Sunteți pe pagina 1din 1

BATTERY ROOM AIR FLOW CALCULATIONS

Battery Room Size (L*B*H) = (6.0 X 4.1 X 4.375) m

Battery Room Air Volume (L*B*H) = 107.6 m3

Extract Fan -01

Extract Fan-01 Air flow (Q) = 469L/Sec = 1688 m3/Hr

Quantity Of Air Flow (Q) = Room air Volume * Number of Air Changes per hour(ACH)

Q = V*ACH

Number of air changes per hour (ACH) = Quantity of air flow/(Room Air Volume)

ACH = Q/V = 1688/(107.6) =15.68

Extract Fan -02

Extract Fan-02 Air flow (Q) = 440L/Sec = 1584 m3/Hr

Quantity Of Air Flow (Q) = Room air Volume * Number of air changes per hour (ACH)

Q = V*ACH

Number of air changes per hour(ACH) = Quantity of air flow/(Room Air Volume)

ACH = Q/V = 1688/(107.6) =14.72