Sunteți pe pagina 1din 16

ARUF Series

Multi-Position,
Multi-speed Air Handler
with PSC Motor
1½ to 5 Tons
Contents
Nomenclature ........................................ 2
Product Specifications ........................... 3
Heater Kit Nomenclature....................... 3
Dimensions ............................................ 4
Airflow Data ........................................... 5
Heat Kit Data .......................................... 6
Wiring Diagrams .................................. 13
Accessories .......................................... 15

Product Features
• Check flowrator for cooling • Rigid SmartFrame™ cabinet
and heat pump applications • Horizontal or vertical
• Direct drive, multi-speed PSC blower motor configuration capabilities
• All-aluminum evaporator coil • 21" depth for easier attic access
• Coil mounting track for quick repositioning • DecaBDE-free thermoplastic drain
• Cabinet air leakage less than 2.0% at pan with secondary drain connections
1.0 inch H₂O when tested in accor- • Screw-less sides and back helps to reduce con-
dance with ASHRAE standard 193 densation when installed in humid locations
• Cabinet air leakage less than 1.4% at • Foil-faced insulation covers the internal
0.5 inch H₂O when tested in accor- casing to reduce cabinet condensation
dance with ASHRAE standard 193 • Galvanized, leather grain-embossed finish
• AHRI certified; ETL listed • Glue-less cabinet insulation retention
• Tool-less filter access
• Field Installed 3 kW – 25 kW electric heater
kits available

* Complete warranty details available from your local dealer or at www.amana-hac.com. To receive the
10-Year Parts Limited Warranty, online registration must be completed within 60 days of installation.
Online registration is not required in California or Québec.

SS-AARUF www.amana-hac.com 6/18


Amana® is a trademark of Maytag Corporation or its related companies and used under license to Goodman Company, L.P., Houston, Texas. Supersedes 1/18
Nomenclature

A R U F 18 B 1 4 AA
1 2 3 4 5,6 7 8 10 11,12

Brand Engineering  *
A Single-­‐piece Major/  Minor  Revisions
Air  Handler *   Not  used  for  inventory  management

Unit  Application Refrigerant  Charge


C Ceiling  Mount  PSC  Motor 4  =  R-­‐410A
D Downflow  PSC  Motor
E Multi-­‐Position  Variable-­‐Speed  Motor Electrical
R Multi-­‐Position  PSC  Motor 1      208/240  V,  1  Phase,  60  Hz
S Multi-­‐Position  EEM  Motor
W Wall  Mount  PSC  Motor Cabinet  Width
B    17½"
Cabinet  Finish C    21"
U Unpainted D      24½"
P Painted
N Uncased Nominal  Capacity  Range  @  13  SEER
25, 29 – 2 Tons       43, 47 – 3½  Tons
Expansion  Device 31 – 2½  Tons 49 – 4 Tons
F Flowrater 37 – 3 Tons 61 – 5 Tons
T Expansion  Valve

HKS X 03 X A AA
1 2 3 4 5 6,7

Unit  Type Revisions


HKS Heat  Kit  for   Engineering  Revisions
Air  Handlers
Phase
Circuit  Breaker A      Single  Phase  208  V E      Three  Phase  240  V
X No  circuit  breaker B      Single  Phase  240  V F      Three  Phase  208/240  V
C Circuit  Breaker C      Single  Phase  208/240  V G      Three  Phase  460  V
D      Three  Phase  208  V
Heating  Capacity  @  240  Volts H Special case 208 V *
03 3.0  kW 15 14.4  kW Cabinet  Size  (MAX)
05 4.5  kW 19 19.2  kW  wth  150F  limit C      C  Cabinet
06 6.0  kW 20 19.2  kW  with  170F  limit D      D  Cabinet
08 8.0  kW 25 25.0  kW X      All  Cabinet  Sizes
10 9.6  kW

*Refer S&R Plate

2 www.amana-hac.com SS-AARUF
Product Specifications

ARUF ARUF ARUF ARUF ARUF ARUF ARUF ARUF ARUF ARUF ARUF
25B14* 29B14* 31B14* 37C14* 43C14* 49C14* 37D14* 43D14* 47D14* 49D14* 61D14*

Nominal Ratings
Cooling (Btu/h) 24,000 25,000 30,000 36,000 42,000 48,000 36,000 42,000 43,000 48,000 60,000

Piston Size 0.051 0.057 0.065 0.072 0.076 0.080 0.072 0.076 0.076 0.080 0.080

Blower
Diameter 9½" 9½" 9½" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝" 1115/16"

Width 6" 6" 6" 8" 8" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝" 10⅝"

Coil Connections
Liquid ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜"
Suction ¾" ¾" ⅞" ⅞" ⅞" ⅞" ⅞" ⅞" ⅞" ⅞" ⅞"
Coil Drain Connect (FPT) ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾"
Electrical Data
Voltage 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230

Min Circuit Ampacity 2.2/2.2 2.2/2.2 2.2/2.2 3.6/3.6 3.6/3.6 4/4 3.6/3.6 4/4 4/4 4/4 6/6

Max. Overcurrent Device (Amps) 15/15 15/15 15/15 15/15 15/15 15/15 15/15 15/15 15/15 15/15 15/15

Minimum VAC 197 197 197 197 197 197 197 197 197 197 197

Maximum VAC 253 253 253 253 253 253 253 253 253 253 253

Blower Motor
Full Load Amps (FLA) 1.75 1.75 1.75 2.85 2.85 3.1 2.85 3.5 3.5 3.5 4.6

Horsepower (HP) ⅓ ⅓ ⅓ ⅓ ⅓ ½ ⅓ ½ ½ ½ ¾
Ship Weight (Lbs.) 100 100 110 130 130 135 140 145 150 145 155

Note: For a properly matched system and piston sizing information, refer to Amana piston kit chart of the corresponding Amana® outdoor unit.
Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOP) for blower without supplemental heat installed.
Refer to unit nameplate and/or Heat Kit Data for specification with approved accessory heaters installed.

SS-AARUF www.amana-hac.com 3
Dimensions

4 1/2" (11.43 cm)


7 3/16" (18.26 cm) 6 1/8" (15.56 cm)

4 5/16" (4.31 cm) 21" (55.88 cm)


K
2 1/8" (5.40 cm)
9 1/4" (23.50 cm) 11 5/16" (28.73 cm)
J
7 1/2" (19.05 cm)
5 1/8" (13.02 cm) 1 5/8" (4.13 cm)
C 3 1/8" (7.94 cm) 1/2" (1.27 cm)

5/8" (1.59 cm) B 5/8" (1.59 cm) 1 3/8" (3.49 cm)


1 5/16" (3.33 cm)

HORIZONTAL DRAIN PORT DETAIL


1 3/4" (4.45 cm)

2 11/16" (6.83 cm) 3 1/16" (7.78 cm)

1 3/4" (4.45 cm)

A
SUCTION TUBE
G LIQUID LINE 2 15/16" (7.46 cm)
INLET TUBE
SEE HORIZONTAL
DRAIN PORT DETAIL 3 3/4" (9.53 cm) 1 5/8" (4.13 cm)
10 3/16" (25.88 cm)
D
E VERTICAL DRAIN PORT DETAIL

SEE VERTICAL
DRAIN PORT DETAIL H

1" (2.54 cm) 19.5" (49.53 cm) 9/16 (1.43 cm)


1 13/16" (4.60 cm) F 1 13/16" (4.60 cm) INLET
INLET (RIGHT SIDE VIEW)
(FRONT VIEW)

Model A" B" C" D" E" F" G" H"

ARUF25B14* 45 16⅜ 17½ 15¼ 12 14⅛ 9⅛ 11⅞

ARUF29B14* 45 16⅜ 17½ 15¼ 12 14⅛ 9⅛ 12¾

ARUF31B14* 537/16 16⅜ 17½ 2311/16 20½ 14⅛ 9⅛ 7⅝

ARUF37C14* 53 /16
7
19⅞ 21 21 /16
13
18⅝ 17 /16
11
10 /16 13
613/16

ARUF43C14* 537/16 19⅞ 21 2113/16 18⅝ 1711/16 1013/16 613/16

ARUF49C14* 537/16 19⅞ 21 2113/16 18⅝ 1711/16 1013/16 613/16

ARUF37D14* 537/16 235/16 24½ 21½ 185/16 213/16 12⅝ 6⅞

ARUF43D14* 53 /16
7
23 /16
5
24½ 21½ 18 /16
5 21 /16
3
12⅝ 6⅞

ARUF47D14* 58 235/16 24½ 26⅛ 22⅞ 213/16 12⅝ 252/16

ARUF49D14* 537/16 235/16 24½ 21½ 185/16 213/16 12⅝ 6⅞

ARUF61D14* 58 235/16 24½ 26⅛ 22⅞ 213/16 12⅝ 252/16

4 www.amana-hac.com SS-AARUF
Airflow Data

Motor Static Pressure (in w.c) Airflow (CFM)


Model
Speed 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Low 650 620 595 540 490 420 275
ARUF25B14 Med 885 865 825 815 750 690 560
High 1255 1225 1130 1090 965 925 800
Low 650 620 595 540 490 420 275
ARUF29B14 Med 885 865 825 815 750 690 560
High 1255 1225 1130 1090 965 925 800
Low 660 625 595 560 500 430 330
ARUF31B14 Med 930 905 865 820 765 700 590
High 1235 1185 1130 1060 990 910 825
Low 1120 1085 1040 1000 940 875 800
ARUF37C14 Med 1425 1385 1345 1285 1220 1145 1060
High 1625 1575 1520 1460 1375 1295 1200
Low 1120 1085 1040 1000 940 875 800
ARUF43C14 Med 1425 1385 1345 1285 1220 1145 1060
High 1625 1575 1520 1460 1375 1295 1200
Low 1295 1255 1225 1175 1120 1055 970
ARUF49C14 Med 1535 1485 1420 1370 1295 1215 1130
High 1755 1680 1590 1515 1425 1340 1250
Low 1155 1115 1070 1015 955 895 840
ARUF37D14 Med 1505 1470 1430 1375 1300 1210 1105
High 1785 1735 1680 1625 1555 1440 1330
Low 1410 1360 1290 1210 1120 1010 920
ARUF43D14 Med 1610 1540 1470 1390 1300 1190 1060
High 1900 1830 1740 1645 1540 1420 1280
Low 1420 1370 1310 1240 1125 1045 960
ARUF47D14 Med 1625 1585 1515 1435 1350 1235 1095
High 1930 1890 1820 1735 1635 1505 1355
Low 1410 1360 1290 1210 1120 1010 920
ARUF49D14 Med 1610 1540 1470 1390 1300 1190 1060
High 1900 1830 1740 1645 1540 1420 1280
Low 1530 1500 1460 1405 1350 1280 1155
ARUF61D14 Med 1950 1885 1830 1785 1745 1670 1595
High 2235 2170 2100 2030 1965 1915 1825
Notes
• Airflow data indicated is at 230V without air filter in place.
• The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on rating plate.
The shaded area indicates ranges in excess of maximum design external static pressure.
• Use the CFM adjustment factors of 0.98 for horizontal left and 0.96 for horizontal right & downflow orientations

SS-AARUF www.amana-hac.com 5
Heat Kit Data

Circuit 1 Circuit 2 Single-Point Kit


Heater Kit Model
Amps MCA¹ MOP² Amps MCA¹ MOP² MCA¹ MOP²
ARUF25B14AC 0/0 2.2/2.2 15/15 --- --- --- --- ---
HKSX03XC - 208 V 10.8 16 20 --- --- --- --- ---
HKSX05XC - 208 V 17.3 24 25 --- --- --- --- ---
HKSX06XC - 208 V No Breaker 21.7 29 30 --- --- --- --- ---
HKSX08XC - 208 V 28.9 38 40 --- --- --- --- ---
HKSX10XC - 208 V 34.7 46 50 --- --- --- --- ---
HKSC05XC - 208 V 17.3 24 25 --- --- --- --- ---
HKSC08XC - 208 V Breaker 28.9 38 40 --- --- --- --- ---
HKSC10XC - 208 V 34.7 46 50 --- --- --- --- ---
HKSX03XC - 240 V 12.5 18 20 --- --- --- --- ---
HKSX05XC - 240 V 20 27 30 --- --- --- --- ---
HKSX06XC - 240 V No Breaker 25 33 35 --- --- --- --- ---
HKSX08XC - 240 V 33.3 44 45 --- --- --- --- ---
HKSX10XC - 240 V 40.0 52 60 --- --- --- --- ---
HKSC05XC - 240 V 20 27 30 --- --- --- --- ---
HKSC08XC - 240 V Breaker 33.3 44 45 --- --- --- --- ---
HKSC10XC - 240 V 40.0 52 60 --- --- --- --- ---
ARUF29B14AC 0/0 2.2/2.2 15/15 --- --- --- --- ---
HKSX03XC - 208 V 10.8 16 20 --- --- --- --- ---
HKSX05XC - 208 V 17.3 24 25 --- --- --- --- ---
HKSX06XC - 208 V No Breaker 21.7 29 30 --- --- --- --- ---
HKSX08XC - 208 V 28.9 38 40 --- --- --- --- ---
HKSX10XC - 208 V 34.7 46 50 --- --- --- --- ---
HKSC05XC - 208 V 17.3 24 25 --- --- --- --- ---
HKSC08XC - 208 V Breaker 28.9 38 40 --- --- --- --- ---
HKSC10XC - 208 V 34.7 46 50 --- --- --- --- ---
HKSX03XC - 240 V 12.5 18 20 --- --- --- --- ---
HKSX05XC - 240 V 20 27 30 --- --- --- --- ---
HKSX06XC - 240 V No Breaker 25 33 35 --- --- --- --- ---
HKSX08XC - 240 V 33.3 44 45 --- --- --- --- ---
HKSX10XC - 240 V 40.0 52 60 --- --- --- --- ---
HKSC05XC - 240 V 20 27 30 --- --- --- --- ---
HKSC08XC - 240 V Breaker 33.3 44 45 --- --- --- --- ---
HKSC10XC - 240 V 40.0 52 60 --- --- --- --- ---
ARUF31B14AC 0/0 2.2/2.2 15/15 --- --- --- --- ---
HKSX03XC - 208 V 10.8 16 20 --- --- --- --- ---
HKSX05XC - 208 V 17.3 24 25 --- --- --- --- ---
HKSX06XC - 208 V No Breaker 21.7 29 30 --- --- --- --- ---
HKSX08XC - 208 V 28.9 38 40 --- --- --- --- ---
HKSX10XC - 208 V 34.7 46 50 --- --- --- --- ---
HKSC05XC - 208 V 17.3 24 25 --- --- --- --- ---
HKSC08XC - 208 V 28.9 38 40 --- --- --- --- ---
Breaker
HKSC10XC - 208 V 34.7 46 50 --- --- --- --- ---
HKSC15XA - 208 V 34.7 46 50 17.3 22 25 67 70
See notes on page 12.
6 www.amana-hac.com SS-AARUF
Heat Kit Data (cont.)

Circuit 1 Circuit 2 Single-Point Kit


Heater Kit Model
Amps MCA¹ MOP² Amps MCA¹ MOP² MCA¹ MOP²
HKSX03XC - 240 V 12.5 18 20 --- --- --- --- ---
HKSX05XC - 240 V 20 27 30 --- --- --- --- ---
HKSX06XC - 240 V No Breaker 25 33 35 --- --- --- --- ---
HKSX08XC - 240 V 33.3 44 45 --- --- --- --- ---
HKSX10XC - 240 V 40.0 52 60 --- --- --- --- ---
HKSC05XC - 240 V 20 27 30 --- --- --- --- ---
HKSC08XC - 240 V 33.3 44 45 --- --- --- --- ---
Breaker
HKSC10XC - 240 V 40.0 52 60 --- --- --- --- ---
HKSC15XB - 240 V 40.0 52 60 20 25 25 77 80
ARUF37C14AD 0/0 3.6/3.6 15/15 --- --- --- --- ---
HKSX03XC - 208 V 10.8 17 20 --- --- --- --- ---
HKSX05XC - 208 V 17.3 25.2 30 --- --- --- --- ---
HKSX06XC - 208 V No Breaker 21.7 31 35 --- --- --- --- ---
HKSX08XC - 208 V 28.9 40 40 --- --- --- --- ---
HKSX10XC - 208 V 34.7 46.9 50 --- --- --- --- ---
HKSC05XC - 208 V 17.3 25.2 30 --- --- --- --- ---
HKSC08XC - 208 V 28.9 40 40 --- --- --- --- ---
HKSC10XC - 208 V 34.7 46.9 50 --- --- --- --- ---
HKSC15XA - 208 V Breaker 34.7 46.9 50 17.3 22 25 68.6 70
HKSC19CA - 208 V 34.7 46.9 50 34.7 43 45 90.2 100
HKSC15XF - 208 V ^ 0 3.6 15 30 38 40 --- ---
HKSC20XF - 208 V ^ 0 3.6 15 38 47 50 --- ---
HKSX03XC - 240 V 12.5 19 20 --- --- --- --- ---
HKSX05XC - 240 V 20 29 30 --- --- --- --- ---
HKSX06XC - 240 V No Breaker 25 35 35 --- --- --- --- ---
HKSX08XC - 240 V 33.3 45.2 50 --- --- --- --- ---
HKSX10XC - 240 V 40 53.6 60 --- --- --- --- ---
HKSC05XC - 240 V 20 29 30 --- --- --- --- ---
HKSC08XC - 240 V 33.3 45.2 50 --- --- --- --- ---
HKSC10XC - 240 V 40 53.6 60 --- --- --- --- ---
HKSC15XB - 240 V Breaker 40 53.6 60 20 25 25 78.6 80
HKSC19CB - 240 V 40 53.6 60 40 50 50 104 110
HKSC15XF - 240 V ^ 0 3.6 15 34.6 43 45 --- ---
HKSC20XF - 240 V ^ 0 3.6 15 43 54 60 --- ---
ARUF37D14AD 0/0 3.6/3.6 15/15 --- --- --- --- ---
HKSX03XC - 208 V 10.8 17 20 --- --- --- --- ---
HKSX05XC - 208 V 17.3 25.2 30 --- --- --- --- ---
HKSX06XC - 208 V No Breaker 21.7 31 35 --- --- --- --- ---
HKSX08XC - 208 V 28.9 40 40 --- --- --- --- ---
HKSX10XC - 208 V 34.7 46.9 50 --- --- --- --- ---

See notes on page 12.

SS-AARUF www.amana-hac.com 7
Heat Kit Data (cont.)

Circuit 1 Circuit 2 Single-Point Kit


Heater Kit Model
Amps MCA¹ MOP² Amps MCA¹ MOP² MCA¹ MOP²
HKSC05XC - 208 V 17.3 25.2 30 --- --- --- --- ---
HKSC08XC - 208 V 28.9 40 40 --- --- --- --- ---
HKSC10XC - 208 V 34.7 46.9 50 --- --- --- --- ---
HKSC15XA - 208 V Breaker 34.7 46.9 50 17.3 22 25 68.6 70
HKSC20DA - 208 V 34.7 46.9 50 34.7 43 45 90.2 100
HKSC15XF - 208 V ^ 0 3.6 15 30 38 40 --- ---
HKSC20XF - 208 V ^ 0 3.6 15 38 47 50 --- ---
HKSX03XC - 240 V 12.5 19 20 --- --- --- --- ---
HKSX05XC - 240 V 20 29 30 --- --- --- --- ---
HKSX06XC - 240 V No Breaker 25 35 35 --- --- --- --- ---
HKSX08XC - 240 V 33.3 45.2 50 --- --- --- --- ---
HKSX10XC - 240 V 40 53.6 60 --- --- --- --- ---
HKSC05XC - 240 V 20 29 30 --- --- --- --- ---
HKSC08XC - 240 V 33.3 45.2 50 --- --- --- --- ---
HKSC10XC - 240 V 40 53.6 60 --- --- --- --- ---
HKSC15XB - 240 V Breaker 40 53.6 60 20 25 25 78.6 80
HKSC20DB - 240 V 40 53.6 60 40 50 50 104 110
HKSC15XF - 240 V ^ 0 3.6 15 34.6 43 45 --- ---
HKSC20XF - 240 V ^ 0 3.6 15 43 54 60 --- ---
ARUF43C14AD 0/0 3.6/3.6 15/15 --- --- --- --- ---
HKSX03XC - 208 V 10.8 17 20 --- --- --- --- ---
HKSX05XC - 208 V 17.3 25.2 30 --- --- --- --- ---
HKSX06XC - 208 V No Breaker 21.7 31 35 --- --- --- --- ---
HKSX08XC - 208 V 28.9 40 40 --- --- --- --- ---
HKSX10XC - 208 V 34.7 46.9 50 --- --- --- --- ---
HKSC05XC - 208 V 17.3 25.2 30 --- --- --- --- ---
HKSC08XC - 208 V 28.9 40 40 --- --- --- --- ---
HKSC10XC - 208 V 34.7 46.9 50 --- --- --- --- ---
HKSC15XA - 208 V Breaker 34.7 46.9 50 17.3 22 25 68.6 70
HKSC19CA - 208 V 34.7 46.9 50 34.7 43 45 90.2 100
HKSC15XF - 208 V ^ 0 3.6 15 30 38 40 --- ---
HKSC20XF - 208 V ^ 0 3.6 15 38 47 50 --- ---
HKSX03XC - 240 V 12.5 19 20 --- --- --- --- ---
HKSX05XC - 240 V 20 29 30 --- --- --- --- ---
HKSX06XC - 240 V No Breaker 25 35 35 --- --- --- --- ---
HKSX08XC - 240 V 33.3 45.2 50 --- --- --- --- ---
HKSX10XC - 240 V 40 53.6 60 --- --- --- --- ---
HKSC05XC - 240 V 20 29 30 --- --- --- --- ---
HKSC08XC - 240 V 33.3 45.2 50 --- --- --- --- ---
HKSC10XC - 240 V 40 53.6 60 --- --- --- --- ---
HKSC15XB - 240 V Breaker 40 53.6 60 20 25 25 78.6 80
HKSC19CB - 240 V 40 53.6 60 40 50 50 104 110
HKSC15XF - 240 V ^ 0 3.6 15 34.6 43 45 --- ---
HKSC20XF - 240 V ^ 0 3.6 15 43 54 60 --- ---
See notes on page 12.
8 www.amana-hac.com SS-AARUF
Heat Kit Data (cont.)

Circuit 1 Circuit 2 Single-Point Kit


Heater Kit Model
Amps MCA¹ MOP² Amps MCA¹ MOP² MCA¹ MOP²
ARUF43D14AC 0/0 4/4 15/15 --- --- --- --- ---
HKSX03XC - 208 V 10.8 18 20 --- --- --- --- ---
HKSX05XC - 208 V 17.3 26 30 --- --- --- --- ---
HKSX06XC - 208 V No Breaker 21.7 31 35 --- --- --- --- ---
HKSX08XC - 208 V 28.9 40.5 45 --- --- --- --- ---
HKSX10XC - 208 V 34.7 48 50 --- --- --- --- ---
HKSC05XC - 208 V 17.3 26 30 --- --- --- --- ---
HKSC08XC - 208 V 28.9 40.5 45 --- --- --- --- ---
HKSC10XC - 208 V 34.7 48 50 --- --- --- --- ---
HKSC15XA - 208 V Breaker 34.7 48 50 17.3 22 25 69 70
HKSC20DA - 208 V 34.7 48 50 34.7 43 45 91 100
HKSC15XF - 208 V ^ 0 4 15 30 38 40 --- ---
HKSC20XF - 208 V ^ 0 4 15 38 47 50 --- ---
HKSX03XC - 240 V 12.5 20 20 --- --- --- --- ---
HKSX05XC - 240 V 20 29 30 --- --- --- --- ---
HKSX06XC - 240 V No Breaker 25 36 40 --- --- --- --- ---
HKSX08XC - 240 V 33.3 46 50 --- --- --- --- ---
HKSX10XC - 240 V 40 54 60 --- --- --- --- ---
HKSC05XC - 240 V 20 29 30 --- --- --- --- ---
HKSC08XC - 240 V 33.3 46 50 --- --- --- --- ---
HKSC10XC - 240 V 40 54 60 --- --- --- --- ---
HKSC15XB - 240 V Breaker 40 54 60 20 25 25 79 80
HKSC20DB - 240 V 40 54 60 40 50 50 104 110
HKSC15XF - 240 V ^ 0 4 15 34.6 43 45 --- ---
HKSC20XF - 240 V ^ 0 4 15 43 54 60 --- ---
ARUF47D14AC 0/0 4/4 15/15 --- --- --- --- ---
HKSX03XC - 208 V 10.8 18 20 --- --- --- --- ---
HKSX05XC - 208 V 17.3 26 30 --- --- --- --- ---
HKSX06XC - 208 V No Breaker 21.7 31 35 --- --- --- --- ---
HKSX08XC - 208 V 28.9 40.5 45 --- --- --- --- ---
HKSX10XC - 208 V 34.7 48 50 --- --- --- --- ---
HKSC05XC - 208 V 17.3 26 30 --- --- --- --- ---
HKSC08XC - 208 V 28.9 40.5 45 --- --- --- --- ---
HKSC10XC - 208 V 34.7 48 50 --- --- --- --- ---
HKSC15XA - 208 V Breaker 34.7 48 50 17.3 22 25 69 70
HKSC20DA - 208 V 34.7 48 50 34.7 44 45 91 100
HKSC15XF - 208 V ^ 0 4 15 30 38 40 --- ---
HKSC20XF - 208 V ^ 0 4 15 38 47 50 --- ---
HKSX03XC - 240 V 12.5 20 20 --- --- --- --- ---
HKSX05XC - 240 V 20 29 30 --- --- --- --- ---
HKSX06XC - 240 V No Breaker 25 36 40 --- --- --- --- ---
HKSX08XC - 240 V 33.3 46 50 --- --- --- --- ---
HKSX10XC - 240 V 40 54 60 --- --- --- --- ---
See notes on page 12.

SS-AARUF www.amana-hac.com 9
Heat Kit Data (cont.)

Circuit 1 Circuit 2 Single-Point Kit


Heater Kit Model
Amps MCA¹ MOP² Amps MCA¹ MOP² MCA¹ MOP²
HKSC05XC - 240 V 20 29 30 --- --- --- --- ---
HKSC08XC - 240 V 33.3 46 50 --- --- --- --- ---
HKSC10XC - 240 V 40 54 60 --- --- --- --- ---
HKSC15XB - 240 V Breaker 40 54 60 20 25 25 79 80
HKSC20DB - 240 V 40 54 60 40 50 50 104 110
HKSC15XF - 240 V ^ 0 4 15 34.6 43 45 --- ---
HKSC20XF - 240 V ^ 0 4 15 43 54 60 --- ---
ARUF49C14AC 0/0 4/4 15/15 --- --- --- --- ---
HKSX03XC - 208 V 10.8 17 20 --- --- --- --- ---
HKSX05XC - 208 V 17.3 26 30 --- --- --- --- ---
HKSX06XC - 208 V No Breaker 21.7 31 35 --- --- --- --- ---
HKSX08XC - 208 V 28.9 40 40 --- --- --- --- ---
HKSX10XC - 208 V 34.7 47 50 --- --- --- --- ---
HKSC05XC - 208 V 17.3 26 30 --- --- --- --- ---
HKSC08XC - 208 V 28.9 40 40 --- --- --- --- ---
HKSC10XC - 208 V 34.7 47 50 --- --- --- --- ---
HKSC15XA - 208 V Breaker 34.7 47 50 17.3 22 25 69 70
HKSC19CA - 208 V 34.7 47 50 34.7 43 45 91 100
HKSC15XF - 208 V ^ 0 4 15 30 38 40 --- ---
HKSC20XF - 208 V ^ 0 4 15 38 47 50 --- ---
HKSX03XC - 240 V 12.5 20 20 --- --- --- --- ---
HKSX05XC - 240 V 20 29 30 --- --- --- --- ---
HKSX06XC - 240 V No Breaker 25 35 40 --- --- --- --- ---
HKSX08XC - 240 V 33.3 46 50 --- --- --- --- ---
HKSX10XC - 240 V 40 54 60 --- --- --- --- ---
HKSC05XC - 240 V 20 29 30 --- --- --- --- ---
HKSC08XC - 240 V 33.3 46 50 --- --- --- --- ---
HKSC10XC - 240 V 40 54 60 --- --- --- --- ---
HKSC15XB - 240 V Breaker 40 54 60 20 25 25 79 80
HKSC19CB - 240 V 40 54 60 40 50 50 104 110
HKSC15XF - 240 V ^ 0 4 15 34.6 43 45 --- ---
HKSC20XF - 240 V ^ 0 4 15 43 54 60 --- ---
ARUF49D14AC 0/0 4/4 15/15 --- --- --- --- ---
HKSX03XC - 208 V 10.8 18 20 --- --- --- --- ---
HKSX05XC - 208 V 17.3 26 30 --- --- --- --- ---
HKSX06XC - 208 V No Breaker 21.7 31 35 --- --- --- --- ---
HKSX08XC - 208 V 28.9 40.5 45 --- --- --- --- ---
HKSX10XC - 208 V 34.7 48 50 --- --- --- --- ---
See notes on page 12.

10 www.amana-hac.com SS-AARUF
Heat Kit Data (cont.)

Circuit 1 Circuit 2 Single-Point Kit


Heater Kit Model
Amps MCA¹ MOP² Amps MCA¹ MOP² MCA¹ MOP²
HKSC05XC - 208 V 17.3 26 30 --- --- --- --- ---
HKSC08XC - 208 V 28.9 40.5 45 --- --- --- --- ---
HKSC10XC - 208 V 34.7 48 50 --- --- --- --- ---
HKSC15XA - 208 V Breaker 34.7 48 50 17.3 22 25 69 70
HKSC20DA - 208 V 34.7 48 50 34.7 43 45 91 100
HKSC15XF - 208 V ^ 0 4 15 30 38 40 --- ---
HKSC20XF - 208 V ^ 0 4 15 38 47 50 --- ---
HKSX03XC - 240 V 12.5 20 20 --- --- --- --- ---
HKSX05XC - 240 V 20 29 30 --- --- --- --- ---
HKSX06XC - 240 V No Breaker 25 36 40 --- --- --- --- ---
HKSX08XC - 240 V 33.3 46 50 --- --- --- --- ---
HKSX10XC - 240 V 40 54 60 --- --- --- --- ---
HKSC05XC - 240 V 20 29 30 --- --- --- --- ---
HKSC08XC - 240 V 33.3 46 50 --- --- --- --- ---
HKSC10XC - 240 V 40 54 60 --- --- --- --- ---
HKSC15XB - 240 V Breaker 40 54 60 20 25 25 79 80
HKSC20DB - 240 V 40 54 60 40 50 50 104 110
HKSC15XF - 240 V ^ 0 4 15 34.6 43 45 --- ---
HKSC20XF - 240 V ^ 0 4 15 43 54 60 --- ---
ARUF61D14AC 0/0 6/6 15/15 --- --- --- --- ---
HKSX03XC - 208 V 10.8 19 20 --- --- --- --- ---
HKSX05XC - 208 V 17.3 27 30 --- --- --- --- ---
HKSX06XC - 208 V No Breaker 21.7 33 35 --- --- --- --- ---
HKSX08XC - 208 V 28.9 42 45 --- --- --- --- ---
HKSX10XC - 208 V 34.7 49 50 --- --- --- --- ---
HKSC05XC - 208 V 17.3 27 30 --- --- --- --- ---
HKSC08XC - 208 V 28.9 42 45 --- --- --- --- ---
HKSC10XC - 208 V 34.7 49 50 --- --- --- --- ---
HKSC15XA - 208 V 34.7 49 50 17.3 22 25 71 80
Breaker
HKSC20DA - 208 V 34.7 49 50 34.7 43 45 92 100
HKSC15XF - 208 V ^ 0 6 15 30 38 40 --- ---
HKSC20XF - 208 V ^ 0 6 15 38 47 50 --- ---
HKSC25DA - 208 V 52 71 80 35 43 45 114 125
HKSX03XC - 240 V 12.5 21 25 --- --- --- --- ---
HKSX05XC - 240 V 20 31 35 --- --- --- --- ---
HKSX06XC - 240 V No Breaker 25 37 40 --- --- --- --- ---
HKSX08XC - 240 V 33.3 47 50 --- --- --- --- ---
HKSX10XC - 240 V 40 56 60 --- --- --- --- ---
See notes on page 12.

SS-AARUF www.amana-hac.com 11
Heat Kit Data (cont.)

Circuit 1 Circuit 2 Single-Point Kit


Heater Kit Model
Amps MCA¹ MOP² Amps MCA¹ MOP² MCA¹ MOP²
HKSC05XC - 240 V 20 31 35 --- --- --- --- ---
HKSC08XC - 240 V 33.3 47 50 --- --- --- --- ---
HKSC10XC - 240 V 40 56 60 --- --- --- --- ---
HKSC15XB - 240 V 40 56 60 20 25 25 81 90
Breaker
HKSC20DB - 240 V 40 56 60 40 50 50 106 110
HKSC15XF - 240 V ^ 0 6 15 34.6 43 45 --- ---
HKSC20XF - 240 V ^ 0 6 15 43 54 60 --- ---
HKSC25DB - 240 V 60 81 90 40 50 50 131 150

¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25


² Maximum Overcurrent Protection = 2.25 X Motor Amps + Heater Amps
--- indicates Not Required
Note : The 208 or 240 in the heat kit part number field is for clarification of the nominal voltage for this model.
^ Three Phase
3
Notation is correct as XB because technically the 240V heater kit application can be used here without any issues.

Heating kW Correction Factor


Supply Voltage 240 230 220 210 208

Correction Factor 1.00 0.92 0.84 0.77 0.75

Multiply the 240-volt heating capacity by correction factors.

12 www.amana-hac.com SS-AARUF
208/240
SEE NOTES 2 & 6 TERMINAL BLOCK SHOWN L1 L2 VOLTS
FOR 50HZ MODELS ONLY EQUIPMENT GROUND
USE COPPER WIRE
BL RD GR WH BR L1 L2

SS-AARUF
SR BK RD GRND
1 PLF PLF 2
PLF 1 2 3 4 5 6 7 8 9 1 PLM
3 PLM 2

PLM 1 2 3 4 5 6 7 8 9 RC EM
NC NO
BK RD PU BL BR WH M1
SEE HI
NOTE 4 EBTDR
M2 COM
BR LO

WH 1 2 3 SEE NOTE 1

TR

GR BK EBTDR R C EBTDR G
SEE NOTE 5 RD 4 24V 5
RD
PU SEE NOTE 1 6 5 4 PLM
G EBTDR RD
R NO C 1 2 3 240 RD WH BR BL GR
K1
BL XFMR-R RD
RD XFMR-C COM TR
K1 PU
5 24V 4 SEE NOTES 2 & 6
C
NC
BL SPEEDUP M1 M2 BL BL
RD COLOR CODE WIRING CODE
BK BLACK GR GREEN FACTORY WIRING
RD RED PU PURPLE HIGH VOLTAGE
BK YL YELLOW BR BROWN LOW VOLTAGE
COPPER POWER SUPPLY SEE
RD PU BL BLUE WH WHITE
(SEE RATING PLATE) NOTE 3 FIELD WIRING
USE MIN. 75°C FIELD WIRE COMPONENT CODE HIGH VOLTAGE
EVAPORATOR MOTOR LOW VOLTAGE
EM
THREE SPEED MOTOR WIRING RC RUN CAPACITOR TR TRANSFORMER
(SELECT MODELS ONLY) (COM) RD LOW BK
SR STRAIN RELIEF PLF FEMALE PLUG CONNECTOR
SEE NOTE 3

www.amana-hac.com
IF REPLACEMENT OF THE ORIGINAL WIRES (M2) BL MEDIUM R RELAY PLM MALE PLUG CONNECTOR
(M1) RC EBTDR FL FUSE LINK
SUPPLIED WITH THIS ASSEMBLY IS NECESSARY BK HIGH ELECTRONIC BLOWER
BR TIME DELAY RELAY TL THERMAL LIMIT
USE WIRE THAT CONFORMS TO THE (TR 1) PU EM EM GRND GROUND
NATIONAL ELECTRIC CODE. BR
3 SPEED BR
PU RC

NOTES:
1. RED WIRES TO BE ON TRANSFORMER TERMINAL "3" FOR 240 VOLTS
AND ON TERMINAL "2" FOR 208 VOLTS.
2. SEE COMPOSITE WIRING DIAGRAMS IN INSTALLATION INSTRUCTIONS
FOR PROPER LOW VOLTAGE WIRING CONNECTIONS.
3. CONFIRM SPEED TAP SELECTED IS APPROPRIATE FOR APPLICATION.
IF SPEED TAP NEEDS TO BE CHANGED, CONNECT APPROPRIATE
MOTOR WIRE (RED FOR LOW, BLUE FOR MEDIUM, AND BLACK FOR
HIGH SPEED) ON "COM" CONNECTION OF THE EBTDR.
INACTIVE MOTOR WIRES MUST BE CONNECTED TO "M1 OR M2"
ON EBTDR.
4. BROWN AND WHITE WIRES ARE USED WITH HEAT KITS ONLY.
5. EBTDR HAS A 7 SECOND ON DELAY WHEN "G" IS ENERGIZED
AND A 65 SECOND OFF DELAY WHEN "G" IS DE-ENERGIZED.
6. LOW VOLTAGE FIELD WIRING TO BE N.E.C CLASS 2 WIRES.
0140A00242-A

Wiring is subject to change. Always


High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
refer to the wiring diagram on the
sources may be present. Failure to do so may cause property damage, personal injury, or death.

13
unit for the most up-to-date wiring.

Wiring Diagram – Air Handler

⚠ Warning
14
NOTE: WHEN INSTALLING HEATER KIT, ENSURE SPEED TAP MUST EXCEED OR EQUAL THE MINIMUM BLOWER TB
CIRCUIT 1
SPEED (MBS) SPECIFIED FOR THE AIRHANDLER/HEATER KIT COMBINATION ON THIS UNIT'S SERIAL PLATE. 1 PH 208-240V
L1 L2
AFTER INSTALLING OPTIONAL HEAT KIT, MARK AN "X" IN THE PROVIDED BELOW.
NO MARK INDICATES NO HEAT KIT INSTALLED. BK RD
PC

L1 TR
1 BK
1 4
BK
HTR3 TL
FL L2
RD 2 2
BK RD
3 5

BK HTR2 PU 3 PU RD
FL TL BL BL

L3 L2 L1 BK BL 4 RD
BK HTR1
FL TL RD PU
EBTDR
BK GR PU
BK 5

RD K1
NO
GND BK XFMR-R
BK 6 WH XFMR-C COM
BK K1

C BK
BL
BK BK BK 7
NC
BL BL
BK WH BR SPEEDUP M1 L1
CC RS
L1 T1 BK BK WH GR
M1 M3 8 RD
Wiring Diagram – Three-Phase Heater Kit

BK BK WH PK
L2 R T2 BK PU
M2 M4 BL
BK 9
L3 T3 BK
PU BR WH BR
WH WH RC EM
SR
CIRCUIT 2 BR
3 PH. 208-240V

AR POWER SUPPLY HKR POWER SUPPLY

www.amana-hac.com
(CIRCUIT 1) (CIRCUIT 2)
L1 L2 L3
L1 L2
PC
208/240 VOLTS COMPONENT CODE COLOR CODE
1 T1 T2 T3
FL HTR3 TL FL HTR2 TL HTR HEAT ELEMENT
EM EVAPORATOR MOTOR BK BLACK
2
EBTDR ELEC. BLOWER TIME DELAY RELAY BL BLUE
RC EM
RS RELAY/SEQUENCER BR BROWN
3
LOW NC NO FL HTR1 TL RC RUN CAPACITOR
M1 GR GREEN
EBTDR 4 TL THERMAL LIMIT
OR ORANGE
TR TRANSFORMER
NOTE:- HIGH COM PK PINK
5 TB TERMINAL BLOCK
PU PURPLE
THIS LABEL MUST BE CC CONTACTOR
M2 M1 RD RED
6 PC 9-PIN CONNECTOR
ATTACHED ON THE 1 2 3 WH WHITE
SR STRAIN RELIEF
7 YL YELLOW
AIRHANDLER IN A PROMINENT TR FL FUSE LINK
CC
LOCATION 8 M4 M3 CB CIRCUIT BREAKER
4 24 VOLT 5

EBTDR 9 RS WIRING CODE


PK BL GR BR W HIGH VOLTAGE
LOW VOLTAGE
RD C GR W2 W1
HEATER CONTROL
0140M00273-A

Wiring is subject to change. Always


High Voltage: Disconnect all power before servicing or installing this unit. Multiple power
refer to the wiring diagram on the
sources may be present. Failure to do so may cause property damage, personal injury, or death.
unit for the most up-to-date wiring.

SS-AARUF
⚠ Warning
Accessories

Expansion Valve Kits for Air Conditioning and Heat Pump Applications

Kit Tonnage:
Description Application Refrigerant
Number Outdoor Unit
TX2N4A Non-bleed Valve AC or HP R-410A 1½ - 2 Ton

TX3N4 Non-bleed Valve AC or HP R-410A 2½ - 3 Ton

TX5N4 Non-bleed Valve AC or HP R-410A 3½ - 5 Ton

Downflow Insulation Kit

DFK-B DFK-C DFK-D

ARUF25B14** ARUF37C14** ARUF37D14**

ARUF29B14** ARUF43C14** ARUF43D14**

ARUF31B14** ARUF49C14** ARUF47D14**

ARUF49D14**

ARUF61D14**

Filters

Chassis Part # Size

B ALFH16201E 16.0” x 20.0”

C ALFH1912201E 19.5” x 20.0”

D ALFH20231E 23.0” x 20.0”

SS-AARUF www.amana-hac.com 15
Notes

Amana® is a trademark of Maytag Corporation or its related companies and used under license to Goodman Company, L.P. All rights reserved. Our continuing
commitment to quality products may mean a change in specifications without notice. © 2018 Goodman Company, L.P. • Houston, Texas • Printed in the USA.

16 www.amana-hac.com SS-AARUF