Sunteți pe pagina 1din 5

4.2.

4 20P-4300A - Potable Water Pump A

1. Equipment Details

Machine ID : 20P-4300A
PRIORITY 6
Machine Name : Potable Water Pump A Normal
Location : BUNGA ORKID-A
Area : MEZZANINEDECK

2.Technical Specification

Machine ID & Name 20P-4300A - Potable Water Pump A


Machine Speed 2973 RPM
Monitored Items
Instrument Used Bently Nevada System1 software &
Snapshot(Portable Data Collector)
Vibration Limits as per ISO 10816 Class 3 (RMS velocity mm/sec.)
Priority 1&2 Danger > 11.2
Priority 3 &4 Alarm 4.5 - 11.2
Priority 5 Still Acceptable 2.8 - 4.5
Priority 6 Acceptable < 2.8

3. Machine Sketch

MOH / 2HL
A-Axial

MOV
MIH

MIA PIA
MIV
PIH
Horizontal V- Vertical
PIV

POH
POA
POV
4.Overall Seismic Vibration Readings
Location RMS velocity mm/sec Envelope in 1m/s2 ? 0.1g
July’16 Aug’16 July’16 Aug’16
20P-4300 A : 13555
MOV 1.163 1.066 0.312 0.312
MOH 1.066 1.744 0.273 0.351
MOA 0.485 0.581 0.078 0.078
MIV 0.581 0.678 0.662 0.701
MIH 0.678 0.678 0.818 0.585
MIA 0.388 0.388 0.546 0.546
PIV 0.678 0.678 0.195 0.390
PIH 0.388 0.485 0.390 0.351
PIA 0.388 0.485 0.390 0.585
POV 0.775 0.581 0.234 0.312
POH 0.485 0.485 0.195 0.273
POA 0.485 0.388 0.507 0.234

5. Plots of marked highest reading


Direct Trends;
Half Spectrum Waterfall Plot;

Half Spectrum Plot;


Enveloped/Demod Direct Trends;

Half Enveloped/Demod Spectrum Waterfall plot;


Half Enveloped/Demod Spectrum Plot;

6. Observations

RMS Velocity: nnn

Spectrum: The spectrum shows dominant amplitude of 0.66mm/sec at 50 Hz. nnnnn

Envelope: The current overall vibration readings are within tolerable limits, hence the machine is
suitable for long-term operation. Trend readings are being monitored for further analysis.

7. Recommendations
nnn