static
system dampers be fixed in the positions agreed pressure at each traverse plane is determined by
upon by all interested parties as being applicable for averaging the static pressure measurements made in
the installation. Also, the temperature of the heating the same traverse. These static pressure values are
coil must be kept constant throughout the test period. used in determining the densities at the traverse
It may be necessary to lock out, disconnect or planes. Procedures for traverses are described in
otherwise modify automatic control devices in order Section 9.4. In order to determine the air flow rates, it
to prevent the positions of the dampers and the is necessary to measure the area of each traverse
temperature of the coil from changing during the test. plane.
Refer to Section 17.5.1 for additional considerations
affecting the test procedure in this type of installation. 3. Determine Ps5 by averaging the pressure
measurements at each of four static pressure taps
2. Normally, velocity pressure measurements would located in the duct fitting at the outlets of the fans.
be made in a single plane, located in a duct common The conditions which exist at Plane 5, including the
to all branches. In this example, a measurement static pressure, are assumed to exist at Plane 2,
plane which provides a satisfactory velocity profile based on their close proximity and the fact that there
cannot be located upstream of the fans or between is no change in area between the two planes. In
the point of connection of the branch ducts and the situations such as this example, it is important to be
outlets of the fans. The alternative, as indicated in the certain that all pressure measurements are referred
diagram, is to make a velocity pressure to the same atmospheric pressure.
measurement traverse in each of two branches. the
velocity pressure for reach branch is determined by 4. Measure the dry-bulb and wet-bulb temperatures
using the root mean square of the velocity pressure at Plane 1 and the dry-bulb temperatures at Planes
measurements made in the traverse. The static 3a, 3b, and 5. Determine pb for the general vicinity of
= (L/5.52) 100
= (0.96/5.52) 100
= 17%
Ps2 = Ps5
= 1.25 in. wg
Ps = Ps2 + SEF 1
= 1.25 + 0.41
= 1.66 in. wg
Qc = 16128 (1720/1710)
= 16222 cfm
2
1
5 STATIC PRESSURE TAPS
PLAN VIEW 3b 3a
RETURN
AIR SPRAY HEATING COIL
SECTION
+
+ +
+
OUTSIDE +
AIR +
+ +
SIDE VIEW
COMMENTS
1. This is a factory assembled, blow-through central be made in a single plane, located in a duct common
station unit. The subject of the test is the fan section, to all branches. In this example, a measurement
which is rated by the manufacturer as an assembly of plane which provides a satisfactory velocity profile
the fan and the cabinet in which the fan has been cannot be located upstream of the fan or between the
installed. As a blow-through unit, the performance point of connection of the branch ducts and the fan
ratings for the fan section are based on operation outlet. The alternative, as indicated in the diagram, is
without the fan outlet ducted. Before proceeding with to make a velocity pressure measurement traverse in
the test, it is essential that all dampers (outside air, each branch. The velocity pressure for each branch
return air, mixing box, multizone, face and bypass, or is determined by using the root mean square of the
volume control) be fixed in the positions agreed upon velocity pressure measurements made in the
by all interested parties as being applicable for the traverse. The static pressure at each traverse plane
installation. Also, the temperatures of heating and is determined by averaging the static pressure
cooling coils must be kept constant throughout the measurements made in the same traverse. These
test period. It may be necessary to lock out, static pressure values are used in determining the
disconnect, or otherwise modify automatic control densities at the traverse plane. Procedures for
devices in order to prevent the positions of the traverses are described in Section 9.4. In order to
dampers and temperatures of the coils from changing determine the air flow rates it is necessary to
during the test. In instances in which a cooling coil is measure the area of each traverse plane.
located between a velocity pressure traverse plane
and the fan, as in this example, the flow of the cooling 3. Determine Ps1 by averaging the static pressure
medium should be stopped or its temperature raised measurements made in a traverse of Plane 1. Ps5
to a level sufficient to prevent condensation on the may be determined in a similar manner or by
cooling coil, otherwise the moisture condensed will averaging the pressure measurements at each of
not be properly taken into account in the four static pressure taps. If it is possible to install
determination of fan air flow rate. Refer to Section suitable pressure taps, their use is preferred in the
17.5.2 for additional considerations affecting the test regions of the fan outlet. Due to the abrupt expansion
procedure in this type of installation. in area from Plane 2 to Plane 5, it is assumed that
there is no conversion of velocity pressure at Plane 2
2. Normally, velocity pressure measurements would to static pressure at Plane 5. Therefore, it is assumed
Where: CALCULATIONS
TEMPORARY DUCT 2 De
WITH SQUARE
CROSS-SECTION, 1.5 De
De = EQUIVALENT
DIAMETER OF DUCT
COMMENTS
1. The subject of the test in this example is the roof be discharging from the ventilator into a region in
ventilator assembly. Before proceeding with the test, which the atmospheric pressure is somewhat
refer to Section 17.4 for considerations affecting the different from that to which all other pressure
test procedure in this type of installation. measurements are referred. When this possibility
exists, it is essential that the static pressure in the
2. Determine Pv3 by using the root mean square of region of the discharging air be measured, referred to
the velocity pressure measurements made in a the same atmospheric pressure as used in all other
traverse of Plane 3, located in the duct which has pressure measurements. In this example, Ps2 was
been installed on the inlet side of the ventilator. measured, referred to the same atmospheric pressure
Determine Ps3 by averaging the static pressure as in the static pressure measurements made at
measurements made in the same traverse. Plane 3.
Procedures for traverses are described in Section
9.4. Measure the area of the traverse plane, A3, 4. Measure the dry-bulb and wet-bulb temperatures
which is located at the tip of the Pitot-static tube. The at the velocity traverse plane. Determine pb for the
duct, temporarily installed for purposes of the test, is general vicinity of the ventilator. These measurements
square in cross-section. Its cross-sectional dimensions are used to determine densities at the planes of interest.
were selected as the maximum permissible for its
installation into the opening in the ventilator mounting 5. Measure the fan speed and the motor amps and
curb. The length of the duct is twice its equivalent volts. Record all pertinent motor nameplate data. For
diameter and the entrance to the duct is flared in oder the horsepower rating of the motor in this example, it
to reduce inlet losses. The installation of a duct of this is recommended that the fan power input be
size and cross-sectional configuration is judged as determined by using the measured watts input to the
creating no significant effect on the performance of motor and motor performance data, obtained from
the ventilator in this example. the motor manufacturer.
3. Ps2, the static pressure at the outlet of the 6. To calculate the Fan Static Pressure:
ventilator, is zero gauge pressure, referred to the
atmospheric pressure in the region of the ventilator Ps = Ps2 - Ps1 - Pv1
outlet. In situations such as this example, the air may = Ps2 - (Ps1 + Pv1)
p3 = pb + (Ps3/13.6)
= 29.37 + (-0.085/13.6)
= 29.36 in. Hg
2 De
2
3
1.5 De
D2
TEMPORARY DUCT
WITH SQUARE
CROSS-SECTION,
De = EQUIVALENT
DIAMETER OF DUCT
COMMENTS
1. The subject of the test in this example is the such as this example, the air may be discharging
propeller fan assembly. Before proceeding with the from the fan into a region in which the atmospheric
test, refer to Section 17.4 for considerations affecting pressure is somewhat different from that to which all
the test procedure in this type of installation. other pressure measurements are referred. When
this possibility exists, it is essential that the static
2. Determine Pv3 by using the root mean square of pressure in the region of the discharging air be
the velocity pressure measurements made in a measured, referred to the same atmospheric
traverse of Plane 3, located in the duct which has pressure as used in all other pressure
been installed on the inlet side of the fan. Determine measurements. In this example, Ps2 was measured,
Ps3 by averaging the static pressure measurements referred to the same atmospheric pressure as in the
made in the same traverse. Procedures for traverses static pressure measurements made at Plane 3.
are described in Section 9.4. Measure the area of the
traverse plane, A3, which is located at the tip of the 4. Measure the dry-bulb and wet-bulb temperatures
Pitot-static tube. The duct, temporarily installed for at the velocity traverse plane. Determine pb for the
purposes of the test, is square in cross-section, with general vicinity of the fan. These measurements are
side dimension of 1.5 D2. The shape and area of the used to determine densities at the planes of interest.
duct cross-section were selected on the basis of
minimizing the effect of the duct on the performance 5. Measure the fan speed and the motor amps and
of the fan while providing velocity pressure readings volts. Record all pertinent motor nameplate data. For
of measurable magnitudes. The length of the duct is the horsepower rating of the motor in this example, it
twice its equivalent diameter, and the entrance to the is recommended that the fan power input be
duct is flared in order to reduce inlet losses. The determined by using the measured watts input to the
installation of the duct is judged as creating no motor and motor performance data obtained from the
significant effect on the performance of the fan in this motor manufacturer.
example.
6. To calculate the Fan Static Pressure:
3. Ps2, the static pressure at the outlet of the fan, is
zero gauge pressure, referred to the atmospheric Ps = Ps2 - Ps1 - Pv1
pressure in the region of the fan outlet. In situations = Ps2 - (Ps1 + Pv1)
Fan direct connected to motor. Motor efficiency data This small value is attributed to the loss at the duct
supplied by motor manufacturer. inlet, and the fan is considered to be operating at free
delivery (Ps = 0).
CALCULATIONS
CONVERSION TO SPECIFIED CONDITIONS
DENSITIES
Qc = 3279 (1725/1775)
For Plane 3 conditions of: = 3187 cfm
It is assumed that ρ1 = ρ3
COMMENTS
1. The subject of the test in this example is the roof 4. Measure the dry-bulb and wet-bulb temperatures
ventilator assembly. Before proceeding with the test, in the region of the inside pressure measurement.
refer to Section 17.1 for considerations affecting the Also, determine pb in the same vicinity.
test procedure in this type of installation.
5. Measure the fan speed and the motor amps and
2. Ps3, the static pressure in the vicinity of the volts. Record all pertinent motor nameplate data. For
ventilator inlet, would normally be determined by the horsepower rating of the motor in this example, it
averaging the static pressure measurements made in is recommended that the fan power input be
a Pitot tube traverse. But in this example, a determined by using the measured watts input to the
temporary duct was not installed and the Pitot tube motor and motor performance data obtained from the
traverse could not be accomplished. In this method motor manufacturer.
for testing a nonducted fan, consider the fan static
pressure (Ps) as the differential pressure, as read on 6. Airflow rates are determined from the fan
a manometer, between the pressure measured inside manufacturer’s certified performance ratings. Draw a
the room (Ps3) and the pressure measured outside fan performance curve from these ratings converted
the room in the vicinity of the ventilator outlet (Ps2). to operation at the test values of fan speed and
These pressures are measured at a sufficient entering air density. The basis for these calculations
distance from the ventilator so as to be unaffected by is described in Section 14. The fan airflow rate is then
the velocity of the entering or leaving air. determined by entering this curve at the test values of
fan static pressure and fan power input.
3. Ps2 is considered to be zero gauge pressure, but
since this measurement is actually part of the OBSERVATIONS
differential pressure described in paragraph 2, it is
necessary to make only one density correction; the SITE MEASUREMENTS
correction is to the differential pressure, which is the
fan static pressure. pb = 29.19 in. Hg
td3 = 79°F
tw3 = 63°F
Ps2 - Ps3 = 0.13 in. wg
N = 1735 rpm
Volts = 229, 229, 232 The fan static pressure is considered to be the
= 230 av differential static pressure.
Watts = 1390
Ps = Ps2 - Ps3
MOTOR NAMEPLATE DATA = 0.13 in. wg
Use:
.40 1.50
x
x BHP
BHP (H)
x
.30 1.25
.20 1.00
STATIC PRESSURE IN. WG (Ps)
x
.10
SP
0 x
7000 8000 9000
CFM(Q)
16D 8D
0.4D
3D Radius D
Static Pressure
Note: Surface finish shall be 32 micro in. or better. The static
orifices may not exceed 0.04 in. diameter. The minimum Pitot
tube stem diameter recognized under this standard shall be
0.10 in. In no case shall the stem diameter exceed 1/30 of the
Total Pressure test duct diameter.
Figure B.1
Field Performance Measurement | 241
Annex C. Double Reverse Tubes
AIR FLOW
TUBE ENDS MUST BE SMOOTH
AND FREE FROM BURRS
SECTION VIEW
STAINLESS STEEL
TUBING PREFERRED
APPROX. 0.375 in. OD
FLEXIBLE TUBING
TOTAL PRESSURE = READING A
CORRECTED FOR MANOMETER
CALIBRATION
READING A ING B
READ
Notes:
DUCT WALL
1½ in. PIPE
HALF-COUPLING
WELDED TO DUCT
Notes:
*SEF 1
Ps4 Ps3
FAN STATIC PRESSURE
Ps = - Ps1 - Pv1 + SEF 1
where Ps1 = Ps4 P v3
Pv1 = Pv3
Figure F.1 - Fan with Inlet Duct Only *SEF 1 is due to
Ps2 = 0
no duct at fan outlet
PLANE 3 PLANE 5 PLANE 2 PLANE 1
ALTERNATE
PLANE 3 PLANE 5 PLANE 2 PLANE 1 PLANE 4 PLANE 3
10 in. wg
1:1
SLOPE
RATIO
2 in. wg
5:1 SLOPE RATIO
Based on an uncertainty equivalent to an indicating column length of 0.05 in. wg in a vertical manometer (1:1 slope
ratio)
8.0
6.0
5.0
4.0
% UNCERTAINTY IN VELOCITY DETERMINATION
3.0
2.0
1.0
MA OPE
SL
NO RA
0.8
ME TIO
TE
0.6 1:1
R
0.5
2:1
0.4
5:1
10
20
:1
:1
0.3
0.2
In order to obtain a representative average velocity in a duct, it is necessary to locate each traverse point
accurately. It is recommended that the number of traverse points increase with increasing duct size. The
distributions of traverse points for circular ducts, as indicated below, are based on log-linear Pitot traverse method.
60º X1 X2
X3
X4
D Xn
Xa = D × Ka
Where:
D is the inside diameter of the duct
Ka is the factor corresponding to the duct size and the traverse point location as indicated in the table below
NUMBER OF
INSIDE TRAVERSE
DIAMETER POINTS IN K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 K14 K15 K16
OF DUCT EACH OF 3
DIAMETERS
LESS THAN
8 .021 .117 .184 .345 .655 .816 .883 .979
8 ft.
8 ft.
THROUGH 12 .014 .075 .114 .183 .241 .374 .626 .759 .817 .886 .925 .986
12 ft.
GREATER
16 .010 .055 .082 .128 .166 .225 .276 .391 .609 .724 .775 .834 .872 .918 .945 .990
THAN 12 ft.
Y Y
X
2 2
100
90
80
70
NUMBER OF TRAVERSE POINTS
60
50
40
30
25
20
15
10
10 15 20 25 30 40 50 60 70 80 100 150 200 250 300
Approximate Precision
Range
No. Measurement Means Application F F Limitations
1. Glass-stem thermometers
Mercury-glass thermometer Temp of gases and liquids by contact -38/575 Less than In gases, accuracy af-
0.1 to 10 fected by radiation
Alcohol-glass thermometer ” -100/100 ” ”
Pentane-glass thermometers ” -200/70 ” ”
Jena or quartz mercury nitrogen
thermometers ” -38/1000 ” ”
2. Gas thermometer Primary standard -459/1000 Less than Requires consid-
0.01 erable skill to use
3. Resistance thermometers
Platinum-resistance thermometer Precision; remote readings; temp of -320/1800 Less than High cost; accuracy
fluids or solids by contact 0.02 to 5 affected by radiation
in gases
Nickel-resistance thermometer Remote readings; temp by contact -150/300 0.3 Accuracy affected by
radiation in gases
Thermistors ” Up to 600 0.1
4. Thermocouples
Pt-Pt-Rh thermocouple Standard for thermocouples 500/3000 0.1 to 5 High cost; also, re-
quires expensive
measuring device
Chromel-alumel thermocouple General testing of high temp; remote Up to 2200 0.1 to 15 Less accurate than
rapid readings by direct contact above
Iron-constantain thermocouple ” Up to 1500 0.1 to 15 Subject to oxidation
Copper-constantan thermocouple Same as above, especially suited for Up to 700 0.1 to 15
Chromel-constantan thermocouple low temp
5. Beckman thermometers For differential temp in same applica- 9 diff 0.018 Must be set for temp
(metastatic) tions as in glass stem thermometer to be measured
6. Bimetallic thermometers For approx temp 0/1000 1, usually Time lag; unsuitable
much more for remote use; un-
reliable
7. Pressure-bulb thermometers
Gas-filled bulb Remote-testing -100/1000 2 Caution must be ex-
ercised so that in-
stallation is correct
Vapor-filled bulb ” 20/500 2 ”
Liquid-filled bulb ” -50/2100 2 ”
8. Optical pyrometers For intensity of narrow spectra band 1500 upward 15
of high temp radiation (remote)
9. Radiation pyrometers For intensity of total high temp radi- Any range
ation (remote)
10. Seger cones (fusion pyrometers) Approx temp (within temp source) 1000/3600 50
11. Indicating crayons Approx temp (in surface) 125/900 ±1%
12. Melting and boiling points of Standards All except ex- Extremely For laboratory use
materials tremely high precise only
temp
100
90
RATED
HORSEPOWER
1
80 2
70
3
60
5
50
10
40
400
30
2500
20
10
0
0 10 20 30 40 50 60 70 80 90 100
% NAMEPLATE HORSEPOWER
CAUTION: THIS CHART IS REPRESENTATIVE ONLY! SINCE THE AMP-LOAD CHARACTERISTICS OF THE
SAME SIZE MOTOR WILL VARY BETWEEN THE VARIOUS MOTOR MANUFACTURERS, IT CANNOT BE USED
TO DETERMINE THE HORSEPOWER OUTPUT OF A MOTOR. USE THE EQUATIONS AS DIRECTED ON THE
PREVIOUS PAGE.
40
DRIVE LOSS, % MOTOR POWER OUTPUT*
30
15
10
8
6
4
3
1.5
1
0.3 0.4 0.6 0.8 1 2 3 4 6 8 10 20 30 40 60 80 100 200 300 400 600
*Drive losses are based on the conventional V-belt, which has been the “work horse” of the drive industry for
several decades.
EXAMPLE
Limit the use of the calculation procedure that is Using the data in Figure N.3 in Annex N, the
based on perfect gas relationships and illustrated in barometric pressure at 1000 ft above sea level is:
Example M2.3, to instances in which the dry-bulb
temperature is 180°F or less. Accurate wet-bulb pb = 29.82 × 0.964
temperature measurements are difficult to obtain = 28.75 in. Hg
when the dry-bulb temperature exceeds 180°F.
The absolute pressure at the fan inlet is:
When the dry-bulb temperature exceeds 180°F, it
may be necessary to rely on site personnel for the p1 = pb + (Ps1/13.6)
water vapor content of the air. Alternately,
= 28.75 + (-3.45/13.6)
commercially available instrumentation for dew point
= 28.50 in. Hg
determination may be used. For the procedure
required to determine density based on the data
The wet-bulb depression is:
provided in either of the above cases, refer to
Psychrometric Tables and Charts by Zimmerman and
td1 - tw1 = 85 - 75
Lavine.1
= 10°F
EXAMPLE M2.1
For dry-bulb temperature of 85°F, absolute pressure
of 28.50 in. Hg and wet-bulb depression of 10°F, use
The conditions that exist at the inlet of a fan that is
the Psychrometric Density Table in Figures N.5 in
not ducted on the inlet side are:
Annex N to obtain:
td1 = 78°F
ρ1 = 0.06829 + 10 × 0.000041
tw1 = 62°F
= 0.0687 lbm/ft3
1. O. T. Zimmerman and I. Lavine, Psychrometric Tables and Charts, 2nd ed. (Dover, N.H.: Industrial Research Service Inc., 1964)
The conditions at a fan inlet are: Dry air is entering a fan inlet, located at an elevation
of 1000 ft above sea level. The pressure and
Ps1 = -8.75 in. wg temperature at the inlet are:
td1 = 146°F
tw1 = 93°F Ps1 = -15 in. wg
td1 = 95°F
The barometric pressure, pb, measured for the
atmosphere to which Ps1 is referred, is 28.15 in. Hg. Barometric pressure, obtained from a nearby airport,
is 29.24 in. Hg at sea level.
The absolute pressure at the fan inlet is:
Using the data in Figure N.3 in Annex N, the
p1 = pb + (Ps1 /13.6) barometric pressure at 1000 ft above seal level is:
= 28.15 + (-8.75/13.6)
= 27.51 in. Hg pb = 29.24 × 0.964
= 28.19 in. Hg
Use Figure N.2 in Annex N to obtain saturated vapor
pressure, pe, of 1.562 in. Hg for the wet-bulb The absolute pressure at the fan inlet is:
temperature of 93°F.
p1 = pb + (Ps1/13.6)
Use the modified Apjohn equation for partial vapor = 28.19 + (-15/13.6)
pressure, pp, to obtain: = 27.09 in. Hg
pp = pe - p1 (td1 - tw1)/2700 Dry air at 29.92 in. Hg and 70°F has a density of
= 1.562 - 27.51 (146 - 93)/2700 0.075 lbm/ft3.
= 1.022 in. Hg
Consider the density of air to be directly proportional
ρ1 is calculated by using perfect gas relationships: to absolute pressure and inversely proportional to
absolute temperature. The density of the air at the fan
inlet is calculated as follows:
1.3257 ( p1 − 0.378 pp )
ρ1 = ρ1 = 0.075 (p1/29.92) [(70 + 460)/(td1 + 460)]
( td1 + 460 )
= 0.075 (27.09/29.92) [530/(95 + 460)]
= 0.0648 lbm/ft3
1.3257 ( 27.51 − 0.378 × 1.022 )
=
(146 + 460 ) EXAMPLE M3.2
Assuming the density of saturated air to be directly The apparent molecular weight of the gas is
proportional to absolute pressure is an determined as follows:
approximation. The uncertainty in the density
determination as a result of this approximation Volume Molecular
increases with increasing temperature and increases Component Fraction × Weight = lb/mole
with increasing variation between the actual absolute
pressure and 29.92 in. Hg, which is the stated CO2 0.055 44 2.42
pressure for the data in Figure N.4. The uncertainty
CO 0.01 28 0.28
will be approximately 1% or less under the following
O2 0.15 32 4.80
conditions:
H2 0.01 2 0.02
• At 120°F and at an absolute pressure within 20% N2 0.775 28 21.70
of 29.92 in. Hg
• At 150°F and at an absolute pressure within 10% 1.00 29.22
of 29.92 in. Hg
• At 180°F and at an absolute pressure within 4% of Apparent molecular weight = (29.22/1.00)
29.92 in. Hg = 29.22
M.4 DETERMINATION OF THE DENSITY OF A The density of the gas at 70°F and 29.92 in. Hg is
GAS OTHER THAN AIR calculated as follows:
The determination of the density of a gas other than Apparent molecular weight 29.22
air may require the use of complex equipment. =
386.7 386.7
Unless specifically qualified, an expert should be
consulted for the proper use of the equipment. If the
gas is a complex mixture of various consitutuents, as = 0.0756 lbm/ft 3
found in certain industrial processes, it is suggested
that the company chemist be consulted for the gas Using the data in Figure N.3 in Annex N, the
analysis. Particular care should be used if the gas is barometric pressure at 2000 ft above sea level is:
toxic, corrosive or explosive; and in these cases,
consideration should be given to substituting air for pb = 29.92 × 0.930
the test. = 27.83 in. Hg
The first two examples in this section illustrate gas The absolute pressure at the fan inlet is:
density determinations based on analyses that
provide the relative amounts of the gas constituents. p1 = pb + (Ps1/13.6)
Typical flue gas density data, which is provided in
= 27.83 + (-22/13.6)
Figure N.6 in Annex N, is illustrated in Example M4.3.
= 26.21 in. Hg
Since the actual density may be significantly different
from the density determined by using typical data, it
Consider the density of the gas to be directly
is recommended that the typical data be used only in
proportional to absolute pressure and inversely
the even that more specific information is not
proportional to absolute temperature. The density of
available.
the gas at the fan inlet is calculated as follows:
The apparent molecular weight of the gas is The absolute pressure at Plane 3 is:
determined as follows:
p3 = pb + (Ps3/13.6)
Volume Molecular = 28.85 + (5.74/13.6)
Component Fraction × Weight = lb/mole = 29.27 in. Hg
CO2 0.055 44 0.00125 Refer to Figure N.6 in Annex N to obtain typical flue
CO 0.01 28 gas density when natural gas is used as the fuel of
0.00036
O2 0.15 32 0.0725 lbm/ft3 at 70°F and 29.92 in. Hg.
0.0047
H2 0.01 2 0.005 Consider the density of the flue gas to be directly
N2 0.775 28 0.0277 proportional to absolute pressure and inversely
proportional to absolute temperature. The density of
1.00 0.0390 the gas at Plane 3 is calculated as follows:
= 0.0662 lbm/ft 3
p1 = pb + (Ps1/13.6)
= 29.35 + (-19.5/13.6)
= 27.92 in. Hg
38 0.061
36 0.062
1. Calculate wet-bulb depression. Enter chart at the left.
34 2. Proceed horizontally to the appropriate dry-bulb 0.063
temperature.
32 3. Read vertically to the absolute pressure. 0.064
4. Then read horizontally to the density.
30 Example 0.065
g
• Given: td = 54°F; tw = 50°F; pb = 29.9 in. Hg
28 28.0 0.066
in. H
28.2 Solution:
28.4 zontally to 54°F dry-bulb temperature;
26 read vertically to 29.9 in. Hg; read horizon- 0.067
URE
28.6 tally to the density -- ρ = 0.0769 lbm/ft3.
SS
28.8
24 29.0 0.068
PRE
29.2
TE
22 29.4 0.069
OLU
29.6
29.8
0.070
ABS
20
30.0
18 0.071
AIR DENSITY, lbm/ft3
16 0.072
WET-BULB DEPRESSION, °F
14 0.073
12 0.074
10 0.075
8 0.076
6 0.077
4 0.078
2 0.079
98 96 94 92 90 88 86 84 82 80 78 76 74 72 70 68 66 64 62 60 58 56 54 52 50 48 46 44 42
0 0.080
DRY-BULB TEMPERATURE, °F
Figure N.1 - Psychrometric Density Chart
Figure N.2 - Thermodynamic Properties of Water at Absolute Vapor Pressures, Inches of Mercury
Note: Specific gravity of standard air at sea level and 29.92 in. Hg = 1.00
1. Robert Jorgensen, ed., Fan Engineering, 7th ed. (Buffalo, NY, Buffalo Forge Co., 1970) p.8 - Reprinted by Permission
WEIGHT IN A WEIGHT IN A
WEIGHT OF WEIGHT OF
CUBIC FOOT VOLUME CUBIC FOOT VOLUME
THE VAPOR THE VAPOR
OF MIXTURE OF MIXTURE
Temp ft3/lb Temp ft3/lb
°F OF °F OF
TOTAL lb/lb lb/lb TOTAL lb/lb lb/lb
DRY AIR VAPOR DRY AIR VAPOR
WEIGHT DRY AIR OF OF WEIGHT DRY AIR OF OF
lb lb lb lb
lb DRY AIR MIXTURE lb DRY AIR MIXTURE
-25 .09134 .000018 .09136 10.95 .00020 .00020 46 .07768 .000509 .07819 12.87 .00655 .00651
-20 .09025 .000024 .09027 11.07 .00027 .00027 47 .00750 .000527 .07803 12.90 .00680 .00675
-15 .08922 .000031 .08925 11.21 .00035 .00035 48 .07731 .000545 .07785 12.93 .00705 .00700
-10 .08820 .000041 .08824 11.34 .00046 .00046 49 .07714 .000567 .07771 12.96 .00734 .00728
-5 .08723 .000053 .08728 11.46 .00061 .00061 50 .07694 .000587 .07753 12.99 .00762 .00756
0 .08625 .000068 .08632 11.59 .00080 .00080 51 .07676 .000608 .07737 13.02 .00792 .00786
5 .08529 .000087 .08538 11.72 .00102 .00102 52 .07657 .000632 .07720 13.06 .00823 .00819
10 .08434 .000110 .08445 11.85 .00130 .00130 53 .07637 .000651 .07702 13.09 .00854 .00845
15 .08340 .000140 .08354 11.99 .00168 .00168 54 .07620 .000675 .07687 13.12 .00884 .00877
20 .08247 .000176 .08264 12.12 .00213 .00213 55 .07600 .000700 .07670 13.15 .00921 .00913
21 .08230 .000185 .08248 12.15 .00225 .00224 56 .07582 .000723 .07654 13.19 .00952 .00943
22 .08210 .000193 .08229 12.18 .00235 .00234 57 .07562 .000749 .07637 13.22 .00989 .00980
23 .08193 .000202 .08213 12.20 .00246 .00245 58 .07544 .000775 .07622 13.25 .01026 .01016
24 .08173 .000213 .08194 12.23 .00260 .00259 59 .07524 .000801 .07604 13.29 .01063 .01052
25 .08156 .000222 .08178 12.26 .00272 .00271 60 .07506 .000829 .07589 13.32 .01103 .01091
26 .08136 .000233 .08159 12.29 .00285 .00284 61 .07486 .000857 .07572 13.35 .01143 .01130
27 .08117 .000243 .08141 12.32 .00300 .00299 62 .07468 .000886 .07557 13.39 .01185 .01171
28 .08099 .000254 .08124 12.34 .00314 .00313 63 .07447 .000916 .07539 13.42 .01229 .01214
29 .08083 .000264 .08109 12.37 .00328 .00327 64 .07429 .000947 .07524 13.46 .01273 .01257
30 .08063 .000277 .08090 12.40 .00345 .00344 65 .07408 .000979 .07506 13.49 .01320 .01303
31 .08043 .000290 .08072 12.43 .00362 .00361 66 .07390 .001012 .07491 13.53 .01368 .01349
32 .08025 .000303 .08055 12.46 .00378 .00376 67 .07369 .001045 .07473 13.57 .01417 .01397
33 .08006 .000315 .08038 12.49 .00393 .00392 68 .07350 .001080 .07458 13.60 .01468 .01447
34 .07989 .000327 .08022 12.51 .00409 .00408 69 .07330 .001115 .07441 13.64 .01520 .01497
35 .07970 .000339 .08004 12.54 .00426 .00425 70 .07310 .001152 .07425 13.68 .01576 .01551
36 .07952 .000353 .07987 12.57 .00444 .00442 71 .07290 .001189 .07409 13.71 .01630 .01604
37 .07933 .000364 .07969 12.60 .00460 .00458 72 .07270 .001229 .07393 13.75 .01691 .01662
38 .07916 .000380 .07954 12.63 .00480 .00478 73 .07250 .001268 .07377 13.79 .01748 .01717
39 .07897 .000394 .07936 12.66 .00499 .00496 74 .07229 .001310 .07360 13.83 .01812 .01780
40 .07880 .000409 .07921 12.69 .00519 .00516 75 .07208 .001352 .07343 13.87 .01876 .01841
41 .07860 .000425 .07902 12.72 .00541 .00538 76 .07188 .001395 .07328 13.91 .01941 .01904
42 .07843 .000440 .07887 12.75 .00561 .00558 77 .07166 .001439 .07310 13.95 .02008 .01968
43 .07825 .000456 .07871 12.78 .00583 .00579 78 .07144 .001485 .07293 13.99 .02079 .02036
44 .07805 .000473 .07852 12.81 .00606 .00602 79 .07124 .001532 .07277 14.03 .02150 .02106
45 .07788 .000491 .07837 12.84 .00630 .00626 80 .07104 .001579 .07262 14.08 .0223 .02174
Figure N.4 - Weights of Air, Water Vapor, and Saturated Mixture of Air and
Water Vapor at Different Temperatures and 29.92 in. Hg
WEIGHT IN A WEIGHT IN A
WEIGHT OF WEIGHT OF
CUBIC FOOT VOLUME CUBIC FOOT VOLUME
THE VAPOR THE VAPOR
OF MIXTURE OF MIXTURE
Temp ft3/lb Temp ft3/lb
°F OF °F OF
TOTAL lb/lb lb/lb TOTAL lb/lb lb/lb
DRY AIR VAPOR DRY AIR VAPOR
WEIGHT DRY AIR OF OF WEIGHT DRY AIR OF OF
lb lb lb lb
lb DRY AIR MIXTURE lb DRY AIR MIXTURE
81 .07081 .001629 .07244 14.12 .02301 .02249 116 .06186 .004427 .06629 16.16 .07157 .06678
82 .07059 .001680 .07227 14.16 .02380 .02325 117 .06154 .004548 .06609 16.24 .07390 .06882
83 .07038 .001733 .07211 14.21 .02462 .02403 118 .06124 .004669 .06591 16.32 .07625 .07084
84 .07015 .001785 .07193 14.26 .02545 .02482 119 .06092 .004794 .06571 16.41 .07869 .07296
85 .06993 .001840 .07177 14.30 .02631 .02566 120 .06060 .004921 .06552 16.50 .08121 .07511
86 .06970 .001898 .07160 14.34 .02723 .02651 121 .06027 .005049 .06532 16.58 .08376 .07729
87 .06947 .001954 .07142 14.39 .02813 .02736 122 .05995 .005183 .06513 16.68 .08646 .07958
88 .06925 .002014 .07126 14.44 .02908 .02826 123 .05960 .005319 .06492 16.77 .08925 .08194
89 .06902 .002072 .07109 14.48 .03002 .02915 124 .05927 .005456 .06473 16.87 .09204 .08428
90 .06880 .002139 .07094 14.53 .03109 .03015 125 .05892 .005598 .06452 16.96 .09502 .08677
91 .06855 .002201 .07075 14.58 .03211 .03111 130 .05713 .006355 .06349 17.49 .11125 .10010
92 .06832 .002267 .07058 14.63 .03318 .03212 135 .05524 .007195 .06244 18.10 .13026 .11523
93 .06809 .002334 .07042 14.69 .03428 .03314 140 .05319 .008128 .06132 18.79 .15280 .13255
94 .06785 .002404 .07025 14.73 .03543 .03422 145 .05100 .009162 .06016 19.60 .17966 .15230
95 .06760 .002474 .07007 14.79 .03660 .03531 150 .04865 .010303 .05895 20.55 .21178 .17478
96 .06736 .002546 .06991 14.84 .03780 .03642 155 .04612 .011547 .05767 21.67 .25038 .20022
97 .06711 .002620 .06973 14.90 .03904 .03757 160 .04340 .012937 .05634 23.03 .29810 .22962
98 .06688 .002692 .06957 14.95 .04025 .03870 165 .04048 .014436 .05492 24.69 .35660 .26285
99 .06660 .002770 .06931 15.01 .04159 .03993 170 .03734 .016118 .05346 26.77 .43168 .30150
100 .06634 .002853 .06919 15.07 .04300 .04124 175 .03398 .017926 .05191 29.43 .52750 .34530
101 .06610 .002937 .06904 15.12 .04443 .04255 180 .03035 .019905 .05036 32.94 .65580 .39525
102 .06583 .003019 .06885 15.18 .04586 .04385 185 .02645 .022062 .04851 37.78 .83410 .45425
103 .06557 .003106 .06868 15.25 .04737 .04523 190 .02228 .024393 .04667 44.85 1.0948 .52270
104 .06530 .003193 .06849 15.31 .04890 .04662 195 .01779 .026957 .04475 56.20 1.5153 .60240
105 .06504 .003283 .06832 15.37 .05048 .04806 200 .01297 .029730 .04270 77.11 2.2923 .69660
106 .06477 .003375 .06814 15.44 .05212 .04953 205 .00782 .032715 .04064 127.9 4.1838 .80500
107 .06451 .003470 .06798 15.50 .05379 .05105 210 .00232 .035942 .03836 431.0 15.493 .93700
108 .06421 .003568 .06778 15.57 .05556 .05264 212 .00000 .037298 .03730 ____ Inf. 1.0000
109 .06394 .003666 .06761 15.64 .05734 .05422
110 .06364 .003766 .06741 15.71 .05917 .05587
Figure N.4 - Weights of Air, Water Vapor, and Saturated Mixture of Air and
Water Vapor at Different Temperatures and 29.92 in. Hg
Note: Approximate average decrease in density per 0.1°F rise in dry-bulb temperature equals .000017 lbm/ft3.
Note: Approximate average decrease in density per 0.1°F rise in dry-bulb temperature equals .000017 lbm/ft3.
OIL 0.075
BAGASSE 0.070
LIGNITE 0.073
WOOD 0.070
The above densities at 70°F and 29.92 in. Hg are based on average fuel analyses and moisture contents
BLAST AREA
DISCHARGE DUCT
OUTLET AREA
CUTOFF
25%
50%
75%
CENTRIFUGAL FAN
100% EFFECTIVE DUCT LENGTH
AXIAL FAN
To calculate 100% effective duct length, assume a minimum of 2½ duct diameters for 2500 fpm or less. Add 1 duct
diameter for each additional 1000 fpm.
If the duct is rectangular, with side dimensions equal to a and b, the equivalent duct diameter is equal to (4ab/π)0.5
CASING
BACKPLATE
RIM
HUB INLET
MOTOR BLADE
GUIDE VANE
IMPELLER
INLET BELL
CASING
BLADE
DIFFUSER
HUB
MOTOR
IMPELLER
CASING
BLADE
HUB
GUIDE VANE
Vaneaxial Fan-Belt Drive
IMPELLER
MECHANISM FOR
CONTROLLING
INLET BOX BEARINGS GUIDE VANES BLADE ANGLE
FAN
CASING
INNER CYLINDER
IMPELLER
DIFFUSER
Vaneaxial Mechanical Draft Fan
Figure R.1 - Common Terminology for Axial and Tubular Centrifugal Fans
DIVERTER
FF
TO
CU
CENTER PLATE
BLAST AREA
DISCHARGE
OUTLET AREA
SIDE SHEET
BACKPLATE
BLADE FF
TO
CU
INLET
SCROLL
IMPELLER
FRAME
RIM
BEARING
SUPPORT
INLET COLLAR
+ +
DRIP TRAY
HOT DECK
+
+ +
+
COLD DECK
CC
+ + +
FLEXIBLE CONNECTION
AS ACCESS SECTION EXT F & BP EXTERNAL FACE AND BYPASS DAMPER FS FAN SECTION
CS COIL SECTION INT F & BP INTERNAL FACE AND BYPASS DAMPER FB FILTER BOX
CC COOLING COIL ELIM ELIMINATORS MB MIXING BOX
HC HEATING COIL SS SPRAY SECTION
MOTOR DESCRIPTION: Mfgr., Nameplate Data (Ident. No., hp, volts, FLA, . . . ), Performance Data
Reference, . . . . .
DRIVE DESCRIPTION: Type, Mfgr., Ident. No., Size, . . . . .
REFERENCE DRAWINGS OR
SKETCHES OF INSTALLATION: System Configuration with Dimensions, Measurement Plane
Locations, . . . . .
MEASUREMENTS
AMBIENT DATA: Barometric Pressure, Dry-Bulb Temp., Wet-Bulb Temp, . . . . .
FAN SPEED
•
•
•
•
n
TOTAL
AVERAGE
CALCULATIONS: (Refer to the various sections of this publication for the appropriate calculation
procedures.)
T.4.2 Dry-bulb temperature. The estimated The estimated uncertainty is based on a broad range
uncertainty in measuring dry-bulb temperature is of duct sizes, accessibility, and the rigidity of ducts
between 0.5% of absolute temperature minimum and under pressure.
2.0% of absolute temperature maximum.
T.4.8 Velocity pressure. An allowance of 2.0%
ed = 0.005 (min) to 0.02 (max) minimum to 5.0% maximum of the reading is
estimated for the mental averaging performed on a
The estimated uncertainty range is based on a broad fluctuating reading. An allowance of 1.0% minimum
temeprature range and the likelihood of stratification. to 2.0% maximum of the reading is estimated for
calibrated manometer uncertainty and relocation of
T.4.3 Web-bulb depression. The estimated the instrument after calibration. In addition, an
uncertainty in measuring wet-bulb depression is allowance of 0.5% minimum to 10.0% maximum of
between 5°F minimum and 10°F maximum. the reading is estimated for instrument precision. No
allowance is included for yaw on the assumption that
ew = 5/(td - tw) (min) to 10/(td - tw) (max) the Pitot-static tube is aligned within 10 degrees of
streamlines. A combined uncertainty can be written
The estimated uncertainty range is based on a broad as:
temperature range with the associated difficulties in
determining wet-bulb readings at high or low ef (min) = [(0.02)2 + (0.01)2 + (0.005)2]0.5
temperatures and the likelihood of stratification. = 0.0229
T.4.4 Fan speed. The estimated uncertainty in ef (max) = [(0.05)2 + (0.02)2 + (0.10)2]0.5
measuring fan speed is between 0.5% minimum and = 0.1136
1.0% maximum.
T.4.9 Static pressure. An allowance of 1.0%
eN = 0.005 (min) to 0.01 (max) minimum to 5.0% maximum of the reading is
estimated for the mental averaging performed on a
The uncertainty range in fan speed is estimated on fluctuating reading. An allowance of 1.0% minimum
the basis of portable instrumentation accuracy and to 2.0% maximum of the reading is estimated for
an allowance for fluctuation in fan speed. calibrated manometer uncertainty and relocation of
the instrument after . In addition, a tolerance of 10%
T.4.5 Power input. The estimated uncertainty in minimum to 20.0% maximum of the fan velocity
measuring power input is betwen 3.0% minimum and pressure should cover the influence of Pitot-static
7.0% maximum. tube yaw or velocity influence on static pressure taps
and other possible effects. A combined uncertainty
eh = 0.03 (min) to 0.07 (max) can be written as:
The estimated uncertainty range is based on the eg (min) = {(0.01)2 + (0.01)2 + (0.005)2 +
various measurement methods and their respective [0.1 Pv/(Ps2 - Ps1)]2}0.5
accuracies, estimated drive losses, and the broad = {0.000225 + [0.1 Pv/(Ps2 - Ps1)]2}0.5
horsepower range encountered in the field.
eg (max) = {(0.05)2 + (0.02)2 + (0.02)2 +
T.4.6 Pitot traverse. A properly performed field [0.2 Pv/(Ps2 - Ps1)]2}0.5
traverse is estimated to have an accuracy of 1.5% = {0.0033 + [0.2 Pv/(Ps2 - Ps1)]2}0.5
minimum to 7.5% maximum.
V = 1.0 - 0.378 {(pe/pb) - [(td - tw)/2700]} T.5.3 Fan static pressure. Fan static pressure
directly involves static pressure measurements.
Uncertainties in density will produce a first-power
For random and independant uncertainties in
uncertainty in fan static pressure while uncertainties
products, the combined uncertainty is determined as
in fan speed will produce a second-power uncertainty
follows:
in fan static pressure when making fan law
conversions. Combining:
∆ρ/ρ = {(∆70.73/70.73)2 + (∆pb/pb)2 + (∆V/V)2 +
(∆R/R)2 + [∆td/(td + 460)]2}0.5 ep = [eg2 + eρ2 + (2eN)2]0.5
Table T.1
eb 0.003 0.007
ed** 0.005 0.020
eW 5/(td - tw) 10/(td - tw)
eN 0.005 0.010
eh 0.030 0.070
ec 0.015 0.075
eA 0.010 0.020
ef 0.0229 0.1136
eg {0.000225 + [0.1 Pv/(Ps2 - Ps1)]2}0.5 {0.0033 + [0.2 Pv/(Ps2 - Ps1)]2}0.5
* These uncertainties do not account for the effect of swirl at the fan inlet. This situation must be corrected in order
to produce acceptable fan-system performance (see Section 5).
T.6 Summary
T.7 Examples
∆Q = 158 cfm
Hc = 18.90 hp
∆H = 0.64 hp
Qc + ∆Q
Qc - ∆Q
Qc
QUOTED FAN
Q, FAN FLOW RATE
PERFORMANCE
CURVES
Hc + ∆H
Hc
H, FAN POWER INPUT
Hc - ∆H
Qc - ∆Q Qc + ∆Q
Qc
Q, FAN FLOW RATE
Figure T.1
TEST POINT
MAXIMUM UNCERTAINTY RANGE
Qc = 25964 cfm
∆Q = 2526 cfm
Psc + ∆P
Psc = 2.54 in. wg
Psc ∆P = 0.20 in. wg
Ps, FAN STATIC PRESSURE
Hc = 17.11 hp
Psc - ∆P ∆H = 1.36 hp
Qc - ∆Q
Qc + ∆Q
Qsc
Q, FAN FLOW RATE QUOTED FAN
PERFORMANCE
CURVES
Hc + ∆H
H, FAN POWER INPUT
Hc
Hc - ∆H
Qc - ∆Q Qc + ∆Q
Qsc
Q, FAN FLOW RATE
Figure T.2
The Air Movement and control Association International, Inc. is a not-for-profit international association of the
world’s manufacturers of related air system equipment primarily, but limited to: fans, louvers, dampers, air
curtains, airflow measurement stations, acoustic attenuators, and other air system components for the industrial,
commercial and residential markets.