Sunteți pe pagina 1din 7

OKE-5116-103 1

DESIGNING AN INTELLIGENT VOLTAGE INSTABILITY DETECTION


SYSTEM IN POWER DISTRIBUTION SYSTEMS IN THE PHILIPPINES
USING IEEE 14 BUS TEST SYSTEM
CHAN, Ian Benedict, GRAY, Janric Micah F., OCAMPO, Anne Bernadine S., RODRIGUEZ, Pocholo L.
Electrical Engineering Department, Faculty of Engineering, University of Santo Tomas
España, Manila, Philippines

Abstract - The state of an electric power system may be classified as either stable or unstable. The borderline of stability is at any
condition for which a slight change in an unfavourable direction of any pertinent quantity will cause instability. Voltage instability
in power distribution systems could lead to voltage collapse and thus power blackouts. The researchers will present an intelligent
system using back propagation algorithm which detects voltage instability and classifies voltage output of an assumed power
distribution system (PDS) as: stable or unstable.

The researcher’s work is the use of voltage output readings as the input patterns to the neural network for training and
generalizing purposes, thus providing a faster instability detection system that simulates a trained operator controlling and
monitoring the 3-phase voltage output of the assumed power distribution system.

Index Terms— Load Stability, Phase Synchronization, Voltage Collapse, Neural Network, Power Distribution System, 3-phase, Back-
Propagation Algorithm
pronounced, the system integrity is endangered mainly due
to protecting devices that trip generation, transmission, or
I. INTRODUCTION1 load equipment. This degradation process may eventually
lead to a blackout in the form of a voltage collapse. (Glavic,
T he study is focused primarily on researching viable
methods for applying real-time voltage instability
detection algorithms, which may be used to improve the
M. & Cutsem, T.V. 2011).

existing models currently being used by substations here in


the Philippines. voltage instability detection algorithms have II. METHODOLOGY
been in development starting as early as the 1930’s, in high
A. Research Method
voltage transmission lines. since then, there had been major
discoveries on the different parameters which may lead to The application of an intelligent voltage instability
these so-called “instabilities”. the study aims to modify and detection system in distribution lines in the Philippines
configure these algorithms, and hopefully be able to apply it requires a research method which focuses on the
to the systems here in the country. Power system voltage quantitative aspect, but at the same time utilizes a certain
instability results from the inability of the combined degree in qualitative. It is qualitative since the research
transmission and generation system to deliver the power requires initial data system from the Institute of Integrated
requested by loads. Electrical Engineers (IIEE) and interview gathered from
engineers working in the Manila Electric Company about
In many power systems throughout the world, voltage their observations and concerns about the voltage
instability is considered as a major threat for secure instability occurring in the grid. A test system for the
operation. In a voltage unstable situation, the voltage drops IEEE 14 Bus system was used for the data that is needed
undergo a dramatic, generally monotonic, decline in the for the training of the model that will be used for the
minutes following a disturbance. When this decrease is too prediction of the voltage instability. These initial
parameters of the test system were altered and varied
using MATLAB. The values obtained will be the
1 Rodriguez, Pocholo L. was with University of Santo Tomas,
information needed to be trained to the WEKA program in
Philippines. He is now with Colegio de San Juan de Letran, College of
Engineering and Information Technology (email:
which the researchers will use for the detection system of
rodriguezpocholo12@gmail.com) the voltage instability.
Ocampo, Anne Bernadine S. was with University of Santo Tomas,
Philippines. (email: Ocampo.annenadine@yahoo.com) From there, the additional information accumulated will
Chan, Ian Benedict was with University of Santo Tomas, require supporting details. These details are where the
Philippines.
Gray, Janric Micah F. is now with University of Santo Tomas,
quantitative research method comes into the picture. The
Philippines. said research method will have a major part in the study
since the numerical data will be used in order to generate A. Training Phase
facts and discover patterns in the research.

B. Research Design

This study aims to apply an intelligent detection system


for voltage instability in transmission lines going to the
distribution system in the Philippines. It exercises the use
of quasi-experimental research design, particularly the
Single-Sample Repeated Measures. Since IEEE 14 Bus
system is a reliable source is “the world's largest technical
professional organization dedicated to inspire a global
community to innovate for a better tomorrow through its
highly-cited publications, conferences, technology
standards, and professional and educational activities.
IEEE is the trusted “voice” for engineering, computing
and technology information around the globe” (IEEE,
FIGURE 1.2. Testing Flow Chart
2016). Through that, the researchers are going to
manipulate some of the dependent variables to utilize the
For the training phase, this is the phase where the group
effectiveness, performance and efficiency of the said
system. This research focuses on aspects such as “Why” builds the model/system. The training points are fed into
and How” of things. In order to check the criterion ANN (Multilayer Perceptron) classifier and did a validation
mentioned, the researchers will use the programs WEKA testing (model testing). The technique used is 10-fold cross
and MATLAB to simulate the voltage instability in the validation technique. Cross validation partitions the training
lines, and to manipulate the necessary variables. dataset into 10 equal subsets. 9 of the subsets are used for
the training model and the 1 left is used for validating and
After using the said programs, the researchers will now testing the model, repeated for K (10) times (called as
use the analysis gathered in order to develop an intelligent folds), then each of their results are averaged to get a single
system. The system created is based on the results of the estimate. (Note: Each subset is used as validation set).
program which has been manipulated to maximize its
effectiveness, performance and efficiency with respect to
the voltage instability in the distribution system. B. Testing Phase

III. FLOWCHART
Flow chart of WEKA program of a simulation of voltage
instability predictor:

FIGURE 1.3. Testing Flow Chart

FIGURE 1.1: Full Flow Chart For the testing phase, the researchers used command
prompt to type in the prediction testing script, then the
Based on the whole flow chart, on the Data part, the results are transferred to excel file, then performed
group separated the number of instances into 80% training accuracy. The result of this process will then be evaluated
and 20% testing and it is fed to the training phase. by the researchers in order to see the accuracy of the
prediction of the system before incorporating it to
distribution systems.
OKE-5116-103 3

The accuracy will depend on the number of data has a voltage value of 1.0 + j 0 P.U. The voltage-controlled
processed by the system and is then subject to improvement bus however, has voltage control capabilities. Instead of a
as stated in the recommendation of the paper. generator, it has tap-adjustable transformer and/or a static
VAR compensator.
IV. SIMULATION RESULTS
Designing a system requires training and sample points The load buses are the ones subjected to study in this
that will be made as a basis of the system. There are data paper since real power and reactive power are known
that needs to be properly checked and evaluated whether it variables. This is because the researchers intend to vary the
is correct or not. In order to check the efficiency of the load and locate and study what instance of load does it
system, with the help of the group’s chosen program, a cause a voltage instability.
legitimate sample of dataset was obtained from WEKA. The These load variables are obtained from IEEE Bus 14
data set that the researchers will use will come from the System, and since voltage magnitude and voltage angle are
result of the simulation of the IEEE 14 Bus Test System in unknown, this instance prove to be a good scenario for this
MATLAB. thesis so that voltage behavior can be observed.
The data set will then be used for the training of the
model from WEKA that will be used for the detection and The researchers have then varied the IEEE 14 Bus Test
prediction of the voltage instability. All the buses included
System 24-hour load profile with respect to a certain
in 24-hour load profile table are load buses. The following
percentage in its load and fed the data to MATLAB in order
buses included in the load profile will be subjected to the
to generate the data needed and to determine on what
testing process to be incorporated in the code in WEKA’s
interface (see Appendix A for 24 hour load profile). percentage of load variation the load instability occurred.
The extent of the detection system for voltage instability
covers the behavior of the load buses for 1 day (24 hours).
The initial data for the system was accumulated from a
reliable source which is IEEE 14 Bus System 24-hour load
profile. As observed, the load (P & Q) is varied every hour
for 24 hours. The values where used as the current load data
of respective buses in WEKA, subject to change per hour.

A. MATLAB Load Profile


TABLE 1.2. 6AM Varied (10%) Load Profile

Table 1.2 indicates a case of load profile in which the


researchers have taken into consideration in the detection
system. Since an increase in load is a factor for
susceptibility in voltage instability of the system, the load is
then varied. As stated in “Voltage Stability Assessment in
Power Network Using Artificial Neural Network,” an
increase in 5% in the voltage can already be considered
unstable. Keeping that in mind, the researchers modified the
initial load parameters (P & Q) from the 24-hour load
profile in IEEE by an increase in 10%, 30%, and 50%. This
TABLE 1.1 6AM Load Profile is to further analyze what specific increase in load will have
a counterpart effect to make the voltage unstable. Looking
The sample case of IEEE 14 BUS SYSTEM indicated at all the tables, it is observed that Bus 14 proved to be the
above represent a brief representation of the initial stable weakest link among all the bus since it experiences constant
values used in the system of WEKA. This is incorporated in voltage violation for every increase in load for all cases.
Matlab in wherein the parameters under study are voltage, The red highlight indicates that the specific bus exceeds
load real power, and load reactive power. the nominal voltage by a minimum of 5%. Bus 14 has been
As such, the basis for load parameter are from the 24- consistent for having a red highlight which means it is
hour load profile, and the researchers used MATLAB so sensitive to voltage violation with just a mere increase in
that variation of the load will correspond a reliable voltage load. Buses 1, 2, 3 6, 7, 8 are the buses that least likely for
change based on Gauss-Seidel Method. voltage violation to occur. In all the cases, even an increase
Also by referring to the table above, the 14 buses have of 50% in the load, the said buses still don’t experience
different types: Slack Bus, Load Bus, and Voltage- voltage instability. The rest of the buses that wasn’t mention
Controlled. Slack Bus is implied as the reference bus and have at least once experienced voltage instability.
must be capable of supplying total losses in the system. It
B. WEKA Data Attributes For next value of load reactive power in bus 2, the value
is 0.05
And so on and so forth for the next buses.

C. Artificial Neural Network

FIGURE 1.3. WEKA Data Attributes

The figure above shows the code inputted by the


researches needed for training the model in WEKA. The
code shows the prediction training of the values which
determines whether the given set of values is stable or
unstable. They indicate the condition or the classification
and declare the type of parameter of a given set of inputs. FIGURE 1.4. Generated Artificial Neural Network
These attributes are arranged vertically and shows the
parameters such as voltage, real power and reactive power The Neural Network of the dataset is obtained from
of the load per bus. The buses included in the detection WEKA. For this paper’s study, a neural network is obtained
system are Bus 2, Bus 3, Bus 4, Bus 5, Bus 6, Bus 9, Bus using the features/attributes stated in this study. After
10, Bus 11, Bus 12, Bus 13 and Bus 14. Theses buses are successfully doing the folds of the system, the group has
under the category of load bus that’s why they are subject to built the model and the model log together with its
observation and analysis in the study. Bus 1, Bus 7, and Bus summary. This model is reliable since the information fed to
8 are not included in the code because they are slack bus or WEKA has undergone series of learning and pattern-
voltage-controlled bus wherein their voltages are constant recognition to derive a stable prediction system. From this
and can be manipulated. Looking back at the figure, the model log, it will show different visualizations like margin
“@attribute cur_” of voltage, voltage angle, load real power curve, threshold curve, cost/benefit analysis, and cost curve.
and load reactive power means that it is the parameter’s This generated model from WEKA will be the one used for
current and initial values. It is their data when t=0. The prediction and in line with that, it is best to test the accuracy
“@attribute next_” code however indicates the parameter’s of the model by testing it with a test data.
next values after being subjected to a change in time. For
easier understanding of data, these represents the values of
voltage, and real and reactive power when t=1. As such,
each data of load bus is taken into consideration in the code.

For a given set of attributes, there is a respective and


corresponding value for each voltage, real power and
reactive power for every load bus. This is indicated in the
figure above. The data is listed horizontally respective of
the type of parameter indicted vertically in the attributes
code. The values included are in per-unit basis. To make
things clearer, by looking at the attribute code and input
data in WEKA, it shows that:
For current voltage in bus 2, the value is 1.045
For current voltage angle in bus 2, the value is 0
For current load real power in bus 2, the value is 0.217
For current load reactive power in bus 2, the value is
0.127
For next value of voltage in bus 2, the value is 1.045
For next value of voltage angle in bus 2, the value is
28.138
For next value of load real power in bus 2, the value is FIGURE 1.5. Actual Artificial Neural Network Design
0.217
OKE-5116-103 5

A neural network usually has 3 basic layers, namely the inaccurate. The accuracy of the prediction was only
input layer, hidden layers, and the output layer. From the 80.18%. This is because the code in WEKA doesn’t
neural network, the attributes declared on the data is indicate a right or wrong in a given set of inputs and thus, it
analyzed and processed by WEKA with declaration of is the system’s job to study and create computational pattern
values that result to a specific output, namely stable or from the input to provide a reliable and accurate detection
unstable. These attributes serve as the input layer and system. It has to study intensively the given values to
parameter of the artificial neural network. When predict a stable value. Because of this, the prediction
processed by WEKA, relationships and patterns are to be obtained a low percentage in accuracy.
generated in the form of weights, which is the lines
connecting the attributes to the neurons
V. CONCLUSION
These weights are usually multipliers that can be seen
Voltage instability was found to be a significant
from the model data generated by WEKA. These weights
impediment on the efficiency and safe operation of power
are then fed into the hidden layers and then
systems, causing fluctuations in the actual voltage readings
assessed/studied by the hidden layers with neurons to
in the power system, which may then lead to the so called
further identify relationships and perform back
“voltage collapse” or blackouts when left unchecked. The
propagation process to minimize the error and increase the
researchers had proposed an early voltage instability
integrity of the system.
detection system based from the PMU’s as input
D. Prediction Accuracy components which then utilize the artificial neural network
to predict the onset of a voltage collapse.
Designing an intelligent detection system for voltage
instability detection requires intensive study in order for the
research study to be effective and efficient. The researchers
gathered data from IEEE 14 Bus System and incorporated it
into the program WEKA. From there, programming
techniques were used in order to create a system that can
detect whether the voltages accumulated are unstable or not.
In totality, the researchers therefore concluded that
detecting voltage instability in the distribution grid is a
FIGURE 1.5. Accuracy Results possibility. WEKA is a favorable program to be used for
detecting voltage instability since it can easily adapt to new
From the figure above, different parameters/results can be inputs based from its learning and study derived from
seen. This is the prediction output of the system based from previous computations by taking into consideration real-
a given set of codes indicated from previous discussions. time basis. Methods such a Gauss-Seidel for variation of
These codes are derived from command prompt and copied load parameters and Artificial Neural Network for
to excel for more clarity of output. Instances, the first generating accurate outputs proved to be a viable option for
training and generating a model for the system. With this
column, represent the number of entries the test data has. In
paper, voltage instability will be detected and thus pave way
the 2nd column, the “actual” column shows the actual result
for distribution utilities to make their response the more
that the test data has. This indicates the ideal voltage
efficient and minimize further casualties such as brownouts
condition the detection system should predict based from its and blackouts from prolonging longer. Since the detection
measured value. The “predicted column” in the 3rd, shows system proved to be viable to detect bus location and time
the predicted results of the detection system using the model which violation occurs, repair response time will be
generated from WEKA or in any case, the output. The error shortened and maximize time efficiency. An increase or
column will determine whether there is an error or none in decrease of 5% in voltage can be further identified for the
the prediction stage. The (+) sign indicates that an error is system to be unstable.
detected, whereas no sign indicates that the predictions were
correct. The prediction column in the 4th however, VI. RECOMMENDATIONS
represents the prediction accuracy of the system. In Figure In applying this study, the researchers recommend that
A4, 1 from the 2nd row indicates that the system correctly the engineer check for the compatibility of the algorithm to
detected the first entry with a confidence level of 50.2%. In the distribution system for practicality purposes. The system
the first row with the error the system depicted the entry by had only been tested, at present, on the inputs from the data
1. This means that the system is 100% sure that the output gathered exclusively from IEEE 14 Bus System. The study
WEKA has predicted is wrong and inaccurate. As such, the was conducted primarily on the notion that voltage
next column shows the bus location and time (24 hour instability was a problem that the distribution utility faces.
setting) where and when the voltage violation had occurred. An advancement to this study is also to specify what kind of
The 1’s and 0’s in the last column indicates whether the load is the bus under observation, whether it is residential,
system is accurate or not, 1 being accurate and 0 being commercial, or industrial. Likewise, it is also better if the
system can determine what increase in load does the voltage REFERENCES
violation occurred. That way, the nature of the parameters  Ainsworth, J. D., Gavrilovic, A., &Thanawala, H. L. (1980)
indicated in the bus as well as the instance of time where Static and Synchronous Compensators for HVDC
voltage instability occurs can be further comprehended and Transmission Convertors Connected to Weak AC Systems. In:
28th session CIGRE, pp 31–41
observational pattern can be acquired.
 Andersson, G., Donalek, P., Farmer, R., Hatziargyriou, N.,
APPENDIX A. 24 HOUR LOAD PROFILE Kamwa, I., &Kundur, P. (2005) Causes of the 2003 major
grids blackouts in North America and Europe, and
Recommendation Means to Improve System Dynamic
Performance. IEEE Trans Power Syst 20(4): 1922–1928.

 Bar-Yam, Y. (1997). Dynamics of Complex Systems. Addison-


Wesley.

 Berizzi, A. (2004). TheItalian2003 Blackout. In IEEE: Power


Engineering Society General Meeting.Denver, CO, pp
1673–1679.

 Cutsem, T. V., &Mailhot, R. (1997) Validation of a Fast Voltage


Stability Analysis Method on the Hydro-Quebec system.
IEEE Trans Power Systems 12(1): 282–292

 Cutsem, T. V., &Vournas, C. D. (1998) Voltage Stability of the


APPENDIX B. TREE VISUALIZATION Electric Power Systems. Kluwer Academic,
NorwellDECISION - ERC Case No. 2005-280 MC - In the
Matter of the Application for Authority to Implement
Major Capital Projects for Year 2006, with Prayer for
Provisional Authority - Angeles Electric Corp. (AEC)
(7/6/2006), available on line- www.erc.gov.ph.

 DECISION, ERC Case No. 2005-010 RC, In the Matter of the


Application for Approval of the (A) Renewal of Electricity
Purchase Agreement and (B) Extended Electricity Purchase
Agreement (EPA) entered into and between Angeles Electric
Corporation (AEC) and Angeles Power, Inc. (API), with
Prayer for Provisional Authority (5/3/2006), available online-
ACKNOWLEDGMENT www.erc.gov.ph.
The researchers would like to thank all those people who
 Glavic, M. (2012). A short Survey of Methods for Voltage
have been very supportive throughout the research and Instability Detection.
those who assisted them in finishing the research.
 Gonen, T., Electric Power Distribution System Engineering,
First and foremost, the researchers would like to thank McGraw-Hill Book Company, New York, 1986
Engr. Danilo C. Guinto, Jr. their EE 515 thesis adviser, for
his valuable insights in aiding the progress and  Guide to WECC/NERC Planning Standards I.D: Voltage Support
and Reactive Power, March 30, 2006, Western Electricity
conceptualization of the research study. Coordinating Council (WECC), available on line-
The researchers would also like to thank Engr. Hyson http://www.wecc.biz/modules.php?op=modload&name=Downl
oads&file=index&req=viewsd ownload&sid=100
Peter R. David, the research project instructor for his
commitment in guiding the researchers in the correct  Hossain, M. J., Pota, H. R., &Ugrinovski, V. (2008) Short and
Long-term Dynamic Voltage Instability. In: 17th IFAC World
process flow of the study. Congress, Seoul, Korea, pp 9392–9397
The researchers would also like to thank the UST
Electrical Engineering Department who lent a helping hand  IEEE (1990) Special publication 90TH0358-2-PWR: voltage
stability of power systems: concepts, analytical tools, and
and gave meaningful advice upon working and finishing the industry experience
research. Moreover, the researchers would like to thank
 Kundur, P., Power System Stability and Control, McGraw-Hill,
their parents for supporting and guiding them in finishing 1994
this study.
And most of all, the researchers would like to thank the  Kundur, P., Power Systems Stability and Control, McGraw-Hill,
New York (1994) pp-959-1024.
Almighty God who guides them from the start till the end of
the research.  Li, F., Zhang, W., Tolbert, L. M., Kueck, J. D., &Rizy, D.
T.,"Assessment of the Economic Benefits from Reactive
Power Compensation," IEEE Power Systems Conference and
Exposition (PSCE), October 29 - November 1, 2006, Atlanta,
Georgia, pp. 1767-1773
OKE-5116-103 7

 Lu, W., Besanger, Y.,Zamai, E.,&Radu, D. (2006). Blackouts:


Description, Analysis and Classification. In: 6th
WSEAS International Conference on Power Systems, pp
429–434.

 Mark Hall, Eibe Frank, Geoffrey Holmes, Bernhard Pfahringer,


Peter Reutemann, Ian H. Witten (2009); The WEKA Data
Mining Software: An Update; SIGKDD Explorations,
Volume 11, Issue 1.

 McCulloch, W., & Pitts, W., (1943). A Logical Calculus of the


Ideas Immanent in Nervous Activity. Bulletin of
Mathematical Biophysics, Vol. 5, pp. 115-133.

 Ohno, T.,&Imai, S. (2006). The1987 Tokyo Blackout. In


IEEEPES: Power Systems Conference and
Exposition. Atlanta, GA, pp 314–318.

 Philippine Grid Code, Energy Regulatory Commission, San


Miguel Avenue, Pasig City, Philippines, available on line-
www.erc.gov.ph.

 Saha, T. K., & Ha, L. T.,“Investigation of Power Loss and


Voltage Stability Limits for Large Wind Farm Connections to
a Subtransmission Network”. IEEE Power Engineering
Society General Meeting, 6-10 June, 2004, Denver, Colorado,
USA.

 Summary of WECC Voltage Stability Assessment Methodology,


Western Electricity Coordinating Council (WECC), available
on line-
www.wecc.biz/modules.php?op=modload&name=Downloads
&file=index&req=g etit&lid=11 03

 Taylor, C. W. (1994) Power System Voltage Stability. McGraw-


Hill, New York

 Taylor, C. W., Power System Voltage stability, McGrawhill,


1993.

 U.S. Canada Power System Outage Task Force(2004).


FinalreportontheAug14, 2003 blackout in the United States
and Canada: causes and recommendations

 Vassell, GS. (1991). Northeast Blackout of 1965. IEEE Power


Eng Rev 11(1): 4–8.

 Voltage Stability Criteria, Undervoltage Load Shedding Strategy


and Reactive Power Reserve Monitoring Methodology, May
1998, Western Electricity Coordinating Council (WECC),
available on line:
http://www.wecc.biz/modules.php?op=modload&name=Dow
nloads&file=index &req=e wsdownload&sid=100

 Vournas, C. D., Sauer, P. W., &Pai, M. A. (1996) Relationships


Between Voltage and Angle Stability of Power Systems. Int J
Electr Power Energy Syst 18(8): 493–500

S-ar putea să vă placă și