CALCUL DE LA CONCEPTION POUR BÂTIMENT DE

SOUS-STATION 5.5 KV (ZONE DE POMPE


BOOSTER )
DESIGN CALCULATION FOR 5.5KV SUBSTATION
BUILDING (BOOSTER PUMP AREA)
DOCUMENT NO : 1604-02-CAL-CI-2189 REV. B APPENDIX-A

1 CAS DE CHARGE LOAD CASES

Poids Propre Dead Load


Cas De Charge 1 Poids Propre de la Structure
Load Case 1 Self Weight of Structure

poids propre de la Structure calculé automatiquement par le facteur 1,07


Self Weight of Structure Automatic calculated by factor 1.07

Cas De Charge 2 Finitions de la terrasse + Charges de la dalle


(Salle de batterie,Salle d'appareillage electrique, Chambre panneau de con
Load Case 2 Roof Finishes + Slab Loads
(Battery room, Electrical Switchgear Room, Control panel room)

Tuile béton préfabriqué 50mm 0.05 x 25 = 1.250 kN/m2


B
Prefabricated concrete tile 50mm
Graviers grossiers de protection 50 mm = 0.05 x 25 = 1.250 kN/m2
Protection gravel 50 mm
Chape d'étanchéité = 48 N/m2 = 0.048 kN/m2
Water proofing course
Béton de régalage d'une épaisseur de 80mm = 0.08 x 25 = 2.000 kN/m2
Levelling concrete 80mm thick
Isolant thermique d'une épaisseur de 80mm = 0.08 x 0.30 = 0.024 kN/m2
80mm thick thermal Insulation
(Panneau à mousse de polyuréthanne (30 kg/m3))
(Polyurethane foam Panel (30 kg/m3))

Poids propre de la dalle en béton armé = 0.15 x 25= 3.750 kN/m2


Selfweight of Reinforced Concrete Slab
Enduit de plafond d'une épaisseur de 15mm = 0.015 x 20 = 0.300 kN/m2
Ceiling Plaster 15mm thick

Charge de Sable sur la toiture = 0.2 = 0.200 kN/m2


Sand Load on Roof

Finitions totales de la terrasse = 8.82 kN/m2


(Salle de batterie)
Total Roof Finishes
(Battery room)

FAUX PLAFOND = 0.5= 0.5 kN/m2


FALSE CEILING

Finitions totales de la terrasse = 9.32 kN/m2


CALCUL DE LA CONCEPTION POUR BÂTIMENT DE
SOUS-STATION 5.5 KV (ZONE DE POMPE
BOOSTER )
DESIGN CALCULATION FOR 5.5KV SUBSTATION
BUILDING (BOOSTER PUMP AREA)
DOCUMENT NO : 1604-02-CAL-CI-2189 REV. B APPENDIX-A

(Salle d'appareillage electrique, Chambre panneau de contrôle)


Total Roof Finishes
(Electrical switchgear room,Control panel room)

Cas De Charge 3 Finitions de la terrasse + Charges de la dalle


(Transformateur)
Load Case 3 Roof Finishes + Slab Loads
(Transformer)
B
Panneau toit "sandwich" = 0.5x4.93= 2.465 kN/m
Sandwich roof panel 0.5x4.93/2= 1.233 kN/m

Panne ( C200x90x8 ) = 30.3x4.93x10/1000= 1.494 kN/m


Purlin ( C200x90x8 ) 30.3x4.93x10/2/1000= 0.747 kN/m

Finitions totales de la terrasse = 3.965 kN/m


Total Roof Finishes 1.985 kN/m

Cas De Charge 4 Charge du parapet + Charge de Mur en bloc plein


Load Case 4 Parapet Load + Solid Block Wall Load
(Considérant qu'il n' y a pas d'ouvertures dans les murs)
(Assuming there is no opening in walls)

Parapet Load
Charge du parapet de 100 x 1100 pour poutre extérieure
Parapet load of 100 x 1100 on External beam
0.1x(1.1+0.075)x25+.04x20x1 3.818 kN/m

Charge du mur
Wall Load
Charge du mur en bloc plein d'une épaisseur de 300mm 0.3x22= 6.600 kN/m2
Load of 300mm Thk Solid Block Wall

Charge du mur en bloc plein d'une épaisseur de 200mm 0.2x22= 4.400 kN/m2
Load of 200mm Thk Solid Block Wall

Charge du mur en bloc plein d'une épaisseur de 100mm 0.1x22= 2.200 kN/m2
Load of 100mm Thk Solid Block Wall

rez de chaussée
GROUND FLOOR
FAISCEAU hauteur déduction charge de la ligne unité remarque
BEAM HEIGHT DEDUCTION LINE LOAD UNIT REMARK
A1-A2 5.30 0.00 34.98 kN/m
CALCUL DE LA CONCEPTION POUR BÂTIMENT DE
SOUS-STATION 5.5 KV (ZONE DE POMPE
BOOSTER )
DESIGN CALCULATION FOR 5.5KV SUBSTATION
BUILDING (BOOSTER PUMP AREA)
DOCUMENT NO : 1604-02-CAL-CI-2189 REV. B APPENDIX-A

REFER
A2-A2A 5.30 0.00 kN/m STAAD
34.98 MODAL
A2A-A3 5.30 0.00 34.98 kN/m
A3-A4 5.30 0.00 34.98 kN/m
A4-A5 5.30 0.00 34.98 kN/m
A5-A6 5.30 0.00 34.98 kN/m
A6-A7 5.30 0.00 34.98 kN/m
B1-B2 5.30 0.00 34.98 kN/m
B2-B2A 5.30 0.00 34.98 kN/m
B2A-B3 5.30 0.00 34.98 kN/m
B3-B4 5.30 0.00 23.32 kN/m
B4-B5 5.30 0.00 23.32 kN/m
B5-B6 5.30 0.00 23.32 kN/m
B6-B7 5.30 0.00 23.32 kN/m
E5-E6 5.30 0.00 34.98 kN/m
E6-E7 5.30 0.00 34.98 kN/m
A1-A11 5.30 0.00 34.98 kN/m
A11-B1 5.30 0.00 34.98 kN/m
B1-C1 3.05 0.00 20.13 kN/m
B1A-C1A 3.05 0.00 20.13 kN/m
C1-C1A 3.05 0.00 20.13 kN/m
A2-A12 5.30 0.00 23.32 kN/m
A12-B2 5.30 0.00 23.32 kN/m
B3-D3 5.30 0.00 23.32 kN/m
B4-D4 5.30 0.00 23.32 kN/m
B5-D5 5.30 0.00 23.32 kN/m
D5-E5 5.30 0.00 23.32 kN/m
A7-A17 5.30 0.00 34.98 kN/m
A17-B7 5.30 0.00 34.98 kN/m
B7-C17 5.30 0.00 34.98 kN/m
C17-E7 5.30 0.00 34.98 kN/m

2 Charge Utile Live Load


(appliquée comme charge sur le plancher en Staad )
(Applied as a floor Load in Staad)

Cas De Charge 5 Charge Utile sur terrasse (accessible)


Load Case 5 Live load at roof slab (accessible) = 2.50 kN/m2

3 Charges de la température Temperature loads


Cas De Charge 6 & 7
Load Case 6 & 7
CALCUL DE LA CONCEPTION POUR BÂTIMENT DE
SOUS-STATION 5.5 KV (ZONE DE POMPE
BOOSTER )
DESIGN CALCULATION FOR 5.5KV SUBSTATION
BUILDING (BOOSTER PUMP AREA)
DOCUMENT NO : 1604-02-CAL-CI-2189 REV. B APPENDIX-A

La charge de la température est appliquée à la structure


entière en utilisant l'installation du logiciel Staad pro
en fournissant une augmentation de la température de 30℃
Temperature load is applied on the entire structure by using STAAD pro facility by
B
providing increase in temprature 30 ℃.

5 Charge d'équipement Equipment loads


Cas De Charge 17
Load Case 17
Poids du matériel(Référence de l’équipement électrique)
Equipment weight(reference of electrical equipment)

Poids du matériel(Référence de l’équipement électrique) 1.20 ton B


Equipment weight(reference of electrical equipment) 4.00 ton
0.40 ton

Load applied to beam = 1.2*10/2/0.8= 7.50 10.00 kN/m


Load applied to beam = 2*10/2/3.15= 3.17 5.00 kN/m
= 0.4*10/1.2= 3.33 3.50 kN/m

Charge appliquée à la dalle de toit A1-B2 (SALLE DE BATTERIE) 19.75 kN/m2


Load applied to roof slab A1-B2 (battery room)

Poids du matériel (HVAC) 3.67 ton B


Equipment weight(HVAC)

Taille du matériel(HVAC) 2.4*6.2 = 14.88 m2


Equipment size(HVAC)

Charge appliquée à la dalle de toit A2A-B4 entre axes 2A et 4 5.00 kN/m2


Load applied to roof slab A2A-B4 between Axis 2A & 4

Charge appliquée à la dalle de toit A4-B6 entre axes 4 et 6 5.00 kN/m2


Load applied to roof slab A4-B6 between Axis 4 & 6

Coque de fondation d'équipement de HVAC 200mm d'épaisseur de béton 5.00 kN/m2


HVAC equipment founadation pad 200mm thichness concrete

6 Charge d'sol Soil loads


Cas De Charge 9
Load Case 9
CALCUL DE LA CONCEPTION POUR BÂTIMENT DE
SOUS-STATION 5.5 KV (ZONE DE POMPE
BOOSTER )
DESIGN CALCULATION FOR 5.5KV SUBSTATION
BUILDING (BOOSTER PUMP AREA)
DOCUMENT NO : 1604-02-CAL-CI-2189 REV. B APPENDIX-A

Coefficient de pression des terres au repos, Ko = 0.5


Earth pressure coefficient at rest
Poids unitaire du sol 18 kN/m3
Unit weight of soil

Pression max en bas Pmax= 0.5x2.5x18= 22.500 kN/m2


B
Max pressure at bottom

min Pression en haut Pmin= 0.000 kN/m2


Min pressure at top

pression sur plaque de fond Pbase= 2.2x18= 39.600 kN/m2


Pressure on baseplate
CALCUL DE LA CONCEPTION POUR BÂTIMENT DE SOUS-STATION
5.5 KV (ZONE DE POMPE BOOSTER )

DESIGN CALCULATION FOR 5.5KV SUBSTATION BUILDING


(BOOSTER PUMP AREA)

DOCUMENT NO : 1604-02-CAL-CI-2189 REV. B


6 Chargeurs de grues Crane loads
Cas De Charge 12--19
Load case 12-19
CALCUL DE CHARGEMENT DU VENT SELON LE NV 65 WIND LOAD CALCULATIONS AS PER NV 65

Vitesse normale du vent pour le site à une hauteu V = 45 m/s


Normal wind speed for the site at a height of 10m
(Se reporter à Cl.4.1 Données de conception d'ingénierie Basis, Doc.
(Refer Cl.4.1Basis Engineering Design Data Doc.No.1604-00-DBM-PM-1301
Pression du vent à la hauteur h qh = V2 (Refer Cl. 1.21 NV 65))
Wind pressure at height h 16.3

Normale Pression du vent en hauteur 10m q10 = 45 ^2 daN/m2


Normal Wind pressure at height 11m 16.3
q10 = 124.2 daN/m2

q10 = 1.242 kN/m2

Pression du vent à toute hauteur, h qh = 2.5 * q10 * ( h + 18) (Refer Cl. 1.24 NV 65))
Wind Pressure at any height, h (h + 60)

Où, h =Hauteur en mètres


Where, h =height in meters

Hauteur Pression normale du vent


Height, h (m) Nomral Wind Pressure qh (kN/m2)

upto 3 1.035

5 1.099

10 1.242

15 1.367

20 1.475

25 1.571

30 1.656

35 1.733

40 1.801

Force du vent F = qh * d * Ks * Ct * A
CALCUL DE LA CONCEPTION POUR BÂTIMENT DE SOUS-STATION
5.5 KV (ZONE DE POMPE BOOSTER )

DESIGN CALCULATION FOR 5.5KV SUBSTATION BUILDING


(BOOSTER PUMP AREA)

DOCUMENT NO : 1604-02-CAL-CI-2189 REV. B


Wind force
Où, d = Coefficient de réduction pour les grandes surfaces (Refer Cl. 1.244-1 NV 65))
Where, d = Reduction coefficient for large area
= 1
Ks = Coefficient de site Site Coefficient (Refer Cl. 1.242 NV 65))
= 1 => Pour la Région I et pour le site normal for Region I and for normal site

Ct = Coefficient de pression Pressure Coefficient

A = Zone projetée Projected Area

Vent normal Wind Normal qh * d * Ks


Remarque
h qh qh * d * Ks(kN/㎡) Remark
Parapet de toilette
Parapet of washroom 4.95 1.10 1.10

Parapet Parapet
7.2 1.16 1.16

Charge de vent sur le mur Wind Load on wall

Longueur du bâtiment Length of building L = 33.00 m B


Largeur du bâtiment Width of building B = 11.30 m
Hauteur du bâtiment Height of building H = 7.20 m
Pression de surface externe
External Surface Pressure Pe = qh * d * Ks * Cpe
où Cpe = Coefficient de pression externe de la surface du bâtiment
Where, Cpe = External Pressure coefficient of building surface
Pression de surface interne
Internal Surface Pressure Pi = qh * d * Ks * Cpi
où Cpi = Coefficient de pression interne de la surface du bâtiment
Where, Cpi = Internal Pressure coefficient of building surface
Par conséquent, la pression nette sur le mur
Therefore, Net Pressure on wallPa = Pe - Pi

Vent à Long Mur


Wind to Long Wall :
la = H / L = 7.20 = 0.22
CALCUL DE LA CONCEPTION POUR BÂTIMENT DE SOUS-STATION
5.5 KV (ZONE DE POMPE BOOSTER )

DESIGN CALCULATION FOR 5.5KV SUBSTATION BUILDING


(BOOSTER PUMP AREA)

DOCUMENT NO : 1604-02-CAL-CI-2189 REV. B


###
L/B = ### = 2.92
11.30
Coefficient go = 1.00 (Refer R-III.5 NV 65)

Vent à Courte Muraille:


Wind to Short Wall :
lb = H / B = 7.20 = 0.64
11.30
B/L = 11.30 = 0.34
###
Coefficient go = 0.85 (Refer R-III.5 NV 65)

Coefficient de pression externe pour la paroi au vent


External Pressure coefficient for windward wall Cpe = 0.80 (Refer Cl. 2.131.11 NV 65)
Coefficient de pression externe pour la paroi sous le vent
External Pressure coefficient for leeward wall Cpe = - (1.3 * go - 0.8 ) (Refer Cl. 2.131.11 NV 65)
Internal Pressure coefficient for walls & roof
Internal Pressure coefficient for walls & roof Cpi = 0.8 * (1.8 -1 go ) (Refer Cl. 2.141 NV 65)
Coefficient d'aspiration interne pour murs et toiture
Internal Suction coefficient for walls & roof Cpi = -0.6 (1.3 * go - 0.8 ) (Refer Cl. 2.141 NV 65)
Coefficient de pression interne pour parapet
Internal Pressure coefficient for parapet Cpi = 0.8 * (1.8 -1 go ) (Refer Cl. 2.143 NV 65)
Coefficient d'aspiration interne pour parapet

Internal Suction coefficient for parepet Cpi = -0.6 (1.3 * go - 0.8 ) (Refer Cl. 2.143 NV 65)

Coefficients de pression externe Cpe pour murs verticaux


External pressure coefficients Cpe for vertical walls
MUR COURT
MUR LONG
VENT POUR WIND TO : SHORT
LONG WALL
WALL
Cpe dans Windward (avant)
0.80 0.80
Cpe in Windward (front)
Cpe dans Leeward (arrière)
-0.50 -0.31
Cpe in Leeward (rear)
De profil
-0.50 -0.31
Side Face
Toit
-0.50 -0.31
Roof
Remarque: le signe "-" indique que la charge est en mouvement loin du mur
Note : "-" sign indicates load is acting away from wall

Coefficients de pression interne Cpi pour parois verticales


CALCUL DE LA CONCEPTION POUR BÂTIMENT DE SOUS-STATION
5.5 KV (ZONE DE POMPE BOOSTER )

DESIGN CALCULATION FOR 5.5KV SUBSTATION BUILDING


(BOOSTER PUMP AREA)

DOCUMENT NO : 1604-02-CAL-CI-2189 REV. B


Internal pressure coefficients Cpi for vertical walls
MUR LONG MUR COURT
VENT POUR WIND TO :
LONG WALL SHORT WALL
Cpi 0.40 -0.30 0.56 -0.18

VENT WIND
0.80

0.30

Aspiration interne Internal Suction

0.5 0.30 0.30

0.30

0.50
0.30 0.50
0.30
0.50 0.50 0.30

0.50
0.30

0.50
Cas 1: Pression externe + aspiration interne Case 1 : External Pressure + Internal Suction
CALCUL DE LA CONCEPTION POUR BÂTIMENT DE SOUS-STATION
5.5 KV (ZONE DE POMPE BOOSTER )

DESIGN CALCULATION FOR 5.5KV SUBSTATION BUILDING


(BOOSTER PUMP AREA)

DOCUMENT NO : 1604-02-CAL-CI-2189 REV. B

VENT WIND
0.80

0.40

0.00
Pression interne Internal Pressure

0.5 0.40 0.40

0.40

0.40 0.50 0.50

0.40
0.50 0.50 0.40

0.40

0.50
Cas 2: Pression externe + Pression interne Case 2 : External Pressure + Internal Pressure
Figure 1: - Coefficient de pression du vent lorsque le vent est normal à la paroi longue
Figure 1 :- Wind Pressure Coefficient when wind normal to long wall
CALCUL DE LA CONCEPTION POUR BÂTIMENT DE SOUS-STATION
5.5 KV (ZONE DE POMPE BOOSTER )

DESIGN CALCULATION FOR 5.5KV SUBSTATION BUILDING


(BOOSTER PUMP AREA)

DOCUMENT NO : 1604-02-CAL-CI-2189 REV. B

VENT WIND
0.00 0.31

0.18

Aspiration interne Internal Suction


0.8 0.18 0.18

0.18

0.31 0.00
0.18 0.31
0.18 0.80 0.80 0.18

0.31
0.18

0.31
Cas 1: Pression externe + aspiration interne Case 1 : External Pressure + Internal Suction

VENT WIND
0.00 0.31

0.56

Pression interne Internal Pressure


0.8 0.56
0.56

0.56
CALCUL DE LA CONCEPTION POUR BÂTIMENT DE SOUS-STATION
5.5 KV (ZONE DE POMPE BOOSTER )

DESIGN CALCULATION FOR 5.5KV SUBSTATION BUILDING


(BOOSTER PUMP AREA)

DOCUMENT NO : 1604-02-CAL-CI-2189 REV. B


0.31

0.56 0.80 0.80 0.56

0.31
0.56

0.31
Cas 2: Pression externe + Pression interne Case 2 : External Pressure + Internal Pressure
Figure 2: - Coefficient de pression du vent lorsque le vent est normal à la paroi courte
Figure 2 :- Wind Pressure Coefficient when wind normal to short wall

Pression nette Pa => Lorsque le vent Normal à longue face du mur


Net Pressure Pa => When Wind Normal to Long Face of Wall

CAS 1 CASE 1
Pa in kN/m , (Vent Normal à Longue Face du Mur Wind Normal to Long Face of Wall)
2

Emplaceme Paroi
Murs avant Paroi arrière Toit
nt latérale
Location Front Wall Rear Wall Roof
Side Wall
Jusqu'à Pe 0.93 -0.58 -0.58 -0.58
parapet Up Pi -0.35 -0.35 -0.35 -0.35
to parapet Pa 1.28 -0.23 -0.23 -0.23

CAS 2 CASE 2
Pa in kN/m , (Vent Normal à Longue Face du Mur Wind Normal to Long Face of Wall)
2

Emplaceme Paroi
Murs avant Paroi arrière Toit
nt latérale
Location Front Wall Rear Wall Roof
Side Wall
Jusqu'à Pe 0.93 -0.58 -0.58 -0.58
parapet Up Pi 0.47 0.47 0.47 0.47
to parapet Pa 0.47 -1.05 -1.05 -1.05

Pression nette Pa => Lorsque le vent est normal à court du mur


Net Pressure Pa => When Wind Normal to Short Face of Wall

CAS 1 CASE 1
Pa in kN/m , (Vent Normal à Court Face du Mur Wind Normal to Short Face of Wall)
2
CALCUL DE LA CONCEPTION POUR BÂTIMENT DE SOUS-STATION
5.5 KV (ZONE DE POMPE BOOSTER )

DESIGN CALCULATION FOR 5.5KV SUBSTATION BUILDING


(BOOSTER PUMP AREA)

DOCUMENT NO : 1604-02-CAL-CI-2189 REV. B


Emplaceme Paroi
Murs avant Paroi arrière Toit
nt latérale
Location Front Wall Rear Wall Roof
Side Wall
Jusqu'à Pe 0.93 -0.36 -0.36 -0.36
parapet Up Pi -0.21 -0.21 -0.21 -0.21
to parapet Pa 1.14 -0.14 -0.14 -0.14

CAS 2 CASE 2
Pa in kN/m , (Vent Normal à Court Face du Mur Wind Normal to Short Face of Wall)
2

Emplaceme Paroi
Murs avant Paroi arrière Toit
nt latérale
Location Front Wall Rear Wall Roof
Side Wall
Jusqu'à Pe 0.93 -0.36 -0.36 -0.36
parapet Up Pi 0.65 0.65 0.65 0.65
to parapet Pa 0.28 -1.00 -1.00 -1.00
PTION POUR BÂTIMENT DE SOUS-STATION
ZONE DE POMPE BOOSTER )

ION FOR 5.5KV SUBSTATION BUILDING


OOSTER PUMP AREA)

APPENDIX - A

ND LOAD CALCULATIONS AS PER NV 65

(Se reporter à Cl.4.1 Données de conception d'ingénierie Basis, Doc. No.1604-00-DBM-PM-1301)


(Refer Cl.4.1Basis Engineering Design Data Doc.No.1604-00-DBM-PM-1301)
PTION POUR BÂTIMENT DE SOUS-STATION
ZONE DE POMPE BOOSTER )

ION FOR 5.5KV SUBSTATION BUILDING


OOSTER PUMP AREA)

APPENDIX - A

I et pour le site normal for Region I and for normal site


PTION POUR BÂTIMENT DE SOUS-STATION
ZONE DE POMPE BOOSTER )

ION FOR 5.5KV SUBSTATION BUILDING


OOSTER PUMP AREA)

APPENDIX - A

(Refer Cl. 2.131.11 NV 65)

(Refer Cl. 2.131.11 NV 65)

(Refer Cl. 2.141 NV 65)

(Refer Cl. 2.141 NV 65)

(Refer Cl. 2.143 NV 65)

(Refer Cl. 2.143 NV 65)


PTION POUR BÂTIMENT DE SOUS-STATION
ZONE DE POMPE BOOSTER )

ION FOR 5.5KV SUBSTATION BUILDING


OOSTER PUMP AREA)

APPENDIX - A

0.50

ration interne Case 1 : External Pressure + Internal Suction


PTION POUR BÂTIMENT DE SOUS-STATION
ZONE DE POMPE BOOSTER )

ION FOR 5.5KV SUBSTATION BUILDING


OOSTER PUMP AREA)

APPENDIX - A

0.00

0.50

ssion interne Case 2 : External Pressure + Internal Pressure


du vent lorsque le vent est normal à la paroi longue
PTION POUR BÂTIMENT DE SOUS-STATION
ZONE DE POMPE BOOSTER )

ION FOR 5.5KV SUBSTATION BUILDING


OOSTER PUMP AREA)

APPENDIX - A

0.00

0.31

ration interne Case 1 : External Pressure + Internal Suction

0.00

0.31
PTION POUR BÂTIMENT DE SOUS-STATION
ZONE DE POMPE BOOSTER )

ION FOR 5.5KV SUBSTATION BUILDING


OOSTER PUMP AREA)

APPENDIX - A

ssion interne Case 2 : External Pressure + Internal Pressure


du vent lorsque le vent est normal à la paroi courte
PTION POUR BÂTIMENT DE SOUS-STATION
ZONE DE POMPE BOOSTER )

ION FOR 5.5KV SUBSTATION BUILDING


OOSTER PUMP AREA)

APPENDIX - A
CALCUL DE LA CONCEPTION POUR BÂTIMENT DE
SOUS-STATION 5.5 KV (ZONE DE POMPE
BOOSTER )
DESIGN CALCULATION FOR 5.5KV SUBSTATION
BUILDING (BOOSTER PUMP AREA)
DOCUMENT NO : 1604-02-CAL-CI-2189 REV. B APPENDIX-A

7 COMBINAISON DE CHARGE (LOAD COMBINATIONS )

Charges principales Primary loads DL = Poids propre Dead Load


LL = Charge Utile Live Load
NWL = Charge du vent(ORDINAIRE) Wind Load(NORMAL)
B EWL = 1.2Charge du vent(ORDINAIRE) 1.2Wind Load(NORMAL)
(Refer Cl. D.1.2.2 BAEL 91)
TL = Charge du température Temperature Load

COMBINAISON DE CHARGE - LIMITE EXTREME LOAD COMBINATION- ULTIMATE LIMIT


LC in STAAD Combinaison de charge Load Combination

101 LOAD 101 1.35D+1.5LL


102 LOAD 102 1.35DL+1.5LL+1.0EWL(X+1)+0.8TL(+)
103 LOAD 103 1.35DL+1.5LL+1.0EWL(X+1)+0.8TL(-)
104 LOAD 104 1.35DL+1.5LL+1.0EWL(X+2)+0.8TL(+)
105 LOAD 105 1.35DL+1.5LL+1.0EWL(X+2)+0.8TL(-)
106 LOAD 106 1.35DL+1.5LL+1.0EWL(X-1)+0.8TL(+)
107 LOAD 107 1.35DL+1.5LL+1.0EWL(X-1)+0.8TL(-)
108 LOAD 108 1.35DL+1.5LL+1.0EWL(X-2)+0.8TL(+)
109 LOAD 109 1.35DL+1.5LL+1.0EWL(X-2)+0.8TL(-)
110 LOAD 110 1.35DL+1.5LL+1.0EWL(Z+1)+0.8TL(+)
111 LOAD 111 1.35DL+1.5LL+1.0EWL(Z+1)+0.8TL(-)
112 LOAD 112 1.35DL+1.5LL+1.0EWL(Z+2)+0.8TL(+)
113 LOAD 113 1.35DL+1.5LL+1.0EWL(Z+2)+0.8TL(-)
114 LOAD 114 1.35DL+1.5LL+1.0EWL(Z-1)+0.8TL(+)
115 LOAD 115 1.35DL+1.5LL+1.0EWL(Z-1)+0.8TL(-)
116 LOAD 116 1.35DL+1.5LL+1.0EWL(Z-2)+0.8TL(+)
117 LOAD 117 1.35DL+1.5LL+1.0EWL(Z-2)+0.8TL(-)
118 LOAD 118 1.35DL+1.0LL+1.5EWL(X+1)+0.8TL(+)
119 LOAD 119 1.35DL+1.0LL+1.5EWL(X+1)+0.8TL(-)
120 LOAD 120 1.35DL+1.0LL+1.5EWL(X+2)+0.8TL(+)
121 LOAD 121 1.35DL+1.0LL+1.5EWL(X+2)+0.8TL(-)
122 LOAD 122 1.35DL+1.0LL+1.5EWL(X-1)+0.8TL(+)
123 LOAD 123 1.35DL+1.0LL+1.5EWL(X-1)+0.8TL(-)
124 LOAD 124 1.35DL+1.0LL+1.5EWL(X-2)+0.8TL(+)
125 LOAD 125 1.35DL+1.0LL+1.5EWL(X-2)+0.8TL(-)
126 LOAD 126 1.35DL+1.0LL+1.5EWL(Z+1)+0.8TL(+)
127 LOAD 127 1.35DL+1.0LL+1.5EWL(Z+1)+0.8TL(-)
128 LOAD 128 1.35DL+1.0LL+1.5EWL(Z+2)+0.8TL(+)
129 LOAD 129 1.35DL+1.0LL+1.5EWL(Z+2)+0.8TL(-)
130 LOAD 130 1.35DL+1.0LL+1.5EWL(Z-1)+0.8TL(+)
131 LOAD 131 1.35DL+1.0LL+1.5EWL(Z-1)+0.8TL(-)
132 LOAD 132 1.35DL+1.0LL+1.5EWL(Z-2)+0.8TL(+)
CALCUL DE LA CONCEPTION POUR BÂTIMENT DE
SOUS-STATION 5.5 KV (ZONE DE POMPE
BOOSTER )
DESIGN CALCULATION FOR 5.5KV SUBSTATION
BUILDING (BOOSTER PUMP AREA)
DOCUMENT NO : 1604-02-CAL-CI-2189 REV. B APPENDIX-A

133 LOAD 133 1.35DL+1.0LL+1.5EWL(Z-2)+0.8TL(-)


134 LOAD 134 1.35DL+1.5EWL(X+1)
135 LOAD 135 1.35DL+1.5EWL(X+2)
136 LOAD 136 1.35DL+1.5EWL(X-1)
137 LOAD 137 1.35DL+1.5EWL(X-2)
138 LOAD 138 1.35DL+1.5EWL(Z+1)
139 LOAD 139 1.35DL+1.5EWL(Z+2)
140 LOAD 140 1.35DL+1.5EWL(Z-1)
141 LOAD 141 1.35DL+1.5EWL(Z-2)
142 LOAD 142 1.35DL+1.35TL(+)
143 LOAD 143 1.35DL+1.35TL(-)

COMBINAISON DE CHARGE- LIMITE DE SERVICE LOAD COMBINATION- SERVICE LIMIT


LC in STAAD Combinaison de la charge Load Combination
1101 LOAD 1101 1.00D+1.0LL
1102 LOAD 1102 1.00DL+1.0LL+0.77NWL(X+1)+1.0TL(+)
1103 LOAD 1103 1.00DL+1.0LL+0.77NWL(X+1)+1.0TL(-)
1104 LOAD 1104 1.00DL+1.0LL+0.77NWL(X+2)+1.0TL(+)
1105 LOAD 1105 1.00DL+1.0LL+0.77NWL(X+2)+1.0TL(-)
1106 LOAD 1106 1.00DL+1.0LL+0.77NWL(X-1)+1.0TL(+)
1107 LOAD 1107 1.00DL+1.0LL+0.77NWL(X-1)+1.0TL(-)
1108 LOAD 1108 1.00DL+1.0LL+0.77NWL(X-2)+1.0TL(+)
1109 LOAD 1109 1.00DL+1.0LL+0.77NWL(X-2)+1.0TL(-)
1110 LOAD 1110 1.00DL+1.0LL+0.77NWL(Z+1)+1.0TL(+)
1111 LOAD 1111 1.00DL+1.0LL+0.77NWL(Z+1)+1.0TL(-)
1112 LOAD 1112 1.00DL+1.0LL+0.77NWL(Z+2)+1.0TL(+)
1113 LOAD 1113 1.00DL+1.0LL+0.77NWL(Z+2)+1.0TL(-)
1114 LOAD 1114 1.00DL+1.0LL+0.77NWL(Z-1)+1.0TL(+)
1115 LOAD 1115 1.00DL+1.0LL+0.77NWL(Z-1)+1.0TL(-)
1116 LOAD 1116 1.00DL+1.0LL+0.77NWL(Z-2)+1.0TL(+)
1117 LOAD 1117 1.00DL+1.0LL+0.77NWL(Z-2)+1.0TL(-)
1118 LOAD 1118 1.00DL+0.77LL+1.0NWL(X+1)+1.0TL(+)
1119 LOAD 1119 1.00DL+0.77LL+1.0NWL(X+1)+1.0TL(-)
1120 LOAD 1120 1.00DL+0.77LL+1.0NWL(X+2)+1.0TL(+)
1121 LOAD 1121 1.00DL+0.77LL+1.0NWL(X+2)+1.0TL(-)
1122 LOAD 1122 1.00DL+0.77LL+1.0NWL(X-1)+1.0TL(+)
1123 LOAD 1123 1.00DL+0.77LL+1.0NWL(X-1)+1.0TL(-)
1124 LOAD 1124 1.00DL+0.77LL+1.0NWL(X-2)+1.0TL(+)
1125 LOAD 1125 1.00DL+0.77LL+1.0NWL(X-2)+1.0TL(-)
1126 LOAD 1126 1.00DL+0.77LL+1.0NWL(Z+1)+1.0TL(+)
1127 LOAD 1127 1.00DL+0.77LL+1.0NWL(Z+1)+1.0TL(-)
1128 LOAD 1128 1.00DL+0.77LL+1.0NWL(Z+2)+1.0TL(+)
1129 LOAD 1129 1.00DL+0.77LL+1.0NWL(Z+2)+1.0TL(-)
1130 LOAD 1130 1.00DL+0.77LL+1.0NWL(Z-1)+1.0TL(+)
1131 LOAD 1131 1.00DL+0.77LL+1.0NWL(Z-1)+1.0TL(-)
CALCUL DE LA CONCEPTION POUR BÂTIMENT DE
SOUS-STATION 5.5 KV (ZONE DE POMPE
BOOSTER )
DESIGN CALCULATION FOR 5.5KV SUBSTATION
BUILDING (BOOSTER PUMP AREA)
DOCUMENT NO : 1604-02-CAL-CI-2189 REV. B APPENDIX-A

1132 LOAD 1132 1.00DL+0.77LL+1.0NWL(Z-2)+1.0TL(+)


1133 LOAD 1133 1.00DL+0.77LL+1.0NWL(Z-2)+1.0TL(-)
1134 LOAD 1134 1.00DL+1.5NWL(X+1)
1135 LOAD 1135 1.00DL+1.5NWL(X+2)
1136 LOAD 1136 1.00DL+1.5NWL(X-1)
1137 LOAD 1137 1.00DL+1.5NWL(X-2)
1138 LOAD 1138 1.00DL+1.5NWL(Z+1)
1139 LOAD 1139 1.00DL+1.5NWL(Z+2)
1140 LOAD 1140 1.00DL+1.5NWL(Z-1)
1141 LOAD 1141 1.00DL+1.5NWL(Z-2)
1142 LOAD 1142 1.00DL+1.00TL(+)
1143 LOAD 1143 1.00DL+1.00TL(-)