PROGRAMMING GUIDE
Little Genius Plus LCD
PG/LGL/V3/0715 www.elmeasure.com

1. FEATURES 4. KEY FUNCTIONS


STAR (Wye)/ DELTA/1 Phase Programmable. Key In SET (Programming) mode In RUN (Measurement) mode
Universal Auxiliary (80 - 300 VAC/DC) supply Right/UP To select the value for editing and To scroll pages to look at different
accept the value after editing parameters in Upward direction.
True RMS measurement
Active energy, positive energy accumulation & reverse Lock. DOWN To edit the value/system type down- To scroll pages to look at different
ward in edit mode and scroll through parameters in Downwards direction.
User configurable (Editable) password the parameters.
'OLD' register to store the previously cleared energy value
Simultaneous sampling of Volts & Amps
5. ENTERING CONFIGURATION (SETUP) MODE
To configure the setup parameters through front panel, the following steps can be
Universal Voltage Input (50 - 550 VAC) and Current Secondary followed.
(0.5A to 6A).
Step Actions Display Reads Range/Options/Comments
PT ratio / CT ratio programmable including CT secondary.
1 Press RIGHT &
DOWN keys together to
first digit “0” is blinking
2. UNIQUE FEATURES enter SETUP
2 Press DOWN key to If any other password
1 row 7 digit displays for readability. decrement the first digit is already use DOWN keys
to “9” sequentially come first digit “1” blinking. to reach the right password
Auto-scaling of kilo, mega & decimal point to digit “1”
Energy selection: Wh/VAh. 3 Press RIGHT key Defines the clearing option
four times to accept the for the meter.
Optional Programmable relay output maximum 2 password.
and tripping time up to 180 seconds.
Press DOWN key for SETUP Mode
Energy display programmable-counter based or resolution based. Press RIGHT key for CLEAR Mode

Energy resetting at 999999KVAh X multiplication factor.

3. WIRING DIAGRAM - LG+5110L CLEAR MODE


Digital Output
AMF 240V RS 485 4 Press RIGHT key Option : (YES) /(NO)
DO1 DO2

Y (for clearing )
U
X

Display CLr “ n” N (for not clearing)


_________
80-300VDC
80-300VAC

Options can be changed by


Single phase S1 AR S2 S1 AY S2 S1AB S2 VR VY VB N pressing DOWN key. Display
connection will prompt to 'y' or 'n'
S1 S2
R
while pressing DOWN key.
N
LINE DELIVERED RECEIVED LOAD
5 Press RIGHT key
Digital Output To accept the edited option.
DO1 DO2
AMF 240V RS 485 Displays Home page
(Clear Mode ends here)
U
X

SETUP MODE
_________
80-300VDC
80-300VAC

6 Press DOWN key Defines the power system


S1 AR S2 S1 AY S2 S1 AB S2 VR VY VB
Delta connection (2E)
N configuration.
3Phase 3 wire system Displays the previously set
configuration
S1 S2
R
Y
7 Press RIGHT key to select Options: STAR /DELTA/1.Ph
S1 S2
B
the configuration options with selected mode blinking
LINE DELIVERED RECEIVED LOAD
N blinking
8 Press DOWN key Use DOWN KEY to
select
Digital Output
RS 485
EL StAr/dELt/1.Ph
AMF 240V
DO1 DO2
9 Press RIGHT key to accept selected mode stops
U
X

STAR/DELTA/1. PHASE blinking


EL StAr/dELt/1.Ph
_________
80-300VDC
80-300VAC

Star connection (3E) 10 Press DOWN key to PT Primary value


S1 AR S2 S1 AY S2 S1 AB S2 VR VY VB N
3Phase 4wire system navigate to next parameter
default/factory set (PT Primary)
S1 S2
R 11 Press RIGHT key to select
Y
S1 S2
B the PT primary value for
S1 S2
N with Fourth digit blinking.
LINE DELIVERED RECEIVED LOAD editing
Can be edited using DOWN key.
12 Press RIGHT key to accept Program Range for PT 29 Press DOWN key Energy value format
the edited value for Fourth Primary : 100V to 999kV. If i.e., the energy accumulated
Fifth digit blinking. Can be
digit. value set is above the limit, in the meter to be displayed
edited using DOWN key. Press
display returns to the in Resolution (default) or
RIGHT key to accept the
maximum PT Pri value Counter format.
edited value. Continue the
Options can be changed using
same method till seventh digit.
RIGHT & DOWN keys.
13 Press RIGHT key Eg: To set 11.00kV 30 Press DOWN key Range:50 to 500ms
Set first four digits (1100) as Can be set using RIGHT &
Decimal point blinking. Can be PO 250.0 (Pulse output On
explained above keep DOWN keys as in step Repeat
set at appropriate location time)
pressing DOWN key to steps 11 to 13 to change the
using DOWN key. Ascertain
place decimal point at 31 Press DOWN key
the correct scale (Kilo/Mega) is Energy Selection.
appropriate location. USE
selected. Kilo/Mega is placed Option : Wh/VAh
DOWN KEY. Letter K/M will
on the right hand side of the 32 Press DOWN key If “n”(no) is selected then
indicate the Kilo/Mega.
display by Letter K/M. Press Meter enters into RUN mode
RIGHT key to accept the blinking.
without affecting any edited
edited value. Values in the setup
14 Press DOWN key to go to Range: 50V to 550V Once the required parameter is programmed press the DOWN key continuously till it
the next parameter. If value set is above the reaches SAVE page directly.
(default/factory set)
limit, display returns to the
(PT Secondary). 6 The List of parameters that can be configured and the range is
maximum PT sec value.
Follow steps 11 to 13 to
change the setting. given below
Sl.No. Parameter Default Range / Options
15 Press DOWN key Program Range for CT setup
Primary 0.5A to 99kA 1 Connection mode(EL) STAR/ DELTA/1.Ph.
(default/factory set) STAR
(CT Primary). Follow steps 11 2 PT Primary (P.P) 415.0 100V- 999kV
to 13 to change the settings.
3 PT Secondary (P.S) 415.0 50V - 550V
4 CT Primary (C.P) 5.000 0.5A - 99kA

16 Press DOWN key CT Secondary 5 CT Secondary (C.S) 5.000 0.5A - 6A


Range: 0.5A to 6A Reverse Lock (rE) no
(default/factory set) (CT 6 0.5A - 6A
Secondary). Follow steps 11 to 7 VA selection (UA) VEC.H Arithmetic (Arth),
13 to change the settings. Vector harmonics (UEC.H).
17 Press DOWN key Option : NO/YES. Reverse Vector (UECt).
lock if yes, blocks energy
(Reverse lock) 8 Digital Output 1 (d1) dSbL Disable, Single Phase, Over V/A
accumulation in case the CT
polarity is reverse. /F/Watts/Wh, Under V/A/F/PF.
18 Press DOWN key Arithmetic (Arth), 9 Digital Output 1 threshold value (d1). 1000 0.001 to 999.9M
Vector harmonics (UEC.H). 10 Digital Output 2 (d2). dSbL Disable, Single Phase, Over V/A
(Method of VA Selection).
Vector (UECt).Can be edited /F/Watts/Wh, Under V/A/F/PF.
using RIGHT/DOWN key.
11 Digital Output 2 threshold value (d2). 1000 0.001 to 999.9M
19 Press DOWN key 1st digital output
parameter can be selected 12 Baud rate (bA) 9600 2400 to 19.2k
(digital Output 1)
using DOWN key. OPTION: 13 Parity (Pr) Even Even/ Odd/ no
Disable, Single Phase, Over 14 Device Id (dU) 1.000 1.000 to 247.0
V/A/F/Watts/Wh ,Under
V/A/F/PF 15 Reverse lock(rE) no Yes/no
20 Press DOWN key 1st digital output threshold 16 Password (PW) 1000 1000 to 9999
value Range : 0.001 to 17 Energy (En) rESL rESL /COUΠ
999.9M
18 POP ON time (PO) 250.0 50 to 500 milliseconds
21 Press DOWN key 2nd digital output
parameter can be selected 19 Energy Selection (E.S) Wh. Wh/VAh
(digital Output 1)
using DOWN key.
OPTION: Disable, Single 7. Enabling and disabling of Auto scrolling
Phase, Over V/A/F/Watts Enabling auto scrolling: Press UP key continuously for 5 seconds or until display shows
/Wh ,Under V/A/F/PF
EnbL Au. for upward scrolling. Press Down key continuously for 5 seconds or until display
22 Press DOWN key 2nd digital output threshold
shows EnbL Au. for downward scrolling.
value Range :0.001 to
Disabling auto scrolling: Press any key (UP/DOWN), display shows dSbL Au. and returns to
999.9M
normal mode.

23 Press DOWN key Range: 1 to 180 seconds 8. LED INDICATION


(digital output trip delay time,
default /factory set :3.000
LED Status Meaning
24 Press DOWN key Range: 1 to 180 seconds Communication ON
(baud rate) TI Pulse / Reserved
(9600 default /factory set)
25 Press DOWN key EUEn (even)/odd(odd)/no
(no parity) Internal 9. Mechanical Specification:
(Parity)
communication error check
26 Press DOWN key Defines the (ID) Dimension Bezel: Panel Cutout:
+2 +2
communications identification 96 x 96 mm (Depth 50mm behind Bezel) 90 -0 x 90 -0 mm
dU. 1.000 (device ID)
number.1 to 247 Follow steps
11 to 13 to change the value.
27 Press DOWN key Range: 1000-9999.
(Password user definable).
CAUTION: memorize the
Password. Use the same
Password for next time.
Instruments will reject other
Passwords.
28 Press RIGHT key to view CAUTION: Password can be
the password reset only at the factory.
Follow steps 11 to 13 to
change the settings.