10.1 INTRODUCTION
Composite structural members are members in which steel and concrete act
together through mechanical interlock, friction, and adhesion. Composite members
are designed to maximize the efficiency of the two materials by using, whenever
possible, the concrete in compression and the steel in tension. In addition to
exploiting the stress–strain characteristics of the two materials to increase the
ultimate capacity of the member, composite systems attempt to gain additional
benefits from the synergy of their interaction. For example, the concrete can be
used to limit global and local buckling problems in thinner steel elements, and the
steel in tubular and round sections can be used to increase the confinement of
the concrete and therefore help to maintain its strength in the postpeak region.
Buildings are seldom constructed only of composite members. Most often,
composite columns are used in the lateral load-resisting systems in combination
with either other composite members to form composite systems or other types of
structural elements to form hybrid systems (Goel and Yamanuchi, 1993; Yamanuchi
et al., 1993; Deierlein, 1995; Deierlein and Leon, 1996). Composite members are
very popular in floor systems where composite beams, stub girders, and composite
joists and trusses are the most economical alternatives in mixed-use structures
(Viest et al., 1996). The stability benefits derived from the presence of a floor slab
for floor members are not addressed in this chapter. It should be noted, however,
that additional care needs to be taken in negative-moment regions of composite
flexural members to ensure that the required rotational capacity is reached (Dekker
et al., 1995). Thus, utilizing the beneficial aspects of composite action requires
design checks that are different from those for typical reinforced-concrete or steel
construction. Additional stability design provisions from composite beams with
web openings and for composite joists and trusses are also available from an
ASCE Task Group on Composite Design (ASCE Task Committee, 1994a, 1996).
456 Guide to Stability Design Criteria for Metal Structures, Sixth Edition Edited by Ronald D. Ziemian
Copyright © 2010 John Wiley & Sons, Inc.
INTRODUCTION 457
be overcome with prefabrication and use of newer technologies (blind bolts for
connections, for example). Moreover, as design provisions evolve and new design
recommendations are adopted, it is likely that more extensive use of composite
columns and other forms of composite construction will be made in the near future.
The advantages of composite construction were recognized early in the twen-
tieth century (Talbot and Lord, 1912), and most multistory buildings were built
with composite columns for fire protection until lightweight, sprayed fireproofing
became available. Recently, composite members and systems are becoming popular
again, primarily because of their stiffness characteristics (Griffis, 1992) and seismic
resistance (Goel and Yamanuchi, 1993). Two excellent complementary references
on composite construction for buildings have recently become available: one for
fundamental mechanics issues (Oehlers and Bradford, 1995) and one for practi-
cal issues (Viest et al., 1996). Both provide more detailed discussions of many of
the issues addressed in this chapter. In addition, the proceedings of several recent
international conferences provide an up-to-date overview of recent experimental
460 COMPOSITE COLUMNS AND STRUCTURAL SYSTEMS
research and analytical advances (Roeder, 1985a; Buckner and Viest, 1988; Wak-
abayashi, 1991; Easterling and Roddis, 1993; Javor, 1994; Buckner and Shahrooz,
1997; Hajjar et al., 2002; Leon and Lange, 2006). No attempt is made in this
chapter to summarize this extensive literature. For older research, on which many
of the current design provisions are based, the third edition of this guide should
be referenced. A complete history of the development of composite construction is
provided by Viest et al. (1996, Chap. 1).
where As is the area of the steel tube, σy the steel yield strength, Ac the area of the
concrete infill, fc the concrete compressive strength, D the tube diameter, and t the
thickness. The strength reduction factor γu = 1.67D −0.112 is used to account for
the effects of size on the concrete compressive strength. The first term in Eq. 10.1
uses 0.89σy as the longitudinal stress capacity of the steel tube to account for the
U.S.– JAPAN RESEARCH PROGRAM 461
effects of tensile hoop stresses required to confine the concrete. The second term in
the equation includes the effects of size and confinement on compression strength.
Comparisons of experimental results with nominal strength predictions using
Eq. 10.1 were quite favorable with a mean value of 0.989 and standard deviation
of 0.052.
The experimental results were also used to develop an equation for calculating
the nominal axial strength Po of square CFT columns:
where σcr is the longitudinal stress capacity of the square steel tube accounting for
the effects of local buckling and is calculated from
σy
σcr = 2 ≤ σy (10.3)
b σy 4.00
0.698 + 0.128 ×
t E 6.97
Equation 10.3 was developed using experimental results for hollow steel tube
stub columns by modifying them to account for the change in the local buckling
mode from hollow to CFT columns—hence, the term 4.00/6.97. The comparisons
of experimental results with nominal strength predictions were quite favorable with
a mean value of 1.032 and standard deviation of 0.058. These predictions were
slightly conservative for columns with small width-to-thickness b/t ratios, which
is probably due to the strain hardening of the thicker steel tubes.
VX + (W − 1)X 2
Y = (10.4)
1 + (V − 2)X + WX 2
in which X = εc /εcco , Y = σc /σcco√, V = Ec εc /σcco , W = 1.50 − 0.017 fc +
√
2.39 σh , where Ec = 6900 + 3320 fc in megapascals, εco = 0.94 × (fc )0.25 ×
10 , and fc = fc × 1.67D −0.112 .
−3
TABLE 10.1 Parameters for CFT Concrete Stress– Strain Model in Compression
Parameters Circular Columns Square Columns
σh
4.1 2t × 0.19 2t 2 (b − t )
σy ×
23 D − 2t b3
σcco
4.1 2t × 0.19σy 1.0
fc 1+ ×
fc D − 2t
εcco
σcco σcco
εco 1.0 + 4.7 × − 1 for ≤ 1.5 1.0
fc fc
σcco σcco
3.4 + 20 × − 1 for > 1.5
fc fc
compressive strength accounting for scale effects, εco the strain at fc , Ec the elastic
modulus, σcco the confined concrete strength, εcco the strain at σcco , and σh the
hoop stress in the steel tube.
Figure 10.4 shows examples of effective stress–strain curves developed using
Eq. 10.4. Figure 10.4a shows effective stress–strain curves for circular CFTs with
(i) fc equal to 55 MPa, (ii) D equal to 305 mm, (iii) D/t ratios equal to 50, 75, and
150, and (iv) σy equal to 317 and 552 MPa. Similarly, Fig. 10.4b shows effective
stress–strain curves for square CFTs with (i) fc equal to 55 MPa, (ii) b equal to
305 mm, (iii) b/t ratios equal to 32, 48, and 64, and (iv) σy equal to 317 and 552
MPa. As shown, confinement improves the strain ductility of the concrete infill
of square CFT columns, and it increases the strength and strain ductility of the
concrete infill of circular CFT columns.
Sakino et al. (2004) proposed elastic–plastic effective stress–strain curves for
the steel tubes of circular CFT columns in compression. The effective yield stress
was equal to 0.89σy . This reduction accounted for the effects of tensile hoop
stresses σh required to provide confinement to the concrete infill. Figure 10.5
shows the effective stress–strain curves proposed for the steel tubes of square
CFT columns in compression. The tubes are categorized into three types (also
referred to as ranks) depending on the wall normalized slenderness ratio αs , which
can be calculated from
2
b σy
αs = × (10.5)
t E
60
fc′ = 55 MPa; D = 305 mm
50
Stress (Mpa) Dt = 50; sy = 552 MPa
40 Dt = 75; sy = 552 MPa
30 Dt = 150; sy = 552 MPa
FIGURE 10.4 Concrete effective stress–strain curves for: (a) circular CFTs; (b) square
CFTs.
1.2 eB, sB
eB, sB
1 eR, sR
eB, sB eR, sR
0.8
Stress (MPa)
eR, sR
0.6
Type 1 or Rank FA
0.4
Type 2 or Rank FB
0.2
Type 3 or Rank FC
0
0 0.002 0.004 0.006 0.008 0.01 0.012
Strain (mm/mm)
FIGURE 10.5 Effective stress–strain curves for steel tubes of square CFTs.
464 COMPOSITE COLUMNS AND STRUCTURAL SYSTEMS
σB σy σy σy
0.698 + 0.128αs 4.00
0.698 + 0.128αs ×
6.97
σy σB
εB σy 6.06 0.801
× − + 1.10 E E
E αs2 αs
√ √ √
σR 1.19 − 0.207 αs 1.19 − 0.207 αs 1.19 − 0.207 αs
εR σy σy σy
3.59 + εB 4.59 3.59 + εB
E E E
three types achieve some residual-stress capacity that remains constant with
increasing strains. Table 10.2 summarizes the parameters required to define these
multilinear effective stress–strain curves shown in Fig. 10.5 for all three types
(or ranks) of steel tubes. In Table 10.2, σB and εB are the stress and strain
corresponding to the onset of local buckling, and σR and εR are the residual stress
and corresponding strain postlocal buckling.
Sakino et al. (2004) showed that the axial load–shortening responses predicted
using these concrete and steel effective stress–strain curves in compression
compared favorably with the experimental results for circular and square CFT
columns for the wide range of material and geometric parameters included in the
investigations.
high-strength steel tubes or tubes with smaller b/t or D/t ratios; (ii) moment
capacity enhancement due to concrete confinement by the steel tube is likely for
circular CFTs with D/t ratios less than 75 and it is negligible for circular CFTs
with D/t greater than 75 and for square CFT columns; and (iii) the effects of
steel tube local buckling should be included when estimating the moment capacity
of square CFTs with large (type 3 or rank FC) b/t ratios.
Fujimoto et al. (2004) also developed fiber models to predict the M–φ relation-
ships of the tested specimens. These fiber models used the effective stress–strain
curves in compression developed by Sakino et al. (2004) for steel and concrete. As
described earlier, these effective stress–strain curves implicitly accounted for the
effects of tube local buckling, concrete confinement, and scale effects. In tension,
the concrete fibers were assumed to have zero stress capacity, and the steel fibers
were assumed to have bilinear stress–strain behavior. The yield stress in tension
was assumed to be equal to 1.08 and 1.10 times the nominal steel yield stress
for circular and square steel tubes, respectively. The fiber models were found to
predict the M–φ behavior and the moment capacities of the tested specimens with
reasonable accuracy.
As part of the U.S.–Japan program, Varma et al. (2000, 2002, 2004, 2005)
conducted experimental and analytical investigations to determine the behavior of
high-strength square CFT columns and to evaluate the effects of various material,
geometric, and loading parameters on their stiffness, strength, and ductility. The
parameters included in the experimental investigations were the steel tube yield
stress (266 to 630 MPa), concrete strength (110 MPa), tube b/t ratio (32 to 48),
and axial load level for beam-columns (10 to 40% of the section axial load capac-
ity Po ). Four CFT stub columns were tested under pure axial compression, eight
CFT beam-columns were tested under constant axial loading (20 or 40% of Po )
and monotonically increasing flexural loading, and eight CFT beam-columns were
tested under constant axial loading (10 to 30% of Po ) and cyclically increasing flex-
ural deformations. The experimental results included the axial load–displacement
responses, and the monotonic and cyclic axial force–moment–curvature (P–M–φ)
responses of the high-strength CFT beam-columns. These were used to determine
the axial stiffness, axial load capacity, flexural stiffness, moment capacity, and
monotonic and cyclic ductility of high-strength CFTs.
The experimental results indicated that the axial stiffness can be predicted using
the transformed section properties of the CFT section. The axial load capacity
can be predicted with reasonable accuracy by superimposing the yield strength of
the steel tube (As Fy ) with 85% of the compressive strength of the concrete infill
(Ac fc ). The initial flexural stiffness of CFT beam-columns can be predicted using
uncracked transformed section properties. The secant flexural stiffness correspond-
ing to 60% of the moment capacity can be predicted using cracked transformed
section properties. The deformation ductility of high-strength CFT beam-columns
decreases significantly with increases in the applied axial force level and the steel
tube b/t ratio. The steel tube yield stress does not seem to have a significant influ-
ence on the ductility. The moment capacity of high-strength CFT beam-columns
can be predicted conservatively using ACI (2005) 318-05 recommendations and
466 COMPOSITE COLUMNS AND STRUCTURAL SYSTEMS
more accurately using the modified Architectural Institute of Japan (AIJ) method
developed by Sakino et al. (2004). The Eurocode (CEN, 2004) provisions overpre-
dicted the moment capacity of high-strength CFT beam-columns.
and crushing, steel yielding and local buckling, and slip between the concrete and
steel. It was developed and calibrated for CFT members made using conventional or
high-strength materials. They also implemented a comparable steel finite element,
where the formulation is suitable for both braced and unbraced frames with steel
girders and steel or CFT braces framing into steel or CFT columns. The formula-
tion is implemented in OpenSEES, which is an open-source finite element analysis
program available from the website http://opensees.berkeley.edu. One to three
elements have been found adequate for modeling members with highly nonlinear
curvature and high axial compression. Tort and Hajjar (2007) used the finite ele-
ment program to conduct parametric studies of damage limit states and to develop
a framework for reliability-based, performance-based design of CFT structures.
The flexural strength M at any given axial load P can be calculated by assuming
a position of the neutral axis, drawing the stress distributions, and summing their
moments about the plastic neutral axis. This locus of points is shown as solid lines
in Fig. 10.6, which schematically illustrates the ultimate strength of SRCs and
CFTs. The lines correspond to the theoretically “exact” solution when nonlinear
constitutive models are used for both steel and concrete, and the effect of con-
finement is appropriately modeled. To compute the capacities, a process analogous
to that for any reinforced-concrete beam-column, in which the reinforcing bars
are transformed into an equivalent thin steel section, can be used. Although this
method is both tedious and computationally intensive, computer programs based on
subdividing the cross section into small elements (finite elements of fiber models)
are available for both SRC and CFT sections (Mahin and Bertero, 1977; Gourley
and Hajjar, 1994; El-Tawil et al., 1995; Gourley et al., 1995). Many commercial
reinforced-concrete computer design packages include some variation of the Mahin
and Bertero (1977) approach as an option. In general, all these models assume strain
continuity between the steel and concrete portions, an assumption that is not sup-
ported by much of the data from experimental programs in which the interface
behavior was monitored. This assumption, however, which simplifies the problem
considerably, appears to have negligible influence on the ultimate strength and a
relatively small influence on the stiffness of the cross section.
The parabolic shape of the interaction curves is similar for SRCs and CFTs
(Fig. 10.6). For SRCs, the difference in flexural capacity between the balance point
(point D) and the pure flexure case (point B) decreases as the amount of structural
steel and longitudinal steel reinforcement increase. Increases in the yield strength
of the structural steel, for example from an A36 to an A572 material, significantly
increases the capacity of the section at both points B and D. As one would expect,
increases in concrete strength do not seem to have a major effect on the flexural
strength at point B because steel yielding governs the strength, but they tend to
increase the distance between points B and D in the interaction diagram. For most
CFTs, the shape in Fig. 10.6 is preserved because in the limit the CFT section can be
468 COMPOSITE COLUMNS AND STRUCTURAL SYSTEMS
FIGURE 10.7 Stress distributions for key points on the interaction diagram.
flexural strengths are determined by assuming nominal yield strengths for the steel
and 0.85 of the cylinder strength for the concrete. For encased shapes, Fig. 10.7
shows the plastic stress distribution for several of the points in the interaction
surface shown in Fig. 10.6. The axial strength Pu , shown in Fig. 10.7a, is given by
where fc is the concrete cylinder strength, d the overall depth, b the width, Fy the
yield strength of the steel shape, Fyr the yield strength of longitudinal reinforce-
ment, As the area of the steel shape, and Ar the area of longitudinal reinforcement.
A simple and elegant solution for other important points in the interaction
surface for the rigid-plastic case can be found by following the procedure pro-
posed by Roik and Bergmann (1989, 1992). Consider the typical case of an encased
shape bent about its major axis and having only four bars as longitudinal reinforce-
ment. Assuming that the neutral axis lies in the web of the steel beam, the plastic
470 COMPOSITE COLUMNS AND STRUCTURAL SYSTEMS
stress distributions for points B through D in Fig. 10.6 correspond to the stress
distributions in Figs. 10.7b through d . Points B and C correspond, respectively,
to the case of no axial load and to an apparently arbitrary point in the interaction
diagram above the balance point. In fact, points B and C correspond to the same
moment because the stress blocks lying within the distance hn in both Figs. 10.7b
and c have their centroid at the plastic neutral axis and thus do not contribute to
the plastic bending capacity of the section. In addition, it needs to be recognized
from both Figs. 10.7b and c that the axial forces from the reinforcement and the
shaded portions of the forces from the steel shape cancel out.
Adding the stress distributions in Figs. 10.7b and c and considering axial loads
only, the total axial load Pconc would still be that at point C . From superimposing
the stress blocks, this axial load will be that given by the concrete section alone
under a uniform stress of 0.85 fc because the contributions from the steel shape
within the distance hn also cancel out, resulting in
The depth of the compression block a can then be calculated from Fig. 10.7b
by assuming that the compressive force in the concrete is equal to the tensile force
in the web of the steel shape within the distance 2hn , which leads to
tw dFy
a= (10.8)
0.85 fc b + 2tw Fy
Pconc
hn = (10.9)
2[0.85 fc b + tw (2Fy − 0.85 fc )]
Knowing either hn or a, the moment capacity of the section for both points B
and C in Fig. 10.6 can easily be calculated.
The final point that needs to be defined is the balance point (point D). The
maximum moment will be obtained when the neutral axis is at the centroid of
the cross section (Fig. 10.7d ), because in this case all the forces are additive with
respect to moment. From Fig. 10.7d , it is clear that all contributions to the axial
load from the steel shape and reinforcement cancel out and thus the axial load at
this point corresponds to that of 0.85fc acting over half of the cross section, or
Pconc /2. The balance moment Mbal is given by
n
Mbal = Zx Fy + 0.5 bd 2 fc + Ari dri (10.10)
j =1
OTHER CONSIDERATIONS FOR CROSS-SECTIONAL STRENGTH 471
where Zx is the plastic section modulus, Ari the area of any rebar, and dri its distance
to the plastic neutral axis.
Equations 10.6 through 10.10 permit a very quick and accurate calculation for
the key points in the interaction curve. Although Fig. 10.7 and Eqs. 10.6 through
10.10 provide a solution for only the simplest case, the above approach is general.
It also applies for cases where the neutral axis is either in the flange of the steel
shape or outside the steel shape and for any number and bar-type distribution.
Equations for bending about both axes and for concrete-filled shapes are given
by Roik and Bergmann (1992) in a much more general format. The two general
approaches discussed above also apply for the case of biaxial bending. The exact
approach only differs in that the assumed inclination of the neutral axis changes
with respect to the principal axes of the cross section (El-Tawil et al., 1993). The
validity of this approach has been verified experimentally (Morino et al., 1988,
1993) and analytically (Virdi and Dowling, 1973; Gourley and Hajjar, 1994).
Although a rigid-plastic approach is also possible in this case, it is not possible
to derive simple, general equations for this case. A simplified approach utilizing
the rigid-plastic capacities computed for both principal axes has been proposed by
Roik and Bergmann (1992) and adopted for the Eurocode (CEN, 2004).
1
S = ≤ 1.0 (10.11)
4.00
0.698 + 0.128 × × αs
6.97
472 COMPOSITE COLUMNS AND STRUCTURAL SYSTEMS
guf′c S sy
k2Xn
Xn k1Xn C
b NEUTRAL AXIS
sy
b
CFT cross-section Concrete Steel
For values of αs less than 4.12, there will be no reduction in the compressive
stress capacity of the steel.
The concrete compression block parameters (k1 and k2 ) shown in Figure 10.8
were calibrated for both conventional and high-strength concrete (up to 120 MPa).
The values of these parameters can be calculated from
in which the concrete compressive strength fc is in megapascals, and γu is the scale
factor discussed earlier. The cross-sectional strength for any combination of axial
load P and bending moment M can be obtained by establishing force equilibrium
using the stress blocks shown in Fig. 10.8 and Eqs. 10.11 through 10.12.
The effect of transverse reinforcement on the concrete strength is typically
ignored when calculating the cross-sectional strength, but designers should be con-
scious that transverse reinforcement will have a major effect on postpeak behavior.
This is of particular importance under seismic loading, where strength and stiffness
degradation will be influenced by the amount and distribution of transverse rein-
forcement. Designers should also understand that the confining effect decreases with
increasing concrete strength because the amount of microcracking and resulting
dilatatory behavior decreases with concrete strength (see Fig. 10.4a). In addition,
the effect of transverse steel is dependent on its spacing and presence of crossties for
the case of encased sections and on the wall thickness for the case of concrete-filled
tubes (sees Fig. 10.4b). O’Shea and Bridge (1996) have found that for tube
diameter-to-thickness ratios greater than 55 and concrete strengths in the range
110 to 120 MPa, the steel tube provides virtually no confinement to the concrete
when both the steel and concrete are loaded together. Confinement effects could
be obtained only if the concrete was loaded and the steel was not bonded to the
concrete. Unbonded tube construction has been considered by Orito et al. (1988).
The effect of shear on the ultimate axial and flexural strength depends primarily
on the shear span M /V ratio, the amount of axial load, and the detailing of the shear
reinforcement. For a cross section with a large axial load and high shear span, it
LENGTH EFFECTS 473
would appear that the shear resistance of the concrete and steel should be additive.
Conversely, for a lightly loaded column with a low shear span, where a substantial
portion of the concrete cross section may not be effective due to flexural or diagonal
cracking, it would seem prudent to limit the shear strength to that of the steel section
and the shear reinforcement. The differences in capacity computed from either set
of assumptions are very large. This is illustrated schematically in Fig. 10.6, where
the flexural capacity of any cross section can be limited by the capacity in shear
given by either the steel alone Vs or the combined capacity Vs+c . In preparing this
plot, it was assumed that the column was in double curvature and that the ultimate
moment capacity could be reached at either end (Vs = 2Mult /L = Aw Fyw ). For
Vs+c , it should be noted that the concrete capacity is dependent on the axial load,
and thus the function is nonlinear.
The rigid-plastic stress distributions discussed in Section 10.3 are consistent
with an assumption of uniform shear throughout the web. To calculate the ultimate
strength properly, the web yield stress Fy,web should be reduced to
Fy,web = Fy − 2τw2 (10.13a)
V
τw = (10.13b)
dtw
where V is the shear at the cross section d in the depth of the steel member and tw
is the thickness of the web of the steel section. Note that shear will be the dominant
failure mode in many columns used in seismic areas, in which case careful detailing
for shear transfer is needed.
Interaction between the steel and concrete portions of composite members results
from a combination of chemical adhesion, friction, and mechanical interlock
(mostly bearing). The most dependable composite action arises from the use
of mechanical shear connectors (generally headed shear studs) that transfer the
FORCE TRANSFER BETWEEN CONCRETE AND STEEL 475
forces between the two materials by direct bearing and shear. From the strength
standpoint, the studs need to be designed to transfer all the shear forces at the
interface between the steel and concrete that are consistent with the development of
the plastic capacity of the cross section. This is typically defined as a full-strength
shear connection. When fewer studs than these are provided, the system is said to
be partial strength.
Although the concepts of full and partial strength are useful to describe the
behavior of members such as composite beams where the two materials are in con-
tact at a small and well-defined boundary, their application to composite columns
is not as straightforward. Studies have shown that the ultimate strength given by a
rigid-plastic approach is usually achieved by short composite columns under mono-
tonic loading irrespective of whether or not mechanical force transfer is provided.
Thus full strength is not as meaningful a design parameter in composite columns
as it is in beams, except for the case where fatigue or seismic loadings govern
the design. In such cases, mechanical shear connectors should be provided because
adhesion and friction are not reliable force transfer mechanisms under these types
of loads.
Full and partial strength are different concepts from full and partial interaction.
Full interaction implies continuity of strains and curvature across the steel concrete
boundaries. Because most shear connectors provide a nonlinear shear strength–slip
behavior (i.e., some slip is needed before the resistance builds up) full interac-
tion cannot be achieved in practice even at service load levels. In most practical
cases, the achievement of ultimate strength in composite systems requires substan-
tial slip at the steel-to-concrete interface, resulting in severe discontinuities in the
strain profile between the steel and concrete. Because most computer programs
developed to calculate ultimate cross-sectional capacity rely on an assumption of
strain compatibility between the materials, large discrepancies would be expected
between their predictions and available experimental results. This, however, is not
the case because at ultimate capacity, when strain discontinuities do exist, their
effect on the stresses is small because both materials are on fairly flat portions of
their respective stress–strain curves. A powerful argument for proposing the use of
rigid-plastic stress distributions for calculating composite member strength is that
they circumvent the need to account for these discontinuities in interface strains.
As long as the strains are larger than both the yield strain for the steel (Fy /E )
and the strain consistent with the attainment of the maximum uniaxial strength
for the concrete (about 0.002 to 0.003), the stress distributions in Fig. 10.7 can
be achieved. The use of rigid-plastic stress distributions also obviates the need to
design for the perpendicular forces that develop at the interface if the steel and
concrete are assumed to remain in contact. These forces are small except for areas
adjacent to large concentrated loads (Robinson and Naraine, 1988) and can easily
be handled by the horizontal projections (heads) of most mechanical connectors.
In both axially loaded specimens and flexural specimens, test results can be
interpreted to imply that chemical adhesion provides a substantial contribution to
the shear transfer in the service load range (Roeder, 1985b; Wium and Lebet,
1990a,b). Quantification of this effect is impossible given both the difficulties in
476 COMPOSITE COLUMNS AND STRUCTURAL SYSTEMS
measuring this property and the large scatter that can be expected from varying
surface conditions, loading history, casting position, size effects, and concrete mix
proportions, to name a few of the relevant variables.
The longitudinal bond between the steel tube and the concrete infill of a CFT
column has been investigated by several researchers, including Virdi and Dowling
(1980), Shakir-Khalil (1991a, 1993a,b), Morishita and Tomii (1982), and Roeder
et al. (1999). These studies indicate that the bond strength increases with the
roughness of the steel at the steel–concrete interface. The bond strength does not
change when shear connectors are used, and the shear connectors contribute to
the load-carrying mechanism only after slip has occurred. The bond strength for
square CFTs is smaller than the bond strength for circular CFTs, and the concrete
compressive strength does not seem to have a consistent effect on the bond strength.
Roeder et al. (1999) compiled numerous bond strength test results from previous
researchers, including 104 circular and 49 square CFT bond tests, and combined
them with their own experimental results. These studies indicate that the bond
strength decreases dramatically as the width b or width-to-thickness ratio increases.
The width b or diameter d of the CFT column has a significant influence on the
shrinkage of the concrete infill, which makes it an important parameter for bond
strength. A linear regression analysis was performed using all of the experimental
data, and the results were used to develop the following expression for average
maximum bond strength (f2σ ) in megapascals:
with 97.5% of the specimens having an average maximum bond strength greater
that that predicted by Eq. 10.14.
Equation 10.14 predicts larger bond stresses for stocky tubes with smaller d /t
ratio and smaller bond stresses for thinner tubes with larger d /t ratio. At the ulti-
mate load, the bond stress can be assumed to be uniformly distributed around the
periphery of the interface and along a length equal to the lesser of the column
length or 3.5 times the diameter of the tube, as shown in Fig. 10.9. Due to bond
deterioration considerations under cyclic loading after initial slip at the serviceabil-
ity load, the bond stress can be assumed to be triangularly distributed over a length
equal to one-half of the tube diameter due to bond deterioration considerations
under cyclic loading after initial slip (see Fig. 10.9). The bond stress evaluation
is needed for axial load transfer; bending moment develops binding action that
enhances the local bond stress capacity. Because shear connectors do not work
well with natural bond stress, axial load transfer should be accomplished entirely
by bond stress or other mechanical connectors.
At ultimate capacity and in the absence of mechanical shear connectors and
adhesion, all forces must be transferred by friction. The normal forces necessary
for friction arise primarily from shear stresses and the differential expansion of
the two materials under load. Shear stresses arise from moment gradients and the
assumption of no vertical separation between the steel and concrete components
(i.e., the assumption of equal curvatures in the steel and concrete portions). The
FORCE TRANSFER BETWEEN CONCRETE AND STEEL 477
f2s f2s
Length No Length
Greater Than No Greater
The Length Than d/2
of the
Column or
3.5 Times
the Diameter
of the Tube
differential expansion results from different values of Poisson’s ratio (ν) and is
dependent on the level of stress and the mix proportions. This effect is very different
for SRCs and CFTs. At low levels of stress, the steel expands more than the concrete
(ν ≈ 0.3 for steel and ν ≈ 0.15 to 0.20 for concrete in the elastic range). This does
not result in any appreciable development of frictional forces unless the entire
load is introduced directly to the steel shape. As the concrete stresses increase over
0.5fc , the dilatational behavior of the concrete begins to take over as microcracking
progresses and the apparent ν of the concrete increases over that of the steel. In
SRCs the confinement effect provided by ties is insignificant because the amount
of transverse reinforcement is volumetrically small and cross ties are typically not
used. In CFTs, on the other hand, the expansion of the concrete is controlled by the
steel section. For round tubes this results in large hoop stresses and the development
of a very efficient confinement effect. This increases the nominal crushing strength
of the concrete and helps maintain the strength in the postpeak region of the
stress–strain curve. The beneficial effects of the encasement are present even in
extreme cases when no shear connection is present and adhesion has been prevented
with the use of lubricants (Orito et al., 1988). The hoop stresses, on the other hand,
result in biaxial state of stress in the tube wall that can lead to early yielding
or buckling. For rectangular and square CFTs, the effect of confinement will be
smaller because of the ineffectiveness of this type of cross section in developing
hoop stresses. The amount of friction that can be developed depends primarily on
the surface conditions, degree of compaction of the concrete, and any longitudinal
out-of-straightness. While experimental results for CFTs show this effect clearly
(Virdi and Dowling, 1980), test results for SRCs are somewhat inconclusive in this
regard (Bryson and Mathey, 1973; Dobruszkes and Piraprez, 1981).
478 COMPOSITE COLUMNS AND STRUCTURAL SYSTEMS
It should be clear from the above discussion that the force transfer between
the steel and concrete portions of a composite member is a complex phenomenon.
At this time, there appear to be no mechanistic models that adequately address
the numerous interactions described above, and the experimental data needed to
calibrate such models are not available. It is clear from the vast majority of
the experimental results, however, that a model that incorporates a sophisticated
interface force transfer mechanism is not necessary to accurately predict the ulti-
mate strength of a composite cross section. Rigid-plastic models such as the one
described above or finite elements with fiber models that assume no slip between
the concrete and steel predict the ultimate strength equally well provided that the
strains achieved in the model are large.
Over the years, a large number of design approaches have been proposed for com-
posite columns. Good summaries of these can be found in Furlong (1968, 1974,
1983, 1988), Basu and Sommerville (1969), Virdi and Dowling (1976), Roberts and
Yam (1983), Roik and Bergmann (1985), Shakir-Khalil (1988), Bradford (1995),
and Varma et al. (2002, 2004). In the United States the design of composite
columns by the AISC (2005) specification is based on the work of Aho and Leon
(1997). The Eurocode 4 (CEN, 2004) procedure is based primarily on the work of
Roik and Bergmann (1992), based on calibrations by Roik and Bergmann (1989)
and Johnson (1997). The Japanese provisions are based on the work of Sakino
et al. (2004).
For encased composite columns, the cross-sectional area of the steel core has
to be greater than or equal to 1% of the total composite section area. The concrete
encasement of the steel core has to be reinforced with continuous longitudinal
bars and lateral ties or spirals. The minimum transverse reinforcement area is
0.009 in.2 /in.(6 mm2 /mm) of tie spacing. The minimum reinforcement ratio for
continuous longitudinal reinforcing (area of reinforcement/gross section area) is
0.4%. For CFT columns, the cross-section area of the steel tube section has to be
greater than 1% of the total composite area.
The maximum b/t ratio for the steel
tube of a square CFT is limited to 2.26 E /Fy . The maximum D/t ratio for the
steel tube of a round CFT is limited to 0.15E /Fy .
The nominal compressive strength Pn for axially loaded composite columns is
determined for the limit state of flexural buckling according to
Pn = Po 0.658(Po /Pe ) for Pe ≥ 0.44Po (10.15)
Pn = 0.877Pe for Pe < 0.44Po (10.16)
where Pe = π 2 EIeff /KL2 and the parameters Po and EIeff are defined in Table 10.3
with
The P–M interaction curve for the axial force–moment capacity of the com-
posite cross section can be developed using the rigid-plastic approach described
in Section 10.3. The “exact” P–M interaction curve can be approximated using
straight lines to connect points B, D, C, and A, as identified in Fig. 10.6. The axial
forces and moment capacities corresponding to these points can be calculated using
the stress block distributions and equations shown in Fig. 10.7. The cross-section
480 COMPOSITE COLUMNS AND STRUCTURAL SYSTEMS
As As
C1 = 0.1 + 2 ≤ 0.3 C3 = 0.6 + 2 ≤ 0.9
Ac + As Ac + As
Strain-compatibility
A Rigid-plastic
Al 2005 Simplified
Axial force, P
As
E
C
Cl
Cd D
Bd B
Moment, M
Fy 0.85fc Fyr
Npl,rd = As + Ac + Ar for encased shapes (10.17)
γs γc γr
Fy f Fyr
Npl,rd = As + Ac c + Ar for concrete-filled tubes (10.18)
γs γc γr
Fy f t Fy Fyr
Npl,rd = As η2 + Ac c 1 + η1 + Ar for concrete-filled circular tubes
γs γc d fc γr
(10.19)
Note that the 0.85 appearing in Eq. 10.17 can be increased to 1.0 for
concrete-filled tubes with λ < 0.5, where λ is defined below.
The benefit of good confinement conditions can only be taken into account for
concrete-filled circular tubes (Eq. 10.19) and if the column is relatively stocky
(λ < 0.5). The coefficients η1 and η2 , which account for concrete confinement, are
functions of the slenderness and the ratio of the eccentricity e of the axial load to
the tube diameter d (which for concentrically loaded columns e/d = 0) and are
defined by
e
where
η10 = 4.9 − 18.5λ + 17λ2 ≥ 0 (10.22)
η2 = 0.25 (3 + 2λ) ≤ 1.0 (10.23)
482 COMPOSITE COLUMNS AND STRUCTURAL SYSTEMS
Length effects are handled by the eurocode with a different approach than in
U.S. codes. In the AISC specification, length effects for composite columns are
accounted for by finding a reduced interaction diagram, similar to the approach
employed for a noncomposite steel column (Fig. 10.10). In Eurocode, on the other
hand, the slenderness parameter of the column is defined by
As Fy + 0.85Ac fc + Ar Fyr
λ= ≤ 2.0 (10.24)
Pe
(EI )eff π 2
Pe = = Ncr (10.25)
(KL)2
Pu ≤ κNpl,rd (10.26)
where Pu is the design axial load. The reduction factor κ is based on the European
strut curves (Fig. 10.12) and is calculated by
1
κ = fk − fk2 − ≤ 1.0 (10.27)
λ2
with
1 − α(λ − 0.2) + λ2
fk = (10.28)
2λ2
and α = 0.21 for concrete-filled circular and rectangular hollow sections (curve a);
α = 0.34 for completely or partly concrete-encased I-sections with bending
about the major axis of the profile (curve b); and α = 0.49 for completely or
partly concrete-encased I-section with bending about the minor axis of the profile
(curve c). Thus, the eurocode uses multiple-column curves specifically derived for
various composite sections.
DESIGN APPROACHES 483
The slenderness effects are then taken as the shaded region in Fig. 10.11, leaving
the usable flexural strength as the distance between the line joining κn Npl,rd and
point A in the failure envelope. Point κn Npl,rd accounts for the effects of variable
end moments and is given as
1−r
κn = κ with − 1 ≤ r ≤ 1 (10.29)
4
where r is the ratio of the end moments Mmin /Mmax . For slender columns with
small eccentricities the Eurocode also requires that the effect of creep be included
in the calculations by modifying the modulus of elasticity of the concrete.
484 COMPOSITE COLUMNS AND STRUCTURAL SYSTEMS
and
1.0 for bending moments from lateral loads in isolated (pinned) columns
β=
0.66 + 0.44r ≥ 0.44
The Eurocode also has checks for local buckling of the steel in compression
members. The limits for local buckling are based on a depth-to-thickness ratio of
the section. For rectangular hollow steel sections with h being the greater overall
dimension of the section,
h
≤ 52ε (10.31)
t
for circular hollow steel sections,
d
≤ 90ε2 (10.32)
t
and for partially encased I-sections,
b
≤ 44ε (10.33)
tf
with Fy in ksi. The 34.08 is the result of a conversion of units to ensure that ε is
nondimensional. These calculations can be ignored for a section entirely encased
in concrete, as the concrete is assumed to prevent local buckling from occurring.
The current International Code Council (ICC, 2005) code references FEMA (2003)
450, which recognizes the following different types of composite structural systems.
Because many of them have a counterpart in steel and concrete, the prefix “C-”
has been used to name the corresponding composite system.
STRUCTURAL SYSTEMS AND CONNECTIONS FOR COMPOSITE AND HYBRID STRUCTURES 485
Steel Plate-Reinforced Shear Walls Since the early 1980s, the concept of
utilizing steel plate shear walls has been popular (Thorburn et al., 1983). The con-
cept is similar to the use of plate girders in bridges, except that the main element
is vertical rather than horizontal. These systems have been used successfully as
retrofits in critical steel structures (e.g., hospitals), where access to the structure
was severely limited by the need to keep it operational during the retrofit construc-
tion. The system basically behaves as a CBF with the tension field action taking the
lateral loads. Composite steel shear walls, in which the steel plate is covered with
concrete and composite action activated by mechanical connectors, have been pos-
tulated as a system with better energy dissipation capacity. Another variation could
be a sandwich configuration where the space between two thin steel plates contain-
ing studs is filled with concrete. In this case, the steel plates act as the formwork and
could be welded directly to an existing steel frame. Great care is needed in connect-
ing the plates to the boundary elements because the shear wall is such an efficient
structural element that it can easily overstress the adjacent columns and beams.
The structural systems discussed above give a flavor of the many variations that
can be developed by combining composite elements. The stability design of many of
these systems has not been investigated extensively and thus the suggested design
procedures are conservative (FEMA 450, 2003). The design of connections in
composite construction has recently been reviewed by Leon and Zandonini (1992)
and Gourley et al. (2008).
10.9 SUMMARY
REFERENCES
ACI (2005), Building Code Requirements for Reinforced Concrete and Commentary, ACI
318–05, American Concrete Institute, Detroit, MI.
Aho, M. F. (1996), “A Database for Encased and Concrete-Filled Columns,” M.S. the-
sis, School of Civil and Environmental Engineering, Georgia Institute of Technology,
Atlanta, GA.
Aho, M. F., and Leon, R. T. (1997), “A Database for Encased and Concrete-Filled Columns,”
Report No. 97-01, Georgia Institute of Technology, School of Civil and Environmental
Engineering, Atlanta, GA.
REFERENCES 487
CEN (2004), Eurocode 4: Design of Composite Steel and Concrete Structures, Part 1–2, Gen-
eral Rules and Rules for Buildings, Comité Europée de Normalisation (CEN), European
Committee for Standardization, Brussels, Belgium.
Deierlein, G. G. (1995), “An Overview of the 1994 NEHRP Recommended Provisions for the
Seismic Design of Composite Structures,” Proc. Struct. Congr. XIII (Ed. M. Sanayaei),
Vol. 2, pp. 1305–1308.
Deierlein, G. G., and Leon, R. T. (1996), “Design Criteria for Composite Steel–Concrete
Structures: Current Status and Future Needs,” in ACI SP: Hybrid and Composite
Structures (Eds. B. Sharooz and G. Sabnis), American Concrete Institute, Farmington
Hius, MI.
Deierlein, G. G., Sheikh, T. M., Yura, J. A., and Jirsa, J. O. (1989), “Beam-Column Moment
Connections for Composite Frames, Part 2,” ASCE J. Struct. Eng., Vol. 115, No. ST11,
pp. 2877–2896.
Dekker, N. W., Kemp, A. R., and Trinchero, P. (1995), “Factors Influencing the Strength
of Continuous Composite Beams in Negative Bending,” J. Constr. Steel Res., Vol. 34,
Nos. 2–3, pp. 161–186.
Dobruszkes, A., and Piraprez, E. (1981), “Détermination de l’Adhérence Naturelle
Acierbéton dans le Cas de Poutres Mixtes Composées d’un Profilé Métallique Enrobe de
Béton,” Rep. MT 241, CRST, Brussels, Belgium.
Easterling, W. S., and Roddis, W. M. K. (Eds.) (1993), Composite Construction in Steel and
Concrete, Vol. 2, American Society of Civil Engineers, New York.
El-Tawil, S., Sanz-Picon, C. F., and Deierlein, G. G. (1993), “Evaluation of ACI 318 and
AISC (LRFD) Strength Provisions for Composite Beam-Columns,” J. Constr. Steel Res.,
Vol. 34, No. 1, pp. 103–123.
El-Tawil, S., Sanz-Picon, C. F., and Deierlein, G. G. (1995), “Evaluation of ACI 318
and AISC (LRFD) Strength Provisions for Composite Columns,” J. Constr. Steel Res.,
Vol. 34, pp. 103–123.
FEMA 450 (2003), NEHRP Recommended Provisions and Commentary for Seismic Regula-
tions for New Buildings and Other Structures. Federal Engineering Management Agency,
Washington, DC, 752 pp.
Fujimoto, T., Mukai, A., Makato, K., Tokiniya, H., and Fukumoto, T. (2004), “Behavior
of Concrete-Filled Steel-Tube Beam Columns,” J. Struct. Eng. ASCE , Vol. 130, No. 2,
pp. 189–202.
Furlong, R. W. (1968), “Design of Steel Encased Concrete Beam Columns,” ASCE J. Struct.
Div., Vol. 94, No. ST1, pp. 267–281.
Furlong, R. W. (1974), “Concrete Encased Steel Beam Columns: Design Tables,” ASCE J.
Struct. Div., Vol. 100, No. ST9, pp. 1865–1883.
Furlong, R. W. (1983), “Column Rules of ACI, SSLC, and LRFD Compared,” ASCE J.
Struct. Eng., Vol. 109, No. ST8, pp. 2375–2386.
Furlong, R. W. (1988), “Steel–Concrete Composite Columns: II,” in Steel–Concrete
Composite Structures (Ed. R. Narayanan), Elsevier Applied Sciences, New York,
pp. 195–220.
Goel, S. C., and Yamanuchi, H. (Eds.) (1993), “Proceedings of the, 1992 U.S.–Japan Work-
shop on Composite and Hybrid Structures,” Res. Rep. UMCEE 92-29, Department of
Civil and Environmental Engineering, University of Michigan, Ann Arbor, MI.
Gourley, B. C. and Hajjar, J. F. (1994), “Cyclic Non-Linear Analysis of Concrete-Filled
Beam Columns and Composite Frames,” Rep. No. ST-94-3, Department of Civil Engi-
neering, University of Minnesota, Minneapolis, MN.
REFERENCES 489
Gourley, B. C., Hajjar, J. F., and Schiller, P. H. (1995), “A Synopsis of Studies of the
Monotonic and Cyclic Behavior of Concrete-Filled Steel Tube Beam-Columns,” Rep.
No. ST-93–5, Department of Civil and Mineral Engineering, University of Minnesota,
Minneapolis, MI.
Gourley, B. C., Tort, C., Denavit, M. D., Schiller, P. H., and Hajjar, J. F. (2008),
“A Synopsis of Studies of the Monotonic and Cyclic Behavior of Concrete-Filled Steel
Tube Beam-Columns,” Report No. UILU-ENG-2008-1802, Newmark Structural Labora-
tory Report Series (ISSN, 1940-9826), Dept. of Civil and Env. Eng., Univ. of Illinois at
Urbana-Champaign, Urbana, II, Apr.
Griffis, L. G. (1986), “Some Design Considerations for Composite-Frame Structures,” AISC
Eng. J., Vol. 23, No. 2, pp. 59–64.
Griffis, L. G. (1992), “Composite Frame Construction.” in Constructional Steel Design (Eds.
P. J. Dowling et al.), Elsevier Applied Science, London, pp. 523–553.
Hajjar, J. F., and Gourley, B. C. (1996), “Representation of Concrete-Filled Steel Tube
Cross-Section Strength,” J. Struct. Eng. ASCE , Vol. 122, No. 11, pp. 1327–1336.
Hajjar, J. F., and Gourley, B. C. (1997), “A Cyclic Nonlinear Model for Concrete-Filled
Tubes. I. Formulation,” J. Struct. Eng. ASCE , Vol. 123, No. 6, pp. 736–744.
Hajjar, J. F., Gourley, B. C., and Olson, M. C. (1997), “A Cyclic Nonlinear Model
for Concrete-Filled Tubes. II. Verification,” J. Struct. Eng. ASCE , Vol. 123, No. 6,
pp. 745–754.
Hajjar, J. F., Hosain, M., Easterling, W. S., and Shahrooz, B. M. (2002). “Composite Con-
struction in Steel and Concrete IV,” Proceedings from the Composite Construction in
Steel and Concrete IV Conference, May 30–June 2, 2000, Banff, Alberta, Canada, ASCE,
Reston, VA.
Hajjar, J. F., Molodan, A., and Schiller, P. H. (1998), “A Distributed Plasticity Model for
Cyclic Analysis of Concrete-Filled Steel Tube Beam-Columns and Composite Frames,”
Eng. Struct., Vol. 20, Nos. 4–6, pp. 398–412.
Harries, K., Mitchell, D., Cook, W. D., and Redwood, R. G., (1993), “Seismic Response
of Steel Beams Coupling Concrete Walls,” ASCE J. Struct. Eng., Vol. 119, No. 12,
pp. 3611–3629.
ICC (2000), International Building Code, International Code Council, Inc., Falls
Church, VA.
Javor, T. (Ed.) (1994), Steel–Concrete Composite Structures, Proc. 3, EXPERTCENTRUM ,
Bratislava, Slovakia.
Johnson, R. P. (1997), “Statistical Calibration of Safety Factors for Encased Concrete
Columns,” in Composite Construction in Steel and Concrete, Vol. 3 (Eds. D. Buckner
and B. Shahrooz), American Society of Civil Engineers, New York.
Johnson, R. P., and Hope-McGill, M. (1972), “Semi-Rigid Joints in Composite Frames,”
Prelim. Rep., 9th Congr. IABSE, pp. 133–144.
Kato, B., and Tagami, J. (1985), “Beam-to-Column Connection of a Composite Structure,”
in Composite and Mixed Construction (Ed. C. Roeder), American Society of Civil Engi-
neers, New York, pp. 205–214.
Leon, R. T. (1990), “Semirigid Composite Construction,” J. Constr. Steel Res., Vol. 15,
No. 2, pp. 99–120.
Leon, R. T. (1994), “Composite Semi-Rigid Construction,” AISC Eng. J., Vol. 31, 2nd
quarter, pp. 57–67.
490 COMPOSITE COLUMNS AND STRUCTURAL SYSTEMS
Leon, R. T., and Bawa, S. (1990), “Performance of Large Composite Columns,” in Mixed
Structures, Proc IABSE Symp., Brussels, Vol. 50, IABSE, Zurich, pp. 179–184.
Leon, R. T., and Lange, J. (2006). “Composite Construction in Steel and Concrete V,”
Proceedings of the Fifth International Conference on Composite Construction in Steel and
Concrete, Kruger National Park, South Africa, July 18–23, 2004, ASCE, Reston, VA.
Leon, R. T., and Zandonini, R. (1992), “Composite Connections,” in Constructional Steel
Design (Eds. P. Dowling et al.), Elsevier Science Publishers, New York, pp. 501–520.
Liu, Z., and Goel, S. C. (1988), “Cyclic Load Behavior of Concrete-Filled Tubular Braces,”
ASCE J. Struct. Eng., Vol. 114, No. 7, pp. 1488–1506.
MacGregor, J. G. (1993), “Design of Slender Concrete Columns—Revisited,” ACI Struct.
J., Vol. 90, No. 3, pp. 302–309.
Mahin, S. A., and Bertero, V. V. (1977), RCCOLA: A Computer Program for R. C. Col-
umn Analysis: Users’ Manual and Documentation, Department of Civil Engineering,
University of California, Berkeley, CA.
Matsui, C., and Tsuda, K. (1987), “Strength and Behavior of Concrete-Filled Steel Square
Tubular Columns with Large Width-Thickness Ratios,” Proc. Pac. Conf. Earthquake
Eng., Vol. 2, Waimkei, New Zealand, pp. 1–9.
Minami, K. (1985), “Beam to Column Stress Transfer in Composite Structures,” in Com-
posite and Mixed Construction (Ed. C. Roeder), ASCE, New York, pp. 215–226.
Morino, S., Kawaguchi, J., Yazuzaki, C., and Kanazawa, S. (1993), “Behavior of
Concrete-Filled Steel Tubular Three-Dimensional Subassemblages,” in Composite Con-
struction in Steel and Concrete, Vol. 2 (Eds. W. S. Easterling and W. M. K. Roddis),
American Society of Civil Engineers, New York, pp. 726–741.
Morino, S., Uchida, Y., and Ozaki, M. (1988), “Experimental Study of the Behavior of SRC
Beam-Columns Subjected to Biaxial Bending,” in Composite Construction in Steel and
Concrete (Eds. D. Buckner and I. M. Viest), American Society of Civil Engineers, New
York, pp. 753–777.
Morishita, Y., and Tomii, M. (1982), “Experimental Studies on Bond Strength between
Square Steel Tube and Encased Concrete Core Under Cyclic Shearing Force and Constant
Loads,” Trans. Jpn. Concrete Inst., Vol. 4, pp. 115–122.
Nakai, H., Kurita, A., and Ichinose, L. H. (1991), “An Experimental Study on Creep of
Concrete Filled Steel Pipes,” Proc. 3rd Int. Conf. Steel–Concrete Compos. Struct (Ed.
M. Wakabayashi), Fukuoka, Japan, pp. 55–60.
Oehlers, D. J., and Bradford, M. A. (1995), Composite Steel and Concrete Structural Mem-
bers: Fundamental Behavior, Pergamon Press, Elmsford, NY.
Orito, Y., Sato, T., Tanaka, N., and Watanabe, Y. (1988), “Study of Unbonded Steel Tube
Concrete Structure,” in Composite Construction in Steel and Concrete (Eds. D. Buckner
and I. M. Viest), American Society of Civil Engineers, New York, pp. 786–804.
O’Shea, M. D., and Bridge, R. Q. (1996), “Circular Thin-Walled Tubes with High Strength
Concrete Infill,” in Composite Construction in Steel and Concrete, Vol. 3 (Eds. D. Buck-
ner and B. Shahrooz), American Society of Civil Engineers, New York.
Ricles, J. M., and Popov, E. P. (1989), “Composite Action in Eccentrically Braced Frames,”
ASCE J. Struct. Eng., Vol. 115, No. 8, pp. 2046–2066.
Roberts, E. H., and Yam, L. C. P. (1983), “Some Recent Methods for the Design of Steel,
Reinforced Concrete and Composite Steel–Concrete Columns in the UK,” ACI J.,
Vol. 80, No. 2, pp. 139–149.
REFERENCES 491
Robinson, H., and Naraine, K. S. (1988), “Slip and Uplift Effects in Composite Beams,”
in Composite Construction in Steel and Concrete (Eds. D. Buckner and I. M. Viest),
American Society of Civil Engineers, New York, pp. 487–497.
Roeder, C. W. (Ed.) (1985a), Composite and Mixed Construction, American Society of Civil
Engineers, New York.
Roeder, C. W. (1985b), “Bond Stress of Embedded Steel Shapes in Concrete,” in Composite
and Mixed Construction (Ed. C. Roeder), ASCE, New York, pp. 227–240.
Roeder, C.W., Cameron, B., and Brown, C.B. (1999), “Composite Action in Concrete Filled
Tubes,” J. Struct. Eng. ASCE , Vol. 125, No. 5, pp. 477–484.
Roik, K., and Bergmann, R. (1985), “Composite Columns: Design and Examples for Con-
struction,” in Composite and Mixed Construction (Ed. C. Roeder), ASCE, New York,
pp. 267–278.
Roik, K., and Bergmann, R. (1989), “Report on Eurocode 4: Clause 4.8 and 4.9—Composite
Columns,” EC4/6/89, Miniter für Raumordnung, Bauwesen, und Stadtgebau der Bun-
desrepublik Deutschland, RSII 1-6741028630, Bonn, Germany.
Roik, K., and Bergmann, R. (1992), “Composite Columns,” in Constructional Steel Design
(Eds. P. Dowling et al.), Elsevier Science Publishers, New York, pp. 443–470.
Sakino, K., Nakahara, H., Morino, S., and Nishiyama, I. (2004). “Behavior of Centrally
Loaded Concrete-Filled Steel-Tube Short Columns,” J. Struct. Eng. ASCE , Vol. 130,
No. 2, pp. 180–188.
Sakino, K., and Tomii, M. (1981), “Hysteretic Behavior of Concrete Filled Square
Steel Tubular Beam-Columns Failed in Flexure,” Trans. Jpn. Concrete Inst ., Vol. 3,
pp. 439–446.
Shahrooz, B. M., Remmetter, M. E., and Qin, F. (1993), “Seismic Design and Performance
of Composite Shear Walls,” ASCE J. Struct. Eng., Vol. 119, No. ST11, pp. 3291–3309.
Shakir-Khalil, H. (1988), “Steel–Concrete Composite Columns: I,” in Steel–Concrete
Composite Structures (Ed. R. Narayanan), Elsevier Applied Sciences, New York,
pp. 163–194.
Shakir-Khalil, H. (1991a), “Bond Strength in Concrete-Filled Steel Hollow Sections,”
in International Conference on Steel and Aluminum Structures, Elsevier Science,
pp. 157–168.
Shakir-Khalil, H. (1991b), “Tests on Concrete-filled Hollow Section Columns,” in Proceed-
ings of 3rd International Conference on Steel-Concrete Composite Structures (Ed. M.
Wakabayashi), Association for International Cooperation and Research in Steel-Concrete
Composite Structures, Fukuoha, Japan, pp. 89–95.
Shakir-Khalil, H. (1993a), “Pushout Strength of Concrete-Filled Steel Hollow Sections,”
Struct. Eng., Vol. 71, No. 3, pp. 230–233.
Shakir-Khalil, H. (1993b), “Resistance of Concrete-filled Steel Hollow Tubes to Pushout
Forces,” Struct. Eng., Vol. 71, No. 3, pp. 234–243.
Sheikh, T. M., Deierlein, G. G., Yura, J. A., and Jirsa, J. O. (1989), “Beam-Column Moment
Connections for Composite Frames, Part 1,” ASCE J. Struct. Div., Vol. 115, No. ST11,
pp. 2858–2876.
Talbot, A. N., and Lord, A. R. (1912), “Tests of Columns: An Investigation of the Value of
Concrete as Reinforcement for Structural Steel Columns,” Bull. 56, University of Illinois
Engineering Experiment Station, Champaign-Urbana, IL.
492 COMPOSITE COLUMNS AND STRUCTURAL SYSTEMS
Thornburn, L. J., Kulak, G. L., and Montgomery, C. J. (1983), “Analysis of Steel Plate Shear
Walls,” Struct. Eng. Rep. No. 107, University of Alberta, Edmonton, Alberta, Canada.
Tomii, M., and Sakino, K. (1979a), “Experimental Studies on the Ultimate Moment of
Concrete Filled Square Steel Tubular Beam-Columns,” Trans. Architect. Inst. Jpn., No.
275, pp. 55–63.
Tomii, M., and Sakino, K. (1979b), “Elasto-Plastic Behavior of Concrete Filled Square Steel
Tubular Beam-Columns,” Trans. Architect. Inst. Jpn., No. 280, pp. 111–120.
Tort, C., and Hajjar, J. F. (2007). “Reliability-Based Performance-Based Design of Rectan-
gular Concrete-Filled Steel Tube (RCFT) Members and Frames,” Structural Engineering
Report No. ST-07-1, Department of Civil Engineering, Institute of Technology, University
of Minnesota, Minneapolis, MN.
Varma, A. H., Ricles, J. M., Sause, R., Hull, B., in and Lu, L. W. (2000), “An Experimental
Evaluation of High Strength Square CFT Columns,” in ACI SP-196: Composite and
Hybrid Systems, (Eds. R. S. Aboutaha and J. M. Bracci), American Concrete Institute,
Farmington Hills, MI, pp. 51–86.
Varma, A. H., Ricles, J. M, Sause, R., and Lu, L. W. (2002), “Experimental Behavior of
High Strength Square Concrete Filled Steel Tube (CFT) Columns,” J. Struct. Eng. ASCE ,
Vol. 128, No. 3, pp. 309–318.
Varma, A. H., Ricles, J. M., Sause, R., and Ream, A. (2004), “Seismic Behavior and Design
of High Strength Square Concrete Filled Steel Tube Beam-Columns,” J. Struct Eng.
ASCE , Vol. 130, No. 2, pp. 169–179.
Varma, A. H., Sause, R., Ricles, J. M., and Qinggang, L. (2005), “Development and Vali-
dation of Fiber Models for High Strength Square CFT Beam-Columns,” ACI Struct. J.,
Vol. 102, No. 1, pp. 73–85.
Viest, I. M. Colaco, J. P., Furlong, R. W., Griffis, L. G., Leon, R. T., and Wyllie, L. A.
(1996), Composite Construction: Design for Buildings, ASCE-McGraw Hill, New York.
Virdi, K. S., and Dowling, P. J. (1973), “The Ultimate Strength of Composite Columns in
Biaxial Bending,” Proc. Inst. Civ. Eng., Part 2, Vol. 55, pp. 251–272.
Virdi, K. S., and Dowling, P. J. (1976), “A Unified Design Method for Composite Columns,”
IABSE Pub. 36, International Association for Bridge and Structural Engineering, IABSE,
Zurich Switzerland, pp. 165–1843.
Virdi, K. S., and Dowling, P. J. (1980), “Bond Strength in Concrete-Filled Steel Tubes,”
IABSE Per. 3/1980. pp. 125–139
Wakabayashi, M. (Ed.) (1991), Steel–Concrete Composite Structures, AICRSCCS, Fukuoka,
Japan.
Wium, J. A., and Lebet, J. P. (1990a), “Pushout Tests on Embedded Steel Plates,” Publ.
ICOM 240, Ecole Polytechnique Fédérale de Lausanne, Lausanne, Switzerland.
Wium, J. A., and Lebet, J. P. (1990b), “Test for the Application of Forces on Short Compos-
ite Columns,” Publ. ICOM 241, Ecole Polytechnique Fédérale de Lausanne, Lausanne,
Switzerland.
Yamanuchi, H., Mahin, S. A., Goel, S. C., and Nishiyama, I. (1993), “U.S.– Japan Coop-
erative Earthquake Research Program on Composite and Hybrid Structures,” Proc.,
1992 U.S.-Japan Workshop Compos. Hybrid Struct., U.S.-Japan Cooperative Research
Program.