1- Determine the C.T. ratio current and the current at operation coil of
differential relay.
2- Determine the percentage differential relay slope and the pickup setting.
Solution: -
S = √3 × V × I
Ia= 63 × 10^3 / (√3 × 132∠0) = (275.55 + 0.0) A
Ib= 63 × 10^3 / (√3 × 132∠120) = (-137.77- j238.63) A
Ic= 63 × 10^3 / (√3 × 132∠-120) =(-137.77+j238.63) A
The CTs on the delta side of the power transformer are to be connected in
wye.
For 132 kv side, the current I132= (63 × 10^3/√3 ×132) =275.55 A
The relay taps can be used to reduce this magnitude mismatch further.
Now calculate the secondary current for both side of power transformer
Appendix A A.3
Phase A:
(Ia sec.− Ib sec.) − Iad sec.= [(4.5925 + j0.0) −(−2.296 –j3.973)] −(3.97725
j2.296) = (6.8885 + j3.973) − (3.97725 - j2.296)
=(2.91125+j6.269)
Phase B:
= (3.9773 – j5.65)
Phase C:
(Ic sec. − Ia sec.) − Icd sec. = [(−2.296 + j3.973) − (4.5925 + j0.0)] − (0+
j4.5924) = (−6.8885+ j3.973) + (0+ j4.5925)
= (− 6.8885− j0.6195) .
Appendix A A.4
6.8885 + j 3.973
2.91125 + j 6.269
0 – j 7.9463
3.9773 – j 5.65
- 6.8885 + j 3.973
- 6.8885 – j 0.6195
2-We have the following data from name plate of transformer in Figure
(A.3)
ILV=1.088× 4.592 = 5
I 1102.214
( FLA −HV ) ( )
TRMIN 3.6
IHV= × CTR CFLV = × 1.089 = 5.55699A
CTRHv 60
I 0.55699
S =SLOPE= DIFF = =0.1055=10.55 %
ITOT 5.278