Documente Academic
Documente Profesional
Documente Cultură
Article 230-79 of the NEC states that for a one family dwelling,
the service disconnecting means shall have a rating of not less than
100 amperes, 3-wire under either of the following conditions: (1) where
the initial computed load is 10 kva or more, or (2) where the initial
installation consists of six or more 2-wire branch circuits.
(d) All other installations the service disconnecting means shall have a
rating of not less than 60 amperes.
1
18 feet above a commercial drive and 22 feet above a street.
The ground wire should be, a min # 8 copper unprotected and the
the ground rod 5/8 inch by 8 feet.
The ground wire can be enclosed in conduit, but the conduit must
be solidly connected to the ground rod and the other end. Grounding shall be in
accordance
with Article 250, parts B,C,D,F,G,H and J.
Top of Page
2
Electrical Circuits
My definition of an electrical system is:
3
• The NEC does not contain any requirements that ungrounded or
• grounded conductors be sized to accommodate voltage drop.
•
• Voltage drop affects the efficiency
• of the equipment, but is not a safety issue.
•
• The NEC recommends [FPN's to 210?9(a), 215?(b),
• and 310?5] a maximum of 3% voltage drop for branch circuits, a maximum
of
• 3% voltage drop for feeders, but a maximum of 5% voltage drop overall for
• branch circuits and feeders combined.
• Many people think that when calculating the number of receptacles the
• load should be reduced by 80%, but this is not the case! Yes, the NEC limits
• the load on receptacle circuits to 80% for portable appliances [210?3(a)]
• and, yes, the maximum continuous load on a branch circuit shall not exceed
• 80% of the circuit rating (protection device) [220?(a) and 384?6(c)],
• but these rules don't apply to the number of receptacles per circuit. I
• wish the NEC were more specific, but it's not.
4
There are many Articles that apply to branch circuits, such as
210; Overcurrent Protection, 240; Wiring Methods, 300; Conductors, 310;
Appliances, 422; Electric Space Heating Equipment, 424; Motors, 430;
and Air-Conditioning, 440.
Air-Conditioning, 440.
5
Article 225 contains the following requirements:
structures. The basic rule is that a ground wire is not required if the
Top of Page
6
Wire Size Table
Only one of many, refer to article 310 of NEC:
Wire size is determined by the load computed for the branch circuit.
The load tells you the size of wire to use and the size of the overcurrent
protection to use. Use only 80% of the maximum current capacity of the wire
and the overcurrent protection (breaker or fuse).
TYPES:fepw,rh,rhw,thw,thwn,xhhw,use,zw
Check asterik note table 310-16
*************************************
| AWG | MAX-AMPS |
| ----------------- | --------------|
| 14 15 |
| 12 | 20 |
| 10 | 30 |
| 8 | 50 |
| 6 | 65 |
| 4 | 85 |
| 3 | 100 |
| 2 | 115 |
| 1 | 130 |
| 1/0 | 150 |
| 2/0 | 175 |
| 3/0 | 200 |
| 4/0 | 230 |
| 250 mcm | 255 |
| 300 mcm | 285 |
| 350 mcm | 310 |
| 400 mcm | 335 |
| 500 mcm | 380 |
| 750 mcm | 475 |
7
*************************************
Top of Page
Wiring Hints
When planning the electrical wiring system there are many things to
consider, the location of the service entrance, the size of the service, the
number and size of the branch circuits just to name a few.
8
• Install the light fixtures in the center of the room or
overhead area. Mount them solid, ceiling fans are heavy.
• If there are more than six steps to a stairwell install 3-way
switches for the light.
• Leave enough wire in the boxes to make good
connections, about 2 inches below the wall box. If you leave
them too long there is too much waste and or, the excess wire
will crowd the box possibly causing shorted circuits. If you cut
them too short, you will have loose connections, from not being
able to properly connect the wires. The code requirement is 6
inches.
• Stay within code requirements at all times, if in doubt
check with the ruling authority, electrical inspector, or power
service provider.
Article 37 Hazardous
Locations
Return to Reference Page
The purpose of classification is to provide safe rules for the isolation of ignition sources
from areas of ignitable or potentially ignitable materials.
NATIONAL ELECTRICAL CODE and NEC are registered trademarks of the National
Fire Protection Association, Inc., Quincy, MA 02269
Explanations, Rules and descriptions taken from the National Electrical Code (r)
Articles 500 thru 516. This page does not completly address the subject of Hazardous
locations. For complete rules and regulations you should consult the NEC (NFPA) 70
Articles 500 thru 516 and the FPNs, This article is an attempt to describe hazardous
(classified) locations as they are covered by the NEC.
Hazardous (classified) locations as described by NEC article 500-2 and the Fine Print
Note. Locations are classified depending on the properties of the flammable vapors,
liquids or gases or combustible dusts or fibers that may be present and the likelihood
that a flammable or combustible concentration or quantity is present.
9
By the above statement we see that classifications are broken into three classes
(1)Flammable vapors, liquids or gases, (2)combustible dusts, and (3) fibers or flyings.
Each Class is broken into two divisions, Division 1 being the highest or most dangerous
and Division 2 being the lowest or not as dangerous level.
500-5 says that Class I locations are those in which flammable gases or vapors are or
may be present in the air in quantities sufficient to produce explosive or ignitable
mixtures.
Class I Division 1:
Class I Division 2:
A Class II, Division 1 location is a location in which combustible dust is in the air under
normal operating conditions in quantities sufficient to produce explosive or ignitible
mixtures; or where mechanical failure or abnormal operation of machinery or
equipment might cause such explosive or ignitible mixtures to be produced, and might
also provide a source of ignition through simultaneous failure of electric equipment,
operation of protection devices, or from other causes; or in which combustible dusts of
an electrically conductive nature may be present in hazardous quantities.
A Class II, Division 2 location is a location where combustible dust is not normally in
the air in quantities sufficient to produce explosive or ignitible mixtures, and dust
accumulations are normally insufficient to interfere with the normal operation of
electrical equipment or other apparatus, but combustible dust may be in suspension in
10
the air as a result of infrequent malfunctioning of handling or processing equipment and
where combustible dust accumulations on, in, or in the vicinity of the electrical
equipment may be sufficient to interfere with the safe dissipation of heat from electrical
equipment or may be ignitible by abnormal operation or failure of electrical equipment.
500-7 covers Class III locations; Class III locations are those that are hazardous because
of the presence of easily ignitible fibers or flyings, but in which such fibers or flyings
are not likely to be in suspension in the air in quantities sufficient to produce ignitible
mixtures.
A Class III, Division 1 location is a location in which easily ignitible fibers or materials
producing combustible flyings are handled, manufactured, or used.
A Class III, Division 2 location is a location in which easily ignitible fibers are stored or
handled.
Top of Page 0 covers boxes and fittings.
11