contents to others without expressed authorization is prohibited. Offenders will be held liable
for the payment of damages. All rights reserved in the event of the grant of a patent, utility
model or ornamental design registration.
General
Contents
Installation
Contents
AC Versions
Maintenance
© Siemens AG • 10/2003
Operating Instructions
Siemens Aktiengesellschaft
3EX5 030
4
4
3
2
2
1
The manufacturer of this surge arrester
Siemens AG
Power Transmission and Distribution Group
High Voltage Division
Quality systems: Model for quality assurance This system was first demonstrated in 1989 to the
DQS (German Association for the Certification of Quality Systems).
The electrical testing laboratories and the materials technology laboratories of the manufacturer
have been certified since 1992 by the German Accreditation Body in accordance with DIN EN 45 001.
If you require further copies of the operating instructions, please order them from the appropriate Siemens office,
indicating the title and order number shown on the title page.
Subject to change.
Note
The equipment covered by these instructions should be installed and serviced only by
competent personnel familiar with good safety practices. This instruction is written for
such personnel and is not intended as a substitute for adequate training an experience in
safe procedures.
This information is intended for the correct installation of this product. Siemens has no control over the condition
of the network, which can be greatly affected by the installation of a product. It is the responsibility of the user to
chose the appropriate method of installation. Under no circumstance is Siemens liable for any direct or indirect
damage caused by the use or misuse of this product.
General
This product is a robustly constructed instrument suitable for installation in the earth connection of a
surge arrester which must be isolated from earth for the counter to operate correctly.
To prevent damage the product must not be subjected to rough handling or mechanical shocks either
during or after installation.
¾ Model 3EX5 030 is suitable for use with single arresters or three phase sets.
¾ Model 3EX5 050 is suitable only for use with a single arrester.
The counter is sealed in a weatherproof housing with a serial number on the back of the housing.
AC Versions
A voltage-free contact is available to allow connection to a remote counter or indicator. The contacts
are related 0,5A 240V AC maximum.
2 © Siemens AG • 10/2003
Installation
Warning
Before any work starts:
¾ switch off and isolate
¾ secure against reclosing
¾ verify that equipment is dead
¾ earth and short circuit the equipment
¾ cover or fence off nearby live parts
Death, severe injury and considerable damage to
property and environmental damage may result if
the safety instructions are not followed.
¾ Confirm that these safety measures have been carried out.
1 Line termination M12 nickel plated brass fitted with 2-nickel plated brass locknuts
2 Moulded resin insulator
3 Hermetically sealed glass display panel
4 Ground termination M12 nickel plated brass fitted with 2-nickel plated brass locknuts
5 M12 × 35 galvanised steel set screw with full nut and spring washer
6 Surge Counter
7 leakage current display (only 3EX5 050)
Fig. 1 Surge counter 3EX5 030 / Surge monitor 3EX5 050
Note
The product should ideally be mounted at eye-level on a horizontal surface such as
cross-channel or angle support.
Operation is not impaired at angles up to 60° total.
A clearance of at least 30mm must be allowed between the live terminal of the surge
counter and any earthed object.
© Siemens AG • 10/2003 3
Connections to the surge counter may be made with either cable or bare conductor with suitable ter-
mination to the M12 line and earth studs, which are nickel plated brass. Care should be taken when
tightening the connections to avoid overstressing the terminals and the use of two spanners is rec-
ommended. Should bare conductor be used this also be isolated from any earthed structure by 30mm.
The max. torque with tightening the nuts/mothers may not are exceeded:
¾ M12: 40Nm
Maintenance
Under normal operating conditions this product does not require any maintenance, except for periodic
cleaning of the glass and the line bushing. The tightness of the connections should be checked at the
same time.
No electrical tests should be undertaken to the counter without the previous agreement of the manu-
facturer.
4 © Siemens AG • 10/2003