Documente Academic
Documente Profesional
Documente Cultură
No. 61 (1999)
Funding for this project was provided by the Cement and Concrete Association
and the Building Research Levy.
ISSN: 0111-7505
EARTHQUAKE LOAD SHARING BETWEEN TIMBER FRAMED AND MASONRY
WALLS
G. J. Beattie
Senior Engineer, Building Research Association of New Zealand
SUMMARY
The lateral load resistance of lightly reinforced masonry walls has always been thought to be quite different from that of
timber framed walls. Timber walls were expected to respond to earthquake loading in a ductile fashion while masonry
walls were expected to behave in a brittle manner. These differences made it difficult to design structures that
incorporate both of these common forms of construction. Since the introduction of the non-specific design standards, it
is now recognised that lightly reinforced masonry walls have a limited amount of ductility, which reduces the bracing
demand. Additional ductile capacity is available in the connections between masonry walls and the ceiling. This was
quantified experimentally. The distribution of lateral force between masonry and timber framed walls was examined in
some typical structures by computer modelling. It was found that the stiffness of a masonry wall system incorporating
the bolted and nailed joint, is not significantly different from that of a timber framed wall system when there is a bolted
and nailed joint at the ceiling to wall junctions. The distribution of lateral load between walls may be obtained using
tributary areas when these joints are used. Diaphragm action must also be considered when there are continuous ceiling
“chords” perpendicular to the bracing walls. Without the presence of diaphragm action, the loads can be distributed on
the basis of tributary area.
It can be seen that the reduction in bracing units using To better replicate the continuity present at the outer
NZS 4203:1992 is very significant and drops to as low edges of the panel and also model the effects of
as 40% of the NZS 4229 requirements. This reduction discontinuities such as doors and windows within the
is caused partially by the recognition that lightly panel, a number of 6.4 m long walls have been subjected
reinforced non-specifically designed masonry walls are to racking tests [9]. Figure 2 gives a typical hysteresis
more ductile than was previously assumed. loop for one of these walls in which plasterboard was
fixed on one side.
In contrast to the above, a comparison [2] of the bracing
requirements of NZS 3604 [7] and those derived from
Timber Partitions Masonry Partitions
Zone A Zone B Zone C Zone A Zone B Zone C
150 series 13 (25) 10 (20) 6.5 (15) 18 (30) 14 (25) 9 (20)
+ veneer 18.5 (30) 14 (25) 9 (20) 24 (40) 18 (35) 12 (30)
0
shown in Figure 3.
-25 -20 -15 -10 -5 0 5 10 15 20 25
-2
-4
-6
-8
Displacement mm
10
5
Load (kN)
0
-30 -20 -10 0 10 20 30
Figure 3: 6.4 m long wall in the racking test rig
-5
-10 The masonry wall was 4.6 m long and consisted of two
linked shear panels 1 m and 1.4 m long with window
-15 and door openings between, to represent a typical
Displacement (mm)
section of exterior wall. Only the cells containing
Figure 2: Load-displacement hysteresis loops for 6.4 vertical reinforcement and the top two courses forming a
m timber frame lined with plasterboard on one face bond beam were grouted. A view of the masonry wall
during testing is given in Figure 4 and the corresponding
During the early cycles to 6 mm, the joints between the load-displacement plot is shown in Figure 5.
plasterboard sheets had opened and this gap width
increased as the wall displacement increased. By the
The difficulty arises in distributing the lateral forces in a
house which has both masonry and timber framed walls.
For a house with a rigid diaphragm ceiling or roof and
no torsional eccentricity, then the assumption that the
lateral capacity of the whole is the sum of that of the
parts is clearly incorrect. This is because when the
stiffer masonry wall is at its ultimate strength the
displacement of the adjacent more flexible timber walls
will be less than that required to reach their ultimate
strength.
Clearly, the strength of the masonry wall is considerably While NZS 4229 requires M12 cast in bolts at 1200 mm
greater than the timber framed wall. Notice that the centres for fixing the plate or the stringer to the wall,
deflections at the peak load are similar in one direction. often builders will substitute proprietary expanding
In the other direction, to achieve peak capacity the masonry anchors of the same strength for ease of
timber framed wall is required to displace about one and construction. The bolted connection is expected to have
a half times as far as the masonry wall. some flexibility in either case.
Gable end in
masonry
construction
M12 bolts at 1200 crs to stringer
Building strap and solid
Wall plate blocking to ceiling joists
300mm
Ceiling
joist
Batten Ceiling diaphragm
fixed to stringer
Ceiling diaphragm
fixed to plate
M12 bolts at 1200 centres
to wall plate
(a) (b)
Figure 6: Alternative fixings for ceilings to masonry walls
Ceiling Top
joist plate
Wall framing
0 It is clear from the plot that the masonry wall and the
-20 -10 M12 cast-in bolts individually have high initial
-5 0 10 20
stiffnesses. However, when they are combined with the
-10 M12 bolt stiffness of the nailed joint to the ceiling, the stiffness of
-15 Match the system is markedly reduced. The system stiffness is
comparable to the stiffness of the wall lined with
-20
Joint Slip (mm)
plasterboard on both sides and the wall lined with
plasterboard on one side and fibre-cement board on the
Figure 10: Third cycle peaks and the best fit curve other.
TABLE 4
DETAILS OF HOUSE MODELS
20 PB = plasterboard
Model # Dimensions (m) Details
FC = fibre cement sheet
PB both sides
18 Timber framed end walls with plasterboard lining and one central masonry wall
1 16 x 8
PB & FC
Timber framed end walls with plasterboard lining and fibre-cement board
2 16 16 PB
x 8 nails
cladding
14 Masonry wall at one end, timber framed central wall with plasterboard lining both
3 16 PB&Bolt&Masonry
x8
Load (kN/m)
faces and timber framed end wall with plasterboard lining and fibre-cement board
12 Masonry cladding
Masonry end walls and two timber framed walls lined with plasterboard on both
4 10 16 M12
x 8 bolts
faces, each at 6 m from the end
8 Timber framed end walls with plasterboard lining and five masonry walls spaced
5 14 x 7.4
randomly between
6
Masonry end walls and a mix of two plasterboard lined timber framed and three
6 16 x 8.5
4 masonry interior walls
2
0
0 0.5 1 1.5 2 2.5 3
Displacement (mm)
Figure 11: Comparison of Stiffnesses Normalised to Loads per Metre