1.1 Scope
This specification covers the requirements for design,
engineering, manufacture, assembly, stage testing, inspection,
testing before supply, packing and loading at works of 33kV
Indoor Switchgear along with its accessories and auxiliary
equipments / instruments etc. and erection, testing &
commissioning as mentioned in this section and in various other
sections of this specification for 33 KV switchgear.
The scope shall encompass and include all the activities listed
above.
3 Number of Phases 3
Bill of Quantities
Three phase, 33kV Indoor Switchgear
One no of 33kV metal clad switchgear,1600A,25kA rms for 1 sec
suitable for 110V DC control supply with following
feeder/equipment for each 33kV Metal clad switchgear.
i) Incomer feeder : 1600A, 2nos.
ii) Outgoing feeder : 1600A, 2 nos.
iii) Spare incomer feeder : 1600A, 1 no.
iv) Spare Outgoing feeder : 1600A, 1 no.
v) Bus Coupler : 1600A, 1 no.
vi) Bus VT : 2 nos.
Earthing Truck
Earthing arrangement for breaker/NT trucks shall be provided
either through integral earth switch separate earthing truck. In
case of latter arrangement, one set of different types of earthing
33KV SWITCHGEAR SPECIFICATIONS
trucks per switchboard shall be supplied.
Recommended Spares
Supplier to propose the list of recommended spares for 3 years of
trouble free operation.
Type Tests, Routine Tests and Acceptance Test:
Bidder shall submit valid reports of type test carried out with in
ten years. These reports should have been conducted as per
technical specification and relevant IS/IEC. In case of more than
ten year old type test reports OR invalid type test reports are
submitted, the tests shall be conducted free of charge. No
separate type test charges shall be paid.
All the Routine and Acceptance test shall be carried out as per
relevant standards.
2 Equipment Specification
2.1 Codes and Standards
Switchgear and Breakers IEC 60298, IEC 60056, IS 13118
2.2 List of fitments on various modules
The various feeders and bus VT panel shall at least contain
following fitments:
3 400-200/1A PS Differential
Protection
V3 VT X X X VT
X X X
9. Current Transformer - 1 no