Documente Academic
Documente Profesional
Documente Cultură
HYDRAULIC CALCULATION
CIVIL
CONTRACTOR DOCUMENT REVIEW R
E MECH
V
LOG DATE : I
ELEC
IN COMM. NO : E I&C
W
A APPROVED PROCESS
B APPROVED AS NOTED D
CONTRACTOR
C NOT APPROVED I RECORD
S
I INFORMATION T PLN PUSMANKON
R PLN UIP NUSRA
APPROVAL DOES NOT RELIEVE CONTRACTOR I
FROM RESPONSIBILITY FOR ERRORS OR B
DEVIATIONS FROM CONTRACT REQUIREMENTS U
T
BY : DATE: I
O
LOG DATE : N
OUT COMM. No. :
CONTRACTOR
CONSULTANT
GLPP-000200-SGA-S1-CS-004 AREA
JOB NO : 17-12318
PAGE : 2 of 8
DISTRIBUTION LIST
PP PLN
PAGE : 3 of 8
PAGE : 4 of 8
TABLE OF CONTENT
Section Page
1. PURPOSE ........................................................................................................ 5
2. REFERENCE ................................................................................................... 5
3. DESIGN INPUT ................................................................................................ 5
4. METHODOLOGY ............................................................................................. 6
5. RESULT ........................................................................................................... 7
JOB NO : 17-12318
PAGE : 5 of 8
1. PURPOSE
This document is prepared as Process Hydraulic Calculation for Fire Water System of the project scope
of work defined in Lombok GECC/GTCC Power Plant (Peaker) 130 – 150 MW . The purpose of this
study is to calculate the pressure drop in the fire water lines and to ensure the pressure in the process is
enough to flow the fluid to its destination.
2. REFERENCE
The following documents are used as references for Hydraulic Calculation:
• Contract Document “Lombok GECC/GTCC Power Plant (Peaker) 130 – 150 MW”.
• Basic Engineering Design Data, GLPP-000200-ZEN-P1-BE-001 Rev 0.
• Process Design Basis, GLPP-000200-ZEN-P1-BR-001 Rev 0.
• Piping and Instrumentation Diagram for Fire Water System, GLPP-000200-SGA-S1-EF-001 Rev 0.
• Layout Fire Fighting Equipment, GLPP-000200-SGA-S1-GA-001.
• General Plot Layout, GLPP-000500-ZEN-GO-PP-001.
• Fire Water Pump Data Sheet, GLPP-000200-SGA-S1-DS-002.
• Jockey Pump Data Sheet, GLPP-000200-SGA-S1-DS-001.
3. DESIGN INPUT
a. Discharge Fire Water Pump
Table 1. Design Input for Hydraulic Calculation of Discharge Pump
Variable (unit) Value Remark
o
Temperature ( C) 27.4 BEDD
2 Discharge Pressure Fire
Initial Pressure (kg/cm g) 8.5
Water Pump
Flowrate (m3/hour) 283.9 Pump Datasheet
Density (kg/m3) 1006 HYSYS
Viscosity (cP) 0.8437 HYSYS
Pipe Diameter (mm) 200 Line Sizing
Elevation Change (m) - assume
Pipe Length (m) 68.7 Piping Layout (Assume)
Fitting: Assume
Swing Check Valve 1
Butterfly Valve 1
Elbow 90o 3
Tee as Elbow 2
.
b. Distribution Ring 1
Table 2. Design Input for Hydraulic Calculation of Distribution Ring 1
PAGE : 6 of 8
c. Distribution Ring 2
Table 3. Design Input for Hydraulic Calculation of Distribution Ring 2
d. Farthest Hydrant
Table 4. Design Input for Hydraulic Calculation to Farthest Hydrant
4. METHODOLOGY
Hydraulic Calculation will be simulated by using software ASPEN HYSYS ver 8.8. HYSYS calculate
pressure drop on pipe which is caused by elevation change, fitting and pipe length. Pipe Diameter,
Properties of fluid, and fitting are used as data input for the simulation.
JOB NO : 17-12318
PAGE : 7 of 8
5. RESULT
Table below indicates the summary of hydraulic calculation result:
No. Description Quantity Initial Residual Min. Destination Remarks
(m3/hr) Pressure Pressure Pressure
(kg/cm2g) (kg/cm2g) (kg/cm2a)
1 Discharge Fire Water 283.9 8.5 8.2 - OK
Pump
2 Distribution Ring 1 142.2 8.2 7.9 - OK
3 Distribution Ring 2 141.7 8.2 7.9 - OK
4 Farthest Hydrant 283.9 7.9 7.7 7.0 OK
JOB NO : 17-12318
PAGE : 8 of 8
ATTACHMENT A
HYDRAULIC CALCULATION