Check for design strength of w all


Total design vertical force; N max = 129.1 kN
Design axial load; N s = 81.7 kN
FAIL - Wall is unsafe in axial loading
Critical secondary moment; M u_critical = 8.2 kNm
Design moment capacity; M = 11.7 kNm
PASS - Wall is safe in bending

Check for shear capacity of w all (AS 3600, cl 9.2.2(a), cl. 8.2.7)
Design shear capacity; V = 48.0 kN
Design shear force; V  d = 3.8 kN
PASS - Wall is safe in shear force
Analysis for service load state (SLS)
Load combination - [1.0 DL + 0.4 LL + 0.7 WL]
No. Ultimate Primary Effective MI Secondary Deflection
moment at mid-ht
Load for deflection Moment
Ps M sa Ie M s
(kN) (kNm) (mm 4 ) (kNm) (mm)
Strip 1 72.8 10.0 178911519 10.3 5
Strip 2 107.6 8.5 141146661 9.1 5
Strip 3 17.5 10.0 192718095 10.0 4
Check for deflection due to service loads (AS 3600 cls 9.3.3)
Critical strip for service load deflection; 2
Deflection at mid-height due to service load;  s_max = 5.3 mm
Allowable ratio for deflection;  = 250
Allowable deflection due to service load;  s_allowable = H wu /  = 20.0 mm
PASS-Deflection is within allowable limit