CHILLED WATER PIPING PRESSURE LOSS CALCULATION

Document No.: Pressure drop calculation for pressure drop of


Project name: VTB Tower
Project No.:
Date: 15/Apr/2019
Rev.: 00
By: Dang Hong Chuyen
Ref doc.:
- ASHRAE 2002. Chapter 35 - Piping design: Hazen -Williams equation
- Density of water 999.80 kg/m3
- Gravity factor: 9.81 m/s2

Water Pipe Velocity Pipe friction loss Fitting Loss DP =1/2*x.r.w2 Actual Equipment Total
flow size Friction Straight Pipe Elbow 90o Reducer Gate valve Check valve Y-strainer Flexible Joint Total head loss Pressure Loss
Piping
Section No. q DN w loss per meter pipe length Friction Q'ty x Dp Q'ty x Dp Q'ty x Dp Q'ty x Dp Q'ty x Dp Q'ty x Dp

(L/min) (mm) (m/s) l(Pa/m) (m) (kPa) (Nos) - (kPa) Nos - kPa (Nos) - (kPa) (Nos) - (kPa) (Nos) - (kPa) (Nos) - (kPa) (Nos) - (kPa) (kPa)

(4) -> CHWP-60 12,900 350 2.235 107.0 5.0 0.54 1 0.39 0.97 1 0.0 1 0 1 1 0.97 0 0 1.51

0.00
Total pressure loss(kPa): 1.51
Safety factor: 1.10
Pump head (kPa): 5.00
Pump head (mWC): 0.0 0.51