45 PLANTA EVAPORADORA
RESULTADOS Observaciones
1 2 3 4 5 6 7 8 9 10
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 10' 1/2" 6.64
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 15' 1/2" 7.30
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 20' 1/2" 7.82
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 25' 1/2" 8.29
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 10' 3/4" 8.12
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 15' 3/4" 8.93
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 20' 3/4" 9.56
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 25' 3/4" 10.13
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 10' 1" 8.32
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 15' 1" 9.15
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 20' 1" 9.79
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 25' 1" 10.38
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 10' 1 1/4" 8.35
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 15' 1 1/4" 9.19
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 20' 1 1/4" 9.83
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 25' 1 1/4" 10.42
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 10' 1 1/2" 9.95
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 15' 1 1/2" 10.95
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 20' 1 1/2" 11.71
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 25' 1 1/2" 12.41
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 10' 2" 13.27
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 15' 2" 14.6
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 20' 2" 15.62
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 25' 2" 16.56
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 10' 2 1/2" 18.53
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 15' 2 1/2" 20.38
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 20' 2 1/2" 21.81
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 25' 2 1/2" 23.12
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 10' 3" 24.48
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 15' 3" 26.93
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 20' 3" 28.81
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 25' 3" 30.54
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 10' 3 1/2" 25.97
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 15' 3 1/2" 28.57
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 20' 3 1/2" 30.57
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 25' 3 1/2" 32.4
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 10' 4 35.24
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 15' 4 38.76
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 20' 4 41.48
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 25' 4 43.97
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 10' 5 48.16
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 15' 5 52.98
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 20' 5 56.68
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 25' 5 60.09
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 10' 6 62.23
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 15' 6 68.45
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 20' 6 73.24
Galvanized Rigid Steel Conduit Concret Wall Concealed Installation 25' 6 77.64
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 10' 1/2" 6.64
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 15' 1/2" 7.30
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 20' 1/2" 7.82
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 25' 1/2" 8.29
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 10' 3/4" 8.12
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 15' 3/4" 8.93
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 20' 3/4" 9.56
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 25' 3/4" 10.13
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 10' 1" 8.32
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 15' 1" 9.15
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 20' 1" 9.79
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 25' 1" 10.38
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 10' 1 1/4" 8.35
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 15' 1 1/4" 9.19
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 20' 1 1/4" 9.83
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 25' 1 1/4" 10.42
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 10' 1 1/2" 9.95
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 15' 1 1/2" 10.95
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 20' 1 1/2" 11.71
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 25' 1 1/2" 12.41
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 10' 2" 13.27
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 15' 2" 14.6
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 20' 2" 15.62
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 25' 2" 16.56
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 10' 2 1/2" 18.53
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 15' 2 1/2" 20.38
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 20' 2 1/2" 21.81
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 25' 2 1/2" 23.12
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 10' 3" 24.48
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 15' 3" 26.93
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 20' 3" 28.81
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 25' 3" 30.54
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 10' 3 1/2" 25.97
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 15' 3 1/2" 28.57
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 20' 3 1/2" 30.57
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 25' 3 1/2" 32.4
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 10' 4 35.24
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 15' 4 38.76
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 20' 4 41.48
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 25' 4 43.97
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 10' 5 48.16
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 15' 5 52.98
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 20' 5 56.68
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 25' 5 60.09
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 10' 6 62.23
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 15' 6 68.45
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 20' 6 73.24
Galvanized Rigid Steel Conduit Concret Block Concealed Installation 25' 6 77.64
Galvanized Rigid Steel Conduit 1 1/4" Concret WallConcealed In15'
Gavlanized Rigid Steel Conduit Concret Block, Brick and Hollow Tile Concealed Installation)
ManHours per One Hundred Linear Feet
Size (Inches) 10' 15' 20' 25'
1/2" 6.64 7.30 7.82 8.29
3/4" 8.12 8.93 9.56 10.13
1" 8.32 9.15 9.79 10.38
1 1/4" 8.35 9.19 9.83 10.42
1 1/2" 9.95 10.95 11.71 12.41
2" 13.27 14.60 15.62 16.56
2 1/2" 18.53 20.38 21.81 23.12
3" 24.48 26.93 28.81 30.54
3 1/2" 25.97 28.57 30.57 32.40
4 35.24 38.76 41.48 43.97
5 48.16 52.98 56.68 60.09
6 62.23 68.45 73.24 77.64
Galvanized Rigid Steel Conduit Mounting, Cutting, Reaming and Threading.
(Walls and Ceiling Exposed Installation)
Size (Inches) Installation Cutting Ream and Thread Strap Supports
1/2" 0.03
3/4" 0.03
1" 0.03
1 1/4" 0.04
1 1/2" 0.04
2" 0.05
2 1/2" 0.05
3" 0.07
3 1/2" 0.09
4 0.12
5 0.18
6 0.23
Clamps Support knockouts
0.28
0.28
0.31
0.35
0.35
0.50
0.50
0.70
0.70
0.95
1.29
1.74
0.5
0.54 108%
0.56 104%
0.58 104%
2,08 20 25 20 30 25 35
3,31 25 30 25 35 30 40
5,26 30 40 35 50 40 55
8,37 40 60 50 70 55 80
13,3 55 80 65 95 75 105
21,2 70 105 85 125 95 140
26,7 85 120 100 145 110 165
33,6 95 140 115 170 130 190
42,4 110 165 130 195 150 220
53,5 125 195 150 230 170 260
67,4 145 225 175 265 195 300
85 165 260 200 310 225 350
107,2 195 300 230 360 260 405
126,7 215 340 255 405 290 455
151,8 240 375 285 445 320 505
177,3 250 420 310 505 350 570
202,7 280 455 335 545 380 615
253,2 320 515 380 620 430 700
303,6 355 575 420 690 475 780
354,7 385 630 460 755 520 855
379,5 400 655 475 785 535 885
405,4 410 680 490 815 555 920
456,0 435 730 520 870 585 985
506,7 455 780 545 935 615 1055
633,4 495 890 590 1065 665 1200
750,1 520 980 625 1175 705 1325
886,7 545 1070 650 1280 735 1455
1.013 560 1155 665 1385 750 1560
Caracteristicas Cable Superflex
AWG/MCM mm2 f Exterior kg/km AmpD AmpA
14 2.08 6.5 55 25 35
12 3.31 7.0 70 30 40
10 5.26 7.5 90 40 55
8 8.37 8.5 130 55 80
6 13.30 10.0 170 75 105
4 21.20 11.0 270 95 140
2 33.60 13.0 400 130 190
1 42.40 14.0 500 150 220
1/0 53.50 15.0 580 170 260
2/0 67.40 16.0 720 195 300
3/0 85.00 18.0 900 225 350
4/0 107.20 19.0 1,100 260 405
250 126.70 22.0 1,300 290 455
350 177.30 26.0 1,800 350 570
500 253.20 30.0 2,600 430 700
Tiempo de despeje de la falla t
Resistividad superficial del terreno Rho_s
Medicion de Resistividad de Terreno
Tension Aplicada V
Corriente Circulante I
Distancia entre P1 y C1 r1
Distancia entre P1 y C2 r2
Distancia entre P2 y C1 r3
Distancia entre P2 y C2 r4
24 C1 r3 P2
10
10 V
r1 r4
100 I
100
10 P1 r2 C2
83.78
2089.37 ohm-m
3.1415926536
300 mt
0.0107
0.8
25
25
2
3 mt
0.00795 mt
0.6 mt
8627 ohm-m
0.0107 mt
1013.425914
1000
1053.70365599
1000
166.25
172.86 t
164.05
26.8518279925
734.49 Ohm
17.25 Ohm
353.24
1.31
5.36
44.00
14.10
42.39
42.48
353.24
36.99
98478707 sergio parra
RESISTIVIDAD DEL TERRENO