Installation and Use Manual

TMS810

Carrier

Intelligence Central Air conditioner Room Constant Temperature Controller

Dear customers,
Thank you very much for selecting the productions of our company for use. Before you using it,
please read the manual carefully first.
At the same time of offering reliable production, we will also offering prefect technical auspice
and post-service.
Please contact us immediately, if you have any question.
Thank you for another time.
1 Production outline
This controller is a numerical indications type central air conditioning constant temperature
controller, applies to control the fan coil which at the tip of central air conditioner, controls the
three wind speed of fan coil、two phrase motorized valves or three phrase motorized valves, and
also controls the electromagnetism valves and wind valves .
The panel button from the left to right is: the menu key: the set temperature to be up“+”
FAN speed、the set temperature to be down “”、systematic switch 。
There is a professional setting button under the right(programmed、manual-replacement、
5Vpower)
2 Technology data
Rated voltage: 220VAC/ 50HZ
Self Power Consumption: <1.5W
Load Current: <3A(Anti-load)
Temperature controlling precision: ±1℃
Constant temperature range: 5-35℃
Dimension : 86mm×86mm×12mm (Height×Width×Thickness)
Material and Color: white PC engineering plastic
3 Mainly function & feature
3.1LCD display in English, outputting signal by osculation of relay.
3.2Four kinds of wind speed pattern designed, slow, middle, high and automatic, Under automatic
wind, it can display the indeed working wind speed.

3.3Anti-dewfall function, it will go on running for 30 seconds after the valve closed.(air blower
controlled)
3.4Three phrase motorized valve can be connected (coupling or tee), and be compatible two phase
motorized valve, electromagnetism valve or wind valve.
3.5Temperature setting range : 5.0―35.0℃, Room temperature display range : 1.0―40.0℃
Temperature controlling precision: ±1℃, Temperature demonstration resolution: 0.1℃
3.6 Timed to turn on and off in 24 hours. And the adjustment step of walk into is 0.5h (30
minutes)
3.7 Function of sleeping to keep the room temperature is comfortable, economical and
energy-conservation.
3.8 Room temperature correct: push the key to correct the room temperature measuring value
directly.
3.9 Programmed local to choose the air blower to controlled or not, it will replace or wait when
the power supplying again after it broken down.
3.10 EL backlight source with pure blue color.
4 Manual of installation
4.1 Must be installed and operated after the electricity is off, or it is easy to damage the system
unit.
4.2Select the correct position to install, and don’t install the product in the position where the sun
shines directly or wet position.
4.3Work Surrounding Temperature : -5.0℃―+40℃
4.4Relative humidity: the Max. relative humidity <92%(anti-dewfall)
4.5 If the product is installed in washing, please use special-purpose waterproof face guard.
5 The Installation Dimensional Drawing
5.1the installation dimensional drawing of the back-cover

5.2 the standard linking principle diagram

1
ON 2

OF F 3
L 4
M 5
H 6
7

Live wire Op e n v a lve C lose va lve Lo w Mid d le hig h Nil line Live wire

6 Installation Step
Join the driver board (the power board ) of controller well up to the air blower coil 、the motorized
valve (electromagnetism valve or wind valve ) and the mains line according to the installation
diagram .
Join the arrange lines of the LCD mother panel and power mother panel well up. (Ps. Note to the
direction.
Lift the back cover of the LCD mother panel off, and urge the power mother panel into the buried
dark box in advanced.
Fix the back cover with the screw. Merge the panel and the back cover into one, and the
installation is over.
7 The button and the showing explanation
8 Initial Establishment
8.1The establishment be dispatched from the factory, The FAN speed: Auto
The running mode: COOL
The Set temperature: 25℃ no function of sleep or timed
8.2The first time of setting up an electric circuit: system closed
9 The Button Function And Operation
9.1Be sure the power has inlet then pull the professional setting button to left.
9.2
the systematic switch, press to choose the state of be ON or waiting , and the first
time to be the state of waiting.
9.3 the menu key, and the regulation order is: temperature setting 、timed for ON or
OFF、choosing COOL/HEAT running mode 、choosing SLEEP function 、replace to the back
state
9.4 FAN Speed Switch , four FAN speed of L、M、H and Auto.
9.5 set temperature to be up or adjust the set value of menu
9.6 set temperature to be down or adjust the set value of menu
10 Simple-easily Operating Legend (goes on after the right installation)

Press , letting system be on


Be awaiting state of power inlet (pull the setting switch on)

Press to adjust the FAN speed


Press to adjust the temperature

11 operating technological process of menu function


11.1 adjusting the set temperature
Press One tim e

The se tting te m p e ra tu re to b e d o wn.

Withd ra wa l hyp o thesis

c Go on to the next m enu

10.2 Setting about timed for be OFF (at the condition of ON)
Pre ss Two tim e

按 键4次
12.Correct the room temperature measuring value
Because of the different installed position and air circulation ,so it is necessary to correct or
compensate the room temperature of system, and the correcting value is:±6℃.

“+” 0.1OC 1 the room temperature to be up for 0.1℃


“-” 0.1OC1 the room temperature to be down for 0.1℃
Let the button go and withdrawal hypothesis

13. Sleep Function


This function is direct against the night sleeping, and change the set temperature automatically
according to the needs of the body needs to the surrounding. Do the effect of comfortable,
economical and energy-conservation.

The change of set temperature as follows:

13.1 running state of cooling


1h time

设定温度自动提升
+2 O C
O
睡眠取消,
+1 C 按原设定值继续运转。

1小时 8小时
时间 Tim e

13.2 running state of heating


Hypothesis temperature automatic drop

Se t tim e

Hyp othe sis te m pe ra ture a uto. Drop


O
-1 C
- 2 OC
-3 O C

Time
0. 5小时 8小时

14 Changing state of Auto speed


14.1 Under the condition of automatic wind, it can display the indeed work wind speed.
If it shows 1only, it means that the air blower has stopped running. (Showing as follows)

c c

Auto: running with M-speed Auto: the air blower has closed.
15.Professional setting (operating by the professional person)
15.1the entering way: pull the setting switch to left, at the same time of pressing , turn the
setting switch to right. Using 1、2 to adjust the setting value, and press to select the serial number
of mode.
Way of being out: closing the setting switch to restart it.
legend of interface:
Serial number of mode
Setting value
Programmed data table:
Mode Setting value Meanings Initial Establishment

0 30 Air blower controlled 32


32 Air blower un-controlled
1 0 Be waiting state when power 0
supplying again after it broken down
1 Be replacement when power
supplying again after it broken down

Mode o Mode o: air blower controlled applies to the tip-system that does not install motorized
valves (water valves), in other words is that: the air blower will stop letting the wind out when the
room temperature reaches to the setting value.
Air blower controlled applies to the tip-system that does not install motorized valves (water
valves), in other words is that: the air blower will stop letting the wind out when the room
temperature reaches to the setting value.
Air blower un-controlled applies to the tip-system that installing motorized valves (water valves),
in other words is that: the valve stop but the air blower will go on running when the room
temperature reaches to the setting value, to ensure the air to be current and temperature to
distributing well-proportioned.

Mode 1: the new state of temperature controller when re-supplying the power after the power be
cut off by man or electricity-net severed.
Be waiting state when power supplying again after it broken down: the temperature controller to be the
state of waiting when power re-supplying after it cut off.
Be replaced when power supplying again after it broken down: the temperature controller replace to the
back state when power re-supplying after it cut off, in other words is that: the time of the temperature
controller’s power cut off was at the state of on, and it will go on running as the back setting value
when the power re-supplying (un-keeping memory about timed function).
This function is suitable specially for the specific place of hotel 、engine room and so on.
15 Dealing with simple unconventionalities
Please ensure another time for that if the live line and nil live have linked exactly, and if the
setting of cool/heat running mode meet to requires.
Unconventionalities Reasons Solving ways
Have given power but no Setting switch haven’t be open Pull the setting switch to right
display The end №7or8 un-linking to Ensure the end № 1and 7
the nil line linking right with power
The arrange lines of the LCD Please examine the arrange
mother panel and driving lines
power become flexible
The indeed fan speed do not The wrong linking with ends Please examine the circuitry
meet to the display value №4、5、6
Right display but wrong Arrange lines haven’t linked Please examine the arrange
controlling well or become flexible lines
Wrong linking Please examine the circuitry
Room temperature precision Temperature have be corrected Re-correct the measuring
(measuring temperature) temperature
Thermal resistor (sensor) Please examine the sensor
The un-fitting installing Improve the installing
position surrounding

16 Attention Points
16.1 When the system unusual or halted, please pull the setting switch to left, and it can be
replaced by tuning to right after three seconds.
16.2 This controller must be installed with the self-governed controlling setting of power, if you
don’t use the controller for a long time (for example: more than one month), please cut the power
of the setting which linking with the controller off.
16.3 The controller must be installed correctly according to the manual by the specialized
technical staff.
16.4 Don’t install the controller near the high temperature heat source or adverse circumstance
position
16.5 Please affirm the voltage of the power and the controller be unanimous or not before
installing.
16.6 Please read the manual carefully first before you using it.