Operating
Manual
For
ASHIDA Under / Over Frequency
Relay
Type: - AUOFMR-2
AS H I D A E l e c t r o n i c s P v t . L t d . Rev 1
Operating Manual for Ashida Under Over Frequency Relay Page 2 of 12
Type : AUOFMR2
Ref: AUOFMR2_New
INDEX
AS H I D A E l e c t r o n i c s P v t . L t d . Rev 1
Operating Manual for Ashida Under Over Frequency Relay Page 3 of 12
Type : AUOFMR2
Ref: AUOFMR2_New
ASHIDA UNDER / OVER FREQUENCY RELAY
TYPE AUOFMR2.
GENERAL: -
ASHIDA under frequency Relay is designed to suit load
conditions of Indian electrical utilities. This is designed using
micro-controller technology & hence has inherent advantages
over other electromagnetic type relays. Transmission
equipment’s nature of the disturbed loads over long distance
makes difficult to control them. Overload results in the form of
fall in frequency. By using this relay, for monitoring the
frequency of supply at distribution centres, gives efficient load
control.
FEATURES: -
• No mechanical springs, screws, torque are involved & hence
it is vibration / impact proof.
• Relay control is software based & hence it resets instantly
(returns to supervisory). Digital display & keyboard setting is
provided on front panel for setting of frequency, delay time,
date etc.
• Display Frequency resolution is of 0.01Hz with accuracy of +
0.01Hz.
• Two independent set points with independent control
contacts.
• Both set points can be adjusted as Over or Under frequency.
• Separate reset frequency control.
• Computer interface - RS232 and RS485.
AS H I D A E l e c t r o n i c s P v t . L t d . Rev 1
Operating Manual for Ashida Under Over Frequency Relay Page 5 of 12
Type : AUOFMR2
Ref: AUOFMR2_New
FRONT PANAL AND CONTROL
AS H I D A E l e c t r o n i c s P v t . L t d . Rev 1
Operating Manual for Ashida Under Over Frequency Relay Page 7 of 12
Type : AUOFMR2
Ref: AUOFMR2_New
FUNCTION DESCRIPTION: -
The unit is having several display function used for man-machine
interface. The following table gives brief description of different display
functions. By using MODE push button the display function can be
changed. The default function is F1, which displays line frequency. If by
using mode switch, the unit is left indicating some other function, then
after some time the relay will automatically switch over to default
functions.
FUNCTIONS DESCRIPTION
F1 Displays Line frequency.
F2 Displays set point 1-the set point can be changed by
using “↑”[increment]& “↓”[decrement] keys. The range of
setting is 40.00 to 65.00 Hz. All settings are done in
foreground. (Note1).
F3 Reset frequency (Hysterisis) The setting range is 0.10 Hz
to 5.00 Hz The actual reset frequency = setting F2 +/-
hysterisis F3.
F4 Displays set point 2. The set point can be changed by
using ↑”[increment]& “↓”[decrement] keys. The range of
setting is 40.00 to 65.00 Hz. All settings are done in
foreground.(Note1)
F5 Reset frequency (Hysterisis). The setting range is 0.10Hz
to 5.00 Hz. The actual reset frequency = setting F4 +/-
hysterisis F5.
F6 Displays time setting for set point 1(0.1sec to 10.0sec).
The setting can be changed by using ↑and ↓ keys. (Note1).
F7 Displays time setting for set point 2(0.1sec to 10.0sec).
The setting can be changed by using ↑and ↓ keys.(Note1)
F8 Address for RS485 communication. (Note2).
F9 Displays Hours & Minutes, it can be set using↑and ↓ keys
FA Displays Month and Date, it can be set using↑and ↓ keys.
FB Displays Year, it can be set using↑and ↓ keys.
FC Trip Type =1for Self Reset (SR), trip type = 2 for Hand
Reset (HR).
E1 Displays Tripping frequency of last fault.
E2 Displays delay setting of last fault.
E3 Displays mSec of last fault.
E4 Displays Minutes & Sec of last fault.
E5 Displays Date & Hours of last fault.
E6 Displays Month & Year of last fault.
Note-1 = All the settings are done in fore ground. After completion of all
settings, relay asks for confirmation. If mode switch is pressed after
completion only then the new settings will come into effect
Note-2 = Address is required when RS485 communication is used.
AS H I D A E l e c t r o n i c s P v t . L t d . Rev 1
Operating Manual for Ashida Under Over Frequency Relay Page 8 of 12
Type : AUOFMR2
Ref: AUOFMR2_New
ON LINE TESTING FACILITY: -
Solid state electronics design makes the relay immune to mechanical
vibrations or environmental ageing degradation. This makes AUOFMR2
relay almost maintenance free. The normal safety checks & time
grading of circuits is the major functional requirement of the relay. To
serve these two purpose, AUOFMR2 relay is equipped with special on-
line (in-situation) testing facility. Push buttons marked TEST & BYPASS
are provided on the front panel to check the relay functioning. These are
accessible after removing the front dust cover. TEST Push button is used
to check calibration of the unit. By pressing this PB internally generated
62.5Hz frequency signal gets connected as input & the display will show
62.5Hz. If one of the set point is in between 50 Hz and 62 Hz then that
set point is treated as over frequency set point and the relay picks up.
After the set time delay the relay gives trip command which also changes
the state of output contact. The BYPASS button is provided to avoid
tripping of external circuit. By pressing BYPASS button the output
contacts get isolated which avoids interruption to the external circuit.
Trip command can be observed by TRIP LED.
TECHNICAL SPECIFICATION: -
i) Frequency setting range : Under Frequency 40.00Hz to 50.00Hz
: Over Frequency 50.00Hz to 65.00Hz
insteps of 0.01Hz.
ii) Accuracy : 0.02Hz.
iii) Delay time adjustment : 0.1sec. to 10.0 sec. in step of 0.05sec.
iv) LED indications : ON / FAULT1 / TIME1 / FAULT2 /
TIME2 / TRIP1 & TRIP2.
v) Aux. Supply : 85 – 250V DC
vi) Frequency Sensing input : Rated 110VAC PT secondary, Range
0.6 to 1.5 times of rated.
: Block Operation below 0.6 of Rated.
vii) Burden on Power supply : 10VA Maximum
viii) Burden on PT : 1VA Maximum on PT
ix) Centre Frequency : 50.00Hz The set point above centre is
over set point and below is under set
point.
x) Reset Frequency : Programmable 0.1Hz to 5.0Hz.
xi) Confirm to : IS 3231 and IS 8686.
xii) Reset Time : Less then 50 milliseconds.
xiii) Time accuracy : Within + 1%.
xiv) Output Contacts : 3 NO, 2 NO + 1 NC, 1 NO + 2 NC, 3NC
each stage. (Specify any one while
ordering)
AS H I D A E l e c t r o n i c s P v t . L t d . Rev 1
Operating Manual for Ashida Under Over Frequency Relay Page 9 of 12
Type : AUOFMR2
Ref: AUOFMR2_New
xv) Contact Type : SR or HR (Set using function FC 1 =
SR, FC 2 = HR)
xvi) Insulation : The relay is conform to IS 3231 2KV
for 1 Minute
xvii) Impulse test : As per IS 8686 - 1977 for 5KV.
xviii) Endurance Test : The relay is tested for simulated fault
tripping operations for over 2000 times.
xix) Noise Interference : Complies with IS: 8686-1977.
xx) Environmental Test : Damp heat cycle test as per IS: 9000
part V.
xxi) Communication Port : RS-485 and RS 232C port.
xxii) Drawing reference : Cabinet CSC1 Vertical MAC00302
xxiii) Back Terminal Ref. : MSEB\ACD00802
TESTING PROCEDURE: -
• Give 85 – 250V DC supply to Aux. Supply of Relay.
• Connect the AC supply to PT input terminal of the relay.
• If the set Frequency 1 is 47.00Hz, delay time set 1 is 10 secs
& Set Frequency 2 is 58.00Hz with time delay set 2 of 5secs.
• Press MODE switch till you get Function F2. The display
shows previous frequency. For setting 47.00Hz frequency
use ↑ ↓ keys.
• Press the MODE switch to get function F4 that shows
previous Set Frequency 2. Then set 58.00Hz frequency using
↑ ↓ keys.
• Press the MODE switch to get function F6 that shows time
delay for Set Frequency 1. Adjust it to 10 seconds using ↑ ↓
keys.
• Press the MODE switch again to get function F7 that shows
time delay for Set Frequency 2. Adjust it to 5 seconds.
• When the input frequency drops to 47.00Hz, ‘Fault 1’ LED
will glow. The delay time is set for 10sec, after completion of
which, relay will trip & TRIP LED glows. When input
frequency crosses 58.00 Hz, ‘Fault 2’LED glows. After
completion of delay time, relay will trip & LED glows. (This
can also be checked by using TEST push buttons).
AS H I D A E l e c t r o n i c s P v t . L t d . Rev 1
Operating Manual for Ashida Under Over Frequency Relay Page 10 of 12
Type : AUOFMR2
Ref: AUOFMR2_New