Documente Academic
Documente Profesional
Documente Cultură
Heat Trace
PSD 161
Systems
OCTOBER 2009
PSDMAGAZINE.ORG
CONTINUING EDUCATION
Self-regulating
Heat Trace Systems
A hot water self-regulating heat trace system can be used for prompt Successful installation of a heat tracing system requires coordination
delivery of hot water at the fixtures. A heating cable system is one of among the various tradespeople involved. Plumbers and electrical and
several accepted methods of providing prompt delivery of hot water. insulation contractors must be made aware of the specific require-
(See Chapter 14.) ments affecting each other’s work.
Today’s buildings are more architecturally complex than those built The information in this chapter will help the designer understand
a decade ago and make ever increasing demands on the interstitial electric heat tracing as it applies to hot water systems. With this infor-
space occupied by HVAC ductwork, mechanical piping, communi- mation, a designer should be able to:
cation wiring, and electrical conduits. This, combined with the need 1. Compare the merits of heat tracing and a recirculation system
to conserve energy and water, challenge engineers to provide cost- based on the requirements of a specific project.
effective, energy-efficient domestic hot water systems. Maintaining the 2. Identify the extent of piping requiring heat tracing. Self-Regulat-
temperature of a domestic hot water system may entail establishing ing Heat Trace Systems
a means to continuously recirculate the water via pumps, valves, and 3. Understand the role of thermal insulation in hot water heat trac-
additional piping. An alternative method is to use self-regulating heat ing.
trace systems. 4. In coordination with an electrical engineer, determine the circuit
Water conservation has become a major concern in the past few breaker/power requirements based on the estimated heat tracing
years. The need to conserve water has led to requirements for the use circuit lengths.
of low-flow fixtures, including faucets, showers, and water closets. The 5. Translate the design requirements into a complete design for a
water wastage that occurs when cooled water is dumped down the project.
drain while the user is waiting for hot water to flow can no longer be tol- All examples and descriptions in this chapter are based on copper
erated. In addition to wasting a precious resource, this practice incurs water piping with fiberglass thermal insulation and other typical
extra energy costs to heat the water and waste treatment costs to pro- design conditions. While design parameters may differ and pipe and
cess the wasted water. The ability to keep a pipe warm close to the point insulation materials other than those discussed can be and frequently
of use is of particular interest with the low-flow fixtures used today. are equipped with heat tracing, such jobs should be undertaken with
the design assistance of a qualified manufacturer’s representative.
Note: All decimal equivalencies in the metric calculations are rounded.
Therefore, the metric conversions shown in the text may vary slightly PRODUCT DESCRIPTION
from theanswers shown in the metric equations. Only Underwriters Laboratories, Inc., listed electric heat tracing sys-
Variables affecting the performance of a heat trace system include: tems for hot water temperature maintenance should be used. (Note:
the system temperature range, time to tap, water wastage, and energy Thirty mA ground fault equipment protection is to be used for all hot
efficiency. Designers should consider these factors along with instal- water heat tracing circuits.) These tested and approved systems are
lation and life-cycle costs when selecting the proper hot water self- based on self-regulating heating cables that are specifically designed for
regulating heat trace system for a particular building. hot water temperature maintenance. (See Figure 1.) Heat is delivered
through a carbon matrix heating element that responds to temperature
SYSTEM DESCRIPTION changes. Whenever the temperature in the heat traced piping begins to
Electric heat tracing systems replace heat lost through the thermal rise, the cable automatically reduces its heat output. Conversely, when
insulation on hot water supply piping to maintain the water at desired the water temperature begins to drop the cable reacts by increasing its
nominal temperatures, eliminating the need for insulated recirculation heat output. This self-regulating feature occurs along the entire length
lines, pumps, and balancing valves. Preventing the hot water from cool- of a heat tracing circuit to ensure that each point receives the amount
of heat necessary to maintain thermal equilibrium.
ing also ensures that hot water is readily available when it is needed.
Heating cables, self-regulating or otherwise, intended for pipe freeze
An electrical heat tracing system is not a substitute for a complete,
protection or general temperature maintenance should not be used for
efficient domestic hot water system. It does not eliminate the need for
hot water temperature maintenance, since their performance has not
an efficient water heater. What a heat tracing system does is provide
been matched to the requirements of hot water applications.
another approach to the design and installation of a hot water system.
It does this by simplifying the hot water distribution system, thereby
minimizing the amount of piping required. Items such as additional SYSTEM COMPONENTS
piping and balancing valves are unnecessary. A hot water temperature maintenance system (such as the one shown
In a heat trace system, a self-regulating heating cable is attached in Figure 2) typically includes the following components:
directly to the hot water supply piping and insulated. A self-regulating 1. Self-regulating heating cable.
heating cable adjusts its power at each point along its length to main- 2. Power connection kit.1
tain nominal temperature throughout the piping system. Electrical 3. Tee/inline splice kit (permits 2 or 3 cables to be spliced together).
energy input is controlled by the cable’s construction to maintain the 4. Cable end termination.
required water temperature at the fixtures. No return piping or circula- 5. Attachment tape (secures cable to pipe, use at 12 to 24 in.
tion pump is required. [305 to 610 mm] intervals).
Reprinted from Domestic Water Heating Design Manual, Second Edition, Chapter 15: “Self-Regulating Heat Trace Systems”
© American Society of Plumbing Engineers, 2008.
conductive core
heating cable
insulating jacket
foil wrap
Figure 2 Components of a Hot Water Temperature Maintenance System.
Source: Courtesy of Thermon Manufacturing Co.
Note: See “System Components,” above, for identification of numbered parts.
tinned-copper braid
Table 2(M) Water Wasted While Waiting for Hot Water to Reach Fixture (mL)
Nom. Diam. Distance from End Temperature Maintenance
Type L to Point of Use (m)
Copper 4.6 6.1 7.6 9.1 12.2
DN22 1420 1895 2365 2970 3815
Source: Courtesy of Thermon Manufacturing Co.
Notes:
1. Remember to add up all the fixtures in a facility and to multiply by both the waste
number shown and the expected number of usages per day.
2. Numbers based on line diameter and distance from end of temperature maintenance.
tion with a kraft paper vapor barrier. Thicknesses range from 1 to 2 in. facilities, such as hospitals, research labs, correctional facilities, and
(25.4 to 50.8 mm) based on line diameter. If a heat traced hot water campus dormitories.
system is designed to use only one cable for each temperature range, In this example, the supply main is located in the interstitial space
the thickness of the insulation will vary. between the first-story ceiling and the second-story floor. Because each
Manufacturers of hot water heat tracing systems have established story has roughly the same layout and water use points are stacked, a
insulation schedules that outline the thicknesses required to keep the riser and drop are used to supply water at each plumbing location.
heat loss within the desired range. Note that in these schedules the Electric heat tracing is installed on the horizontal mains and the
insulation on piping 1 ¼ in. (DN35) in diameter and smaller is over- risers. Since the distance between the horizontal piping and the first-
sized to allow space for the heating cable. story runouts is minimal (less than 15 ft [4.57 m]), heating cable is not
After the installation of the heating cable and thermal insulation required beyond the horizontal line connecting the main to the riser.
is completed, the piping is identified with stick-on labels to note the Since this example is of a four-story facility, it is recommended that
presence of electric heat tracing. This labeling gives notice to facility heating cable be installed up to the feed point for the third story. The
maintenance workers that heating cable has been installed under the line feeding from level three to level four again is less than 15 ft (4.57
insulation should any pipe maintenance or renovations be required. m), and under most conditions a line of this length does not require
heat tracing. Untraced lines should be installed so as to prevent rapid
HEAT TRACING HOT WATER PIPING heat loss between uses.
The design of a heat tracing temperature maintenance system for mains While this example is somewhat simplistic, the design principles it
and branch lines can be done on the plumbing drawings. (See Figure demonstrates can be applied to a project of any size.
4.) By referring to the manufacturer’s heating cable selection chart for
the desired maintenance temperature, the designer can determine the HOT WATER HEAT TRACING TERMS
maximum heating cable circuit length for circuit breakers of different The following terms apply to all hot water heat tracing systems and may
sizes. Taking this information into account when laying out the hot aid in the selection of the appropriate system for each project.
water lines will ensure optimum use of the circuit lengths. 1. System temperature range. For a return system, this is the
Note, in Figure 4, that the main and branch lines are heat traced and allowable temperature drop to the end of the system plus any
insulated while the short runouts are only insulated. (Runouts that additional variability caused by improper system balancing.
feed individual points of use typically contain less than ½ gal [1.89 L] of With return systems, there is a trade-off between desired system
water. If the faucet flow rate is above 1½ gpm [0.1 L/sec], hot water will performance and the life-cycle cost of the system. For a heating
reach the point of use within 10 sec.) If the distance between the branch cable system, the system temperature range is the range around
line and the point of use is much longer than 40 ft (12.19 m) or the flow
the nominal maintenance temperature.
rate is lower, the potential for water wastage and the time required for
2. Unheated distance. This is the distance in feet (meters) between
hot water to reach the point of use may be beyond the levels considered
the last maintained leg of hot water piping and the point of use.
acceptable for the facility. To remedy this situation, simply heat trace
For example, if hot water temperature is maintained only for the
closer to the point of use.
main run, the distance from the main to the point of use is the
unheated distance.
COMBINING HORIZONTAL MAINS WITH SUPPLY RISERS 3. Time to tap. This is the time required for hot water to reach the
Designers of multilevel facilities often duplicate floor plans over several fixture when the fixture is turned on. If the hot water temperature
levels, which simplifies the layout of electrical, HVAC, and mechanical is not maintained all the way to the fixture, the cold water in the
equipment. This practice also simplifies the layout of hot water supply pipe must be drawn out before the user gets hot water. The length
lines, unless there is a maze of recirculation piping and balancing of the wait is called time to tap. It is a function of the unheated
valves are required. Figure 5 shows a layout typical of two to four-story distance, the gpm (L/sec) flow rate, and the diameter of the pipe.
PSD 161
tion from other materials may result in a wrong answer.
Please print or type; this information will be used to process your credits.
Name_________________________________________________________________________________________________________
Title __________________________________________________ ASPE Membership No._____________________________________
Organization___________________________________________________________________________________________________
Billing Address_ ________________________________________________________________________________________________
City_ _________________________________________ State/Province_________________________ Zip_______________________
Country_______________________________________________ E-mail_ _________________________________________________
Daytime telephone_ ____________________________________ Fax_____________________________________________________
PE State _ _____________________________________________ PE No._ _________________________________________________
I am applying for the following continuing education credits: ❏ ASPE Member ❏ Nonmember
Each examination: $25 Each examination: $35
I certify that I have read the article indicated above. Limited Time: No Cost to ASPE Member
Payment: ❏ Personal Check (payable to ASPE) $
❏ Business or government check $
❏ DiscoverCard ❏ VISA ❏ MasterCard ❏ AMEX $
Signature If rebilling of a credit card charge is necessary, a $25 processing fee will be charged.
ASPE is hereby authorized to charge my CE examination fee to my
credit card
Expiration date: Continuing education credit will be given
for this examination through October 31, 2010.
Applications received after that date will not be processed. Account Number Expiration date