Digitrip 1150 - IEEE Curves

Moderately Inverse

60
50
20

40
.9

9
2

10
4

7
6

30
5
.7
.8
.5
.6

10000
2 HOURS

9000
8000
7000
Circuit Breaker Time/Current Curves (Phase Current)
6000
Magnum DS and Magnum SB Circuit Breakers
5000 Response: Moderately Inverse & Short Delay Trip
This curve is for 50Hz or 60Hz applications.
1 HOUR

4000

3000 Notes:

1. This curve is shown as a multiple of the PICKUP setting (Ir). The TimeDial
setting combined with SHORT PU and SHORT TIME setting (shown in heavy
lines) depict the IEEE Moderately Inverse response. The Instantaneous,
shown as a separate response, can be set to OFF.
2000
2. Curve Equation:
Trip = TimeDial *[0.0515/ ( I0.0 2-1) + 0.114], where I is a multiple of Ir.
1000
900 For current > 1.2xIr tolerance is [±15%] or [-15%, +90 ms], whichever is larger.
800 TimeDial curve goes to flat response at 14xIr with a shorter time of TimeDial
700 function or SHORT TIME function prevailing if curves overlap. The ShortTime
600 function and the TimeDial function act independently and the entire TimeDial
500 curves continue to be active even after the curves intersect.

400 3. With Zone Selective Interlocking enabled, max trip times w/o aux power are as
follows:
300
3 Phase fault
60 Hz 75ms
50 Hz 85ms
200
When only one pole is carrying current and a fault occurs, trip times increase to
90ms at 60Hz and 95ms at 50 Hz, however with Aux power these times would
be reduced by 10%

100 4. The actual pick up point (indicated by rapid flashing of Unit Status LED on the
90 product) occurs at 110% of the Ir, current, with a ±5% tolerance. The SHORT
Adjustable PICKUP
80 PU settings have conventional 100% ± 5% as their pick up point.
setting 0.4 to 1.0x In = Ir
1 MINUTE

70
60
with 0.05 increments
See Note 4 5. SHORT PU also has a M1 setting , which may extend out where the
50 SHORT PU will become active.
Adjustable Range M1 setting
40 Narrow Frame:
200A through 1250A 1.5 to 14x Ir M1=14x In
30 1600A 1.5 to 12x Ir M1=12x In
2000A (IEC only) 1.5 to 10x Ir M1=12x In
Adjustable TimeDial Standard Frame:
20 Setting 0.10 to 5.00 200A through 1250A 1.5 to 14x Ir M1=14x In
With 0.10 increments 1600A, 2000A, 2500A 1.5 to 12x Ir M1=12x In
See Note 2
3000A, 3200A 1.5 to 10x Ir M1=10x In
Double Wide Frame:
10 See Note 6 2000A, 2500A 1.5 to 14x Ir M1=14x In
9 3000A, 3200A, 4000A, 5000A 1.5 to 12x Ir M1=12x In
8 6000A, 6300A (IEC only) 1.5 to 10x Ir M1=10x In
7
6
5.00 6. The end of the curve is determined by the interrupting rating of the circuit
5 4.50 breaker.
4 4.00
7. SHORT TIME: FLAT only
3.50 Tolerance is +0/ -80 ms of setting except
3 3.00 0.10s setting is 0.06 to 0.13
Adjustable 0.15s setting is 0.10 to 0.17
TIME IN SECONDS

2.50
SHORT TIME 0.20s setting is 0.15 to 0.22
2 2.00 0.10s to 0.50s
With 8. Curve applies from -20°C to +55°C ambient. Temperatures above +85°C cause
1.50 0.05 increments automatic trip.
See Note 7
9. These curves are comprehensive for the complete family of Magnum breakers,
1.00 including all frame sizes, ratings, and constructions. The total clearing times
1
.9 shown are conservative and consider the maximum response times of the trip
0.80 unit, the circuit breaker opening, and the interruption of the current under
.8
.7 factors that contribute to worst case conditions, like: maximum rated voltages,
0.60 single phase interruption, and minimum power factor. Faster clearing times are
.6
0.50 possible depending on the specific system conditions, the type of Magnum
.5 0.50 s Circuit Breaker applied, and if any arc reduction settings are employed. Contact
0.40 Eaton for additional information.
.4
0.30
.3

0.20
.2

0.10
.1
.09
.08
.07
.06
.05

.04 Adjustable SHORT PU Minimum clearing time


1.5x to 10x or 12x or 14x Ir See Note 9
.03 With 0.5 increments
See Notes 4,5

.02

.01
1

7
.9

8
.6
.7

30

50
2

20

40

60
10

70

90
100
.8

80
.5

Current in Multiples of Long Pickup ( Ir )

Dwg. No.: 70C1038


July 2012