Sunteți pe pagina 1din 4

HISAC Ultima - Test Report

HEADER : Test Date Time: 12-03-2019 14:45:57


Substation SDSTP STATION Breaker ID BAY 419 B PH Gas Pressure 7.5 Bar
(LEFT)
Bay 419 BAY Breaker Type 3AP2FI Air Pressure NIL
Operator Ajithkumar Serial Number 20453 Oil Pressure NIL
Manufacturer SCOPE Voltage (kV) 400
SETTINGS :
Trigger Option DCRM Sampling Speed (kC) 10 Reistance Range mW 4000
Plot Length(ms) 450 Delay tco (ms) 300 Delay toc (ms) 150
Current Range C1(A) 25 Current Range C2(A) 25 Current Range C3(A) 25
Current Range C4(A) 10 Current Range C5(A) 10 Current Range C6(A) 10
Velocity Enabled PIR Disabled Auxiliary Disabled
Analog Channels Enabled

T1 (mm) 143 T2 (mm) 0 T3 (mm) 0


Velocity Points :
Close1 20 % Open1 80 % DefClose 10 ms
Close2 80 % Open2 20 % DefOpen 10 ms

GRAPH :

This report is generated by HISAC Ultima Software from SCOPE T&M Pvt. Ltd. Pune, India.
15/03/2019
Page 1 of 4
HISAC Ultima - Test Report

Travel Results :
TR1 TR2 TR3 TR4 TR5 TR6
Mechanism Travel (mm) 57.2 0 0 0 0 0
Contact Travel (mm) 143 0 0 0 0 0
Close - Datum Velocity (m/s) 3.35 0 0 0 0 0
Open - Datum Velocity (m/s) 4.68 0 0 0 0 0
Close - Over Travel (mm) 7.09 0 0 0 0 0
Open - Rebound (mm) 0.6 0 0 0 0 0

Coil Current Results:


Coil Current (A) C1 C2 C3 C4 C5 C6
5.45 10.41 0 0 0 0

This report is generated by HISAC Ultima Software from SCOPE T&M Pvt. Ltd. Pune, India.
15/03/2019
Page 2 of 4
45:57

This report is generated by HISAC Ultima Software from SCOPE T&M Pvt. Ltd. Pune, India.
15/03/2019
Page 3 of 4
This report is generated by HISAC Ultima Software from SCOPE T&M Pvt. Ltd. Pune, India.
15/03/2019
Page 4 of 4