Documente Academic
Documente Profesional
Documente Cultură
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2016.2601379, IEEE
Transactions on Smart Grid
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2016.2601379, IEEE
Transactions on Smart Grid
ods for fault location, where the estimation best explains the x 1–x
measured values. A different approach by Azizi et al. [13] c-phase
and Dobakhshari et al. [14] formulates the problem as an b-phase
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2016.2601379, IEEE
Transactions on Smart Grid
the measurement vector and X = [x, |II + + T can be seen from (13), these elements of Jacobian matrix can
f |, I f ]
6 the un-
known variable vector. Equation (6) can be re-written in a easily be calculated without the need for separating the real
compact form as and imaginary parts of the complex variable Ẑ pf in (2).
Equations (11)-(12) give elements of Jacobian related to
M − F (X) = 0, (7)
the voltage magnitude measurements. The remaining non-zero
where F is a vector function relating the unknown variables to elements of J corresponding to phase-angle measurements can
the measurements as given by the right side of (6). If there are be calculated by partial derivatives of F as follows.
two or more voltage phasor measurements, an overdetermined
∂ 6 ∆V +
p ∂ 6 Ẑ pf (x)
system of equations is resulted from (5), which can be solved Jp,1 = = , (14)
∂x ∂x
by the Newton-Raphson method [25], iteratively, as follows
Z ip Z jp
+
sinh(γγ ij lij x) sinh(γγ ij lij (1 − x))
Ẑ pf (x) = (2)
1 1 γ ij lij γ ij lij
+ + tanh x + tanh (1 − x)
sinh(γγ ij lij x) sinh(γγ ij lij (1 − x)) 2 2
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2016.2601379, IEEE
Transactions on Smart Grid
sequence qu
(14) can be calculated by (B.4) in Appendix B, where Z (x) cannot be lo
should be replaced with Ẑ pf . Nevertheless
( ) type, in pract
∂Ẑ pf (x) ∗
Re Ẑ pf (x) Ẑ pf (x)
∂ Ẑ pf (x) ∂x
− 2
∂x
F
Ẑ (x)
+
∂ 6 ∆V p pf
= −j INCLUDE IN
∂x Ẑ pf (x)
(16)
Actual
To analyze the computational burden of the proposed Faulted
method, it should be noted that the Jacobian matrix J is a
2(m + n) by 3 matrix, and thus JT J inverted in (9), is a 3 by
3 matrix. Therefore, matrix inversion in (9) is computationally
inexpensive as a 3 by 3 matrix is only needed to be inverted.
This is not the case for some of the previously reported wide-
area fault-location methods [9], [10].
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2016.2601379, IEEE
Transactions on Smart Grid
TABLE I TABLE II
FAULT L OCATION ON THE 9-B US T EST S YSTEM D IFFERENT P RE -FAULT O PERATING C ONDITIONS IN THE 9-B US S YSTEM
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2016.2601379, IEEE
Transactions on Smart Grid
TABLE IV
~
S ENSITIVITY A NALYSIS OF E STIMATION E RROR WITH I NEXACT
N ETWORK PARAMETERS (9-B US S YSTEM ) 4
10
9
Type (pu) 5 3
2% 4% 6% 8%
~
G
[13] -1.515 -3.197 -4.821 -6.389 1
0.1 8
Proposed 0.151 0.187 0.219 0.248
SLG
[13] -1.267 -2.8 -4.279 -5.706
29
28
0.5
27
Proposed -0.812 -1.684 -2.647 -3.707 ~ 2
[13] -1.005 -2.344 -3.635 -4.880 6
C
0.9
Proposed -0.502 -1.874 -3.293 -4.751
[13] -1.606 -3.288 -4.911 -6.478
0.1
Proposed -0.385 -0.797 -1.195 -1.582
31
~
LL
[13] -1.442 -2.974 -4.451 -5.878 13 7 9
0.5 22
Proposed -0.437 -0.920 -1.401 -1.882
[13] -1.256 -2.595 -3.885 -5.129
G
0.9
39
0.1
Proposed -0.350 -0.731 -1.202 -1.462
DLG
[13] -1.532 -3.064 -4.541 -5.968
40
0.5
25
11
26
C
[13] -1.635 -3.317 -4.940 -6.507
G
~
0.1
Proposed -0.425 -0.869 -1.297 -1.710 20
3PH ~
[13] -1.480 -3.011 -4.489 -5.915 12
0.5
21
20
22
~
[13] -1.285 -2.623 -3.913 -5.158
0.9 16
Proposed -0.396 -0.822 -1.244 -1.663 19
~
18
avoids using external network parameters, are compared with
21
the proposed method. 17
Case 1 assumes that synchronized voltage measurements
are available at buses 4, 6 and 8. Case 2 considers GSL at
bus 6, and therefore, previous WAFL methods have to use only Fig. 4. Single-line diagram of the 22-bus test system.
two voltage synchrophasors at buses 4 and 8, the latter being
as can be seen in Case 3 of Table III. Sensitivity analysis of
far from the fault point. Case 3 demonstrates the advantage
fault-location estimation on this line, as reflected in Table IV,
of the proposed method in the face of GSL. Although phase-
reveals that the proposed method outperforms [13] for different
angle of voltage measurement at bus 6 is not available, its
fault types along this line, when network parameters vary by
magnitude is incorporated in the fault-location procedure by
2% to 8%.
the proposed formulation. Fault-location results in Table III
It is worth noting that there are many other WAFL methods
show that when network parameters are 100% accurate, all
proposed in the literature. In [8], only two voltage measure-
methods present accurate results for all measurement cases.
ments are utilized, and therefore the method is prone to GSL.
It should be noted that the proposed method in [15] requires
The proposed method in [9] involves estimating phase-angle
synchronized measurements at all border buses 4, 6 and 8, and
values of measurements, and hence needs more computational
is paralyzed by GSL at bus 6. As network parameters vary
effort. Bad data detection and identification may also become
in practice according to weather and loading conditions [27],
problematic, since voltage measurements are divided by each
simulations are repeated considering an additional situation
other. Comparison of fault-generated waveforms with those
of 5% error in network parameters. Fault-location accuracy
calculated and recorded offline is another approach pursued
deteriorates with error in network parameters. This inaccuracy
in [28]–[31]. This approach does not lend itself to large-scale
is pronounced when the unsynchronized measurement at bus 6
power systems, where faults of different types, locations and
is dismissed in Case 2. When voltage measurement at bus 6 is
resistance values have to be simulated and stored in a database.
not utilized due to GSL, the method in [15] is inapplicable as
before and the method in [13] leads to less accurate results
due to error in network parameters. Using unsynchronized C. Fault Location on 22-Bus Test System
voltage measurement at bus 6, the proposed method yields To examine the application of the proposed method in a
more accurate results than those of previous WAFL methods, large system, a 22-bus test system, whose single line diagram
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2016.2601379, IEEE
Transactions on Smart Grid
TABLE V TABLE VI
FAULT L OCATION ON L ONG T RANSMISSION LINES OF THE 22-B US T EST W IDE A REA FAULT L OCATION OF L INE 16-18 IN 22-B US T EST S YSTEM
S YSTEM
Network WAFL FL estimation error (%)
FL estimation error (%) Parameters Method No GSL GSL at PMU 19
Faulted Fault
Fault Distance (pu) No Error in [13] 0.016 -0.072
Line Type
0.1 0.3 0.5 0.7 0.9 Parameters Proposed 0.007 0.015
3PH 0.0135 0.0024 -0.0021 0.0061 0.0078 5% Error in [13] -0.014 11.249
LL 0.0099 -0.0027 0.0397 0.0034 0.0047 Parameters Proposed -0.068 0.395
16-18
SLG 0.0267 0.0166 0.0766 0.0395 0.1853
DLG 0.0073 0.0106 0.0117 0.0298 0.0355
3PH 0.0009 0.0037 0.0013 0.008 0.0052
at bus 19, there will be no measurement to give information on
LL -0.0096 -0.0049 -0.0038 0.0023 -0.0023 bus 18. This can also be figured out from Fig. 1(b), where fault
10-12
SLG -0.0562 -0.098 0.1122 -0.093 0.2418 current is expected to be supplied from both ends of the line.
DLG -0.0151 -0.006 0.0024 0.0077 -0.0236
When all parameters are exact this problem does not appear as
3PH 0.004 0.0085 0.0035 0.0074 -0.0042
LL -0.0055 -0.0004 -0.002 0.0014 -0.0123 the weak interconnection gives exact value of the fault current
11-12
SLG 0.0923 0.1014 0.1118 0.1046 0.0913 from bus 18. However, as shown in Table VI, when there is
DLG -0.0177 -0.0069 -0.0011 0.0117 0.0049
only 5% error in network parameters, fault current cannot be
3PH 0.0074 0.0085 0.0057 0.0099 0.0112
LL -0.0045 -0.0015 -0.002 0.001 0.0058 estimated accurately and hence fault location will have more
13-14
SLG 0.029 0.1309 0.1793 0.2126 0.3342 than 11% error if unsynchronized voltage measurements are
DLG -0.0186 -0.0076 -0.0024 0.0074 0.0122
not utilized, as is the case in previous WAFL methods such as
3PH 0.0024 -0.0006 0.0018 0.0031 0.0068
LL -0.0063 -0.0125 -0.0072 -0.0063 0.0031 [13]. It can be seen from Table VI that when there is no GSL,
3-9
SLG -0.0369 0.0066 -0.0589 -0.1137 -0.102 even with 5% error in network parameters both [13] and the
DLG -0.0417 -0.0458 -0.0377 -0.0245 -0.0284
proposed method show quite accurate results. It has already
3PH -0.0192 -0.0093 0.0157 0.0304 0.0219
LL -0.0217 -0.0093 0.0086 0.01 0.0056 been observed in [16], [35] that in large-scale networks,
17-21
SLG 0.3451 0.3432 0.4126 0.528 0.7342 more PMUs lead to more accurate fault-location estimation.
DLG 0.0074 0.0168 0.0415 0.0552 0.0619 However, the absence of synchronized measurements at one
3PH 0.0264 0.0527 0.0366 0.0101 -0.0115
LL 0.0133 0.0395 0.0276 -0.0021 -0.0213 end of the line makes previous WAFL methods significantly
12-17
SLG 0.0599 0.1238 0.1459 0.3769 0.3267 vulnerable to even a slight error in network parameters. The
DLG -0.0054 0.0405 0.0423 0.0187 0.0063 proposed method, in contrast, shows a good robustness against
this error in network parameters by using the magnitude of
is shown in Fig. 4, is adopted for simulations. Based on observ-
measured voltage at bus 19, i.e. |∆V∆V 19 |.
ability criteria [32]–[34], synchronized voltage measurements
Table VII reflects sensitivity analysis of fault location on
at buses 1, 5, 9, 12, 16 and 19 are assumed to be available.
this line, revealing that the proposed method outperforms the
Table V shows fault-location results for faults of different
previous method for different fault types along different points
types on different points of long transmission lines of the
of the line, when network parameters are not exact. The
network. It can be seen from Table V that fault-location
advantage of the proposed method, therefore, becomes clear
accuracy stays well beneath 1% for all the fault cases. The
when network parameters are inexact, as is the case in practice
reason is taking full capacitance of the line into account in
due to loading and weather conditions [27].
the proposed formulation, as depicted in Fig 1.
Table VIII shows the convergence process for a bolted SLG
It should be noted that many fault-location methods require fault at 10% of line 16-18. The initial values for |II + +
f | and I f
6
fault type identification and/or fault resistance estimation. are calculated by (18) and (20), respectively. This expedites
The proposed method, however, locates the faults, accurately, the iterative process as can be seen in Table VIII. A similar
irrespective of fault type and resistance. This can clearly be behavior is observed for all simulation cases, where at most
observed from Tables I and V. five iterations are carried out. The average elapsed time for
fault location is less than 10 ms, on a 2.1 GHz dual-core
D. Impact of GPS Signal Loss on 22-Bus Test System processor with 4 GB of RAM.
The influence of the fault resistance for different faults
It has been proved in [14] that if all of the measurements
along this line is reflected in Table IX. It is observed that
are taken from one of the terminals of the faulted line, fault
the proposed method is robust against fault resistance, thanks
location is impossible to carry out. This implies that when
to considering the full capacitance of the line.
the parallel path to the faulted line is a weak interconnection,
WAFL will be unsuccessful if no measurement is utilized from
the far end of the line. This situation can be experienced in 22- VIII. C ONCLUSION
Bus test system when there is a DLG fault at 10% of line 16- A novel method for wide-area fault location of transmission
18. The parallel path to this line is line 12-17; if GLS occurs lines by both synchronized and unsynchronized measurements
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2016.2601379, IEEE
Transactions on Smart Grid
TABLE VII
S ENSITIVITY A NALYSIS OF E STIMATION E RROR WITH I NEXACT results have shown that faults at different points of the network
N ETWORK PARAMETERS (22-B US S YSTEM ) can be located regardless of fault type. Even for transmission
lines not equipped with any synchronized or unsynchronized
FL estimation error (%)
Fault d measuring device, the estimation error is far below 1% for
Method Error in Network Parameters
Type (pu)
2% 4% 6% almost all faults.
[13] -4.744 -9.199 -13.389 It has been observed that WAFL methods using sparse syn-
0.1
Proposed -0.025 -0.037 -0.053
SLG chronized measurements can be significantly vulnerable when
[13] -3.585 -7.042 -10.28
0.5 there is a slight error in network parameters. The proposed
Proposed 0.367 0.734 1.081
[13] -2.479 -4.906 -7.163 method, however, integrates unsynchronized measurements,
0.9
Proposed 0.846 1.609 2.335
and hence, provides useful information from the part of
[13] -4.684 -9.143 -13.337
0.1 the network with no available synchronized measurements.
Proposed -0.016 -0.023 -0.036
LL
0.5
[13] -3.782 -7.234 -10.466 This has resulted in decreasing the error of fault-location
Proposed 0.422 0.825 1.206
estimation for a long transmission line from 11% in a previous
[13] -2.709 -5.130 -7.381
0.9 method, which used only synchronized measurements, to less
Proposed 0.854 1.665 2.437
0.1
[13] -4.673 -9.132 -13.325 than 0.5%, thanks to utilizing an additional unsynchronized
Proposed -0.016 -0.022 -0.034
DLG measurement in the proposed method.
[13] -3.717 -7.171 -10.405
0.5
Proposed 0.420 0.830 1.218
[13] -2.616 -5.041 -7.295 A PPENDIX A
0.9
Proposed 0.856 1.690 2.485
PARTIAL D ERIVATIVE OF M AGNITUDE F UNCTION
[13] -4.659 -9.119 -13.314
0.1
Proposed -0.015 -0.019 -0.03 Expanding Z (x) in terms of its real and imaginary parts
3PH
[13] -3.789 -7.241 -10.473
0.5
Proposed 0.437 0.855 1.250
yields
[13] -2.736 -5.156 -7.405 Z (x) = P (x) + jQ(x) (A.1)
0.9
Proposed 0.899 1.746 2.553
Derivating the magnitudes of functions at two sides of (A.1)
TABLE VIII leads to
C ONVERGENCE B EHAVIOR OF THE P ROPOSED M ETHOD
∂ Z (x)
= ∂ P 2 (x) + Q2 (x)
p
Iteration Estimated x Estimated Estimated ∂x ∂x
Number (pu) |II +
f | (pu)
6 I+f (Deg)
∂P (x) ∂Q(x) (A.2)
0 0.5 5.0968 -76.5
P (x) + Q(x)
1 0.0966728 5.0337 -78.34
= p ∂x ∂x
2 0.1002947 5.0398 -78.12 P 2 (x) + Q2 (x)
3 0.1002928 5.0396 -78.16
4 0.1002928 5.0396 -78.16 On the other hand, derivating both sides of (A.1) yields
Total Time 7.917 ms Z (x)
∂Z ∂P (x) ∂Q(x)
= +j (A.3)
TABLE IX
∂x ∂x ∂x
I NFLUENCE OF FAULT R ESISTANCE ON E STIMATION ACCURACY Getting the conjugate of (A.1) and multiplying it by (A.3)
leads to
FL estimation error (%)
Fault d
Fault Resistance (Ω) ∂ZZ (x) ∂P (x) ∂Q(x)
Z (x)∗ =
Type (pu) +j P (x) −jQ(x)
0 50 100 200 ∂x
∂x ∂x
0.1 -0.0292 -0.019 -0.0279 -0.1222 ∂P (x) ∂Q(x)
SLG 0.5 -0.0884 -0.0476 -0.0015 0.071516 = P (x) + Q(x) (A.4)
0.9 -0.1786 -0.2 -0.2139 -0.22415 ∂x ∂x
∂P (x) ∂Q(x)
0.1 -0.0098 -0.008 -0.0019 0.0054 −j Q(x) + P (x)
LL 0.5 0.0055 -0.0135 -0.0154 -0.0111 ∂x ∂x
0.9 -0.0036 -0.0328 -0.0395 -0.0376
Using (A.4) we can rewrite (A.2) as
0.1 -0.0164 -0.014 -0.041 -0.0045
DLG 0.5 -0.0039 -0.0097 0.0029 0.0283 Z (x)
∂Z ∗
0.9 -0.0124 -0.0243 -0.0161 -7.7e-5
Re Z (x)
∂ Z (x) ∂x
0.1 -0.0142 -0.0115 -0.0088 -0.0045 = (A.5)
3PH 0.5 0.0057 0.0014 0.0034 0.003 ∂x Z (x)
0.9 -0.0031 -0.0113 -0.015 -0.0255
A PPENDIX B
has been presented in this paper. Only positive-sequence PARTIAL D ERIVATIVE OF P HASE -A NGLE F UNCTION
voltage measurements are used in the method and therefore
Writing (A.1) in polar form results in
it is inherently immune against CT saturation as well as
unreliable zero-sequence parameters of the line. Simulation Z (x) = R(x)ej δ(x) (B.1)
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2016.2601379, IEEE
Transactions on Smart Grid
Derivating both sides of (B.1) results in [14] A. S. Dobakhshari and A. M. Ranjbar, “A novel method for fault location
of transmission lines by wide-area voltage measurements considering
Z (x)
∂Z ∂R(x) j δ(x) ∂δ(x) measurement errors,” IEEE Trans. Smart Grid, vol. 6, no. 2, pp. 874–
= e +j Z (x) (B.2)
∂x ∂x ∂x 884, 2015.
[15] M. K. Neyestanaki and A. M. Ranjbar, “An adaptive PMU-based wide
Therefore, the derivative of phase angle of Z (x) with respect area backup protection scheme for power transmission lines,” IEEE
to x can be written as Trans. Smart Grid, vol. 6, no. 3, pp. 1550–1559, 2015.
[16] A. S. Dobakhshari and A. M. Ranjbar, “A wide-area scheme for power
∂R(x) Z (x) system fault location incorporating bad data detection,” IEEE Trans.
∂ZZ (x)
− ∂x Power Del., vol. 30, no. 2, pp. 800–808, 2015.
∂δ(x) ∂x R(x)
= −j (B.3) [17] A. Esmaeilian and M. Kezunovic, “Fault location using sparse syn-
∂x Z (x) chrophasor measurement of electromechanical wave oscillations,” IEEE
Trans. Power Del., vol. PP, no. 99, pp. 1–1, 2016.
Recall from (B.1) that R(x) = Z (x) and hence substituting [18] G. Feng and A. Abur, “Fault location using wide-area measurements
(A.5) into (B.3) yields and sparse estimation,” IEEE Trans. Power Syst., vol. PP, no. 99, pp.
1–8, 2015.
Z (x)
∂Z ∗ [19] M. Majidi, M. Etezadi-Amoli, and M. S. Fadali, “A sparse-data-driven
Re Z (x) Z (x) approach for fault location in transmission networks,” IEEE Trans. Smart
Z (x)
∂Z ∂x
− Grid, vol. PP, no. 99, pp. 1–9, 2015.
∂x Z (x)2
∂ 6 Z (x) [20] M. M. Saha, J. Iżykowski, and E. Rosolowski, Fault location on power
= −j (B.4) networks. Springer, 2010.
∂x Z (x)
[21] W. Yao, Y. LIU, D. Zhou, Z. Pan, J. Zhao, M. Till, L. Zhu, L. Zhan,
Q. Tang, and Y. Liu, “Impact of gps signal loss and its mitigation in
power system synchronized measurement devices,” IEEE Transactions
on Smart Grid, vol. Early Access, 2016.
R EFERENCES [22] D. Novosel, D. G. Hart, E. Udren and J. Garitty, “Unsynchronized two-
terminal fault location estimation,” IEEE Trans. Power Del., vol. 11,
[1] J. Pfeifenberger, J. Chang, and J. Tsoukalis. Investment trends no. 1, pp. 130–138, 1996.
and fundamentals in U.S. transmission and electricity infrastructure. [23] A. Abur and A. G. Exposito, Power system state estimation: theory and
[Online]. Available: http://www.brattle.com/system/publications/pdfs/ implementation. CRC Press, 2004.
000/005/190/original/Investment Trends and Fundamentals in US [24] K. Kreutz-Delgado, The Complex Gradient Operator and the CR-
Transmission and Electricity Infrastructure.pdf Calculus. University of California, San Diego, 2009. [Online].
[2] M. Kezunovic, “Smart fault location for smart grids,” IEEE Trans. Smart Available: http://dsp.ucsd.edu/∼kreutz/Publications/kreutz2009complex.
Grid, vol. 2, no. 1, pp. 11–22, 2011. pdf
[3] M. Korkali, H. Lev-Ari, and A. Abur, “Traveling-wave-based fault- [25] H. Saadat, Power system analysis. McGraw-Hill:New York, 1999.
location technique for transmission grids via wide-area synchronized [26] Matpower: A matlab power system simulation package. [Online].
voltage measurements,” IEEE Trans. Power Syst., vol. 27, no. 2, pp. Available: http://www.pserc.cornell.edu/matpower/
1003–1011, 2012. [27] V. Terzija, Z. M. Radojevic, and G. Preston, “Flexible synchronized
[4] M. Korkali and A. Abur, “Optimal deployment of wide-area synchro- measurement technology-based fault locator,” IEEE Trans. Smart Grid,
nized measurements for fault-location observability,” IEEE Trans. Power vol. 6, no. 2, pp. 866–873, 2015.
Syst., vol. 28, no. 1, pp. 482–489, 2013. [28] A. Salehi Dobakhshari and A. Ranjbar, “A circuit approach to fault
[5] S. Azizi, S. Afsharnia, and M. Sanaye-Pasand, “Fault location on multi- diagnosis in power systems by wide area measurement system,” Int.
terminal DC systems using synchronized current measurements,” Int. Trans. Elect. Energy Syst., vol. 23, no. 8, pp. 1272–1288, 2013.
Jour. Elect. Power & Energy Syst., vol. 63, pp. 779–786, 2014. [29] Z. Galijasevic and A. Abur, “Fault location using voltage measurements,”
[6] S. Azizi, M. Sanaye-Pasand, M. Abedini, and A. Hassani, “A traveling- IEEE Trans. Power Del., vol. 17, no. 2, pp. 441–445, 2002.
wave-based methodology for wide-area fault location in multiterminal [30] M. Kezunovic and Y. Liao, “Fault location estimation based on matching
DC systems,” IEEE Trans. Power Del., vol. 29, no. 6, pp. 2552–2560, the simulated and recorded waveforms using genetic algorithms,” in 7th
2014. Int. Conf. Develop. Power Syst.Protect., 2001, pp. 399–402.
[7] Y. Chen, D. Liu, and B. Xu, “Wide-area traveling wave fault location [31] A. S. Dobakhshari and A. M. Ranjbar, “Transmission grid fault diagnosis
system based on IEC61850,” IEEE Trans. Smart Grid, vol. 4, no. 2, pp. by wide area measurement system,” in 3rd IEEE PES Innovative Smart
1207–1215, 2013. Grid Technologies Europe (ISGT Europe), 2012, pp. 1–7.
[8] Y. Liao, “Fault location for single-circuit line based on bus-impedance [32] N. M. Manousakis, G. N. Korres, and P. S. Georgilakis, “Taxonomy
matrix utilizing voltage measurements,” IEEE Trans. Power Del., vol. 23, of PMU placement methodologies,” IEEE Trans. Power Syst., vol. 27,
no. 2, pp. 609–617, 2008. no. 2, pp. 1070–1077, 2012.
[9] N. Kang and Y. Liao, “Double-circuit transmission-line fault location [33] S. Azizi, A. S. Dobakhshari, S. A. Nezam Sarmadi A. M. Ranjbar,
with the availability of limited voltage measurements,” IEEE Trans. “Optimal PMU placement by an equivalent linear formulation for
Power Del., vol. 27, no. 1, pp. 325–336, 2012. exhaustive search,” IEEE Trans. Smart Grid, vol. 3, no. 1, pp. 174–
[10] ——, “Double-circuit transmission-line fault location utilizing synchro- 182, 2012.
nized current phasors,” IEEE Trans. Power Del., vol. 28, no. 2, pp. [34] S. Azizi, A. Salehi Dobakhshari, S. Nezam Sarmadi, A. Ranjbar, and
1040–1047, 2013. G. Gharehpetian, “Optimal multi-stage PMU placement in electric power
[11] Q. Jiang, X. Li, B. Wang, and H. Wang, “PMU-based fault location using systems using boolean algebra,” Int. Trans. Elect. Energy Syst., vol. 24,
voltage measurements in large transmission networks,” IEEE Trans. no. 4, pp. 562–577, 2014.
Power Del., vol. 27, no. 3, pp. 1644–1652, 2012. [35] S. Azizi, M. Sanaye-Pasand, and M. Paolone, “Locating faults on
[12] A. Salehi-Dobakhshari and A. M. Ranjbar, “Application of synchronised untransposed, meshed transmission networks using a limited number
phasor measurements to wide-area fault diagnosis and location,” IET of synchrophasor measurements,” IEEE Trans. Power Syst., vol. Early
Gen. Transm. Distrib., vol. 8, no. 4, pp. 716–729, 2014. Access, 2016.
[13] S. Azizi and M. Sanaye-Pasand, “A straightforward method for wide-
area fault location on transmission networks,” IEEE Trans. Power Del.,
vol. 30, no. 1, pp. 264–272, 2015.
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.