1 50W TYPICALLY
Limits according to the Catalogue for Technical Data – 50W TYPICALLY – Page :
5. SUPPLY OFF
TERMINALS (CLOSED) - (X11:2,X11:3) :
SUPPLY ON
TERMINALS (CLOSED) -:(X11:1,X11:3) :
APPLIED
CURRENT DISPLAY VALUE %ERROR
PHASE
Expected
Injected Expected Measured Measured
SETTING Drop Out
PHASE Current Pick Up Pick Up Drop Out
Idmin (A) Value (A)
I bias A Value (A) Value (A) Value (A)
as shown figure.
A current is injected into the R phase which is used as the bias current and another current
is injected into the Y phase which is used as differential current.
Inject a bias current of 1A in the R phase. The relay will trip and any contacts associated with the R
phase will operate.
Tested by: Witnessed by:
Name Eng. Name:
Signature & Date : Signature & Date :
AL-FANAR CONTRACTING
Slowly increase the current in the Y phase until phase Y trips . Record the phase Y current
magnitude and check that it corresponds to the following equation;
I-Section 1
When bias current is between:
0 ≤ Ibias ≤ Endsection1*IBase
Limits; ± 2 %Ir According to the Catalogue for Commissioning and Maintenance – Page132
ІI – SLOPE Section 2
When bias current is between:
Tested by: Witnessed by:
Name Eng. Name:
Signature & Date : Signature & Date :
AL-FANAR CONTRACTING
IBase = 3000A
Slope Idmin set I bias Id Id Measured Errors %
section2 A calculated R Y B R Y B
(Trip)
Limits; ± 2 %Ir According to the Catalogue for Commissioning and Maintenance – Page132
9. FINAL SETTING:
Tested by: Witnessed by:
Name Eng. Name:
Signature & Date : Signature & Date :
AL-FANAR CONTRACTING
CT Ratio 3000 / 1 A
R
Y
B
Injection Current =
R
Y
B
Accuracy:
10 BIAS CHARACTRISTIC
I-Section1
Set End section1 = 1.25*IBase
Slope Idmin set I bias Id Id Measured Errors %
section1 A calculated R Y B R Y B
(Trip)
Limits; ± 2 %Ir According to the Catalogue for Commissioning and Maintenance – Page132
ІI – SLOPE Section2
Tested by: Witnessed by:
Name Eng. Name:
Signature & Date : Signature & Date :
AL-FANAR CONTRACTING
End section2=3*Ibase
Id Id Measured Errors %
Slope
Idmin I bias A calculated
section2 R B Y R B Y
(Trip)
Id Id Measured Errors %
Slope
Idmin I bias A calculated
section3 R B Y R B Y
(Trip)
Checked
Function Remote
Local Relay
Relay
Disconnect a fiber optic channel '' Alarm should appeared''
Communication equipment
R 1
Y 1
B 1
R 1
Y 1
B 1
C) INTERTRIP CHECK
Put a jumper between terminals '' & '' intertrip output contact, the remote end CB should
tripped, and repeat this from remote end.