Section Page
1 Description of operation 4
2 Performance specification 20
3 Relay settings 28
4 Communication interface 36
5 Applications guide 40
6 Installation 48
7 Commissioning 50
8 Maintenance 56
9 Diagrams 60
10 Addendum 66
7. RELAY HARDWARE
Figures
4
Tables
RHO MANUAL
Description of operation
1 INTRODUCTION where: IP = steady state relay current prior to the
overload
q = qF . e
-t
t or t = t In q conditions (ie when Ieq < Iq) by multiplying the
2
output is given if the thermal state exceeds the setting.
Ieq
qF = 2
x 100% 2.1.5 Overload alarm level
Iq
The thermal overload setting Iq is expressed as a An instantaneous alarm output is given if the equivalent
fraction of the relay nominal current and is equivalent to thermal current Ieq exceeds the thermal overload
the factor k.IB as defined in the IEC60255-8 thermal setting Iq.
operating characteristics. It is the value of current
2.1.6 Load increase alarm level
above which 100% of thermal capacity will be reached
after a period of time and it is therefore normally set A further alarm is available to provide warning of a
slightly above the full load current of the protected sudden increase in load. The alarm level is set as a
motor. multiple of the thermal overload setting Iq.
ts l
Stalled Motor
Thermal Withstand
Characteristic
Thermal Protection Motor Starting
Motor Starting Operating Characteristic
Characteristic Charateristic
Current Current
Istart
Istart
The earth fault alarm is not affected by the inhibit
Current
feature and may be used to issue a back-trip signal to
an upstream circuit breaker.
Figure 4 - Start time greater than locked rotor
withstand Time
2.5 Phase unbalance protection
In this configuration, the first timer ts1 can be used to
provide additional protection against the motor running
Separate protection is available for the conditions of
up but drawing starting current for an excessive time.
phase unbalance, loss of phase and reverse phase
Timer ts1 runs for current above ISTART regardless of the
sequence. This feature can be programmed to operate
signal from the zero speed switch to provide excessive
either as phase difference protection or as negative
start time protection.
phase sequence overcurrent protection. It can also be
disabled altogether.
2.3 Overcurrent protection for phase
short circuits
2.5.1 Phase difference protection
Time and date can be set either via the relay fascia
Any status input can be programmed to receive a trip
using appropriate commands in the System
signal from another device such as an emergency stop
Configuration Menu, or via the communications
signal. The status input should firstly be mapped to the
interface. In the latter case, relays connected in a
trip output contact in the output configuration menu, so
communications network can be synchronised by a
that energisation of the status input results in a trip
global command.
signal being issued. If the same trip contact is specified
in the ‘fault trigger’ setting then the relay will switch to Alternatively, synchronising pulses can be received via
the fault data mode and indicate that an external trip a status input. To use this feature one of the status
has occurred. inputs must be assigned to the “Clock Sync” feature in
the Status Configuration Menu. Additionally the “Clock
3.16 Temperature inputs
Sync Period” setting in the System Configuration Menu
For variants where RTD or thermistor inputs are should be set either to “seconds” or to “minutes” as
available then the values returned by each of these are appropriate, depending on the period of the
displayed. Failed inputs are identified by the word synchronising signals expected from the controlling
The Rho 3 event recorder feature allows the time The Rho 3 incorporates a number of self-monitoring
tagging of any change of state of the relay. Each event features. Each of these initiates a reset sequence which
is logged with the full date and time and actual event can be used to generate an alarm output. In addition,
condition every 2.5msec. The following events are the Protection Healthy LED gives visual indication.
logged:-
A watchdog feature monitors the microprocessor. The
relay program memory is continuously checked for data
g Change of setting (though not the actual setting
corruption using a CRC routine.
changes). Also indication of which group of setting
The power supply is continuously supervised. Any
is active
g
failure is detected with sufficient time warning so that
Change of state of output relays
g
the microprocessor can be shut down in a safe and
Change of state of status inputs
g
controlled manner.
Change of state of any protection characteristic
g Trip Indication reset
4.5 Password feature
g Trip test
g Trip supply failure The programmable password feature enables the user
g Circuit breaker maintenance aarms to enter a 4 character alpha-numeric code. As soon as
g Circuit breaker failure the user attempts to change a setting the password is
requested before any setting alternations are allowed.
The event storage buffer holds up to 500 records. Once the password has been validated, the user is
When the event buffer is full, then any new record over- said to be “logged on” and if no further changes are
writes the oldest. made within 1 hour then the user will automatically be
“logged out”, re-enabling the password feature.
Event records are stored in RAM with a capacitor
providing back-up during breaks in auxiliary supply. Note that the password validation screen also displays
a numerical code. If the password is lost or forgotten,
4.3 Communications this code can be communicated to Reyrolle Protection
by authorised personnel, and the password can be
A fibre optic communication port is provided.
retrieved.
Communication is compatible with the IEC60870-5-103
FT 1.2 transmission and application standards. The The relay is supplied with the password set to “NONE”
fibre optic interface gives superior EMC performance. which means the feature is de-activated.
A user friendly software package is available to allow
transfer of the following:
g Relay settings
g Waveform records
g Event records
g Instruments and meters
g Control functions
14
RHO MANUAL
Description of operation
5 USER INTERFACE 5.4 Keypad
The user interface is designed to provide a user-friendly Five push buttons are used to control the functions of
method of entering settings and retrieving data from the the relay by moving around the menu display. They are
➪ ENTER and CANCEL. Note that
➪
➪
relay. labelled
the ➪ button is also labelled TEST/RESET.
5.1 General arrangement
The Rho 3 motor protection relay fascia includes a 16 Only two push buttons are accessible when the front
cover is on. These are the ➪ and buttons, allowing
➪
character by 2 line, backlit, liquid crystal display, 5 light
emitting diodes and 5 push buttons. read access to all displays.
Starter-Yellow LED self-resetting screens. All screens can be viewed even if the
password is not known - the password only protects
This LED indicates that any pole is measuring current the relay against unauthorised changes.
above the thermal current setting or high set
overcurrent. 2. While viewing an editable screen, ENTER allows the
Motor Starting-Red LED, self-resetting user to change the displayed data, indicated by
flashing character, as long as the changes are
This LED indicates when the current exceeds the motor
➪
➪
➪
➪
the screen to view mode and allows / to move The cases have been divided internally into noisy and
to the previous/next screen. quiet areas in order to improve noise immunity and
reduce RFI emissions. The only direct connection from
There are eight separate “Settings Groups”, allowing the the quiet components to the external environment is via
relay to be easily switched from one group to another. the optical serial communications interface, which is
Grouped settings are found in the protection, O/P relay immune to radiated or conducted interference.
configuration, status configuration sub-menus and in part
7.2 Front cover
of the data storage sub-menu. All other settings are
common. The different settings groups can be viewed or
and ➪ buttons, allowing
➪
This allows access to the
edited independently and indication of which group is
all of the menus discussed previously to be viewed but
presently being viewed is given by the “G?” character in
not changed. The only “action” which is permitted is to
the top left of the display.
reset the Fault Data Display, latched output relays and
A description of the purpose of each Rho 3 relay setting, the trip LED by using the TEST/RESET function of the
the actual setting ranges and default values can be button.
found elsewhere in this manual.
7.3 Terminal blocks
7 RELAY HARDWARE
These are of the standard Epsilon design, consisting of
The range of Rho 3 relays are housed in the Epsilon 28 terminals per block, with either one or two blocks
case, with 2 case sizes being necessary to cover the depending on the variant of the relay. All inputs and
available variants - E6 and E8. Figure 7 shows the Rho outputs (except for the serial communications interface)
3 HMI layout. are made through these connectors. The fibre optic
serial communication cables are connected via SMA
7.1 Internal construction connectors.
Features
1 Relay type
1 6 2 Red LED - motor starting
3 Yellow LED
7
4 Page-up key
8 5 Page-down key
9 6 Green LED protection healthy
2 7 Contrast adjustment
10 8 LCD display (backlit)
3
11 9 Green LED - motor running
4
10 Red LED - relay trip
11 Enter key
5 12 12 Test and reset key - also enables
sub-menu access
13 13 Cancel key
1. GENERAL
4. CHARACTERISTICS
5.1 Accuracy
5.2 Accuracy general
5.3 Accuracy influencing factors
6. THERMAL WITHSTAND
7. BURDENS
9. ENVIRONMENTAL WITHSTAND
20
RHO MANUAL
Performance specification
1 GENERAL Status input performance
Nominal voltage Operating range The status inputs perform according to the
30/34 18V to 37.5V requirements of ESI48-4 ESI 1.
48/54 37.5V to 60V
Note that alternative status inputs can be ordered,
110/125 87.5V to 137.5V
which can be driven directly from 110V or 220V, without
220/250 175V to 280V
a dropper resistor. These special low current types will
operate with input currents of less than 10mA.
NB Status operating voltage need not be the same as
the main energising voltage. For 110/125 volt or
220/250 volt working, a standard Rho 3 relay with 48/54
volt status will be supplied for use with external dropper
resistors as follows:-
Thermal setting Iq 0.50 to 2.00 xIn D 0.05xIn P/F alarm IHA OFF, 0.5 to 20xIn D 0.1xIn
NPS weighting factor ‘K’ 0.0 to 10.0 D 0.1 P/F alarm delay tHA 0.0 to 1.0sec D 0.01sec
Heating constant th 0.5 to100.0 mins D 0.5 min 1.0 to 30.0sec D 0.1sec
Starting constantts 0.50 to 1.50 x th D 0.05 P/F trip IHS OFF, 0.5 to 20xIn D 0.1xIn
Cooling constant tc 1 to 100 x th D 1 P/F trip delay tHS 0.0 to 1.0sec D 0.01sec
Hot/cold ratio OFF, 5 to 100% D 5% 1.0 to 30.0sec D 0.1sec
Thermal capacity alarm OFF, 50 to 100% D 1% E/F alarm IEA OFF, 0.005 to 1.000xIn D
Load Increase alarm OFF, 0.5 to 1.0 x Iq D 0.05 xIq 0.005xIn
Thermal restart inhibit 20 to 100% D 1% E/F alarm delay tEA 0.0 to 1.0sec D 0.01sec
Operate time (cold), mins 1.0 to 30.0sec D 0.1sec
see figure 1. Ieq 2 OFF, 0.005 to 1.000xIn D
t = t.Ln E/F trip IEF
Ieq 2 (Iq )
2
0.005xIn
E/F trip delay tEF 0.0 to 1.0sec D 0.01sec
Ieq =
Ö I + K.I
2
1 2
2 Operate time -
Negative sequence, t=
1
x tm
secs
( I2
2
Note 2: the thermal alogorithm operates using one of
Iq )
three time constants (th, ts or tc), chosen according to
the magnitude of Ieq as follows:
If Ieq < ISTOP then t = tc (cooling condition)
4.4 Number of starts protection
If ISTOP ² Ieq < ISTART then t = th (running condition)
If Ieq ³ ISTART then t = tS (starting condition). Max. starts OFF, 1 to 20 D1
Max. starts period 1 to 60 mins D 1 min
Note 3: While the Hot/Cold ratio setting is entered as a Start inhibit delay 1 to 60 mins D 1 min
22
percentage value, the factor H/C which appears in the Min. time between starts OFF, 1 to 60 mins D 1 min
equation for the Operate Time (Hot Curve) is actually a
per-unit value.
Figure 1 and Figure 2 illustrate examples of cold and
hot curves.
RHO MANUAL
Performance specification
Note:
4.5 Temperature inputs
1 Where unbalance protection is configured in NPS
Input type Range for alarm and trip mode, the claim assumes a period of balanced 3
RTD (100W Pt, 100W Ni, 0 - 250°C D 1° phase operation prior to the unbalance occurring.
120W Ni, 10W Cu) In the case of the relay being switched onto an
Other RTD 100 - 350W D 1W unbalanced system ‘from cold’, then an additional
Thermistor (PTC, NTC) 100 - 1000W D10W 1100 - 100ms may be required for the NPS algorithm to
30000W D100W stabilise.
2 It is advised that the unbalance protection should
not be configured in phase difference mode when
5 ACCURACY REFERENCE
operating on 60Hz systems.
CONDITIONS
Temperature protection
General IEC60255-3,
RTD (100W Pt, ± 2°C
IEC60255-8
100W Ni,120W Ni)
Auxiliary supply Nominal
RTD (10W Cu) ± 5°C
Frequency 50/60Hz
Other RTD ± 1W
Ambient temperature 20°C
Thermistor (PTC, NTC) ± 5%
7 BURDENS
Operating range -10°C to +55°C
Variation
2.5kV common (longitudinal) mode ² 3%
1.0kV series (transverse) mode ² 3%
Variation
8kV contact discharge ² 5%
Variation
20MHz to 1000MHz, 10V/m ² 5%
Variation
4kV 5/50ns 2.5kHz repetitive ² 3%
Variation
Vibration response 0.5gn ² 5%
Vibration endurance 1.0gn ² 5%
Variation
Shock response 5 gn 11ms ² 5%
Shock withstand 15 gn 11ms ² 5%
Bump test 10 gn 16ms ² 5%
Variation
Seismic Response 1gn ² 5%
Mechanical classification
10000.00
1000.00
100.00 t = 100
Time (secs)
t = 50
t = 30
t = 20
10.00 t = 15
t = 10
t =5
t =3
t =2
1.00 t =1
t = 0.5
0.10
0.0 2.0 4.0 6.0 8.0 10.0 26
Overload Level (Multiple of Setting Iq )
Figue 1 IEC60255-8 cold curve operate times for varying time constants
NB. operate times are in seconds, time constants are set in minutes
RHO MANUAL
Performance specification
10
1
Time (seconds)
0.1
Ip=0.3
0.01 Ip=0.5
Ip=0.7
Ip=0.9
0.001
0.0 2.0 4.0 6.0 8.0 10.0
Overload Level (Multiple of Setting I q )
Figue 2 IEC60255-8 hot curves for varying levels of prior load current
NB. operate times are in seconds, time constants are set in minutes
RHO MANUAL
Relay settings
11. MAINTENANCE
28
RHO MANUAL
Relay settings
Notes: (1) Settings applied where named RTD types are selected.
Settings applied where other RTD types are selected.
Settings applied where thermistors are selected.
7 OUTPUT CONFIGURATION MENU
11 MAINTENANCE MENU
34
RHO MANUAL
Communication interface
1. INTRODUCTION
Appendix A
Methods of communication connection
36
RHO MANUAL
Communication interface
1 INTRODUCTION to the receive input of the first Argus relay should not be
This document describes how to connect the IEC60870- more than 6m. The distance from the transmit output of
5-103 compliant Informative Communication Interface to the last Argus to the receive input of the converter may
a control system or interrogating computer. be up to 43m.
No other types of cable are suitable for use with Argus
To access the interface you will need appropriate
relays.
software within the control system or, on the
interrogating computer, for example, Reydisp Evolution. 2.2 Transmission method
More detailed information regarding the communications Half Duplex serial asynchronous transmission. In
interface can be found in a separate manual, the IEC60870-5-103 the line idle state is defined as Light
IEC60870-5-103 Communications Interface. This On. This can alternatively be selected as Light Off in
contains information about the format and content of the the Communications Interface menu of the settings list if
data available. It is available to developers writing required for use with alternate hardware (See Section
software to interrogate the relays. 2.3.4).
Sigma 3 is a fibre optic to dual RS232 interface. It has 2.3.2 Parity setting
one fibre optic port for connection to the relay(s), and IEC60870-5-103 defines the method of transmission as
two electrical RS232 ports. The rear electrical port is using Even Parity. However, in some instances an
intended for connection to a control system. The front alternative may be required. This option allows the
port allows local access, for example, from a laptop PC. setting of parity to None. Default Even.
When a device is connected to the front port the rear is
2.3.3 Address setting
overridden.
The address of the relay must be set to a value between
Sigma 4 is a portable fibre optic to RS232 conversion 1 and 254 inclusive before communication can take
unit. place. Setting the address to zero disables
communications to the relay. All relays in an optical ring,
2 CONNECTION SPECIFICATION AND
as illustrated in figure 3, must have a unique address.
RELAY SETTINGS
Address 255 is reserved as a global broadcast address.
2.1 Recommended cable Default zero.
Selection of fibre optic cable is critical. Fibres should be
2.3.4 Line idle setting
terminated with 9mm SMA connectors.
The line idle setting must be set to be compatible with
The recommended type is 200µm Plastic Coated Silica the device connected to the relay IEC60870-5-103
(PCS). This will allow a maximum transmission distance defines a line idle state of Light On. The Sigma range
of 100m between Argus relays. This will also be the of products for connecting to the fibre-optic ports on
maximum distance between the ring network and the the relays support either Light ON or OFF. All sigma
fibre to RS232 converter. units are supplied Light Off. Sigma 1 has internal DIL
switches to set the condition for each fibre optic
Alternatively, 1mm polymer cable may be used to channel, Sigma 3 and 4 have an internal jumper to set
reduce cost. This will provide transmission distances of the state of their fibre optic channel. Refer to diagrams
up to 43m between relays. Note that the distance from in appendix A. The setting allows you to switch the line
the transmit output of the RS232 / fibre optic converter idle state to that suitable for your hardware. The
following table shows the line-idle settings for the from one relay to the next. When using this method all
Honeywell type HFM5500 fibre-optic to RS232 relays in the ring must have Data Echo = ON selected
convertors. Default off. in the Communications Interface menu of the settings
list. Otherwise this setting is to be Data Echo = OFF.
Device Line Idle Setting Required Note, if the address setting is zero Data Echo = ON will
HFM5500-AAM, HFM5500-AAF Light Off still allow echo data. Default off.
HFM5500-BAM, HFM5500-BAF Light On
2.4 Modems
The communications interface has been designed to
2.3.5 Connection method allow data transfer over a telephone system via
Communication networks can be connected as Star, modems. For more information regarding using and
figure 4, or Optical Ring, figure 3, configuration. The installing modems refer to document 434/TIR/7 Remote
Optical Ring architecture requires data to be passed Communication to Argus Relays.
Tx Rx Tx
Local
Sigma 4
(SG4-101..102) Rx
Laptop computer
Tx Rx Tx
Local
Telephone Sigma 4
Network (SG4-101..102) Rx
Modem Modem
Laptop computer
Control System
Rx Tx Rx Tx
Sigma 3 Serial optical link
System
(SG3-101)
Local
Tx
Rx Tx Rx Tx Rx
Laptop computer
Note, each Serial Optical Link consists of two fibres, a transmit and a receive
Control System
or Master Serial Optical Link
Sigma 1
Sigma 3 Up to 29 serial optical links to relays
(SG1-102..108)
or
Sigma 4 38
2. MULTIFUNCTION APPLICATIONS
3.1 Phase fault alarm setting (IHA) and time delay tHA)
3.2 Phase fault trip setting (IHS) and time delay (tHS)
3.3 Earth fault alarm setting IEA and time delay (tEA)
3.4 Earth fault trip setting (IEF) and time delay (tEF)
3.5 Earth fault inhibit setting (IEI)
3.6 Undercurrent protection
7. OTHER FEATURES
Controlled by: Vacuum circuit breakers sequence components from the three phase input line
Locked rotor current: 5 x full load currents. These are used to generate an equivalent
Run-up time: 4 secs thermal current Ieq which is calculated from the
Full load current = KVA = 985 machine negative sequence withstand (NPS weighting
Ö3 KV 1.73 X 6.6 factor), this figure should be used. If no figure is
The starting current can be taken to be the same as the records of the Rho should be studied and the motor
locked rotor current ie, 5 x 86.2 = 431 amps. manufacturer consulted before decreasing the
weighting factor.
Negative sequence currents give rise to additional rotor 2.6 Cooling time constant, tc
heating, they produce a substantial rotor current at
approximately twice system frequency. At this When a motor is switched off the rotor de-cellerates and
frequency, skin effects in rotor bars can cause eventually stops. During the run-down state and
significant rotor heating. Usual thermal limit curves standstill state the motor windings will cool down but
supplied by machine manufacturers assume positive they are likley to have a different time constant for
sequence currents only from a perfectly balanced cooling than for heating up during running. This is
supply. Rho relays are settable to give complete motor because during the start-up and running state there is
protection under all supply conditions. forced cooling experienced by the windings due to the
rotor movement.
2.4 Heating time constant, th
The cooling time constant of the motor is therefore
The relay heating time constant th is settable from 0.5 always longer than the heating time constant for
to 100 minutes in 0.5 steps, figure 1 shows the family of running. The factor of tc/th is not specified by the motor
curves. Using the example of the motor parameters manufacturer very often. Typical factors are 5 to 10 x,
quoted under item 2 above and reading values from however for large motors which are totally enclosed and
Figure 1:- also ones that normally rely heavily on forced cooling
due to motion of the rotor, the factor can be as high as
At a locked rotor current of 5 x FLC (which is about the
60x.
starting current) and a run-up time of 4 seconds and
allowing two consecutive starts ie 8 seconds total run- The net result of choosing a high value for tc is that it
up time, the th value from figure 1 is just over 3 may not be possible to start the motor immediately after
minutes. As the safe stall time from cold is 11 seconds, a shut down.
the th value could be set to 5. he stall time from hot, ie
In this example, the cooling time constant has not been
7 secs gives a th value of 3. If this lower value of 3 is
specified either as a time constant or as a multiple of its
chosen, there is the possibility of nuisance tripping after
heating time constant. We will therefore choose 10 x,
the motor has been in service for some time with longer
which is the default.
run-up times and higher currents. It would be better to
select the value of 5 which allows two starts in quick 2.7 Hot/cold curve ratio
succession. Of course, if the actual th heating time (hot spot weighting)
constant of the motor is given by the manufacturer, then
this figure could be set on the relay. The Rho 3 relay allows adjustment of the Hot/Cold curve
operating time ratio. This allows a weighting factor for
2.5 Starting time constant, ts motor winding hot spots to be applied. Motors with
onerous hot spots are overdesigned for normal load and
When a motor is running at full design speed, the
by selecting a high value of H/C it allows advantage to
airflow and ventilation is designed to give optimum
be taken of the overdesign for overload, ie longer
cooling. On starting, the current is nearly the stall value
operating time. Selecting the Hot/Cold ratio (H/C) to
but the ventilation is reduced. If this time constant is
100% (ie a high weighting factor) results in the relay
known, it can be set on the relay. If not, then set the
indicating 100% thermal capacity being available when
time constant (settable 0.5 to 1.5 of the heating time
the motor has been running at full load for a sufficiently
constant th) to 1.0, ie the same as th.
long time to reach steady after a motor-switch on. The
The time constant switches from th to ts as current hot and cold operating time curves are the same.
levels above the set value of ISTART. When ts is set
A low weighting factor would be 5%. Switching H/C to
below 1.0 x Iq, this feature assists in ensuring that a
off is equivalent to H/C = 0. In this case, when
stall on start up does not exceed the motor withstand
operating at full load, the relay would indicate little
time. However where the stall withstand time (e.g from
thermal capacity available, eg 100% used. The hot 42
‘hot’) is less than the run-up time it is still necessary to
operating time curve is then much faster than the cold.
provide a tachometric speed switch on the rotor shaft
as described previously. The time constant switches An indication of the motor hot spot characteristic is the
from th to ts at current levels above the set valve of ratio of hot stall withstand to the cold withstand, th/tc.
ISTART With no hot spots (eg a cable) this ratio would be = 1.
RHO MANUAL
Application guide
In our example th/tc = 7/11 = 0.64. The H/C setting to 2.8 Thermal capacity alarm setting
be applied to the relay is then established from the
This setting is expressed as a percentage of the
following:
thermal capacity set as above. It is settable 50 to 100%
th/tc = (1 - H/C).
of the set capacity and gives an instantaneous alarm
Therefore H/C = 1 - th/tc = 0.36 (eg say 35%)
output if its setting is exceeded. Typically this would be
set to 95%.
10000.00
1000.00
100.00
th = 100
th = 50
Time (secs)
th = 30
th = 20
th = 15
10.00 th = 10
th = 5
th = 3
th = 2
1.00 th = 1
th = 0.5
0.10
1.0 10.0
Overload (*Iq)
2.13 Stall and locked rotor protection also be used to implement a multi-stage tripping
Once the maximum permissible number of starts have 6.1 RTD inputs
occurred within the defined period then starting is
RTD inputs may be selected from a number of types,
inhibited for the duration of the start inhibit delay
namely 100½ Platinum (standard type DIN 43760),
setting.
100½ Nickel, 120½ Nickel, 10½ Copper or ‘other’.
Typically, two or three consecutive starts are permitted
The named types have reasonably linear, known
for a large motor which means that the motor and
characteristics and the measured resistances are
driven machine have to slow down to a stop before a
converted into temperatures between -50°C and
start is attempted. The coasting down time may be
+250°C and displayed. Alarm and trip settings are also
many minutes and the time interval should reflect this.
programmed in terms of temperature. If the ‘other’ type
The motor manufacturer should be consulted, and if the is selected then measurements and settings are
start duty is severe then the manufacturer may impose displayed as resistances up to 350½
a deliberate waiting time between starts, this must be
set on the relay. 6.2 Thermistor inputs
7.1 Trip circuit supervision To avoid giving spurious alarm messages while the
circuit breaker is operating, the status input should be
Based on the Electricity Association standard schemes
programmed to have a 500mSec drop-off delay.
referenced H6, a status input on the Argus relay can be
used to supervise the trip circuit with the associated The schemes are shown in figure 1.
Circuit breaker
auxiliary contacts
Rho 3 trip
relay contacts Trip coil
+VE -VE
For 110/125Vdc
2k7 ohms Note: If the trip circuit is
not healthy, Rho 3 relays
‘TRIP CCT FAIL’ message
Rho 3 Status
Input 50v
3. RELAY DIMENSIONS
4. FIXINGS
4.1 Crimps
4.3 Communications
5. ANCILLARY EQUIPMENT
48
RHO MANUAL
Installation
1. UNPACKING, STORAGE viewing position is at eye level, and this is particularly
AND HANDLING important when using the built-in instrumentation
features.
On receipt, remove the relay from the container in
which it was received and inspect it for obvious The relay should be mounted on the circuit breaker or
damage. It is recommended that the relay is not panel to allow the operator the best access to the relay
removed from the case. To prevent the possible ingress functions.
of dirt, the sealed polythene bag should not be opened
3 RELAY DIMENSIONS
until the relay is to be used.
The relay is supplied in modular case range size 6 or 8.
If damage has been sustained a claim should
The larger case is used with RTD inputs. Diagrams are
immediately be made against the carrier, also inform
provided elsewhere in this manual.
Reyrolle Protection and the nearest Reyrolle agent.
When not required for immediate use, the relay should 4 FIXINGS
be returned to its original carton and stored in a clean,
dry place. 4.1 Crimps
As there are no user serviceable parts in the relay, then 4.3 Communications
there should be no requirement to remove any modules
9mm SMA fibre optic connections - 2 per relay (refer to
from the chassis.
section 4 - Communications Interface).
If any modules have been removed or tampered with,
then the guarantee will be invalidated. Reyrolle 5 ANCILLARY EQUIPMENT
Protection reserve the right to charge for any
The relay can be interrogated locally or remotely by
subsequent repairs.
making connection to the fibre optic terminals on the
2 RECOMMENDED MOUNTING rear of the relay. For local interrogation a portable PC
POSITION with a fibre to RS232 modem is required. The PC must
be capable of running Microsoft Windows Ver 3.1 or
The relay uses a liquid display (LCD) which is used in greater, and it must have a standard RS232 port in
programming and or operation. The LCD has a viewing order to drive the modem. For remote communications
angle of ± 70° and is back lit. However, the best more specialised equipment is required. See the
section on communications for further information.
RHO MANUAL
Commissioning
2. INSPECTION
3. APPLYING SETTINGS
4. PRECAUTIONS
5. TESTS
5.1 Insulation
5.2 Secondary injection
5.2.1 Pickup and reset
5.2.2 Thermal characteristics
5.2.3 Over/under current protection
5.2.4 Phase unbalance protection
5.2.5 Number of starts
5.2.6 Temperature protection
5.2.7 Output and status configuration
5.2.8 Circuit breaker fail
50
RHO MANUAL
Commissioning
1 REQUIRED TEST EQUIPMENT according to the settings which are currently being
displayed. There is an ’active setting group’ on which
g 500V Insulation resistance test set
the relay operates and an ‘edit/view setting group’
which is visible on the display and which can be
g Variable secondary injection current source rated
altered. This allows the setting in one group to be
10A or greater
altered while protection continues to operate on a
different unaffected group. The ‘active setting group’
g Time interval meter
and the ‘edit setting group’ are selected in the ‘System
Configuration Menu’.
g Primary injection equipment
Elsewhere in the setting menu system, those settings
g A d.c. supply with nominal voltage within the which can be altered or different groups are indicated
working range of the relay’s d.c. auxiliary supply by the symbols G1, G2 etc. in the top left of the display.
rating Other settings are common to all groups.
4 PRECAUTIONS
g A d.c. supply with nominal voltage within the
working range of the relay’s d.c. input rating Before testing commences the equipment should be
isolated from the current transformers and the CT’s
Additional equipment for testing the communications short circuited in line with the local site procedures.
channel: The tripping and alarm circuits should also be isolated
where practical.
g Portable PC with the fibre optic modem
Ensure that the correct d.c. auxiliary voltage is applied
connections
to the circuit. See the relevant scheme diagrams for
the relay connections.
g Portable printer to operate from the above PC
5 TESTS
2 INSPECTION
5.1 Insulation
Ensure that all connections are tight and in accordance
with the relay wiring diagram and the scheme diagram. Connect together all of the C.T. terminals and measure
Check the relay is correctly programmed and the relay the insulation resistance between these terminals and
is fully inserted into the case. Refer to the Description all of the other relay terminals connected together and
of Operation for programming the relay. to earth.
For high levels of current the thermal level of the relay 5.2.8 Circuit breaker fail
Table 1
54
RHO MANUAL
Maintenance
1 MAINTENANCE INSTRUCTIONS
56
RHO MANUAL
Maintenance
1 MAINTENANCE INSTRUCTIONS
Please copy this sheet and use it to report any defect which may occur.
Telephone no:
Fax no:
Site: Circuit:
Date found: During commissioning: During maintenance: From a system fault: Other, please state:
Describe defect:
Date received: Contact name: Reference no: Date acknowledged: Date of reply: Date cleared:
58
RHO MANUAL
Diagrams
Figue 2 Typical schematic diagram Rho 3 motor protection (separate core balance CT and two line CT’s)
- size 6 case
Figure 3 Typical schematic diagram Rho 3 motor protection with RTD (line CT’s only)
- size 8 case
60
DIGITAL MOTOR PROTECTION RHO3 (Seperate Core Balance CT)
TERMINAL BLOCKS VIEWED FROM REAR
BUSBARS RHO3 Motor Protection
A B C (1) 53 TERM BLOCK 3 TERM BLOCK 2 TERM BLOCK 1
7
54 1A (6)
5
Figue 1
SMA Connectors 77
33 (5) Resistance Temperature Detector.
34
STATUS I/P 3 79
TX RTD7 81
(6) Terminal block 3 & E8 case used for
35
80 RTD Inputs.
STATUS I/P 2 82
36 RTD8
RX 84
83
C B
Typical schematic diagram Rho 3 motor protection (three line CT’s separate core
PHASE ROTATION
TERMINAL BLOCKS VIEWED FROM
BUSBAR RHO3 Motor Protection
A B C (1) 53 TERM BLOCK 3 TERM BLOCK 2 TERM BLOCK 1
7
54 1A (6)
5 RELAY 57 29 1 2
55 A Phase I/P 58 30
5A 6 1 59 60 31 32 3 4
56
49 8 61 62 33 34 5 6
P1 64 36 7 8
50 1A 63 35
S S S 10 RELAY
51 B Phase I/P 65 66 37 38 9 10
9 2
52 5A 67 68 39 40 11 12
S S S 45 16 69 70 41 42 13 14
P2
46 1A 18 RELAY 71 72 43 44 15 16
47 C Phase I/P 3 73 74 45 46 17 18
17
48 5A 75 76 47 48 19 20
11 22
25 77 78 49 50 21
RELAY
1A 12 79 80 51 52 23 24
26 4
27 Earth Fault I/P 19 81 82 53 54 25 26
28 5A RELAY 83 84 55 56 27 28
20
5
21
RELAY KE
22 6 1 Short
23 2 Long
RELAY
24 3 CT Shorting
7 (5) RTD EXPANSION PCB.
(4) EXPANSION PCB
57
38
STATUS I/P 9 61
RTD1 63
62
39
1 STATUS I/P 8 64
D.C + 40 RTD2 66
Input 1 65
- 41
STATUS I/P 7 67
42 RTD3 69 NOTES:
Case Earth 68
43 (1) CT Circuits are shown connected to
M Earth 1 STATUS I/P 6 70
44 RTD4 72 relay 1A tap, use alternative tap for
71 for 5A rated CTs
3 29
Figure 2 Typical schematic diagram Rho 3 motor protection with RTD (line CT’s only)
+ STATUS I/P 5 73
(2) CT and Earth connections are typical
STATUS I/P 4 30 RTD5 75 only.
- 74 (3) Application scheme shown for
31
STATUS I/P 4 76 3 Phase Motor.
Fibre-Optic 32 RTD6 78
A (4) Expansion pcb (7 O/P + 9 Status I/P).
SMA Connectors 77
33 (5) Resistance Temperature Detector.
34
STATUS I/P 3 79
T RTD7 81
(6) Terminal block 3 & E8 case used for
80 RTD Inputs.
35
STATUS I/P 2 82
36 RTD8 84
R
83
C B
PHASE
62
TERMINAL BLOCKS VIEWED FROM
BUSBAR RHO3 Motor Protection
A B C (1) 53 TERM BLOCK 3 TERM BLOCK 2 TERM BLOCK 1
7
54 1A (6)
5 RELAY 57 29 1 2
55 A Phase I/P 58 30
5A 6 1 59 60 31 32 3 4
56
49 8 61 62 33 34 5 6
P1 64 36 7 8
50 1A 63 35
S S 10 RELAY
51 B Phase I/P 65 66 37 38 9 10
9 2
52 5A 67 68 39 40 11 12
S S 45 16 69 70 41 42 13 14
P2
46 1A 18 RELAY 71 72 43 44 15 16
47 C Phase I/P 3 73 74 45 46 17 18
17
48 5A 75 76 47 48 19 20
11 22
25 77 78 49 50 21
P1 RELAY
S 1A 12 79 80 51 52 23 24
26 4
27 Earth Fault I/P 19 81 82 53 54 25 26
28 5A RELAY 83 84 55 56 27 28
20
5
P2 S
21
RELAY KE
22 6 1 Short
23
balance CT’s and no RTD inputs)
2 Long
RELAY
24 3 CT Shorting
7 (5) RTD EXPANSION PCB.
(4) EXPANSION PCB
57
37
38
STATUS I/P 9 61
RTD1 63
62
39
1 STATUS I/P 8 64
D.C + 40 RTD2 66
Input 1 65
- 41
STATUS I/P 7 67
42 RTD3 69 NOTES:
Case Earth 68
43
M Earth 1 STATUS I/P 6 70 (1) CT Circuits are shown connected to
44 RTD4 72 relay 1A tap, use alternative tap for
71
3 29 for 5A rated CTs
+ STATUS I/P 5 73
STATUS I/P 4 30 RTD5 75 (2) CT and Earth connections are typical
- 74
31 only.
STATUS I/P 4 76
Fibre-Optic 32 RTD6 78 (3) Application scheme shown for
A
SMA Connectors 77 3 Phase Motor.
33
34
STATUS I/P 3 79 (4) Expansion pcb (7 O/P + 9 Status I/P).
T RTD7 81
80
35 (5) Resistance Temperature Detector.
STATUS I/P 2 82
36 RTD8 84 (6) Terminal block 3 & E8 case used for
R
83
C B RTD Inputs.
Figure 3 Typical schematic diagram Rho 3 motor protection (two line CT’s separate core
PHASE
155.5(E6)
31 207.5(E8) 150 201.5
216.5
10 130 9.75 182
4.5
4.5
FLUSH
159
159
168
168
177
151.5
Figure 4 Rho 3 outline and cutout diagram
MINIMUM CLEARANCE 25
3.6mm DIA -4 HOLES 3.6mm DIA -4 HOLES
PANEL CUT- PANEL CUT-
FLUSH MOUNTING FLUSH MOUNTING
(E6 CASE SIZE) (E8 CASE SIZE)
RHO3/D2
64
RHO MANUAL
Addendum
1. INTRODUCTION
2. NON-MOTOR APPLICATIONS
66
RHO MANUAL
Addendum
1 INTRODUCTION The unbalanced current function need not be selected,
it is available should this feature be considered useful
Rho 3 series of relays has been developed primarily to
(eg phase difference or n.p.s overcurrent).
provide a multi function protection system for 3-phase
a.c. induction motors, typically for those employed on 2.2 Single phase Vs three phase
high voltage systems with ratings in excess of 75kW. thermal overload
The principal protection functions are those related to If it is known that the three phases can have
thermal overload and this function, along with many of significantly different loads and that the three phase
the others incorporated in Rho 3, are suitable for conductors of the electrical plant being protected are
protecting other items of plant, eg cables, power independent, eg single phase cables as apposed to 3-
transformers, etc. The relay incorporates phase cables, then it may be considered that the
comprehensive thermal characteristics to IEC60255-8 averaging feature of Rho 3's thermal overload function
(thermal electrical relays). may not be adequate to protect all three phases
against overload damage. In this case a separate Rho
A series of Rho 3 variants is available specifically for
3 relay is required for each phase. Each relay must be
plant other than motors. The only difference between
employed connecting all three phase current inputs in
Rho 3 supplied for non-motor applications and those
series thus employing three relays in total for the three
for motor applications is that on the latter there are two
phases of the primary circuit.
additional LED's available on the relay fascia plate
engraved "Motor Starting" and "Motor Running". These Drawing Rho 3/D5 attached shows the recommended
are not included on the Rho 3 relays supplied for non- schematic diagram for single phase protection. The
motor applications. three relays each have an earth fault c.t. input as well
as three phase overcurrent inputs. The recommended
All setting and programming features, also the
scheme shows all three earth fault elements connected
input/output, relay configuration and the communication
in series.
features are identical. Any features in the setting menu
which is specific to motors need not be selected when If instantaneous, sensitive earth fault is required and the
a Rho 3 for non-motor application is employed for c.t. residual connection application shown is employed
protecting other plant, eg cables, transformers, (eg for power transformer primary circuit earth fault) it
capacitor banks, etc. may be necessary to employ a stabilising resistor to
prevent mal-operation at circuit switch-on.
In the following, information is given about the
application of Rho 3 for non-motor electrical plant. Drawing Rho 3/D4 shows the schematic distance for
For all other data refer to the main Technical Manual. three phase overload, employing only one relay.
2 NON-MOTOR APPLICATIONS
3 DIAGRAMS FOR NON-MOTOR
2.1 Negative phase APPLICATIONS
sequence/unbalanced current
Figure 1: Rho 3/D4 - Typical schematic diagram for Rho
Other than generators and motors, electrical plant is 3 three phase thermal overload protection (non-motor
usually tolerant of negative phase sequence current (ie applications)
resulting from 3-phase unbalanced currents).
Figure 2: Rho 3/D5 - Typical schematic diagram for Rho
For these applications the negative phase sequence 3 single phase thermal overload protection (non-motor
(n.p.s.) current weighting factor must be set to zero, the applications)
thermal protection then uses the average of the three
RMS phase currents instead of an equivalent current
compiled from positive phase sequence (p.p.s) and
n.p.s. current x a weighting factor.
TERMINAL BLOCKS VIEWED FROM
BUSBAR RHO3 Thermal Protection
A B C (1) 53 TERM BLOCK TERM BLOCK TERM BLOCK
7
54 1A (6)
5 RELAY 5 2 1 2
55 A Phase I/P 5 3
5A 6 1 5 6 3 3 3 4
56
49 8 6 6 3 3 5 6
P1 6 3 7 8
50 1A 6 3
S S 1
applications)
S RELAY
51 B Phase I/P 6 6 3 3 9 1
9 2
52 5A 6 6 3 4 1 1
S S S 45 1 6 7 4 4 1 1
P2
46 1A 1 RELAY 7 7 4 4 1 1
47 C Phase I/P 3 7 7 4 4 1 1
1
48 5A 7 7 4 4 1 2
1 2
25 7 7 4 5 2
RELAY
26 1A 1 4 7 8 5 5 2 2
27 Earth Fault I/P 1 8 8 5 5 2 2
28 5A RELAY 8 8 5 5 2 2
2
5
2
RELAY KE
2 6 1 Short
2 2 Long
RELAY
2 3 CT Shorting
7 (5) RTD EXPANSION PCB.
(4) EXPANSION PCB
57
37
38
STATUS I/P 9 61
RTD1 63
62
39
1 STATUS I/P 8 64
D.C + 40 RTD2 66
Input 1 65
- 41
STATUS I/P 7 67
42 RTD3 69 NOTES:
Case Earth 68
43 (1) CT Circuits are shown connected to
Earth 1 STATUS I/P 6 70
44 RTD4 relay 1A tap, use alternative tap for
72
71 for 5A rated CTs
3 29
+ STATUS I/P 5 73
(2) CT and Earth connections are typical
STATUS I/P 4 30 RTD5 75 only.
- 74 (3) Application scheme shown for
31
STATUS I/P 4 76 3 Phase Thermal Protection
Fibre-Optic 32 RTD6 78
A .(4) Expansion pcb (7 O/P + 9 Status I/P).
SMA Connectors 77
33 (5) Resistance Temperature Detector.
34
STATUS I/P 3 79
T RTD7 81
(6) Terminal block 3 & E8 case used for
35
80 RTD Inputs.
STATUS I/P 2 82
36 RTD8
R 84
83
C B
PHASE
Figure 1: Rho 3/D4 - Typical schematic diagram for Rho 3 three phase thermal overload protection (non-motor
68
RHO3 Thermal Protection TERMINAL BLOCKS VIEWED FROM
BUSBAR
A B C (1) PHASE A RELAY
53 7 TERM BLOCK TERM BLOCK TERM BLOCK
54 1A (6)
Phase I/P 5 RELAY 5 2 1 2
55 5 3
5A 6 1 5 6 3 3 3 4
56
49 8 6 6 3 3 5 6
P1 6 3 7 8
50 1A 6 3
S S S 1 RELAY
51
Phase I/P 6 6 3 3 9 1
9 2
52 5A 6 6 3 4 1 1
S S S 45 1 6 7 4 4 1 1
P2
46 1A 1 RELAY 7 7 4 4 1 1
47 Phase I/P 3 7 7 4 4 1 1
1
48 5A 7 7 4 4 1 2
PHASE B RELAY 1 2
53 25 7 7 4 5 2
RELAY
54 1A 26 1A 1 4 7 8 5 5 2 2
55 Phase I/P 27 Earth Fault I/P 1 8 8 5 5 2 2
56 5A 28 5A RELAY 8 8 5 5 2 2
2
49
5
2
50 1A RELAY KE
51 Phase I/P 2 6 1 Short
protection (non-motor applications)
52 5A 2 2 Long
45 RELAY
2 3 CT Shorting
1A
7 (5) RTD EXPANSION PCB.
46
(4) EXPANSION PCB
47 Phase I/P 57
37
48 5A STATUS I/P 9
38 RTD1 61
25 63
62
26 1A 39
1 STATUS I/P 8 64
27 Earth Fault I/P D.C + 40 RTD2 66
28 5A Input 1 65
- 41
STATUS I/P 7 67
42 RTD3 69 NOTES:
Case Earth 68
43 (1) CT Circuits are shown connected to
PHASE C RELAY Earth 1 STATUS I/P 6 70
53 44 RTD4 relay 1A tap, use alternative tap for
72
54 1A 71 for 5A rated CTs
3 29
55 Phase I/P + STATUS I/P 5 73
(2) CT and Earth connections are typical
STATUS I/P 4 30 RTD5 75 only.
56 5A
- 74 (3) Application scheme shown for
A 49 31
STATUS I/P 4 76 Single Phase Thermal Protection
50 1A Fibre-Optic 32 RTD6 78 .
(4) Expansion pcb (7 O/P + 9 Status I/P).
SMA Connectors 77
51 Phase I/P 33 (5) Resistance Temperature Detector.
5A 34
STATUS I/P 3 79
52 T RTD7 (6) Terminal block 3 & E8 case used for
81
45 35
80 RTD Inputs.
C B 46 1A STATUS I/P 2 82
36 RTD8
R 84
47 Phase I/P 83
48 5A
PHASE
25
26 1A
27 Earth Fault I/P
28 5A
Figure 2: Rho 3/D5 - Typical schematic diagram for Rho 3 single phase thermal overload
RHO MANUAL
Addendum
4 INSTALLATION AND
COMMISSIONING
5
1
2 7
3 8
4 9
10
1 Relay type
3 Page-up key
4 Page-down key
8 Enter key
10 Cancel key
70
The policy of Easun Reyrolle is one of continuous improvement and development. The company therefore reserves the right to supply equipment which may
differ slightly from described and illustrated in this publication.
IMAGIC CREATIVES
HOSUR WORKS BANGALORE WORKS
#98, Sipcot Industrial Complex, #17/3 Arakere,
Hosur 635 126, India. Bannerghatta Road,
Sales Offices
Mumbai Delhi Kolkata
Tel: +91 22 22855415 Tel: +91 11 25747321 Tel: +91 33 22848320
Fax: +91 22 22825703 Fax: +91 11 25747320 Fax: +91 33 22848326
Email: mumbai@easunreyrolle.net Email: delhi@easunreyrolle.net Email: kolkata@easunreyrolle.net
Bangalore Chennai Secunderabad
Tel: +91 80 26685496 Tel: +91 44 24346425 Telefax: +91 40278 17847
Fax: +91 22 26685446 Fax: +91 44 24346435 Email: hyderabad@easunreyrolle.net Corporate Office