Sunteți pe pagina 1din 2

to put the type of fixtures, for

Insert these columns after "total


example, F11, F12
length"column

Power factor to be considered as 0.945


this "voltage drop"
column to be shifted
to last

Change this into


"Wattage" and this
value must be equal for example, if there are 2 no's of 2X35W fixtures,
to No of fixtures totally it becomes 2x2x35 = 140W and this value
multiplied by its watts should come in "Wattage column"
current verification: for circuit L1/1 (first row)

In the previous page example


there is a total wattage of 140W
Now divide this 140W by 230 and power factor, 140 / (0.945 x 230) =~ 0.64A

S-ar putea să vă placă și