Documente Academic
Documente Profesional
Documente Cultură
No part of the manual is to be copied or reproduced in any form without the express agreement of
Integrated Environmental Solutions Limited.
1 Introduction ...............................................................................................................................5
2 ASHRAE Loads ............................................................................................................................6
2.1 Internal Gain Inclusion and Saturation .................................................................................6
2.2 Diversity Factors ..................................................................................................................8
2.3 Design Day Profiles ............................................................................................................ 10
3 Reporting New Variables .......................................................................................................... 12
3.1 Duct Leakage ..................................................................................................................... 12
3.2 Fan Configuration .............................................................................................................. 13
4 Generating Loads Reports ......................................................................................................... 14
4.1 Select results file................................................................................................................ 16
4.2 Select report sections to generate ...................................................................................... 16
4.3 Report generator settings .................................................................................................. 17
4.3.1 Select report sections to generate ............................................................................................................ 17
4.3.2 Oversizing .................................................................................................................................................. 18
4.4 HTML Reports .................................................................................................................... 20
4.5 Content Manager ............................................................................................................... 21
5 Room and Zone Loads Reports .................................................................................................. 23
5.1 Project and Climate ........................................................................................................... 23
5.2 Space Loads and Ventilation .............................................................................................. 27
5.3 Zone and Room Loads Reports ........................................................................................... 31
5.3.1 Cooling Zone/Room Peak .......................................................................................................................... 35
5.3.2 Heating Zone/Room Peak .......................................................................................................................... 38
5.3.3 Cooling Summary ....................................................................................................................................... 39
5.3.4 Heating Summary ...................................................................................................................................... 40
5.3.5 Areas & Thermal Transmittance ................................................................................................................ 40
5.3.6 Temperatures & Setpoints ......................................................................................................................... 42
5.3.7 Airflow ....................................................................................................................................................... 44
5.3.8 Checks ........................................................................................................................................................ 45
6 HVAC Loads and Sizing Reports ................................................................................................. 47
6.1 Project and Climate ........................................................................................................... 48
6.2 Plant Loops and Equipment ............................................................................................... 51
6.3 Space Loads and Ventilation .............................................................................................. 55
6.4 Space Conditioning Loads Reports...................................................................................... 59
6.4.1 Cooling Coil Peak ....................................................................................................................................... 64
6.4.2 Cooling System/Zone/Room Peak ............................................................................................................. 70
6.4.3 Heating Coil Peak ....................................................................................................................................... 71
6.4.4 Cooling Coils and Room Units .................................................................................................................... 72
6.4.5 Heating Coils and Room Units ................................................................................................................... 73
6.4.6 Areas .......................................................................................................................................................... 74
6.4.7 Temperatures ............................................................................................................................................ 75
E: Prototype Systems
System types and common features of Prototype Systems in the HVAC Systems Library
VE 2017 ApacheHVAC User Guide Part F: Loads Analysis and Reporting Tools iv
1 Introduction
For VE 2017 the loads reporting structure has been overhauled and new functionality has been added to
allow for more user control over loads runs.
To enhance the load runs, ASHRAE Loads now supports flexible user control and differentiation between
Room & Zone Loads and System Loads. The following can be independently determined for the different
types of loads analyses, with settings for each being retained by the software:
Section 2 of this user guide discusses the details of these load run options and settings.
As well as improvements to the loads runs, functionality has also been added which allows new variables
to be reported i.e. duct leakage and fan configuration. These new features give further insight into the
impact of system sizing runs, which had not been previously possible with the VE, see Section 3.
Finally, a new reporting structure provides new report types and uses a single page PDF format, which
allows the user to quickly interrogate their room, zone, and system loads run at different levels easily and
effectively. This new format also allows reports to be easily shared and printed if needed, see Section 4 and
Section 5.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 5
2 ASHRAE Loads
ASHRAE loads includes flexible user control settings, which can be independently configured for Room &
Zone Loads and System Loads. The new functionality is detailed in the following sections.
Figure 2-1: ASHRAE Room and Apache System loads dialog with the option to include internal gains for the
heating loads engaged
Once internal gains are included (optional for heating loads, always included for cooling loads) then the
user has the ability to set saturation conditions for these gains. Here we will discuss the ability to saturate
internal gains both for heating and cooling loads runs.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 6
Figure 2-2: ASHRAE Room and Apache System loads dialog with the option to saturate internal gains profiles
for peak heating and cooling loads
Yes
This interprets all internal gain profile values that are greater than zero as being equal to 1.0
(100%) during sizing runs. However, this only occurs if the appropriate setting has been engaged
in the internal gain either through building template manager or via space data, see Figure 2-3.
The ‘Allow profiles to saturate for loads analysis?’ is checked by default.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 7
Figure 2-3: Internal gains dialog, accessed from the Building Template Manager, with the option to allow
profile saturation for loads analysis engaged
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 8
Figure 2-4: Internal gains dialog, accessed from the Building Template Manager, with the Diversity factor
set to 0.8 for the selected lighting gain
This option is available for both heating and cooling loads calculations. By default, diversity factors are excluded
for Room & Zone Loads and included for System Loads.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 9
Figure 2-5: ApacheHVAC System loads and sizing dialog with the Diversity Factors not applied to internal
gains for heating loads, but applied to internal gains for cooling loads
Figure 2-6: Sample heating & cooling design day profiles shown as part of a weekly profile in ApPro
These design day profiles are the default reference in the Room & Zone loads and System Loads dialogs. By
unchecking the “Default” box in the loads dialog for heating and/or cooling loads, users can select a day of
the week for use in load calculation runs in place of the design day profiles if desired.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 10
Figure 2-7: ASHRAE ApacheHVAC Room and HVAC Zone Loads dialog with the default selection of heating
& cooling design day profiles shown
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 11
3 Reporting New Variables
In order to provide a full and informative report, new functionality has been added into the VE to cater for
new variables. These are detailed as follows:
Figure 3-1: Duct thermal properties dialog shown with 10% of airflow leaking into the zone where the
component is located.
See ApacheHVAC User Guide part B for more information about the Ductwork thermal properties
component.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 12
3.2 Fan Configuration
The loads reports are now able to report the fan location relative to the AHU cooling coil. The ‘Fan
Configuration’ is reported in multiple locations in the system loads reports see Section 5 for more
information. The following terminology is used in the reports:
For any system wherein either one or both of the two required links (AHU Cooling Coil and Supply fan) is
not present or the flow-path node configuration makes it impossible to determine the relative location of
these two components, the Fan configuration row in the report will read “undetermined”.
Further details about the fan component can be found in ApacheHVAC User Guide part B.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 13
4 Generating Loads Reports
The ‘Generate loads and sizing reports’ dialog is available from the following locations:
ASHRAE Loads dialog
ApacheHVAC toolbar button
VistaPro (selecting a .clg, .htg, .cln, or .htn file in VistaPro, or selecting multiple files and clicking
“Room and Zone Loads / System Loads and Sizing for ApacheHVAC” button)
Selected navigators (PRM and Prototype system sizing)
Figure 4-1: Generate loads and sizing reports dialog access within the ASHRAE Loads dialog
Figure 4-2: Generate loads and sizing reports dialog accessed from the ApacheHVAC toolbar
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 14
Figure 4-3: Generate loads and sizing reports dialog access within VistaPro
Figure 4-4: Generate loads and sizing reports dialog within the VE, shown with a pair of .clg and .cln files
selected in VistaPro
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 15
Note that system level sizing using ASHRAE Loads analysis must be completed to provide the .cln and .htn
results files necessary for generating system loads reports. This can be done via ApacheHVAC, the 90.1 PRM
Navigator, or directly from the ASHRAE Loads dialog.
Zone loads
A single page report is presented for each zone within the selected results file. This page shows
a detailed breakdown of each zone in terms of peak heating & cooling loads, as well as displaying
ancillary information like temperatures, airflows, engineering checks etc. based on the Room &
Zone Loads run. This selection will be greyed out if HVAC zones do not exist in the project.
Further details can be found in Section 5.3.
Room loads
Similar to the zone loads report, this page shows the peak heating & cooling loads at a room
level. Further details can be found in Section 5.3.
The HVAC Loads & Sizing reports are presented as a series of single page PDFs broken down over the
following six types:
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 16
Plant loops & equipment
This report presents data for each active plant loop and associated equipment in a series of
frames. Depending on the amount of active loops, this may flow across multiple pages. Further
details can be found in Section 6.2.
System loads
A single page report is presented for each system within the selected results file. This page
shows a detailed breakdown of each system in terms of peak coil performance as well as
displaying ancillary information like temperatures, airflow, engineering checks etc. based on the
System Loads run. Further details can be found in Section 6.4.
The user can select which reports are generated by checking or unchecking each report. By default, no
reports are included.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 17
Figure 4-5: Peak Time for Loads Reporting dialog where user can select relevant peaking device to
determine peak time for loads reporting
If the results file has more than one HVAC system then these are listed and are individually selectable. Once
the system is selected the dialog will auto select the most appropriate heating and cooling peaking device
based on the system type and configuration e.g. in this case the system is 07a VAV with Reheat and the
software has auto selected the AHU cooling coil and the Zone reheat coils as the relevant peaking devices.
These selections can be overridden by the user by simply selecting from the appropriate dropdown for each
load report type (system/zone/room).
It should be noted that room units cannot currently be selected as a peaking device.
4.3.2 Oversizing
A dropdown selector has been provided to allow the user to determine, at the time of report generation,
whether the reported values will include the application of oversizing factors. For coils and equipment, this
applies to the oversizing factors for each of these items within the ApacheHVAC interface.
In the case of zone loads, the inclusion of oversizing factors reports values for zone cooling loads and zone
heating loads in the Space loads and ventilation report after the application of oversizing factors set for
each zone on the Zone Loads & Supply Airflows tab of the System Parameters dialog in ApacheHVAC. When
Room components are used (rather than Zone components) in ApacheHVAC, each Room is equivalent to
an HVAC Zone. When this is true, the loads for Rooms on each system within the Space loads and Ventilation
report are similarly affected.
This does not affect the contributing loads on the detailed Room Loads and Zone Loads reports.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 18
Figure 4-6: Generate system loads and sizing reports dialog with option to include or exclude oversizing
factors for coils, equipment, and zone loads highlighted
The inclusion/exclusion of oversizing factors has the following impact on the different report types:
Project and Climate
Regardless of the toggle, the project cooling and heating loads are coincident peak values for all
conditioned spaces without oversizing.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 19
Space loads and ventilation
Zone loads for cooling and heating are each coincident peak values with respect to constituent
rooms with/without oversizing factors applied. Zone airflows are design values that include
oversizing and other influences as set for individual zones in System Parameters.
Dynamic notes have been added to each report to reflect the user selection in this dialog.
Figure 4-7: Generate system loads and sizing reports dialog with options for HTML reports highlighted
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 20
4.5 Content Manager
When the user selection is complete, the selected reports can be generated by clicking the ‘OK’ button. The
PDF containing these reports will be generated and has the same name as the .clg, .htg, .cln, and .htn files
from the Loads run. It is saved to the project scripts folder and is added to content manager for future
viewing.
Figure 4-8: Content Manager alert that appears following the generation of any loads reports
Content manager is the reports repository in the VE and can be accessed via a popup after the report
generation process is complete as shown above or via the tools menu at anytime, as well as accessed from
some navigators.
Content manager lists the available reports on the left hand side frame and displays the contents on the
right hand side. Reports can be fully investigated, filtered, deleted, or opened externally in a local PDF
viewer.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 21
Figure 4-9: Content manager and PDF viewer showing an example loads report page
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 22
5 Room and Zone Loads Reports
Four report types are available for loads and sizing:
Project and Climate
Space Loads and Ventilation
Zone Loads
Room Loads
These new reports types are based around a single page PDF format, with report pages organized according
to a linear scheme. This means that, where applicable, the information pertaining to the building (as is the
case in the Project and Climate report) or a zone or room (as it the case for the loads reports) are contained
on a single page. This makes the interrogation of the reports quick, easy and effective.
In the case of the Space Loads and Ventilation report the report may overlap onto multiple pages depending
on the size of the project.
The header within each report references the report type (left hand side), the project name (center) and
the VE version (right hand side). The following reports have additional information in the header:
In each report the notes to the right hand side of the footer contains the following information:
Results file name
Date and time of generation
Reference to the report type
Page number relative to the total pages for that report type
Notes specific to the report type are contained on the left hand side of the footer.
For all reports where data is not available or applicable a dash (-) is used.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 23
project loads summary. It is a single page report generated for each results file. It contains the following six
frames:
Model Data
Location Data
Design Weather Data
Heating Calculation Data
Cooling Calculation Data
Project Loads Summary
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 24
Model Data:
The model data frame contains the following information:
Location Data:
The location data frame contains the following information:
Data label Data source
Location Taken from the ‘Location & Site Data’ tab in ApLocate
Latitude Taken from the ‘Location & Site Data’ tab in ApLocate
Longitude Taken from the ‘Location & Site Data’ tab in ApLocate
Altitude Taken from the ‘Location & Site Data’ tab in ApLocate
Time Zone Taken from the ‘Location & Site Data’ tab in ApLocate
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 25
Design Weather Data:
The design weather data frame contains the following information:
Data label Data source
Source Taken from the ‘Design Weather Data’ tab in ApLocate
Monthly percentile - Taken from the ‘Design Weather Data’ tab in ApLocate
heating
Monthly percentile - Taken from the ‘Design Weather Data’ tab in ApLocate
cooling
Barometric pressure This is atmospheric pressure taken from the design
weather data
Air density Taken from the ‘Location & Site Data’ tab in ApLocate.
This is one of the following:
Standard value which is the same for all locations
(default)
Custom value which can be entered by the user
Derived value. Here the user can enter elevation and
reference dry bulb and relative humidity values to
derive the air density
Air specific heat Constant value of 1019J/kgK in SI and 0.7886 Btu/lb·°F in
IP
Density-spec heat Product of air density and specific heat
product
Summer Ground Taken from the ‘Location & Site Data’ tab in ApLocate
reflectance
Winter Ground Taken from the ‘Location & Site Data’ tab in ApLocate
reflectance
Carbon dioxide Taken from the ‘Location & Site Data’ tab in ApLocate
(ambient)
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 26
Heating Calculation Data:
The heating calculation data frame contains the following information:
Data label Data source
Results file Name of associated .htg file
Calculated Date and time of calculation
Profile Month Taken from Apache System Loads settings
Outdoor winter design Taken from the ‘Design Weather Data’ tab in ApLocate
temp
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 27
System Loads in this report are the sum of peak values from the Room & Zone loads analysis run––i.e.,
before system sizing has been performed.
One report is shown per system with the system name in the header. In the case of PTAC and Single Zone
systems the name also includes a layer number for easier cross reference.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 28
System Level:
The following information is provided for the system:
Data label Data source
Sensible Cooling Load Sum of peak values from the Room & Zone Loads run for
all zones on the system
Latent Cooling Load Sum of peak values from the Room & Zone Loads run for
all zones on the system
Total Cooling load (also Sum of the above
provided per unit floor
area)
Cooling Airflow (also Sum of peak values from the Room & Zone Loads run at
provided per unit floor the time of peak cooling load
area)
Heating load (also Sum of peak values from the Room & Zone Loads run for
provided per unit floor all zones on the system
area)
Heating Airflow (also Sum of peak values from the Room & Zone Loads run at
provided per unit floor the time of peak heating load
area)
Outdoor Airflow Req. This is system minimum outdoor ventilation requirement
(also provided per unit before considering the possibility of a greater requirement
floor area) for outside air to make up for total system exhaust airflow
and is equivalent to Vot in the System Parameters UI
Min OA Airflow (also Not populated when System loads have not been
provided per unit floor calculated
area)
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 29
Zone Level:
The following information is provided for each zone served by the system:
Data label Data source
Sensible Cooling Load Coincident peak value from the Room & Zone Loads run
as recorded in the System Parameters dialog, subject to
user edit, for all rooms in the zone
Latent Cooling Load Coincident peak value from the Room & Zone Loads run
as recorded in the System Parameters dialog, subject to
user edit for all rooms in the zone
Total Cooling load (also Sum of the above
provided per unit floor
area)
Cooling Airflow (also The Zone Cooling Max Airflow from the System
provided per unit floor Parameters UI
area)
Heating load (also Coincident peak value from the Room & Zone Loads run
provided per unit floor as recorded in the System Parameters dialog, subject to
area) user edit for all rooms in the zone
Heating Airflow (also The Zone Heating Max Airflow from the System
provided per unit floor Parameters UI
area)
Outdoor Airflow Req. Zone Ventilation Max/Total Required from the System
(also provided per unit Parameters UI
floor area)
Min OA Airflow (also Not populated when System loads have not been
provided per unit floor calculated
area)
Figure 5-3: Zone Airflow Distribution table showing a system 7a with completed system sizing and user edits
(orange text) and a system 5b with completed room & zone level sizing, but without completed system sizing
(blue text). All autosized values appear in green text.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 30
Room Level:
The following information is provided for each room served by the system:
Data label Data source
Sensible Cooling Load Peak value from the Room & Zone Loads run as recorded
in the System Parameters dialog, subject to user edit for
the room
Latent Cooling Load Peak value from the Room & Zone Loads run as recorded
in the System Parameters dialog, subject to user edit for
the room
Total Cooling load (also Sum of the above
provided per unit floor
area)
Cooling Airflow (also The Zone Cooling Max Airflow from the System
provided per unit floor Parameters UI multiplied by the room airflow apportioning
area) factor (%) as per the Zone Airflow Distribution table.
Heating load (also Peak value from the Room & Zone Loads run for the room
provided per unit floor
area)
Heating Airflow (also The Zone Heating Max Airflow from the System
provided per unit floor Parameters UI multiplied by the room airflow apportioning
area) factor (%) as per the Zone Airflow Distribution table
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 31
Cooling
Cooling Peak
This is the breakdown of all the gains and losses contributing to the peak zone or room load.
Cooling Summary
This shows peak load information of the room or zone
Heating
Heating Peak
This is the breakdown of all the gains and losses contributing to the peak zone or room load.
Heating Summary
This shows peak load information of the room or zone
Supplementary information
Areas & Thermal Transmittance
Areas of components of the room or zone, with area-weighted U-values shown
Temperatures & Setpoints
Zone or room temperatures and setpoints
Airflow
Zone or room airflows (only infiltration information will be displayed if an ApacheHVAC file is
not associated with the Zone & Room Loads run).
Checks
Engineering checks relevant to the zone or room accordingly
The following images show examples of zone and room loads reports.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 32
Figure 5-4: Zone Loads report page
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 33
Figure 5-5: Room Loads report page
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 34
5.3.1 Cooling Zone/Room Peak
Figure 5-6: Cooling Peak section of Zone and Room Loads report pages
This frame itemizes gains contributing to the peak cooling load in a room or zone. The name of this frame
is dynamic and will update depending on whether a room or zone load report is generated.
This frame is broken down across the series of rows and columns, which are detailed as follows:
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 35
Rows (reported gain classes):
Envelope Gains/Losses
These are the gains/losses associated with the envelope e.g. external walls, roofs, solar,
ventilation associated with the envelope, etc.
Internal Building Gains/Losses
These the gains/losses associated with the internal structures
Internal Gains
These the gains/losses associated with internal contributions within the room/zone e.g. lights,
people, equipment
Columns:
Zone/Room Sensible/Latent
These are the gains/losses associated with the room or zone itself
Net Value
These are the gains/losses that directly contribute to the peak load
Per Floor Area
Displays, for each row, the value in the adjacent ‘Net Value’ column expressed per floor area of
the reported room or zone
Percent of total
Displays, for each row, the value in the ‘Net Value’ column expressed as a percentage of the
total appearing at the bottom of that column (or a dash if the ‘Net Value’ column contains a
dash).
The time of peak load is shown at the top of this frame along with the outside air dry bulb (DB), outside air
wet bulb (WB) and the outside air relative humidity (RH) at that time.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 36
Envelope Gains/Losses:
Data label Data source
External Walls Conduction gain - external wall from the .clg file
Roofs Conduction gain – roof from the .clg file
Ground/Exposed Floors Conduction gain - ground floor from the .clg file
External Doors Conduction gain – external doors from the .clg file
Windows Conduction Conduction gain - external glazing from the .clg file
Skylight Conduction Conduction gain – rooflights from the .clg file
Solar Solar gain from the .clg file
Infiltration Infiltration gain from the .clg file
Nat/Aux Vent Natural vent gain + Aux mech vent gain from the .clg file
Internal Gains:
Data label Data source
Lights Lighting gain from the .clg file
People People gain from the .clg file
Misc,Computers,Equip Equipment gain from the .clg file
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 37
5.3.2 Heating Zone/Room Peak
Figure 5-7: Heating Peak section of Zone and Room Loads report pages
This section itemizes gains (reported gain classes) contributing to the peak heating load in the room or zone.
As with the cooing peak, this determines the wording of the header.
The derivations of entries in this part of the report (under the headings ‘Room’ or ‘Zone’ and ‘Net Total’)
follow the same procedures as those in the cooling room or zone peak section, with the following
exceptions:
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 38
Inputs are taken from the .htg file rather than the .clg file.
So long as the ‘Default’ box is checked in the Heating Loads section of the ASHRAE Loads dialog,
the ‘Time of peak’ on the report shall display ‘Heating Design’.
The column for Latent Load is not relevant and therefore is omitted
Figure 5-8: Cooling Summary section of Room and Zone Loads report pages
This frame summarizes the peak cooling load values for the room or zone. Details of reported values are as
follows:
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 39
5.3.4 Heating Summary
Figure 5-9: Heating Summary section of Room and Zone Loads report pages
This frame summarizes the peak heating load values for the room or zone. Details of reported values are as
follows:
Data label Data source
Sensible heating load Sensible cooling load from the *.htg file
(Btu/h)
Design zone air temp for Taken from the System Parameters dialog to reflect the air
Supply Airflow temperature used for calculating Design Supply Airflow; A
calculation (°F/°C) dash will appear where Design Supply Airflow is not
calculated because an ApacheHVAC file was not
associated with the Room & Zone Loads calculation
Figure 5-10: Areas & Thermal Transmittance section of Zone & Room Loads report pages
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 40
This frame details the gross surface areas of the zones or rooms. The frame also outlines the glazing area in
the relevant surfaces and shows this as a percentage. This frame is broken down into rows of external and
internal areas, across the series columns, which are detailed as follows:
Columns:
Total Area
The area of the surface, for each row, for the relevant room or zone
Glazing
The area of the surface, for each row, that is glazed for the relevant room or zone
Glazing %
Displays, for each row, the value in the adjacent ‘Glazing’ column expressed as a percentage of
the total area
U-value
Displays, for each row, the area-weighted U-value for the relevant room or zone
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 41
5.3.6 Temperatures & Setpoints
Figure 5-11: Temperatures & Setpoints section of Zone Loads report pages
This frame reports relevant temperatures at zone and room level, in columns for cooling and heating,
detailed as follows:
Zone level:
Data label Data source
Supply air (design) This is the zone level design temperature and is obtained
from the system parameters UI for heating and cooling
(‘Zone loads & airflows tab’ - cooling and heating design
zone air temperatures)
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 42
Room level:
Data label Data source
Supply air (design) This is the room level design temperature and is obtained
from the system parameters UI for heating and cooling
(‘Room loads & airflows tab’ - cooling and heating design
room air temperatures)
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 43
5.3.7 Airflow
Figure 5-12: Airflow section of Room & Zone Loads report pages
This frame reports relevant airflows at zone and room level as detailed below:
Note, for rooms in zones the zone flow is distributed among the rooms as per the proportioning in the zone
airflow distribution table (ZAD)
Data label Data source
Supply (design) This is the room level design airflow and is obtained from
the system parameters UI for heating and cooling. (‘Zone
loads & Supply Airflows tab’)
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 44
5.3.8 Checks
Figure 5-13: Checks section of Room & Zone Loads report pages
This frame provides a series of engineering checks, which can be used to verify performance at zone and
room level.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 45
Outdoor air cfm/ft2 The outdoor air flow is taken from the Zone Airflow Distribution
table (ZAD) (ventilation airflow) and along with floor area is used
to calculate the required values.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 46
6 HVAC Loads and Sizing Reports
Six report types are available for loads and sizing:
Project and Climate
Plant Loops and Equipment
Space Loads and Ventilation
System Loads
Zone Conditioning Loads
Room Conditioning Loads
These new reports types are based around a single page PDF format, with report pages organized according
to a linear scheme. This means that, where applicable, the information pertaining to the building (as is the
case in the Project and Climate report) or a system, zone or room (as it the case for the loads reports) are
contained on a single page. This makes the interrogation of the reports quick, easy and effective.
In the case of the Loops & Equipment report or the Space Loads and Ventilation report the report may
overlap onto multiple pages depending on the size of the project.
The header within each report references the report type (left hand side), the project name (center) and
the VE version (right hand side). The following reports have additional information in the header:
In each report the notes to the right hand side of the footer contains the following information:
Results file name
Date and time of generation
Reference to the report type
Page number relative to the total pages for that report type
Notes specific to the report type are contained on the left hand side of the footer.
For all reports where data is not available or applicable a dash (-) is used.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 47
6.1 Project and Climate
The project and climate report is the first report to be displayed unless it is unchecked. It shows a
breakdown of model, location, weather and calculation data for the selected results file as well as giving a
project loads summary. It is a single page report generated for each results file. It contains the following six
frames:
Model Data
Location Data
Design Weather Data
Cooling Calculation Data
Heating Calculation Data
Project Loads Summary
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 48
Model Data:
The model data frame contains the following information:
Location Data:
The location data frame contains the following information:
Data label Data source
Location Taken from the ‘location & Site Data’ tab in ApLocate
Latitude Taken from the ‘location & Site Data’ tab in ApLocate
Longitude Taken from the ‘location & Site Data’ tab in ApLocate
Altitude Taken from the ‘location & Site Data’ tab in ApLocate
Time Zone Taken from the ‘location & Site Data’ tab in ApLocate
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 49
Design Weather Data:
The design weather data frame contains the following information:
Data label Data source
Source Taken from the ‘Design Weather Data’ tab in ApLocate
Monthly percentile - Taken from the ‘Design Weather Data’ tab in ApLocate
heating
Monthly percentile - Taken from the ‘Design Weather Data’ tab in ApLocate
cooling
Barometric pressure This is atmospheric pressure taken from the design
weather data
Air density Taken from the ‘location & Site Data’ tab in ApLocate.
This is one of the following:
Standard value which is the same for all locations
(default)
Custom value which can be entered by the user
Derived value. Here the user can enter elevation and
reference dry bulb and relative humidity values to
derive the air density
Air specific heat Constant value of 1019J/kgK in SI and 0.7886 Btu/lb·°F in
IP
Density-spec heat Product of air density and specific heat
product
Summer Ground Taken from the ‘location & Site Data’ tab in ApLocate
reflectance
Winter Ground Taken from the ‘location & Site Data’ tab in ApLocate
reflectance
Carbon dioxide Taken from the ‘location & Site Data’ tab in ApLocate
(ambient)
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 50
Heating Calculation Data:
The heating calculation data frame contains the following information:
Data label Data source
Results file Name of associated .htn file
Calculated Date and time of calculation
Profile Month Taken from Apache System Loads settings
Outdoor winter design Taken from the ‘Design Weather Data’ tab in ApLocate
temp
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 51
Figure 6-2: Plant Loops and Equipment report page
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 52
Condenser loop pump Condenser water loop flow rate multiplied by condenser
power water loop specific pump power both taken from the .asp
file
Pre-cooling loop Chilled water loop pre-cooling capacity taken from the
capacity .asp file
Equipment name and Taken from the .asp file for each chiller:
capacities - Chiller Name: Reference name from the .asp file
Capacity: Design condition cooling capacity, Qdes
Equipment name and Taken from the .asp file
capacities – Cooling Name: Cooling tower (set label)
Tower Capacity: Heat rejection, Qhrdes
Equipment name and Taken from the .asp file
capacities – Fluid cooler Name: Fluid Cooler (set label)
Capacity: Heat rejection, Qhrdes
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 53
Secondary pump power Combination of two parameters - Hot water loop
secondary flow rate multiplied by the relevant specific
pump power summed for all secondary loops
Equipment name and Taken from the .asp file for each boiler:
capacities - Boilers Name: Reference name from the .asp file
Capacity: Design condition heating capacity, Qdes
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 54
6.3 Space Loads and Ventilation
The space loads and ventilation report is the third report to be displayed unless it is unchecked. This report
shows a high-level breakdown of the space loads and ventilation values for each system within the results
file. It can flow onto multiple pages if the HVAC file contains more than one system.
The data shown in this table is consistent with that shown for the Zone Airflow Distribution table within
ApacheHVAC, and thus includes only those spaces/zones assigned to Principal Room/Zone components.
Therefore, the Space Loads and Ventilation report is a summary of loads for the Principal Room/Zone spaces
on each system, and not a listing of coil loads, which might include additional loads for non-principal spaces,
outdoor air ventilation, etc.
It should be noted that this table is populated via the ApacheHVAC .asp file either via the system loads run
results (.clg file or .htn file) or the via the Room & Zone Loads run results (.clg or .htg file) depending on the
level being reported.
The report also shows zone and room level loads and airflows. Zone loads are the coincident peak for all
rooms in each zone, and are set by the Room & Zone Loads run. Zone airflows are the zone cooling and
heating max airflows from the System Parameters UI. Room level loads data in the table are the non-
coincident peak value from the Room & Zone Loads run for the room.
Both Room Loads and Zone Loads (the coincident peak for the rooms in each zone) in this report are
populated from the System Parameters dialog and Zone Airflow Distribution table in the .asp file. These
values are typically generated from the Room & Zone loads analysis run––i.e., normally using ‘saturated’
gain profiles, without diversity factors, and before any influence from system operation and controls.
System Loads in this report are coincident peak values from the System loads analysis run––i.e., normally
using the same gain profiles and diversity factors as in the full dynamic simulation, and including the
influences of system operation and controls.
One report is shown per system with the system name in the header. In the case of PTAC and Single Zone
systems the name also includes a layer number for easier cross reference.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 55
Figure 6-3: Space Loads and Ventilation report page
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 56
System Level:
The following information is provided for the system:
Data label Data source
Sensible Cooling Load Coincident peak value from the System Loads run for all
zones on the system
Latent Cooling Load Coincident peak value from the System Loads run for all
zones on the system
Total Cooling load (also Sum of the above
provided per unit floor
area)
Cooling Airflow (also The system airflow peak from the System Loads run at the
provided per unit floor time of peak cooling load
area)
Heating load (also Coincident peak value from the System Loads run for all
provided per unit floor zones on the system
area)
Heating Airflow (also The system airflow peak from the System Loads run at the
provided per unit floor time of peak heating load
area)
Outdoor Airflow Req. This is system minimum outdoor ventilation requirement
(also provided per unit before considering the possibility of a greater requirement
floor area) for outside air to make up for total system exhaust airflow
and is equivalent to Vot in the System Parameters UI
Min OA Airflow (also Minimum outdoor air from the System Loads run at
provided per unit floor cooling vs. heating peak times
area)
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 57
Zone Level:
The following information is provided for each zone served by the system:
Data label Data source
Sensible Cooling Load Coincident peak value from the Room & Zone Loads run
as recorded in the System Parameters dialog, subject to
user edit, for all rooms in the zone
Latent Cooling Load Coincident peak value from the Room & Zone Loads run
as recorded in the System Parameters dialog, subject to
user edit for all rooms in the zone
Total Cooling load (also Sum of the above
provided per unit floor
area)
Cooling Airflow (also The Zone Cooling Max Airflow from the System
provided per unit floor Parameters UI
area)
Heating load (also Coincident peak value from the Room & Zone Loads run
provided per unit floor as recorded in the System Parameters dialog, subject to
area) user edit for all rooms in the zone
Heating Airflow (also The Zone Heating Max Airflow from the System
provided per unit floor Parameters UI
area)
Outdoor Airflow Req. Zone Ventilation Max/Total Required from the System
(also provided per unit Parameters UI
floor area)
Min OA Airflow (also Minimum outdoor air from the System Loads run at
provided per unit floor cooling vs. heating peak times
area)
Figure 6-4: Zone Airflow Distribution table showing a system 7a with completed system sizing and user edits
(orange text) and a system 5b with completed room & zone level sizing, but without completed system sizing
(blue text). All autosized values appear in green text.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 58
Room Level:
The following information is provided for each room served by the system:
Data label Data source
Sensible Cooling Load Peak value from the Room & Zone Loads run as recorded
in the System Parameters dialog, subject to user edit for
the room
Latent Cooling Load Peak value from the Room & Zone Loads run as recorded
in the System Parameters dialog, subject to user edit for
the room
Total Cooling load (also Sum of the above
provided per unit floor
area)
Cooling Airflow (also The Zone Cooling Max Airflow from the System
provided per unit floor Parameters UI multiplied by the room airflow apportioning
area) factor (%) as per the Zone Airflow Distribution table.
Heating load (also Peak value from the Room & Zone Loads run for the room
provided per unit floor
area)
Heating Airflow (also The Zone Heating Max Airflow from the System
provided per unit floor Parameters UI multiplied by the room airflow apportioning
area) factor (%) as per the Zone Airflow Distribution table
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 59
Cooling
Cooling coil peak
This is the breakdown of all the gains and losses contributing to the peak coil load (as selected
in the report generator settings)
System/Zone/Room peak
This is an equivalent breakdown at the system/zone/room peak time depending on the report
level
Cooling coils and room units
This shows peak performance information of associated coils and room units relevant to the
report level
Heating
Heating coil peak
This is the breakdown of all the gains and losses contributing to the peak coil load (as selected
in the report generator settings)
Heating coils and room units
This shows peak performance information of associated coils and room units relevant to the
report level
Supplementary information
Areas
Areas served by the system broken down cross all three levels
Temperatures
System temperatures relevant to the level
Airflow
System airflows relevant to the level
Checks
System checks relevant to the level
The following images show an example of a system, zone and room loads report.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 60
Figure 6-5: System Loads report page
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 61
Figure 6-6: Zone Conditioning Loads report page
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 62
Figure 6-7: Room Conditioning Loads report page
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 63
6.4.1 Cooling Coil Peak
Figure 6-8: Cooling Coil Peak section of System, Zone, and Loads report pages
This frame itemizes gains contributing to the load on a cooling coil at a peak time associated with the
peaking device as selected in the report generator settings. The name of this frame is dynamic and will
update depending on the peaking device selected.
This frame is broken down across the series of rows and columns, which are detailed as follows:
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 64
Rows (reported gain classes):
Envelope Gains/Losses
These are the gains/losses associated with the envelope e.g. external walls, roofs, solar,
ventilation associated with the envelope, etc.
Internal Building Gains/Losses
These the gains/losses associated with the internal structures and other gain/losses from
exchange between neighbouring elements like duct leakage, conduction and non-principle
spaces
Internal Gains
These the gains/losses associated with internal contributions within the room/zone e.g. lights,
people, equipment
Mechanical Gains/Losses
These are gains/losses associated with mechanical elements within the system itself
Columns:
Zone/Room
These are the gains/losses associated with the room or zone itself (aggregated at system and
zone level as appropriate)
RA Plenum
The RA Plenum column lists the gains/losses associated with the particular Room/Zone at hand
accruing directly to the RA Plenum (or a portion of such gains where the plenum is shared).
These gains include, for example, Lighting Gains fraction to plenum for lights in that particular
Room/Zone, Supply Air Leakage and Duct Heat Gain/Loss
Net Value
These are the gains/losses that directly contribute to the coil load and in most cases are a sum
of the system/zone/room column and the plenum column. However, there are exceptions,
which will be detailed below.
Percent of total
Displays, for each row, the value in the adjacent ‘Net Value’ column expressed as a percentage
of the total appearing at the bottom of that column (or a dash if the ‘Net Value’ column contains
a dash).
Where appropriate the room level gains/losses are aggregated to zone level and to system level.
The peak time of the selected peaking device is shown at the top of this frame along with the outside air
dry bulb (DB), outside air wet bulb (WB) and the outside air relative humidity (RH) at that time.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 65
Envelope Gains/Losses:
Data label Data source
External Walls Conduction gain - external wall from the .clg file
Roofs Conduction gain – roof from the .clg file
Ground/Exposed Floors Conduction gain - ground floor from the .clg file
External Doors Conduction gain – external doors from the .clg file
Windows Conduction Conduction gain - external glazing from the .clg file
Skylight Conduction Conduction gain – rooflights from the .clg file
Solar Solar gain from the .clg file
Infiltration Infiltration gain from the .clg file
Nat/Aux Vent Natural vent gain + Aux mech vent gain from the .clg file
Internal Gains:
Data label Data source
Lights Lighting gain from the .clg file
People People gain from the .clg file
Misc,Computers,Equip Equipment gain from the .clg file
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 66
The budget method makes use of known quantities to determine unknown ones in air flow networks. It
describes a system as a control volume which has inlets and outlets. Net mass flow into a control volume is
zero (that is, outflow is balanced with inflow). Heat flowing into and out of a control volume is tracked by
noting the inlet and outlet temperatures. In addition to the heat flowing into and out of the control volume,
all gains are tracked within the volume. Unknown gains can be determined via difference based upon these
known heat flows.
Mechanical Gains/Losses:
Data label Data source
Ventilation (sensible) This is the net sensible heat added to the system by
mechanical ventilation.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 67
SA Duct (conduction) This is the conduction heat gain to ducts (and thus to
supply air on route to the subject space). This gain
represents a transfer of heat to the system from a space
(possibly the exterior space). If that space is in the same
system, or the same zone, it will be balanced in the
system or zone account by an equal loss from that space
(part of the space’s ‘Duct conduction’ gain, see above). If
the space is exterior or in a different system, the gain
constitutes a net gain to the control volume.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 68
Dehumid Oversizing† This parameter is intended to report the additional coil
capacity resulting specifically from the cooling of the
supply air, as driven by system or zone setpoints for max
RH, to a temperature below the SAT required for sensible
space cooling, which is then followed immediately by
reheating of the supply airflow to the SAT for space
cooling. This added capacity for dehum followed by reheat
(which may be accomplished by a heat pipe, runaround
coil, or similar means between the AHU cooling and
heating coils, with the heating coil as backup) is required
to avoid overcooling any space already at min airflow as
an unintended consequence of controlling humidity.
In the case of plenums, for a principal room (in a Room Loads Report) or a principal zone (in a Zone Loads
Report) which has a dedicated RA plenum in the same multiplex layer, the ‘RA Plenum’ column lists, in each
row, the total gain to the RA plenum.
For a room which forms part of a zone with a dedicated RA plenum in the same multiplex layer, the ‘RA
Plenum’ column lists, in each row, a portion of the total gain to the RA plenum. In this case the gain is
distributed among the rooms for reporting purposes in the usual proportions (based on air supply to the
rooms), with the exception that any lighting gain via light fittings is apportioned to the room from which it
originates.
For a principal room (in a Room Loads Report) or a principal zone (in a Zone Loads Report) which shares an
RA plenum with other principal rooms or zones in the same multiplex the gains are distributed as per the
apportioning logic for the room/zone column.
For a System Report, the RA Plenum column lists the total gains accruing directly to RA Plenums associated
with all principal rooms or zones in the system.
Note: any spaces - including RA plenums – that are not in a multiplex do not generate gains in the ‘RA
Plenum’ column. Their gains contribute to ‘Non-Principal Spaces’ gains for the air handling system.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 69
6.4.2 Cooling System/Zone/Room Peak
Figure 6-9: Cooling System/Zone/Room Peak section of System, Zone, and Loads report pages
This section is headed ‘Room Peak’ in Room Loads Reports, ‘Zone Peak’ in Zone Loads Reports and ‘System
Peak’ in System Loads Reports. It itemizes gains (reported gain classes) to a room or zone (or a set of rooms
or zones in the case of a System Loads Report) at the time of peak room cooling. This is defined as when
the variable ‘Space conditioning sensible’ for the subject room (or in the case of Zone and System Loads
Reports multiple rooms or zones) totaled over all the relevant rooms or zones, is at its maximum negative
value.
The derivations of entries in this part of the report (under the column headings ‘Room’ and ‘Percent of
Total’) follow the same procedures as those in the ‘... COOLING ... PEAK’ section, with the following
exceptions:
Mechanical Gains/Losses – these do not apply and are reported as dashes (–).
Values in the ‘Percent of Total’ column refer to the adjacent values in the ‘(Sensible)’ column.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 70
6.4.3 Heating Coil Peak
Figure 6-10: Heating Coil Peak section of System, Zone, and Loads report pages
This section itemizes gains (reported gain classes) contributing to the load on a heating coil or other heating
device at a peak time specified in the report generator settings. As with the cooing coil peak, this determines
the wording of the header.
The derivations of entries in this part of the report (under the headings ‘Room’ (or ‘Zone’) ‘RA Plenum’ and
‘Net Total’) follow the same procedures as those in the cooling coil peak section, with the following
exceptions:
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 71
Inputs are taken from the .htn file rather than the .clg file.
So long as the ‘Default’ box is checked in the Heating Loads section of the ASHRAE Loads dialog,
the ‘Time of peak’ on the report shall display ‘Heating Design’.
Setpoints are used in the calculation of some of the mechanical gains/losses, in this case these
are heating setpoints rather than cooling setpoints.
The rows for Latent Cooling Load and Dehumid Oversizing are not relevant and therefore are
omitted
Figure 6-11: Cooling Coils and Room Units section of System, Zone, and Loads report pages
This frame shows the design values for the cooling coils and cooling room units in the system. Devices at
system level are shown on the system report and their proportional contribution at zone and room level
are shown on those reports. Devices at zone level are shown on the zone report and their proportional
contribution at room level is shown on the room level report.
The following cooling devices are reported:
System cooling coil
Ventilation cooling coil
Indirect and direct evaporative cooling
FCU, FPB or Active beam
Room units. In this case only the capacity and entering/leaving water temperatures are shown
The oversizing toggle affects the capacities displayed in this frame and a note directly under the frame
indicates if oversizing has been included or not.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 72
Data label Data source
Total Capacity This is the total capacity taken from the .asp file. In the
case of evaporative cooling this is calculated from
conditions in the .clg file
Sensible Capacity This is the sensible capacity. The proportion of total to
sensible is obtained from the .clg file and this is then
applied to the total from the .asp to get the design
sensible capacity
Airflow This is the airflow from the .asp file. When the .asp is not
a valid source it is taken from the .clg file
Entering DB/WB/RH This is the entering conditions from the .asp file. When the
.asp is not a valid source the values are taken from the
.clg file
Leaving DB/WB/RH This is the leaving conditions from the .asp file. When the
.asp is not a valid source the values are taken from the
.clg file
Figure 6-12: Heating Coils and Room Units section of System, Zone, and Loads report pages
This frame shows the design values for the heating coils and heating room units in the system. Devices at
system level are shown on the system report and their proportional contribution at zone and room level
are shown on those reports. Devices at zone level are shown on the zone report and their proportional
contribution at room level is shown on the room level report.
The following heating devices are reported:
System heating coil
Ventilation heating coil
Pre-heat coil
Re-heat coil
FCU, FPB or Active beam
Room units. In this case only the capacity and entering/leaving water temperatures are shown
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 73
The oversizing toggle affects the capacities displayed in this frame and the same note referenced in the
cooling coil and room units frame indicates if oversizing has been included or not.
6.4.6 Areas
Figure 6-13: Areas section of System, Zone, and Loads report pages
This frame details the gross surface areas of the zones or rooms served by the system. These are then
summed to give the areas at system level. The frame also outlines the glazing area in the relevant surfaces
and shows this as a percentage.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 74
Data label Data source
Wall External wall area + external glazing area (excluding doors
and holes)
6.4.7 Temperatures
Figure 6-14: Temperatures section of System, Zone, and Loads report pages
This frame reports relevant temperatures at system, zone and room level. The parameters change
depending on the reporting level.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 75
System level:
Note, where appropriate the data source is at the time of peak system cooling and heating loads,
respectively (coincident peak value for all zones on the system).
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 76
Fan Motor Temp Rise This is the temperature rise due to the motor and is given
(dT) by:
𝑄𝐹 (𝑉)(1−𝜂𝑀 (𝑉))
Δ𝑇𝑀 = 𝜂𝑀 (𝑉)𝜌𝑉𝑐𝑝
Where,
𝑄𝐹 (𝑉) - is the total fan power at time of peak flowrate 𝑉.
Δ𝑇𝐹 = Δ𝑇 − Δ𝑇𝑀 .
Zone level:
Note, where appropriate the data source is at the time of peak zone cooling and heating loads, respectively
(coincident peak value for all rooms in each zone).
Data label Data source
Supply air (design) This is the zone level design temperature and is obtained
from the system parameters UI for heating and cooling
(‘Zone loads & airflows tab’ - cooling and heating design
zone air temperatures)
Supply air (actual) The actual zone supply temperature is obtained from the
.clg and .htn. This is determined by querying the node
entering the zone
Return air (actual) The actual zone return temperature is obtained from the
.clg and .htn. This is determined by querying the node
leaving the zone
Plenum (actual) This is the actual plenum temperature obtained from the
.clg and .htn. This is determined by querying the node
directly downstream of the plenum component
Mixed air (actual) Same as the system mixing temperature
Zone Fan Temp Rise (dT) This parameter is shown only when there is a zone-level
fan, such as in a fan-coil unit or FPB.
At zone level the reports show the complete fan temp rise
which is obtained from the .clg and .htn file
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 77
Room level:
Note, where appropriate the data source is at the time of peak room cooling and heating loads, respectively.
Data label Data source
Supply air (design) This is the room level design temperature and is obtained
from the systems parameters UI for heating and cooling
(‘Zone loads & airflows tab’ - cooling and heating design
zone air temperatures). Note that for rooms in zones, this
is the same for each room.
Supply air (actual) The actual room supply temperature is obtained from the
.clg and .htn. This is determined by querying the node
entering the room. Note that for rooms in zones, this is the
same for each room.
Room Setpoint (design) This is obtained from the ‘Systems Schedules and
Setpoints’ dialog
Room throttling range This is currently blank (not reported) and may be included
in future versions
Room (actual) The room temperature is obtained from the .clg and .htn
Return air (actual) The actual room return temperature is obtained from the
.clg and .htn. This is determined by querying the node
leaving the room. Note that for rooms in zones, this is the
same for each room.
Plenum (actual) This is the actual plenum temperature obtained from the
.clg and .htn. This is determined by querying the node
directly downstream of the plenum component. Note that
for rooms in zones, this is the same for each room.
Mixed air (actual) Same as the system mixing temperature
Zone Fan Temp Rise (dT) This parameter is shown only when there is a room-level
fan, such as in a fan-coil unit or FPB.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 78
6.4.8 Airflow
Figure 6-15: Airflow section of System, Zone, and Loads report pages
This frame reports relevant airflows at system, zone and room level. The parameters change depending on
the reporting level.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 79
System level:
Note, where appropriate the data source is at the time of peak system cooling and heating loads,
respectively (coincident peak value for all zones on the system).
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 80
Ventilation (actual) This is the actual system ventilation and is obtained from
the .clg and .htn respectively. The source of this data
varies depending on the system configuration i.e.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 81
Zone level:
Note, where appropriate the data source is at the time of peak zone cooling and heating loads, respectively
(coincident peak value for all rooms in each zone)
Data label Data source
Supply (design) This is the zone level design airflow and is obtained from
the system parameters UI for heating and cooling. (‘Zone
loads & Supply Airflows tab’)
Supply (actual) This is the actual system supply airflow into the zone and
is obtained from the .clg and .htn. This is determined by
querying the node entering the zone
Reheat Minimum This is the minimum primary airflow for the zone, obtained
(design) from the system parameters UI
Leakage at Design Flow This is the zone leakage airflow and is obtained by
multiplying the percentage leakage by the supply design
flow
Return (actual) This is the actual zone return airflow and is obtained from
the .clg and .htn. This is determined by querying the node
leaving the zone
Exhaust (actual) This is the flow on the zone exhaust path obtained from
the .clg and .htn respectively
Ventilation (requirement) This is the zone ventilation requirement and is taken from
the system parameters dialog (‘Max req.’ from the ‘Zone
Ventilation & Exhaust’ tab)
Ventilation (actual) This is the actual zone ventilation and is obtained from the
.clg and .htn respectively. The source of this data varies
depending on the system configuration i.e.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 82
Room level:
Note, where appropriate the data source is at the time of peak room cooling and heating loads, respectively.
In addition, for rooms in zones the zone flow is distributed among the rooms as per the proportioning in
the zone airflow distribution table (ZAD)
Data label Data source
Supply (design) This is the room level design airflow and is obtained from
the system parameters UI for heating and cooling. (‘Zone
loads & Supply Airflows tab’)
Supply (actual) This is the actual system supply airflow into the room and
is obtained from the .clg and .htn. This is determined by
querying the node entering the room
Reheat Minimum This is the minimum primary airflow for the room, obtained
(design) from the system parameters UI
Leakage at Design Flow This is the room leakage airflow and is obtained by
multiplying the percentage leakage by the supply design
flow.
Return (actual) This is the actual room return airflow and is obtained from
the .clg and .htn. This is determined by querying the node
leaving the room
Exhaust (actual) This is the flow on the room exhaust path obtained from
the .clg and .htn respectively
Ventilation (requirement) This is the room ventilation requirement and is taken from
the system parameters dialog (‘Max req.’ from the ‘Zone
Ventilation & Exhaust’ tab).
Ventilation (actual) This is the actual room ventilation and is obtained from
the .clg and .htn respectively. The source of this is the
same as for zones.
Infiltration This is the infiltration rate for the room and is obtained
from the .clg and .htn
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 83
6.4.9 Checks
Figure 6-16: Checks section of System, Zone, and Loads report pages
This frame provides a series of engineering checks, which can be used to verify performance at system,
zone and room level. Most of these checks already exist in the system parameters UI and are sourced from
there.
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 84
cfm/ft2 – Cooling & Sourced from the system parameters UI for each zone (Zone
Heating airflow, turndown & engineering checks tab). This data is then
used to calculate system level value.
At zone and room level the outdoor air flow is taken from the
Zone Airflow Distribution table (ZAD) (ventilation airflow) and
along with floor area is used to calculate the required values.
Outdoor air Sourced from the system parameters UI for system level (Zone
cfm/person airflow, turndown & engineering checks tab).
At zone and room level the outdoor air flow is taken from the
Zone Airflow Distribution table (ZAD) (ventilation airflow) and
along with No. of people is used to calculate the required values.
Peak latent Load This value is determined based on the peak Latent Load at the
(Btu/h) system cooling coil (independent of the overall cooling coil
peak) and is distributed out to the zone and room as per the
proportioning in the Zone Airflow Distribution table (ZAD)
VE 2017 ApacheHVAC User Guide part F: Loads Analysis and Reporting Tools 85