Documente Academic
Documente Profesional
Documente Cultură
Coolers &
PSD 159
Central Water
Systems
Continuing Education from Plumbing Systems & Design
JULY/AUGUST 2009
PSDMAGAZINE.ORG
CONTINUING EDUCATION
Reprinted from Plumbing Engineer Design Handbook, Vol. 4, Chapter 12: “Potable Water Coolers and Central Water Systems”
© American Society of Plumbing Engineers, 2008.
Figure 2
Bottled Water Cooler
Figure 4
Pressure-type
Pedestal Water Cooler
Source: Halsey Taylor
Hermetically sealed motor compressors commonly are used for and then through a restrictor device to the compartment. When the com-
alternating-current (AC) applications, both 50 hertz (HZ) and 60 Hz. pressor operates, both water cooling and compartment cooling take place.
Belt-driven compressors generally are used only for direct-current The thermostat usually is located to be more affected by the compartment
(DC) and 25-Hz supply. The compressors are similar to those used in temperature, so the amount of compressor operation and water cooling
household refrigerators and range from 0.08 horsepower (hp) to 0.5 hp available depends considerably on the usage of the compartment.
(0.06 kilowatt [kW] to 0.37 kW). Some compartment coolers, generally pressure types, are equipped
Forced-air-cooled condensers are most commonly used. In coolers with more elaborate systems, ones in which separate thermostats and
rated less than 10 gallons per hour (gph) (38 liters per hour [L/h]), natu- solenoid valves are used to switch the refrigerant flow from a common
ral convection, air-cooled (static) condensers sometimes are included. high side to either the water-cooling evaporator or the compartment
Water-cooled condensers of tube-on-tube construction are used on evaporator. A more recently developed method of obtaining the two-
models intended for high ambient temperatures or where lint and dust temperature function uses two separate and distinct systems, each
in the air make air-cooled types impractical. having its own compressor, high side, refrigerant flow-metering device,
Capillary tubes are used almost exclusively for refrigerant flow con- and controls.
trol in hermetically sealed systems.
Pressure-type coolers often are equipped with precoolers to trans-
Stream Regulators
Since the principal function of a pressure-type water cooler is to pro-
fer heat from the supply water to the wastewater. When drinking from
vide a drinkable stream of cold water from a bubbler, it usually is pro-
a bubbler stream, the user wastes about 60 percent of the cold water
vided with a valve to maintain a constant stream height, independent
down the drain. In a precooler, the incoming water is put in a heat
of supply pressure. A flow rate of 0.5 gallon per minute (gpm) (0.03 liter
exchange relationship with the wastewater. Sometimes the cold waste-
per second [L/s]) from the bubbler generally is accepted as providing
water also is used to subcool the liquid refrigerant. A precooler with
an optimum stream for drinking.
this arrangement is called an “economizer.” Coolers intended only to
dispense water into cups are not equipped with precoolers since there Water Conditioning
is no appreciable quantity of wastewater. Most water coolers are classified by UL in accordance with National Sani-
Most water coolers manufactured today consist of an evaporator tation Foundation (NSF)/ANSI 61: Drinking Water System Components—
formed by refrigerant tubing bonded to the outside of a water circuit. Health Effects and with the Safe Drinking Water Act, which protects public
The water circuit is usually a tank or a coil of large tubing. Materials health by regulating the nation’s public drinking water and its sources.
used in the water circuit are usually nonferrous or stainless steel. Since Also, this legislation makes professional engineers, contractors, architects,
the coolers dispense water for human consumption, sanitary require- building owners, and maintenance staff responsible for the quality of water
ments are essential. (See Underwriters Laboratories [UL] 399: Drinking dispensed from the equipment and fixtures they provide.
Water Coolers.) The effects of lead are devastating to the human body, as it accumu-
Water coolers that also provide a refrigerated storage space, com- lates on vital organs and alters the neurological system. Children are
monly referred to as “compartment cooler,” have the same control particular sensitive to lead because of their development stage—their
compromises common to all refrigeration devices that attempt two- bodies are still developing their vital organs. Even in low concentra-
temperature refrigeration using a single compressor. tions, lead can hinder growth and create learning disabilities. High lead
Most bottle-type compartment coolers are provided with the simplest levels can promote seizures, unconsciousness, and in extreme cases,
series system, one in which the refrigerant feeds first to a water-cooling coil death from encephalopathy.
JULY/AUGUST 2009 Plumbing Systems & Design 5
CONTINUING EDUCATION: Potable Water Coolers and Central Water Systems
AIR BALANCING WATER
AIR BALANCING DOME
VENT VALVE WATER
CHILLED DOMESTIC
FILTER
VENT VALVE CHILLED WATER
FILTER
WATER WATER
WATER (OPTIONAL) SUPPL
(OPTIONAL)
SUPPLY SUPPLY
SUPPLY
AIR
AIR VENT
VENT
RECIRCULATING
RECIRCULATING PUMP
PUMP
CHILLER
MECHANICAL
CHILLER STORAGE TANK
10TH MECHANICAL PENTHOUSESTORAGE TANK
FLOOR PENTHOUSE
10TH
9TH FLOOR 10TH FLOOR
OR FLOOR
24-hour operation, duplex pumps are installed, with each pump occupancies is given in Table 2. Table 3 is used to convert the usage load
being used 12 hours per day. in gph (L/h) to the refrigeration load in British thermal units per hour
• Controls consisting of high- and low-pressure cutouts, freeze (Btuh) (watts [W]). The heat gain from the distribution piping system is
protection, and thermostatic control to limit the temperature of based on a circulating water temperature of 45°F (7.2°C). Table 4 lists
the water leaving the chiller. A flow switch or differential pressure the heat gains for various ambient temperatures. The length of all lines
control also should be provided to stop the compressor when must be included when calculating the heat gain in the distribution
there is no flow through the cooler. Another desirable item is a piping. Table 5 tabulates the heat input from variously sized circulating
time switch that can be used to operate the plant during periods pump motors.
of building occupancy. The total cooling load consists of the heat removed from the makeup
Distribution Piping System water, heat gains from the piping, heat gains from the storage tank, and
The distribution piping delivers chilled water to the drinking fountains. heat input from the pumps. A safety factor of 10 percent to 20 percent is
Systems can be upfeed as shown in Figure 15 or downfeed as shown in added before selecting a condensing unit. The size of the safety factor is
Figure 16. The piping can be galvanized steel, copper, or brass designed governed by usage. For example, in a building with weekend shutdowns,
for a working pressure of 125 psig (861 kPa). the higher safety factor allows pickup when reopening the building on
Monday morning when the total volume of water in the system would
Drinking Water Coolers and Central Systems need to be cooled to the operating temperature. Since the water to the
The makeup cold water lines are made of the same material as the dis- chiller is a mixture of makeup and return water, the chiller selection
tribution piping. When the water supply has objectionable characteris- should be based on the resultant mixed water temperature.
tics, such as high iron or calcium content, or contains odoriferous gases
in solution, a filter should be installed in the makeup water line. Circulating Pump
Insulation is necessary on all the distribution piping and the stor- The circulating pump is sized to circulate a minimum of 3 gpm (0.2 L/s)
age tanks. The insulation should be glass fiber insulation—such as that per branch or the gpm (L/s) necessary to limit the temperature rise of
normally used on chilled-water piping, with a conductivity (k) of 0.22 the circulatory water to 5°F (2.8°C), whichever is greater. Table 6 lists
(32) at a 50°F (10°C) mean temperature and a vapor barrier jacket—or the circulating pump capacity needed to limit the temperature rise of
equal. All valves and piping, including the branch to the fixture, should the circulated water to 5°F (2.8°C). If a separate pump is used to cir-
be insulated. The waste piping from the drinking fountain, including culate water between the evaporator and the storage tank, the energy
the trap, should be insulated. This insulation is the same as is recom- input to this pump must be included in the heat gain.
mended for use on cold water lines.
Storage Tank
Drinking Fountains The storage tank’s capacity should be at least 50 percent of the hourly
Any standard drinking fountain can be used on a central drinking usage. The hourly usage may be selected from Table 2.
water system. Drinking fountains typically are made of vitreous china
Distribution Piping
or stainless steel. However, the automatic volume or stream regulator
Sizing
provided with the fountain must be capable of providing a constant
General criteria for sizing distribution piping for a central, chilled
stream height from the bubbler with inlet pressures up to 125 psig (861
drinking water system are as follows:
kPa). (See Figures 17 and 18.)
1. Limit the maximum velocity of the water in the circulating piping
System Design to 3 feet per second (fps) (0.9 meters per second [m/s]) to prevent
Refrigeration the water from having a milky appearance.
For an office building, a usage load of 5 gph (19 L/h) per fountain for an 2. Avoid excessive friction head losses. The energy necessary to cir-
average corridor and office is normal. The water consumption for other culate the water enters the water as heat and requires additional
PSD 159
tion from other materials may result in a wrong answer.
CE Questions — “Potable Water Coolers & Central Water Systems” (PSD 159)
1. Approximately what percentage of the human body is water? 7. The water quality delivered by water coolers is governed by
a. 25 percent what standard?
b. 50 percent a. ANSI A117.1
c. 75 percent b. ANSI 61
d. 100 percent c. ASPE 45
d. none of the above
2. What function does water play in the human body?
a. cushions joints 8. What temperature water typically is provided by central chilled
b. carries nutrients drinking water systems?
c. regulates temperature a. 45°F
d. all of the above b. 50°F
c. 55°F
3. The average temperature of a compartment cooler should not
d. 60°F
exceed ________.
a. 50°F 9. Drinking fountain distribution piping can be which of the
b. 46°F following materials?
c. 54.4°F a. brass
d. 73.9°F b. copper
c. galvanized steel
4. Which of the following does not have means for collecting or
d. all of the above
disposing of wastewater?
a. pressure-type water cooler 10. What is the required rated capacity for one bubbler for a retail
b. bottled water cooler store?
c. cafeteria cooler a. 5 gph
d. drainless water cooler b. 15 gph
c. 20 gph
5. Which of the following is the most popular wheelchair-
d. 25 gph
accessible unit today?
a. explosion proof 11. What is the heat input of a 1-hp circulating pump?
b. barrier free a. 249 W
c. vandal resistant b. 373 W
d. none of the above c. 559 W
d. 746 W
6. Typically what percentage of cold water is wasted when a user
drinks from a bubbler stream? 12. With regard to drinking fountains, UL 399 covers what?
a. 40 percent a. safety
b. 50 percent b. refrigeration systems
c. 60 percent c. sanitation
d. 70 percent d. both a and c
Please print or type; this information will be used to process your credits.
Name_________________________________________________________________________________________________________
Title __________________________________________________ ASPE Membership No._____________________________________
Organization___________________________________________________________________________________________________
Billing Address_ ________________________________________________________________________________________________
City_ _________________________________________ State/Province_________________________ Zip_______________________
Country_______________________________________________ E-mail_ _________________________________________________
Daytime telephone_ ____________________________________ Fax_____________________________________________________
PE State _ _____________________________________________ PE No._ _________________________________________________
I am applying for the following continuing education credits: ❏ ASPE Member ❏ Nonmember
Each examination: $25 Each examination: $35
I certify that I have read the article indicated above. Limited Time: No Cost to ASPE Member
Payment: ❏ Personal Check (payable to ASPE) $
❏ Business or government check $
❏ DiscoverCard ❏ VISA ❏ MasterCard ❏ AMEX $
Signature If rebilling of a credit card charge is necessary, a $25 processing fee will be charged.
ASPE is hereby authorized to charge my CE examination fee to my
credit card
Expiration date: Continuing education credit will be given
for this examination through August 31, 2010.
Applications received after that date will not be processed. Account Number Expiration date