Sunteți pe pagina 1din 408

EDMT281426

Heat pump 50Hz

RZQS, RZQ series


EDMT281426

Part 1 SkyAir RZQS, RZQ series ................................................... 5


1. External appearance ...............................................................................7
2. Model name, power supply and nomenclature .......................................9
2.1 Model name and power supply ................................................................9
2.2 Nomenclature .........................................................................................10
3. Functions...............................................................................................11
4. Specifications ........................................................................................12
4.1 FCQ........................................................................................................12
4.2 FHQ........................................................................................................16
4.3 FAQ ........................................................................................................20
4.4 FBQ-DB..................................................................................................22
4.5 FVQ ........................................................................................................26
5. Dimensions and service space .............................................................31
5.1 Indoor unit ..............................................................................................31
5.2 Wired remote controller ..........................................................................43
5.3 Wireless remote controller......................................................................45
5.4 Outdoor unit............................................................................................48
5.5 Installation Service Space ......................................................................53
6. Piping diagrams ....................................................................................61
6.1 Indoor unit + outdoor unit .......................................................................61
7. Wiring diagrams ....................................................................................66
7.1 Indoor unit ..............................................................................................66
7.2 Outdoor unit............................................................................................73
8. Field wiring ............................................................................................79
9. Electric characteristics ..........................................................................84
9.1 RZQS-A, RZQ-L .....................................................................................84
9.2 RZQ-HA..................................................................................................89
10.Capacity tables......................................................................................93
10.1 Capacity tables.......................................................................................93
10.2 Capacity correction factor by the length of refrigerant piping ...............109
11.Operation limits ...................................................................................110
12.Fan performance.................................................................................111
12.1 FBQ-DB................................................................................................111
13.Airflow auto adjustment characteristics...............................................114
13.1 FBQ-DB................................................................................................114
14.Air velocity and temperature distributions ...........................................117
14.1 FHQ......................................................................................................117
15.Sound level .........................................................................................120
15.1 Indoor unit ............................................................................................120
15.2 Outdoor unit..........................................................................................137
16.Accessories.........................................................................................153
16.1 Indoor unit ............................................................................................153
16.2 Outdoor unit..........................................................................................157

Part 2 Installation of indoor / outdoor unit ............................... 159


1. Centre of gravity..................................................................................160
2. Installation of indoor unit .....................................................................163
2.1 FCQ71KAVEA / FCQ100KAVEA / FCQ125KAVEA /
FCQ140KAVEA....................................................................................163

Table of contents 1
EDMT281426

2.2 FHQ71BWV1A / FHQ100BWV1A / FHQ125BWV1A...........................190


2.3 FHQ140CAVEA....................................................................................215
2.4 FAQ71CVEA / FAQ100CVEA ..............................................................235
2.5 FBQ71DBVEA / FBQ100DBVEA / FBQ125DBVEA /
FBQ140DBVEA....................................................................................265
2.6 FVQ50CVE / FVQ60CVE.....................................................................292
2.7 FVQ71CVEB / FVQ100CVEB / FVQ125CVEB / FVQ140CVEB..........322
3. Installation of outdoor unit ...................................................................353
3.1 RZQS50AV1 / RZQS60AV1 / RZQ71LV1 / RZQ100LV1 /
RZQ125LV1 .........................................................................................353
3.2 RZQ140LV1 .........................................................................................369
3.3 RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A ...........................385
3.4 Equivalent piping length of joints (reference) .......................................401

2 Table of contents
EDMT281426 Publication list

Publication list
Refrigerant Inverter/ Series Book No. Type, Hz Model name of Area Note Published
Non Inverter indoor / outdoor unit in
- Indoor units
FCQ71/100/125/140KVEA
FFQ25/35/50/60BV1B
FHQ35/50/60/71/100/125BVV1B
FBQ50/60BV1A
FBQ71/100/125/140DV1
EDHK281002 H/P 50Hz Hong Kong Jun. 2010
- Outdoor units
RZQ71KBV1
RZQ100/125/140HY4A
RXS25/35EBVMA
RXS50/60FVMA
RKS25/35EBVMA
RKS50/60FVMA
- Indoor units
FCQ50/60LUV1V
FCQ71-140LUV1
FFQ25-60BV1B
FHQ50/60BVV1V
FHQ35/71/100/125BVV1B
FHQ140CAVEA
RZQ FDXS25-60CVMA - New lineup of indoor units:
FBQ50-71BV1A FCQ50/60LUV1V
FBQ50/60DV1V FHQ50/60BVV1V
EDVN281408 H/P 50Hz FBQ71-140DV1 Vietnam FBQ50/60DV1V Sep. 2014
FVQ50/60CVE FVQ50/60CVE
FVQ71-140CVEB
- New lineup of outdoor units:
- Outdoor units RZQ50/60KBV1V
RZQ50/60KBV1V
R410A Inverter RZQ50/60KBV4A
RZQ71-140KCV4A
RZQ100-140HAY4A
RXS25/35EBVMA
RXS50FAVMA
RXS50-71FVMA

- Indoor units - Addition of indoor unit:


FAQ71CVEA
FAQ71/100CVEA
Australia
EDMT281315 H/P 50Hz - Outdoor units India - Model change of indoor unit: Sep. 2013
FAQ100BVV1B
RZQ71/100KCV4A ↓
RZQ100HAY4A
FAQ100CVEA
- New line-up of indoor units:
FHQ71/100/125BWV1A
- Indoor units FBQ71/100/125/140DBVEA
FCQ71/100/125/140KAVEA
FHQ71/100/125BWV1A - Model change of indoor units:
FHQ140CAVEA FCQ71/100/125/140KVEA
FAQ71/100CVEA ↓
FBQ71/100/125/140DBVEA Vietnam FCQ71/100/125/140KAVEA
RZQS
RZQ EDMT281426 H/P 50Hz FVQ50/60CVE India Mar. 2015
FVQ71/100/125/140CVEB Hong Kong - New line-up of outdoor units:
RZQS50/60AV1
- Outdoor units RZQ71/100/125/140LV1
RZQS50/60AV1
RZQ71/100/125/140LV1 - Discontinued outdoor units:
RZQ100/125/140HAY4A RZQ71KBV1
RZQ50/60KBV4A
RZQ71-140KCV4A

EDMT281426 as shown by .

Table of contents 3
Publication list EDMT281426

4 Table of contents
EDMT281426

Part 1 1

SkyAir
RZQS, RZQ series
Model series
Power
Class 50 60 71 100 125 140
supply
FCQ 71KA 100KA 125KA 140KA VEA
71BW 100BW 125BW V1A
FHQ
140CA VEA
Indoor
FAQ 71C 100C VEA
unit
FBQ 71DB 100DB 125DB 140DB VEA
50C 60C VE
FVQ
71C 100C 125C 140C VEB
RZQS 50A 60A V1
Outdoor
71L 100L 125L 140L V1
unit RZQ
100HA 125HA 140HA Y4A

1. External appearance ...............................................................................7


2. Model name, power supply and nomenclature .......................................9
2.1 Model name and power supply ................................................................9
2.2 Nomenclature .........................................................................................10
3. Functions...............................................................................................11
4. Specifications ........................................................................................12
4.1 FCQ........................................................................................................12
4.2 FHQ........................................................................................................16
4.3 FAQ ........................................................................................................20
4.4 FBQ-DB..................................................................................................22
4.5 FVQ ........................................................................................................26
5. Dimensions and service space .............................................................31
5.1 Indoor unit ..............................................................................................31
5.2 Wired remote controller ..........................................................................43
5.3 Wireless remote controller......................................................................45
5.4 Outdoor unit............................................................................................48
5.5 Installation Service Space ......................................................................53
6. Piping diagrams ....................................................................................61
6.1 Indoor unit + outdoor unit .......................................................................61
7. Wiring diagrams ....................................................................................66
7.1 Indoor unit ..............................................................................................66

SkyAir RZQS, RZQ series 5


EDMT281426

7.2 Outdoor unit............................................................................................73


8. Field wiring ............................................................................................79
9. Electric characteristics ..........................................................................84
9.1 RZQS-A, RZQ-L .....................................................................................84
9.2 RZQ-HA..................................................................................................89
10.Capacity tables......................................................................................93
10.1 Capacity tables.......................................................................................93
10.2 Capacity correction factor by the length of refrigerant piping ...............109
11.Operation limits ...................................................................................110
12.Fan performance.................................................................................111
12.1 FBQ-DB................................................................................................111
13.Airflow auto adjustment characteristics...............................................114
13.1 FBQ-DB................................................................................................114
14.Air velocity and temperature distributions ...........................................117
14.1 FHQ......................................................................................................117
15.Sound level .........................................................................................120
15.1 Indoor unit ............................................................................................120
15.2 Outdoor unit..........................................................................................137
16.Accessories.........................................................................................153
16.1 Indoor unit ............................................................................................153
16.2 Outdoor unit..........................................................................................157

6 SkyAir RZQS, RZQ series


EDMT281426 External appearance

1. External appearance
1
Indoor unit

FCQ FHQ-BW FHQ-CA

FAQ-C FBQ-DB FVQ

Wired
remote controller

BRC1C61 BRC1D61 BRC1E62

Wireless
remote controller

BRC7F634F (for FCQ)


BRC7EA63W (for FHQ-BW)
BRC7GA53 (for FHQ-CA)
BRC7EB518 (for FAQ-C)
BRC4C65 (for FBQ-DB)

Signal receiver unit Signal receiver unit Signal receiver unit


(for FCQ) (for FHQ-BW) (for FHQ-CA)

Signal receiver unit Signal receiver unit


(for FAQ-C) (for FBQ-DB)

SkyAir RZQS, RZQ series 7


External appearance EDMT281426

Outdoor unit

RZQS50AV1
RZQS60AV1

RZQ71LV1 RZQ100LV1 RZQ125LV1 RZQ140LV1

RZQ100HAY4A
RZQ125HAY4A
RZQ140HAY4A

8 SkyAir RZQS, RZQ series


EDMT281426 Model name, power supply and nomenclature

2. Model name, power supply and nomenclature


1
2.1 Model name and power supply

Indoor unit Outdoor unit


Power supply intake
Type Model name Model name
FCQ71KAVEA RZQ71LV1
FCQ100KAVEA RZQ100LV1
Outdoor unit: 1 phase, 220-240V, 50Hz
FCQ125KAVEA RZQ125LV1
Ceiling mounted cassette FCQ140KAVEA RZQ140LV1
(Round flow) type
FCQ100KAVEA RZQ100HAY4A
FCQ125KAVEA RZQ125HAY4A Outdoor unit: 3 phase, 415V, 50Hz
FCQ140KAVEA RZQ140HAY4A
FHQ71BWV1A RZQ71LV1
FHQ100BWV1A RZQ100LV1
Outdoor unit: 1 phase, 220-240V, 50Hz
FHQ125BWV1A RZQ125LV1
Ceiling suspended type FHQ140CAVEA RZQ140LV1
FHQ100BWV1A RZQ100HAY4A
FHQ125BWV1A RZQ125HAY4A Outdoor unit: 3 phase, 415V, 50Hz
FHQ140CAVEA RZQ140HAY4A
FAQ71CVEA RZQ71LV1
Outdoor unit: 1 phase, 220-240V, 50Hz
Wall mounted type FAQ100CVEA RZQ100LV1
FAQ100CVEA RZQ100HAY4A Outdoor unit: 3 phase, 415V, 50Hz
FBQ71DBVEA RZQ71LV1
FBQ100DBVEA RZQ100LV1 Indoor unit: 1 phase, 220-240V, 50Hz
FBQ125DBVEA RZQ125LV1 Outdoor unit: 1 phase, 220-240V, 50Hz
Duct connection middle
and high static pressure FBQ140DBVEA RZQ140LV1
type FBQ100DBVEA RZQ100HAY4A
Indoor unit: 1 phase, 220-240V, 50Hz
FBQ125DBVEA RZQ125HAY4A Outdoor unit: 3 phase, 415V, 50Hz
FBQ140DBVEA RZQ140HAY4A
FVQ50CVE RZQS50AV1
Outdoor unit: 1 phase, 220-240V, 50Hz
FVQ60CVE RZQS60AV1
FVQ71CVEB RZQ71LV1
FVQ100CVEB RZQ100LV1
Outdoor unit: 1 phase, 220-240V, 50Hz
Floor standing type FVQ125CVEB RZQ125LV1
FVQ140CVEB RZQ140LV1
FVQ100CVEB RZQ100HAY4A
FVQ125CVEB RZQ125HAY4A Outdoor unit: 3 phase, 415V, 50Hz
FVQ140CVEB RZQ140HAY4A

SkyAir RZQS, RZQ series 9


Model name, power supply and nomenclature EDMT281426

2.2 Nomenclature

Indoor unit

F C Q 71 KA VE A

Standard symbol
A: Australia
B: Europe
Power supply symbol
V1: 1 phase, 220-240V, 50Hz
VE: 1 phase, 220-240/220V, 50/60Hz
Indicates major design category
Capacity indication
Refrigerant and type
Q: R410A, Heat pump or Cooling only
Shape
C: Ceiling mounted cassette (Round flow)
H: Ceiling Suspended
A: Wall Mounted
B(-DB): Duct connection middle and high static
pressure
V: Floor Standing
Unit category
F: Air cooled split indoor unit

Outdoor unit

R Z Q S 50 A V1
Standard symbol
A: Australia
Power supply symbol
V1: 1 phase, 220-240V, 50Hz
Y4: 3 phase, 380-415V, 50Hz
Indicates major design category
Capacity indication
Grade and refrigerant symbol
S: Inverter (High grade model), R410A
Refrigerant and type
Q: R410A, Heat Pump
Inverter / Non inverter
Z: Inverter
Unit category
R: Air cooled split outdoor unit

10 SkyAir RZQS, RZQ series


EDMT281426 Functions

3. Functions
1
Indoor FVQ50/60CVE
FCQ71-140KAVEA FHQ71-125BWV1A FHQ140CAVEA FAQ71/100CVEA FBQ71-140DBVEA
unit FVQ71-140CVEB
Category Function RZQS50/60AV1
Outdoor RZQ71-140LV1 RZQ71-125LV1 RZQ140LV1 RZQ71/100LV1 RZQ71-140LV1
RZQ71-140LV1
unit RZQ100-140HAY4A RZQ100/125HAY4A RZQ140HAY4A RZQ100HAY4A RZQ100-140HAY4A
RZQ100-140HAY4A
Inverter control { { { { { {
Auto swing { { { { — {
Swing pattern selection { — — — — —
Draft prevention function (heating) { { { { — —
Independent up-and-down airflow — — — — — {
DC fan motor (Indoor unit) { — { { { {
Switchable fan speed { (3 step) { (2 step) { (3 step) { (3 step) { (3 step) { (3 step)
Auto airflow rate — — — { (*5) — { (*5)
Comfort
High fan speed mode — — — { — { (*8)
Program “Dry” { { { { { {
High ceiling application { { (*7) { (*7-2) — — —
Two selectable temperature-sensors (*1) { { { { { {
Hot start (after defrost) { { { { { {
Year-round cooling applicable { { { { { {
Night quiet operation (*2) { { { { { {
Setpoint auto reset (*5) { { { { { {
Setpoint range set (*5) { { { { { {
Remote
controller Weekly schedule timer { (*3) { (*3) { (*3) { (*3) { (*3) { (*5)
Off timer (programmed) (*5) { { { { { {
On/Off timer (*6) { { { { { {
Anti-bacterial air filter { { { — { (*4) {
Mould-proof air filter — — — { — —
Cleanliness
Silver ion anti-bacterial drain pan { — — — { —
Mould-proof drain pan — — — — — —
Drain pump mechanism { { (*4) { (*4) { (*4) { —
Pre-charged for up to 30 m (*2) { { { { { {
Pre-charged for up to 10 m (*2) — — — — — —
Long-life filter { { { — { (*4) {
Work &
Filter sign { { { { { {
servicing
Ceiling soiling prevention { — — — — —
Low gas pressure detection (*2) { { { { { {
Emergency operation { { { { { {
Self-diagnosis function { { { { { {
Auto-restart { { { { { {
Auto-cooling/heating change-over { { { { { {
Control by 2 remote controllers { { { { { {
Control Group control by 1 remote controller { { { { { {
features External command control { (*4) { (*4) { (*4) { (*4) { (*4) { (*4)
Central remote control { { (*4) { { { {
Interlock control { { { { { {
DIII-NET communication standard { — { { { {
High-efficiency filter { — — — { —
Options Ultra long-life filter { — — — — —
Fresh air intake kit { — { — — —
Others Anti corrosion treated heat exchangers (*2) { { { { { {
Notes: {: Functions exist.
—: No functions
*1: Applicable when wired remote controller is used
*2: For the outdoor units
*3: Applicable when BRC1D61 or BRC1E62 is used
*4: Option
*5: Applicable when BRC1E62 is used
*6: Applicable when BRC1C61 is used
*7: Installable on max. 3.5 m high ceiling
*7-2: Installable on max. 4.3 m high ceiling
*8: Applicable for FVQ50-100

SkyAir RZQS, RZQ series 11


Specifications EDMT281426

4. Specifications
4.1 FCQ

FCQ (Ceiling mounted cassette (Round flow) type)


Indoor unit FCQ71KAVEA FCQ100KAVEA
Model
Outdoor unit RZQ71LV1 RZQ100LV1
Power supply 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
Power supply intake Outdoor unit side Outdoor unit side
kW 7.1 (3.2-8.0) 10.0 (5.0-11.2)
Cooling capacity *1 *2 Btu/h 24,200 (10,900-27,300) 34,100 (17,100-38,200)
kcal/h 6,100 (2,800-6,900) 8,600 (4,300-9,600)
kW 8.0 (3.5-9.0) 11.2 (5.1-12.8)
Heating capacity *1 *2 Btu/h 27,300 (11,900-30,700) 38,200 (17,400-43,700)
kcal/h 6,900 (3,000-7,700) 9,600 (4,400-11,000)
Indoor unit FCQ71KAVEA FCQ100KAVEA
Colour — —
Dimensions H×W×D mm 256×840×840 298×840×840
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 2×10×1.2 2×12×1.2
Face area m² 0.446 0.535
Type Turbo fan Turbo fan
Motor output W 56 120
Fan
m³/min 21/17.5/13.5 32/26/20
Airflow rate (HH/H/L)
cfm 741/618/477 1,130/918/706
Sound pressure level (HH/H/L) *3 dB(A) 35/31.5/28 43/37.5/32
Mass kg 21 24
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
connections
Gas mm φ15.9 (Flare) φ15.9 (Flare)
Drain mm VP25 (I.D.φ25×O.D.φ32) VP25 (I.D.φ25×O.D.φ32)
Wired BRC1C61/BRC1D61/BRC1E62 BRC1C61/BRC1D61/BRC1E62
Remote controller (option)
Wireless BRC7F634F BRC7F634F
Model BYCP125K-W1 BYCP125K-W1
Colour Fresh white Fresh white
Decoration
panel (option) Dimensions H×W×D mm 50×950×950 50×950×950
Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Mass kg 5.5 5.5
Outdoor unit RZQ71LV1 RZQ100LV1
Colour Ivory white Ivory white
Dimensions H×W×D mm 770×900×320 990×940×320
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 2×34×1.4 2×44×1.4
Face area m² 0.650 0.884
Model 2YC63FXD 2YC63FXD
Comp. Type Hermetically sealed swing type Hermetically sealed swing type
Motor output kW 1.7 2.08
Type Propeller fan Propeller fan
Fan Motor output W 70 200
Airflow rate m³/min 52 76
Cooling dB(A) 49 51
Sound pressure
level *3 Heating dB(A) 51 53
Night quiet mode dB(A) 45 47
Mass kg 64 75
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
Gas mm φ15.9 (Flare) φ15.9 (Flare)
connections
Drain mm φ26 (Hole) φ26 (Hole)
Safety devices High pressure switch. Fuse. High pressure switch. Fuse.
Capacity step % Compressor revolution speed control (Inverter system) Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve Electronic expansion valve
Max. length m 50 (Equivalent length 70m) 75 (Equivalent length 90m)
Ref. piping
Max. height difference m 30 30
Model R410A R410A
Refrigerant
Charge (factory charge) kg 2.0 (Charged for 30m) 2.9 (Charged for 30m)
Model Refer to the nameplate of compressor. Refer to the nameplate of compressor.
Ref. oil
Charge L 0.75 0.75
Specification C: 3D089639F C: 3D089639F
Drawing No. Sound (Indoor) C: 4D094558 C: 4D094559
Sound (Outdoor) C: 4D075745A, C: 4D075748A C: 4D089676, C: 4D089677A

Notes: *1. The above data are based on the following conditions. Conversion formulae
Cooling Heating Piping length kcal/h=kW×860
Indoor: 27°CDB, 19°CWB Indoor: 20°CDB, 15°CWB 7.5m Btu/h=kW×3412
Outdoor: 35°CDB, 24°CWB Outdoor: 7°CDB, 6°CWB (Horizontal) cfm=m³/min×35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

12 SkyAir RZQS, RZQ series


EDMT281426 Specifications

FCQ (Ceiling mounted cassette (Round flow) type) 1


Indoor unit FCQ125KAVEA FCQ140KAVEA
Model
Outdoor unit RZQ125LV1 RZQ140LV1
Power supply 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
Power supply intake Outdoor unit side Outdoor unit side
kW 12.5 (5.7-14.0) 13.6 (6.2-15.5)
Cooling capacity *1 *2 Btu/h 42,700 (19,500-47,800) 46,400 (21,200-52,900)
kcal/h 10,800 (4,900-12,000) 11,700 (5,300-13,300)
kW 14.0 (6.0-16.2) 16.0 (6.2-18.0)
Heating capacity *1 *2 Btu/h 47,800 (20,500-55,300) 54,600 (21,200-61,400)
kcal/h 12,000 (5,200-13,900) 13,800 (5,300-15,500)
Indoor unit FCQ125KAVEA FCQ140KAVEA
Colour — —
Dimensions H×W×D mm 298×840×840 298×840×840
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 2×12×1.2 2×12×1.2
Face area m² 0.535 0.535
Type Turbo fan Turbo fan
Motor output W 120 120
Fan
m³/min 33/28/22.5 33/28/22.5
Airflow rate (HH/H/L)
cfm 1,165/988/794 1,165/988/794
Sound pressure level (HH/H/L) *3 dB(A) 44/39/34 44/40/36
Mass kg 24 24
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
connections
Gas mm φ15.9 (Flare) φ15.9 (Flare)
Drain mm VP25 (I.D.φ25×O.D.φ32) VP25 (I.D.φ25×O.D.φ32)
Wired BRC1C61/BRC1D61/BRC1E62 BRC1C61/BRC1D61/BRC1E62
Remote controller (option)
Wireless BRC7F634F BRC7F634F
Model BYCP125K-W1 BYCP125K-W1
Colour Fresh white Fresh white
Decoration
Dimensions H×W×D mm 50×950×950 50×950×950
panel (option)
Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Mass kg 5.5 5.5
Outdoor unit RZQ125LV1 RZQ140LV1
Colour Ivory white Ivory white
Dimensions H×W×D mm 1,170×900×320 1,430×940×320
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 2×52×1.4 2×64×1.4
Face area m² 1.01 1.286
Model JT100G-VD@T3 JT100G-VD@T3
Comp. Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor output kW 2.4 3.15
Type Propeller fan Propeller fan
Fan Motor output W 70+70 200+200
Airflow rate m³/min 95 140
Cooling dB(A) 51 54
Sound pressure
level *3 Heating dB(A) 53 56
Night quiet mode dB(A) 47 50
Mass kg 98 108
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
Gas mm φ15.9 (Flare) φ15.9 (Flare)
connections
Drain mm φ26 (Hole) φ26 (Hole)
Safety devices High pressure switch. Fuse. High pressure switch. Fuse.
Capacity step % Compressor revolution speed control (Inverter system) Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve Electronic expansion valve
Max. length m 75 (Equivalent length 90m) 75 (Equivalent length 90m)
Ref. piping
Max. height difference m 30 30
Model R410A R410A
Refrigerant
Charge (factory charge) kg 3.15 (Charged for 30m) 4.2 (Charged for 30m)
Model Refer to the nameplate of compressor. Refer to the nameplate of compressor.
Ref. oil
Charge L 1.2 1.5
Specification C: 3D089639F C: 3D089639F
Drawing No. Sound (Indoor) C: 4D094560 C: 4D094561
Sound (Outdoor) C: 4D075741A, C: 4D075747A C: 4D089680A, C: 4D089681A

Notes: *1. The above data are based on the following conditions. Conversion formulae
Cooling Heating Piping length kcal/h=kW×860
Indoor: 27°CDB, 19°CWB Indoor: 20°CDB, 15°CWB 7.5m Btu/h=kW×3412
Outdoor: 35°CDB, 24°CWB Outdoor: 7°CDB, 6°CWB (Horizontal) cfm=m³/min×35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

SkyAir RZQS, RZQ series 13


Specifications EDMT281426

FCQ (Ceiling mounted cassette (Round flow) type)


Indoor unit FCQ100KAVEA FCQ125KAVEA
Model
Outdoor unit RZQ100HAY4A RZQ125HAY4A
Power supply 3 phase, 415V, 50Hz 3 phase, 415V, 50Hz
Power supply intake Outdoor unit side Outdoor unit side
kW 10.0 (5.0-11.2) 12.5 (5.7-14.0)
Cooling capacity *1 *2 Btu/h 34,100 (17,100-38,200) 42,700 (19,500-47,800)
kcal/h 8,600 (4,300-9,600) 10,800 (4,900-12,000)
kW 11.2 (5.1-12.8) 14.0 (6.0-16.2)
Heating capacity *1 *2 Btu/h 38,200 (17,400-43,700) 47,800 (20,500-55,300)
kcal/h 9,600 (4,400-11,000) 12,000 (5,200-13,900)
Indoor unit FCQ100KAVEA FCQ125KAVEA
Colour — —
Dimensions H×W×D mm 298×840×840 298×840×840
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 2×12×1.2 2×12×1.2
Face area m² 0.535 0.535
Type Turbo fan Turbo fan
Motor output W 120 120
Fan
m³/min 32/26/20 33/28/22.5
Airflow rate (HH/H/L)
cfm 1,130/918/706 1,165/988/794
Sound pressure level (HH/H/L) *3 dB(A) 43/37.5/32 44/39/34
Mass kg 24 24
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
connections
Gas mm φ15.9 (Flare) φ15.9 (Flare)
Drain mm VP25 (I.D.φ25×O.D.φ32) VP25 (I.D.φ25×O.D.φ32)
Wired BRC1C61/BRC1D61/BRC1E62 BRC1C61/BRC1D61/BRC1E62
Remote controller (option)
Wireless BRC7F634F BRC7F634F
Model BYCP125K-W1 BYCP125K-W1
Colour Fresh white Fresh white
Decoration
Dimensions H×W×D mm 50×950×950 50×950×950
panel (option)
Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Mass kg 5.5 5.5
Outdoor unit RZQ100HAY4A RZQ125HAY4A
Colour Ivory white Ivory white
Dimensions H×W×D mm 1,345×900×320 1,345×900×320
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 2×60×1.4 2×60×1.4
Face area m² 1.15 1.15
Model JT1G-VDYR@T JT1G-VDYR@T
Comp. Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor output kW 1.7 2.2
Type Propeller fan Propeller fan
Fan Motor output W 70+70 70+70
Airflow rate m³/min 100 100
Cooling dB(A) 49 50
Sound pressure
level *3 Heating dB(A) 51 52
Night quiet mode dB(A) 45 45
Mass kg 108 108
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
Gas mm φ15.9 (Flare) φ15.9 (Flare)
connections
Drain mm φ26 (Hole) φ26 (Hole)
Safety devices High pressure switch. Fuse. High pressure switch. Fuse.
Capacity step % Compressor revolution speed control (Inverter system) Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve Electronic expansion valve
Max. length m 75 (Equivalent length 90m) 75 (Equivalent length 90m)
Ref. piping
Max. height difference m 30 30
Model R410A R410A
Refrigerant
Charge (factory charge) kg 4.3 (Charged for 30m) 4.3 (Charged for 30m)
Model Refer to the nameplate of compressor. Refer to the nameplate of compressor.
Ref. oil
Charge L 1.2 1.2
Specification C: 3D092994B C: 3D092994B
Drawing No. Sound (Indoor) C: 4D094559 C: 4D094560
Sound (Outdoor) C: 4D061464A, C: 4D061483A C: 4D061473A, C: 4D061484A

Notes: *1. The above data are based on the following conditions. Conversion formulae
Cooling Heating Piping length kcal/h=kW×860
Indoor: 27°CDB, 19°CWB Indoor: 20°CDB, 15°CWB 7.5m Btu/h=kW×3412
Outdoor: 35°CDB, 24°CWB Outdoor: 7°CDB, 6°CWB (Horizontal) cfm=m³/min×35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

14 SkyAir RZQS, RZQ series


EDMT281426 Specifications

FCQ (Ceiling mounted cassette (Round flow) type) 1


Indoor unit FCQ140KAVEA
Model
Outdoor unit RZQ140HAY4A
Power supply 3 phase, 415V, 50Hz
Power supply intake Outdoor unit side
kW 13.6 (6.2-15.4)
Cooling capacity *1 *2 Btu/h 46,400 (21,200-52,600)
kcal/h 11,700 (5,300-13,200)
kW 16.0 (6.2-18.0)
Heating capacity *1 *2 Btu/h 54,600 (21,200-61,400)
kcal/h 13,800 (5,300-15,500)
Indoor unit FCQ140KAVEA
Colour —
Dimensions H×W×D mm 298×840×840
Type Cross fin coil
Coil Rows×Stages×Fin pitch 2×12×1.2
Face area m² 0.535
Type Turbo fan
Motor output W 120
Fan
m³/min 33/28/22.5
Airflow rate (HH/H/L)
cfm 1,165/988/794
Sound pressure level (HH/H/L) *3 dB(A) 44/40/36
Mass kg 24
Liquid mm φ9.5 (Flare)
Piping
connections
Gas mm φ15.9 (Flare)
Drain mm VP25 (I.D.φ25×O.D.φ32)
Wired BRC1C61/BRC1D61/BRC1E62
Remote controller (option)
Wireless BRC7F634F
Model BYCP125K-W1
Colour Fresh white
Decoration
Dimensions H×W×D mm 50×950×950
panel (option)
Air filter Resin net (with mould resistance)
Mass kg 5.5
Outdoor unit RZQ140HAY4A
Colour Ivory white
Dimensions H×W×D mm 1,345×900×320
Type Cross fin coil
Coil Rows×Stages×Fin pitch 2×60×1.4
Face area m² 1.15
Model JT1G-VDYR@T
Comp. Type Hermetically sealed scroll type
Motor output kW 2.9
Type Propeller fan
Fan Motor output W 70+70
Airflow rate m³/min 100
Cooling dB(A) 50
Sound pressure
level *3 Heating dB(A) 52
Night quiet mode dB(A) 46
Mass kg 108
Liquid mm φ9.5 (Flare)
Piping
Gas mm φ15.9 (Flare)
connections
Drain mm φ26 (Hole)
Safety devices High pressure switch. Fuse.
Capacity step % Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve
Max. length m 75 (Equivalent length 90m)
Ref. piping
Max. height difference m 30
Model R410A
Refrigerant
Charge (factory charge) kg 4.3 (Charged for 30m)
Model Refer to the nameplate of compressor.
Ref. oil
Charge L 1.2
Specification C: 3D092994B
Drawing No. Sound (Indoor) C: 4D094561
Sound (Outdoor) C: 4D061482B, C: 4D061485B

Notes: *1. The above data are based on the following conditions. Conversion formulae
Cooling Heating Piping length kcal/h=kW×860
Indoor: 27°CDB, 19°CWB Indoor: 20°CDB, 15°CWB 7.5m Btu/h=kW×3412
Outdoor: 35°CDB, 24°CWB Outdoor: 7°CDB, 6°CWB (Horizontal) cfm=m³/min×35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

SkyAir RZQS, RZQ series 15


Specifications EDMT281426

4.2 FHQ

FHQ (Ceiling suspended type)


Indoor unit FHQ71BWV1A FHQ100BWV1A
Model
Outdoor unit RZQ71LV1 RZQ100LV1
Power supply 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
Power supply intake Outdoor unit side Outdoor unit side
kW 5.8 (3.2-8.0) 9.0 (5.0-11.2)
Cooling capacity *1 *2 Btu/h 19,800 (10,900-27,300) 30,700 (17,100-38,200)
kcal/h 5,000 (2,800-6,900) 7,700 (4,300-9,600)
kW 7.5 (3.5-9.0) 10.2 (5.1-12.8)
Heating capacity *1 *2 Btu/h 25,600 (11,900-30,700) 34,800 (17,400-43,700)
kcal/h 6,500 (3,000-7,700) 8,800 (4,400-11,000)
Indoor unit FHQ71BWV1A FHQ100BWV1A
Colour White White
Dimensions H×W×D mm 195×1,160×680 195×1,400×680
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 3×12×1.75 3×12×1.75
Face area m² 0.233 0.293
Type Sirocco fan Sirocco fan
Motor output W 62 130
Fan
m³/min 17/—/14 24/—/20
Airflow rate (H/M/L)
cfm 600/—/494 847/—/706
Sound pressure level (H/M/L) *3 dB(A) 39/—/35 42/—/37
Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Mass kg 27 32
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
connections
Gas mm φ15.9 (Flare) φ15.9 (Flare)
Drain mm VP20 (I.D.φ20×O.D.φ26) VP20 (I.D.φ20×O.D.φ26)
Wired BRC1C61/BRC1D61/BRC1E62 BRC1C61/BRC1D61/BRC1E62
Remote controller (option)
Wireless BRC7EA63W BRC7EA63W
Outdoor unit RZQ71LV1 RZQ100LV1
Colour Ivory white Ivory white
Dimensions H×W×D mm 770×900×320 990×940×320
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 2×34×1.4 2×44×1.4
Face area m² 0.650 0.884
Model 2YC63FXD 2YC63FXD
Comp. Type Hermetically sealed swing type Hermetically sealed swing type
Motor output kW 1.7 2.08
Type Propeller fan Propeller fan
Fan Motor output W 70 200
Airflow rate m³/min 52 76
Cooling dB(A) 49 51
Sound pressure
level *3 Heating dB(A) 51 53
Night quiet mode dB(A) 45 47
Mass kg 64 75
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
Gas mm φ15.9 (Flare) φ15.9 (Flare)
connections
Drain mm φ26 (Hole) φ26 (Hole)
Safety devices High pressure switch. Fuse. High pressure switch. Fuse.
Capacity step % Compressor revolution speed control (Inverter system) Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve Electronic expansion valve
Max. length m 50 (Equivalent length 70m) 75 (Equivalent length 90m)
Ref. piping
Max. height difference m 30 30
Model R410A R410A
Refrigerant
Charge (factory charge) kg 2.0 (Charged for 30m) 2.9 (Charged for 30m)
Model Refer to the nameplate of compressor. Refer to the nameplate of compressor.
Ref. oil
Charge L 0.75 0.75
Specification C: 3D089650B C: 3D089650B
Drawing No. Sound (Indoor) C: 4D090911 C: 4D090912
Sound (Outdoor) C: 4D075745A, C: 4D075748A C: 4D089676, C: 4D089677A

Notes: *1. The above data are based on the following conditions. Conversion formulae
Cooling Heating Piping length kcal/h=kW×860
Indoor: 27°CDB, 19°CWB Indoor: 20°CDB, 15°CWB 7.5m Btu/h=kW×3412
Outdoor: 35°CDB, 24°CWB Outdoor: 7°CDB, 6°CWB (Horizontal) cfm=m³/min×35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

16 SkyAir RZQS, RZQ series


EDMT281426 Specifications

FHQ (Ceiling suspended type) 1


Indoor unit FHQ125BWV1A FHQ140CAVEA
Model
Outdoor unit RZQ125LV1 RZQ140LV1
Power supply 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
Power supply intake Outdoor unit side Outdoor unit side
kW 11.0 (5.7-14.0) 13.0 (6.2-15.5)
Cooling capacity *1 *2 Btu/h 37,500 (19,500-47,800) 44,400 (21,200-52,900)
kcal/h 9,500 (4,900-12,000) 11,200 (5,300-13,300)
kW 13.2 (6.0-16.2) 15.7 (6.2-18.0)
Heating capacity *1 *2 Btu/h 45,000 (20,500-55,300) 53,600 (21,200-61,400)
kcal/h 11,400 (5,200-13,900) 13,500 (5,300-15,500)
Indoor unit FHQ125BWV1A FHQ140CAVEA
Colour White Fresh white
Dimensions H×W×D mm 195×1,590×680 235×1,590×690
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 3×12×1.75 3×14×1.5
Face area m² 0.341 0.398
Type Sirocco fan Sirocco fan
Motor output W 130 150
Fan
m³/min 30/—/25 34/29/24
Airflow rate (H/M/L)
cfm 1,059/—/883 1,200/1,024/847
Sound pressure level (H/M/L) *3 dB(A) 44/—/39 46/42/38
Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Mass kg 35 38
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
connections
Gas mm φ15.9 (Flare) φ15.9 (Flare)
Drain mm VP20 (I.D.φ20×O.D.φ26) VP20 (I.D.φ20×O.D.φ26)
Wired BRC1C61/BRC1D61/BRC1E62 BRC1C61/BRC1D61/BRC1E62
Remote controller (option)
Wireless BRC7EA63W BRC7GA53
Outdoor Unit RZQ125LV1 RZQ140LV1
Colour Ivory white Ivory white
Dimensions H×W×D mm 1,170×900×320 1,430×940×320
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 2×52×1.4 2×64×1.4
Face area m² 1.010 1.286
Model JT100G-VD@T3 JT100G-VD@T3
Comp. Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor output kW 2.4 3.15
Type Propeller fan Propeller fan
Fan Motor output W 70+70 200+200
Airflow rate m³/min 95 140
Cooling dB(A) 51 54
Sound pressure
level *3 Heating dB(A) 53 56
Night quiet mode dB(A) 47 50
Mass kg 98 108
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
Gas mm φ15.9 (Flare) φ15.9 (Flare)
connections
Drain mm φ26 (Hole) φ26 (Hole)
Safety devices High pressure switch. Fuse. High pressure switch. Fuse.
Capacity step % Compressor revolution speed control (Inverter system) Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve Electronic expansion valve
Max. length m 75 (Equivalent length 90m) 75 (Equivalent length 90m)
Ref. piping
Max. height difference m 30 30
Model R410A R410A
Refrigerant
Charge (factory charge) kg 3.15 (Charged for 30m) 4.2 (Charged for 30m)
Model Refer to the nameplate of compressor. Refer to the nameplate of compressor.
Ref. oil
Charge L 1.2 1.5
Specification C: 3D089650B C: 3D089650B
Drawing No. Sound (Indoor) C: 4D090913 C: 4D069651D
Sound (Outdoor) C: 4D075741A, C: 4D075747A C: 4D089680A, C: 4D089681A

Notes: *1. The above data are based on the following conditions. Conversion formulae
Cooling Heating Piping length kcal/h=kW×860
Indoor: 27°CDB, 19°CWB Indoor: 20°CDB, 15°CWB 7.5m Btu/h=kW×3412
Outdoor: 35°CDB, 24°CWB Outdoor: 7°CDB, 6°CWB (Horizontal) cfm=m³/min×35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

SkyAir RZQS, RZQ series 17


Specifications EDMT281426

FHQ (Ceiling suspended type)


Indoor unit FHQ100BWV1A FHQ125BWV1A
Model
Outdoor unit RZQ100HAY4A RZQ125HAY4A
Power supply 3 phase, 415V, 50Hz 3 phase, 415V, 50Hz
Power supply intake Outdoor unit side Outdoor unit side
kW 9.2 (5.0-11.2) 11.2 (5.7-14.0)
Cooling capacity *1 *2 Btu/h 31,400 (17,100-38,200) 38,200 (19,500-47,800)
kcal/h 7,900 (4,300-9,600) 9,600 (4,900-12,000)
kW 10.5 (5.1-12.8) 13.5 (6.0-16.2)
Heating capacity *1 *2 Btu/h 35,800 (17,400-43,700) 46,100 (20,500-55,300)
kcal/h 9,000 (4,400-11,000) 11,600 (5,200-13,900)
Indoor unit FHQ100BWV1A FHQ125BWV1A
Colour White White
Dimensions H×W×D mm 195×1,400×680 195×1,590×680
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 3×12×1.75 3×12×1.75
Face area m² 0.293 0.341
Type Sirocco fan Sirocco fan
Motor output W 130 130
Fan
m³/min 24/—/20 30/—/25
Airflow rate (H/M/L)
cfm 847/—/706 1,059/—/883
Sound pressure level (H/M/L) *3 dB(A) 42/—/37 44/—/39
Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Mass kg 32 35
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
connections
Gas mm φ15.9 (Flare) φ15.9 (Flare)
Drain mm VP20 (I.D.φ20×O.D.φ26) VP20 (I.D.φ20×O.D.φ26)
Wired BRC1C61/BRC1D61/BRC1E62 BRC1C61/BRC1D61/BRC1E62
Remote controller (option)
Wireless BRC7EA63W BRC7EA63W
Outdoor unit RZQ100HAY4A RZQ125HAY4A
Colour Ivory white Ivory white
Dimensions H×W×D mm 1,345×900×320 1,345×900×320
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 2×60×1.4 2×60×1.4
Face area m² 1.15 1.15
Model JT1G-VDYR@T JT1G-VDYR@T
Comp. Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor output kW 2.3 2.7
Type Propeller fan Propeller fan
Fan Motor output W 70+70 70+70
Airflow rate m³/min 100 100
Cooling dB(A) 49 50
Sound pressure
level *3 Heating dB(A) 51 52
Night quiet mode dB(A) 45 45
Mass kg 108 108
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
Gas mm φ15.9 (Flare) φ15.9 (Flare)
connections
Drain mm φ26 (Hole) φ26 (Hole)
Safety devices High pressure switch. Fuse. High pressure switch. Fuse.
Capacity step % Compressor revolution speed control (Inverter system) Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve Electronic expansion valve
Max. length m 75 (Equivalent length 90m) 75 (Equivalent length 90m)
Ref. piping
Max. height difference m 30 30
Model R410A R410A
Refrigerant
Charge (factory charge) kg 4.3 (Charged for 30m) 4.3 (Charged for 30m)
Model Refer to the nameplate of compressor. Refer to the nameplate of compressor.
Ref. oil
Charge L 1.2 1.2
Specification C: 3D093018A C: 3D093018A
Drawing No. Sound (Indoor) C: 4D090912 C: 4D090913
Sound (Outdoor) C: 4D061464A, C: 4D061483A C: 4D061473A, C: 4D061484A

Notes: *1. The above data are based on the following conditions. Conversion formulae
Cooling Heating Piping length kcal/h=kW×860
Indoor: 27°CDB, 19°CWB Indoor: 20°CDB, 15°CWB 7.5m Btu/h=kW×3412
Outdoor: 35°CDB, 24°CWB Outdoor: 7°CDB, 6°CWB (Horizontal) cfm=m³/min×35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

18 SkyAir RZQS, RZQ series


EDMT281426 Specifications

FHQ (Ceiling suspended type) 1


Indoor unit FHQ140CAVEA
Model
Outdoor unit RZQ140HAY4A
Power supply 3 phase, 415V, 50Hz
Power supply intake Outdoor unit side
kW 13.2 (6.2-15.4)
Cooling capacity *1 *2 Btu/h 45,100 (21,200-52,600)
kcal/h 11,400 (5,300-13,200)
kW 16.0 (6.2-18.0)
Heating capacity *1 *2 Btu/h 54,600 (21,200-61,400)
kcal/h 13,800 (5,300-15,500)
Indoor unit FHQ140CAVEA
Colour Fresh white
Dimensions H×W×D mm 235×1,590×690
Type Cross fin coil
Coil Rows×Stages×Fin pitch 3×14×1.5
Face area m² 0.398
Type Sirocco fan
Motor output W 150
Fan
m³/min 34/29/24
Airflow rate (H/M/L)
cfm 1,200/1,024/847
Sound pressure level (H/M/L) *3 dB(A) 46/42/38
Air filter Resin net (with mould resistant)
Mass kg 38
Liquid mm φ9.5 (Flare)
Piping
connections
Gas mm φ15.9 (Flare)
Drain mm VP20 (I.D.φ20×O.D.φ26)
Wired BRC1C61/BRC1D61/BRC1E62
Remote controller (option)
Wireless BRC7GA53
Outdoor unit RZQ140HAY4A
Colour Ivory white
Dimensions H×W×D mm 1,345×900×320
Type Cross fin coil
Coil Rows×Stages×Fin pitch 2×60×1.4
Face area m² 1.15
Model JT1G-VDYR@T
Comp. Type Hermetically sealed scroll type
Motor output kW 2.9
Type Propeller fan
Fan Motor output W 70+70
Airflow rate m³/min 100
Cooling dB(A) 50
Sound pressure
level *3 Heating dB(A) 52
Night quiet mode dB(A) 46
Mass kg 108
Liquid mm φ9.5 (Flare)
Piping
Gas mm φ15.9 (Flare)
connections
Drain mm φ26 (Hole)
Safety devices High pressure switch. Fuse.
Capacity step % Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve
Max. length m 75 (Equivalent length 90m)
Ref. piping
Max. height difference m 30
Model R410A
Refrigerant
Charge (factory charge) kg 4.3 (Charged for 30m)
Model Refer to the nameplate of compressor.
Ref. oil
Charge L 1.2
Specification C: 4D083754
Drawing No. Sound (Indoor) C: 4D069651D
Sound (Outdoor) C: 4D061482B, C: 4D061485B

Notes: *1. The above data are based on the following conditions. Conversion formulae
Cooling Heating Piping length kcal/h=kW×860
Indoor: 27°CDB, 19°CWB Indoor: 20°CDB, 15°CWB 7.5m Btu/h=kW×3412
Outdoor: 35°CDB, 24°CWB Outdoor: 7°CDB, 6°CWB (Horizontal) cfm=m³/min×35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

SkyAir RZQS, RZQ series 19


Specifications EDMT281426

4.3 FAQ

FAQ (Wall mounted type)


Indoor unit FAQ71CVEA FAQ100CVEA
Model
Outdoor unit RZQ71LV1 RZQ100LV1
Power supply 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
Power supply intake Outdoor unit side Outdoor unit side
kW 7.1 (3.2-8.0) 10.0 (5.0-11.2)
Cooling capacity *1 *2 Btu/h 24,200 (10,900-27,300) 34,100 (17,100-38,200)
kcal/h 6,100 (2,800-6,900) 8,600 (4,300-9,600)
kW 8.0 (3.5-9.0) 11.2 (5.1-12.8)
Heating capacity *1 *2 Btu/h 27,300 (11,900-30,700) 38,200 (17,400-43,700)
kcal/h 6,900 (3,000-7,700) 9,600 (4,400-11,000)
Indoor unit FAQ71CVEA FAQ100CVEA
Colour Fresh white Fresh white
Dimensions H×W×D mm 290×1,050×238 340×1,200×240
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 2×18×1.2 2×20×1.2
Face area m² 0.279 0.347
Type Cross flow fan Cross flow fan
Motor output W 48 64
Fan
m³/min 18/16/14 26/23/19
Airflow rate (H/M/L)
cfm 635/565/494 918/812/671
Sound pressure level (H/M/L) *3 dB(A) 45/42/40 49/45/41
Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Mass kg 13 17
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
connections
Gas mm φ15.9 (Flare) φ15.9 (Flare)
Drain mm VP13 (I.D.φ13×O.D.φ18) VP13 (I.D.φ13×O.D.φ18)
Wired BRC1C61/BRC1D61/BRC1E62 BRC1C61/BRC1D61/BRC1E62
Remote controller (option)
Wireless BRC7EB518 BRC7EB518
Outdoor unit RZQ71LV1 RZQ100LV1
Colour Ivory white Ivory white
Dimensions H×W×D mm 770×900×320 990×940×320
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 2×34×1.4 2×44×1.4
Face area m² 0.650 0.884
Model 2YC63FXD 2YC63FXD
Comp. Type Hermetically sealed swing type Hermetically sealed swing type
Motor output kW 1.7 2.08
Type Propeller fan Propeller fan
Fan Motor output W 70 200
Airflow rate m³/min 52 76
Cooling dB(A) 49 51
Sound pressure
level *3 Heating dB(A) 51 53
Night quiet mode dB(A) 45 47
Mass kg 64 75
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
Gas mm φ15.9 (Flare) φ15.9 (Flare)
connections
Drain mm φ26 (Hole) φ26 (Hole)
Safety devices High pressure switch. Fuse. High pressure switch. Fuse.
Capacity step % Compressor revolution speed control (Inverter system) Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve Electronic expansion valve
Max. length m 50 (Equivalent length 70m) 75 (Equivalent length 90m)
Ref. piping
Max. height difference m 30 30
Model R410A R410A
Refrigerant
Charge (factory charge) kg 2.0 (Charged for 30m) 2.9 (Charged for 30m)
Model Refer to the nameplate of compressor. Refer to the nameplate of compressor.
Ref. oil
Charge L 0.75 0.75
Specification C: 3D089651A C: 3D089651A
Drawing No. Sound (Indoor) C: 4D100001 C: 4D100002A
Sound (Outdoor) C: 4D075745A, C: 4D075748A C: 4D089676, C: 4D089677A

Notes: *1. The above data are based on the following conditions. Conversion formulae
Cooling Heating Piping length kcal/h=kW×860
Indoor: 27°CDB, 19°CWB Indoor: 20°CDB, 15°CWB 7.5m Btu/h=kW×3412
Outdoor: 35°CDB, 24°CWB Outdoor: 7°CDB, 6°CWB (Horizontal) cfm=m³/min×35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

20 SkyAir RZQS, RZQ series


EDMT281426 Specifications

FAQ (Wall mounted type) 1


Indoor unit FAQ100CVEA
Model
Outdoor unit RZQ100HAY4A
Power supply 3 phase, 415V, 50Hz
Power supply intake Outdoor unit side
kW 10.0 (5.0-11.2)
Cooling capacity *1 *2 Btu/h 34,100 (17,100-38,200)
kcal/h 8,600 (4,300-9,600)
kW 11.2 (5.1-12.8)
Heating capacity *1 *2 Btu/h 38,200 (17,400-43,700)
kcal/h 9,600 (4,400-11,000)
Indoor unit FAQ100CVEA
Colour Fresh white
Dimensions H×W×D mm 340×1,200×240
Type Cross fin coil
Coil Rows×Stages×Fin pitch 2×20×1.2
Face area m² 0.347
Type Cross flow fan
Motor output W 64
Fan
m³/min 26/23/19
Airflow rate (H/M/L)
cfm 918/812/671
Sound pressure level (H/M/L) *3 dB(A) 49/45/41
Air filter Resin net (with mould resistance)
Mass kg 17
Liquid mm φ9.5 (Flare)
Piping
connections
Gas mm φ15.9 (Flare)
Drain mm VP13 (I.D.φ13×O.D.φ18)
Wired BRC1C61/BRC1D61/BRC1E62
Remote controller (option)
Wireless BRC7EB518
Outdoor unit RZQ100HAY4A
Colour Ivory white
Dimensions H×W×D mm 1,345×900×320
Type Cross fin coil
Coil Rows×Stages×Fin pitch 2×60×1.4
Face area m² 1.15
Model JT1G-VDYR@T
Comp. Type Hermetically sealed scroll type
Motor output kW 1.7
Type Propeller fan
Fan Motor output W 70+70
Airflow rate m³/min 100
Cooling dB(A) 49
Sound pressure
level *3 Heating dB(A) 51
Night quiet mode dB(A) 45
Mass kg 108
Liquid mm φ9.5 (Flare)
Piping
Gas mm φ15.9 (Flare)
connections
Drain mm φ26 (Hole)
Safety devices High pressure switch. Fuse.
Capacity step % Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve
Max. length m 75 (Equivalent length 90m)
Ref. piping
Max. height difference m 30
Model R410A
Refrigerant
Charge (factory charge) kg 4.3 (Charged for 30m)
Model Refer to the nameplate of compressor.
Ref. oil
Charge L 1.20
Specification C: 4D084142C
Drawing No. Sound (Indoor) C: 4D100002A
Sound (Outdoor) C: 4D061464A, C: 4D061483A

Notes: *1. The above data are based on the following conditions. Conversion formulae
Cooling Heating Piping length kcal/h=kW×860
Indoor: 27°CDB, 19°CWB Indoor: 20°CDB, 15°CWB 7.5m Btu/h=kW×3412
Outdoor: 35°CDB, 24°CWB Outdoor: 7°CDB, 6°CWB (Horizontal) cfm=m³/min×35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

SkyAir RZQS, RZQ series 21


Specifications EDMT281426

4.4 FBQ-DB

FBQ-DB (Duct connection middle and high static pressure type)


Indoor unit FBQ71DBVEA FBQ100DBVEA
Model
Outdoor unit RZQ71LV1 RZQ100LV1
Power supply Indoor unit 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
Outdoor unit 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
Power supply intake Indoor/Outdoor unit side Indoor/Outdoor unit side
kW 7.1 (3.2-8.0) 10.0 (5.0-11.2)
Cooling capacity *1 *2 Btu/h 24,200 (10,900-27,300) 34,100 (17,100-38,200)
kcal/h 6,100 (2,800-6,900) 8,600 (4,300-9,600)
kW 8.0 (3.5-9.0) 11.2 (5.1-12.8)
Heating capacity *1 *2 Btu/h 27,300 (11,900-30,700) 38,200 (17,400-43,700)
kcal/h 6,900 (3,000-7,700) 9,600 (4,400-11,000)
Indoor unit FBQ71DBVEA FBQ100DBVEA
Colour — —
Dimensions H×W×D mm 300×1,000×700 300×1,400×700
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 3×16×1.75 3×16×1.75
Face area m² 0.249 0.383
Type Sirocco fan Sirocco fan
Motor output W 350 350
Fan m³/min 18/16.5/15 32/27.5/23
Airflow rate (HH/H/L)
cfm 635/582/530 1,130/971/812
External static pressure Pa 50-200 *5 50-200 *5
Sound pressure level (HH/H/L) *3 dB(A) 37/34.5/32 38/35.5/33
Air filter — *4 — *4
Mass kg 36 46
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
connections
Gas mm φ15.9 (Flare) φ15.9 (Flare)
Drain mm VP25 (I.D.φ25×O.D.φ32) VP25 (I.D.φ25×O.D.φ32)
Wired BRC1C61/BRC1D61/BRC1E62 BRC1C61/BRC1D61/BRC1E62
Remote controller (option)
Wireless BRC4C65 BRC4C65
Outdoor unit RZQ71LV1 RZQ100LV1
Colour Ivory white Ivory white
Dimensions H×W×D mm 770×900×320 990×940×320
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 2×34×1.4 2×44×1.4
Face area m² 0.650 0.884
Model 2YC63FXD 2YC63FXD
Comp. Type Hermetically sealed swing type Hermetically sealed swing type
Motor output kW 1.7 2.08
Type Propeller fan Propeller fan
Fan Motor output W 70 200
Airflow rate m³/min 52 76
Cooling dB(A) 49 51
Sound pressure
level *3 Heating dB(A) 51 53
Night quiet mode dB(A) 45 47
Mass kg 64 75
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
Gas mm φ15.9 (Flare) φ15.9 (Flare)
connections
Drain mm φ26 (Hole) φ26 (Hole)
Safety devices High pressure switch. Fuse. High pressure switch. Fuse.
Capacity step % Compressor revolution speed control (Inverter system) Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve Electronic expansion valve
Max. length m 50 (Equivalent length 70m) 75 (Equivalent length 90m)
Ref. piping
Max. height difference m 30 30
Model R410A R410A
Refrigerant
Charge (factory charge) kg 2.0 (Charged for 30m) 2.9 (Charged for 30m)
Model Refer to the nameplate of compressor. Refer to the nameplate of compressor.
Ref. oil
Charge L 0.75 0.75
Specification C: 3D089655C C: 3D089655C
Drawing No. Sound (Indoor) C: 4D094596 C: 4D094597
Sound (Outdoor) C: 4D075745A, C: 4D075748A C: 4D089676, C: 4D089677A

Note: *1. The above data are based on the following conditions. Conversion formulae
Cooling Heating Piping length kcal/h=kW×860
Indoor: 27°CDB, 19°CWB Indoor: 20°CDB, 15°CWB 7.5m Btu/h=kW×3412
Outdoor: 35°CDB, 24°CWB Outdoor: 7°CDB, 6°CWB (Horizontal) cfm=m³/min×35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.
*4. Air filter is not standard accessory, but please mount it in the duct system of the suction side.
Select its dust collection efficiency (gravity method) 50% or more.
*5. Initial setting is standard.

22 SkyAir RZQS, RZQ series


EDMT281426 Specifications

FBQ-DB (Duct connection middle and high static pressure type) 1


Indoor unit FBQ125DBVEA FBQ140DBVEA
Model
Outdoor unit RZQ125LV1 RZQ140LV1
Power supply Indoor unit 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
Outdoor unit 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
Power supply intake Indoor/Outdoor unit side Indoor/Outdoor unit side
kW 12.0 (5.7-14.0) 13.0 (6.2-15.5)
Cooling capacity *1 *2 Btu/h 40,900 (19,500-47,800) 44,400 (21,200-52,900)
kcal/h 10,300 (4,900-12,000) 11,200 (5,300-13,300)
kW 14.0 (6.0-16.2) 16.0 (6.2-18.0)
Heating capacity *1 *2 Btu/h 47,800 (20,500-55,300) 54,600 (21,200-61,400)
kcal/h 12,000 (5,200-13,900) 13,800 (5,300-15,500)
Indoor unit FBQ125DBVEA FBQ140DBVEA
Colour — —
Dimensions H×W×D mm 300×1,400×700 300×1,400×700
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 3×16×1.75 3×16×1.75
Face area m² 0.383 0.383
Type Sirocco fan Sirocco fan
Motor output W 350 350
Fan m³/min 39/33.5/28 39/33.5/28
Airflow rate (HH/H/L)
cfm 1,377/1,183/988 1,377/1,183/988
External static pressure Pa 50-200 *5 50-200 *5
Sound pressure level (HH/H/L) *3 dB(A) 40/38/36 40/38/36
Air filter — *4 — *4
Mass kg 46 46
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
connections
Gas mm φ15.9 (Flare) φ15.9 (Flare)
Drain mm VP25 (I.D.φ25×O.D.φ32) VP25 (I.D.φ25×O.D.φ32)
Wired BRC1C61/BRC1D61/BRC1E62 BRC1C61/BRC1D61/BRC1E62
Remote controller (option)
Wireless BRC4C65 BRC4C65
Outdoor unit RZQ125LV1 RZQ140LV1
Colour Ivory white Ivory white
Dimensions H×W×D mm 1,170×900×320 1,430×940×320
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 2×52×1.4 2×64×1.4
Face area m² 1.010 1.286
Model JT100G-VD@T3 JT100G-VD@T3
Comp. Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor output kW 2.4 3.15
Type Propeller fan Propeller fan
Fan Motor output W 70+70 200+200
Airflow rate m³/min 95 140
Cooling dB(A) 51 54
Sound pressure
level *3 Heating dB(A) 53 56
Night quiet mode dB(A) 47 50
Mass kg 98 108
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
Gas mm φ15.9 (Flare) φ15.9 (Flare)
connections
Drain mm φ26 (Hole) φ26 (Hole)
Safety devices High pressure switch. Fuse. High pressure switch. Fuse.
Capacity step % Compressor revolution speed control (Inverter system) Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve Electronic expansion valve
Max. length m 75 (Equivalent length 90m) 75 (Equivalent length 90m)
Ref. piping
Max. height difference m 30 30
Model R410A R410A
Refrigerant
Charge (factory charge) kg 3.15 (Charged for 30m) 4.2 (Charged for 30m)
Model Refer to the nameplate of compressor. Refer to the nameplate of compressor.
Ref. oil
Charge L 1.2 1.5
Specification C: 3D089655C C: 3D089655C
Drawing No. Sound (Indoor) C: 4D094598 C: 4D094598
Sound (Outdoor) C: 4D075741A, C: 4D075747A C: 4D089680A, C: 4D089681A

Note: *1. The above data are based on the following conditions. Conversion formulae
Cooling Heating Piping length kcal/h=kW×860
Indoor: 27°CDB, 19°CWB Indoor: 20°CDB, 15°CWB 7.5m Btu/h=kW×3412
Outdoor: 35°CDB, 24°CWB Outdoor: 7°CDB, 6°CWB (Horizontal) cfm=m³/min×35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.
*4. Air filter is not standard accessory, but please mount it in the duct system of the suction side.
Select its dust collection efficiency (gravity method) 50% or more.
*5. Initial setting is standard.

SkyAir RZQS, RZQ series 23


Specifications EDMT281426

FBQ-DB (Duct connection middle and high static pressure type)


Indoor unit FBQ100DBVEA FBQ125DBVEA
Model
Outdoor unit RZQ100HAY4A RZQ125HAY4A
Power supply Indoor unit 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
Outdoor unit 3 phase, 415V, 50Hz 3 phase, 415V, 50Hz
Power supply intake Indoor/Outdoor unit side Indoor/Outdoor unit side
kW 10.0 (5.0-11.2) 12.0 (5.7-14.0)
Cooling capacity *1 *2 Btu/h 34,100 (17,100-38,200) 40,900 (19,500-47,800)
kcal/h 8,600 (4,300-9,600) 10,300 (4,900-12,000)
kW 11.2 (5.1-12.8) 14.0 (6.0-16.2)
Heating capacity *1 *2 Btu/h 38,200 (17,400-43,700) 47,800 (20,500-55,300)
kcal/h 9,600 (4,400-11,000) 12,000 (5,200-13,900)
Indoor unit FBQ100DBVEA FBQ125DBVEA
Colour — —
Dimensions H×W×D mm 300×1,400×700 300×1,400×700
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 3×16×1.75 3×16×1.75
Face area m² 0.383 0.383
Type Sirocco fan Sirocco fan
Motor output W 350 350
Fan m³/min 32/27.5/23 39/33.5/28
Airflow rate (HH/H/L)
cfm 1,130/971/812 1,377/1,183/988
External static pressure Pa 50-200 *5 50-200 *5
Sound pressure level (HH/H/L) *3 dB(A) 38/35.5/33 40/38/36
Air filter — *4 — *4
Mass kg 46 46
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
connections
Gas mm φ15.9 (Flare) φ15.9 (Flare)
Drain mm VP25 (I.D.φ25×O.D.φ32) VP25 (I.D.φ25×O.D.φ32)
Wired BRC1C61/BRC1D61/BRC1E62 BRC1C61/BRC1D61/BRC1E62
Remote controller (option)
Wireless BRC4C65 BRC4C65
Outdoor unit RZQ100HAY4A RZQ125HAY4A
Colour Ivory white Ivory white
Dimensions H×W×D mm 1,345×900×320 1,345×900×320
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 2×60×1.4 2×60×1.4
Face area m² 1.15 1.15
Model JT1G-VDYR@T JT1G-VDYR@T
Comp. Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor output kW 1.9 2.4
Type Propeller fan Propeller fan
Fan Motor output W 70+70 70+70
Airflow rate m³/min 100 100
Cooling dB(A) 49 50
Sound pressure
level *3 Heating dB(A) 51 52
Night quiet mode dB(A) 45 45
Mass kg 108 108
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
Gas mm φ15.9 (Flare) φ15.9 (Flare)
connections
Drain mm φ26 (Hole) φ26 (Hole)
Safety devices High pressure switch. Fuse. High pressure switch. Fuse.
Capacity step % Compressor revolution speed control (Inverter system) Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve Electronic expansion valve
Max. length m 75 (Equivalent length 90m) 75 (Equivalent length 90m)
Ref. piping
Max. height difference m 30 30
Model R410A R410A
Refrigerant
Charge (factory charge) kg 4.3 (Charged for 30m) 4.3 (Charged for 30m)
Model Refer to the nameplate of compressor. Refer to the nameplate of compressor.
Ref. oil
Charge L 1.2 1.2
Specification C: 3D093012B C: 3D093012B
Drawing No. Sound (Indoor) C: 4D094597 C: 4D094598
Sound (Outdoor) C: 4D061464A, C: 4D061483A C: 4D061473A, C: 4D061484A

Notes: *1. The above data are based on the following conditions. Conversion formulae
Cooling Heating Piping length kcal/h=kW×860
Indoor: 27°CDB, 19°CWB Indoor: 20°CDB, 15°CWB 7.5m Btu/h=kW×3412
Outdoor: 35°CDB, 24°CWB Outdoor: 7°CDB, 6°CWB (Horizontal) cfm=m³/min×35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.
*4. Air filter is not standard accessory, but please mount it in the duct system of the suction side.
Select its dust collection efficiency (gravity method) 50% or more.
*5. Initial setting is standard.

24 SkyAir RZQS, RZQ series


EDMT281426 Specifications

FBQ-DB (Duct connection middle and high static pressure type) 1


Indoor unit FBQ140DBVEA
Model
Outdoor unit RZQ140HAY4A
Power supply Indoor unit 1 phase, 220-240V, 50Hz
Outdoor unit 3 phase, 415V, 50Hz
Power supply intake Indoor/Outdoor unit side
kW 13.0 (6.2-15.4)
Cooling capacity *1 *2 Btu/h 44,400 (21,200-52,600)
kcal/h 11,200 (5,300-13,200)
kW 16.0 (6.2-18.0)
Heating capacity *1 *2 Btu/h 54,600 (21,200-61,400)
kcal/h 13,800 (5,300-15,500)
Indoor unit FBQ140DBVEA
Colour —
Dimensions H×W×D mm 300×1,400×700
Type Cross fin coil
Coil Rows×Stages×Fin pitch 3×16×1.75
Face area m² 0.383
Type Sirocco fan
Motor output W 350
Fan m³/min 39/33.5/28
Airflow rate (HH/H/L)
cfm 1,377/1,183/988
External static pressure Pa 50-200 *5
Sound pressure level (HH/H/L) *3 dB(A) 40/38/36
Air filter — *4
Mass kg 46
Liquid mm φ9.5 (Flare)
Piping
connections
Gas mm φ15.9 (Flare)
Drain mm VP25 (I.D.φ25×O.D.φ32)
Wired BRC1C61/BRC1D61/BRC1E62
Remote controller (option)
Wireless BRC4C65
Outdoor unit RZQ140HAY4A
Colour Ivory white
Dimensions H×W×D mm 1,345×900×320
Type Cross fin coil
Coil Rows×Stages×Fin pitch 2×60×1.4
Face area m² 1.15
Model JT1G-VDYR@T
Comp. Type Hermetically sealed scroll type
Motor output kW 2.9
Type Propeller fan
Fan Motor output W 70+70
Airflow rate m³/min 100
Cooling dB(A) 50
Sound pressure
level *3 Heating dB(A) 52
Night quiet mode dB(A) 46
Mass kg 108
Liquid mm φ9.5 (Flare)
Piping
Gas mm φ15.9 (Flare)
connections
Drain mm φ26 (Hole)
Safety devices High pressure switch. Fuse.
Capacity step % Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve
Max. length m 75 (Equivalent length 90m)
Ref. piping
Max. height difference m 30
Model R410A
Refrigerant
Charge (factory charge) kg 4.3 (Charged for 30m)
Model Refer to the nameplate of compressor.
Ref. oil
Charge L 1.2
Specification C: 3D093012B
Drawing No. Sound (Indoor) C: 4D094598
Sound (Outdoor) C: 4D061482B, C: 4D061485B

Notes: *1. The above data are based on the following conditions. Conversion formulae
Cooling Heating Piping length kcal/h=kW×860
Indoor: 27°CDB, 19°CWB Indoor: 20°CDB, 15°CWB 7.5m Btu/h=kW×3412
Outdoor: 35°CDB, 24°CWB Outdoor: 7°CDB, 6°CWB (Horizontal) cfm=m³/min×35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.
*4. Air filter is not standard accessory, but please mount it in the duct system of the suction side.
Select its dust collection efficiency (gravity method) 50% or more.
*5. Initial setting is standard.

SkyAir RZQS, RZQ series 25


Specifications EDMT281426

4.5 FVQ

FVQ (Floor standing type)


Indoor unit FVQ50CVE FVQ60CVE
Model
Outdoor unit RZQS50AV1 RZQS60AV1
Power supply 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
Power supply intake Outdoor unit side Outdoor unit side
kW 5.0 (3.2-5.6) 5.8 (3.2-6.0)
Cooling capacity *1 *2 Btu/h 17,100 (10,900-19,100) 19,800 (10,900-20,500)
kcal/h 4,300 (2,800-4,800) 5,000 (2,800-5,200)
kW 6.0 (3.5-7.0) 7.0 (3.5-8.0)
Heating capacity *1 *2 Btu/h 20,500 (11,900-23,900) 23,900 (11,900-27,300)
kcal/h 5,200 (3,000-6,000) 6,000 (3,000-6,900)
Indoor unit FVQ50CVE FVQ60CVE
Colour Fresh white Fresh white
Dimensions H×W×D mm 1,850×600×270 1,850×600×270
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 2×40×1.75 2×40×1.75
Face area m² 0.400 0.400
Type Sirocco fan Sirocco fan
Motor output W 64 64
Fan
m³/min 18/16/14 18/16/14
Airflow rate (H/M/L)
cfm 635/565/494 635/565/494
Sound pressure level (H/M/L) *3 dB(A) 43/41/38 43/41/38
Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Mass kg 39 39
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
connections
Gas mm φ15.9 (Flare) φ15.9 (Flare)
Drain mm VP20 (I.D.φ20×O.D.φ26) VP20 (I.D.φ20×O.D.φ26)
Wired BRC1C61/BRC1E62 BRC1C61/BRC1E62
Remote controller (option)
Wireless — —
Outdoor unit RZQS50AV1 RZQS60AV1
Colour Ivory white Ivory white
Dimensions H×W×D mm 770×900×320 770×900×320
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 2×34×1.4 2×34×1.4
Face area m² 0.650 0.650
Model 2YC63FXD 2YC63FXD
Comp. Type Hermetically sealed swing type Hermetically sealed swing type
Motor output kW 1.3 1.6
Type Propeller fan Propeller fan
Fan Motor output W 70 70
Airflow rate m³/min 52 52
Cooling dB(A) 48 48
Sound pressure
level *3 Heating dB(A) 50 50
Night quiet mode dB(A) 44 44
Mass kg 64 64
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
Gas mm φ15.9 (Flare) φ15.9 (Flare)
connections
Drain mm φ26 (Hole) φ26 (Hole)
Safety devices High pressure switch. Fuse. High pressure switch. Fuse.
Capacity step % Compressor revolution speed control (Inverter system) Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve Electronic expansion valve
Max. length m 50 (Equivalent length 70m) 50 (Equivalent length 70m)
Ref. piping
Max. height difference m 30 30
Model R410A R410A
Refrigerant
Charge (factory charge) kg 2.0 (Charged for 30m) 2.0 (Charged for 30m)
Model Refer to the nameplate of compressor. Refer to the nameplate of compressor.
Ref. oil
Charge L 0.75 0.75
Specification C: 3D089653B C: 3D089653B
Drawing No. Sound (Indoor) C: 4D073851A C: 4D073851A
Sound (Outdoor) C: 4D090424, C: 4D090423 C: 4D090424, C: 4D090423

Notes: *1. The above data are based on the following conditions. Conversion formulae
Cooling Heating Piping length kcal/h=kW×860
Indoor: 27°CDB, 19°CWB Indoor: 20°CDB, 15°CWB 7.5m Btu/h=kW×3412
Outdoor: 35°CDB, 24°CWB Outdoor: 7°CDB, 6°CWB (Horizontal) cfm=m³/min×35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

26 SkyAir RZQS, RZQ series


EDMT281426 Specifications

FVQ (Floor standing type) 1


Indoor unit FVQ71CVEB FVQ100CVEB
Model
Outdoor unit RZQ71LV1 RZQ100LV1
Power supply 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
Power supply intake Outdoor unit side Outdoor unit side
kW 7.1 (3.2-8.0) 10.0 (5.0-11.2)
Cooling capacity *1 *2 Btu/h 24,200 (10,900-27,300) 34,100 (17,100-38,200)
kcal/h 6,100 (2,800-6,900) 8,600 (4,300-9,600)
kW 8.0 (3.5-9.0) 11.2 (5.1-12.8)
Heating capacity *1 *2 Btu/h 27,300 (11,900-30,700) 38,200 (17,400-43,700)
kcal/h 6,900 (3,000-7,700) 9,600 (4,400-11,000)
Indoor unit FVQ71CVEB FVQ100CVEB
Colour Fresh white Fresh white
Dimensions H×W×D mm 1,850×600×270 1,850×600×350
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 2×40×1.75 (2×22×1.75)×2
Face area m² 0.400 0.400 (0.220×2)
Type Sirocco fan Sirocco fan
Motor output W 64 152
Fan
m³/min 18/16/14 28/25/22
Airflow rate (H/M/L)
cfm 635/565/494 988/883/777
Sound pressure level (H/M/L) *3 dB(A) 43/41/38 50/47/44
Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Mass kg 39 47
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
connections
Gas mm φ15.9 (Flare) φ15.9 (Flare)
Drain mm VP20 (I.D.φ20×O.D.φ26) VP20 (I.D.φ20×O.D.φ26)
Wired BRC1C61/BRC1E62 BRC1C61/BRC1E62
Remote controller (option)
Wireless — —
Outdoor unit RZQ71LV1 RZQ100LV1
Colour Ivory white Ivory white
Dimensions H×W×D mm 770×900×320 990×940×320
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 2×34×1.4 2×44×1.4
Face area m² 0.650 0.884
Model 2YC63FXD 2YC63FXD
Comp. Type Hermetically sealed swing type Hermetically sealed swing type
Motor output kW 1.7 2.08
Type Propeller fan Propeller fan
Fan Motor output W 70 200
Airflow rate m³/min 52 76
Cooling dB(A) 49 51
Sound pressure
level *3 Heating dB(A) 51 53
Night quiet mode dB(A) 45 47
Mass kg 64 75
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
Gas mm φ15.9 (Flare) φ15.9 (Flare)
connections
Drain mm φ26 (Hole) φ26 (Hole)
Safety devices High pressure switch. Fuse. High pressure switch. Fuse.
Capacity step % Compressor revolution speed control (Inverter system) Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve Electronic expansion valve
Max. length m 50 (Equivalent length 70m) 75 (Equivalent length 90m)
Ref. piping
Max. height difference m 30 30
Model R410A R410A
Refrigerant
Charge (factory charge) kg 2.0 (Charged for 30m) 2.9 (Charged for 30m)
Model Refer to the nameplate of compressor. Refer to the nameplate of compressor.
Ref. oil
Charge L 0.75 0.75
Specification C: 3D089653B C: 3D089653B
Drawing No. Sound (Indoor) C: 4D073851A C: 4D073852
Sound (Outdoor) C: 4D075745A, C: 4D075748A C: 4D089676, C: 4D089677A

Notes: *1. The above data are based on the following conditions. Conversion formulae
Cooling Heating Piping length kcal/h=kW×860
Indoor: 27°CDB, 19°CWB Indoor: 20°CDB, 15°CWB 7.5m Btu/h=kW×3412
Outdoor: 35°CDB, 24°CWB Outdoor: 7°CDB, 6°CWB (Horizontal) cfm=m³/min×35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

SkyAir RZQS, RZQ series 27


Specifications EDMT281426

FVQ (Floor standing type)


Indoor unit FVQ125CVEB FVQ140CVEB
Model
Outdoor unit RZQ125LV1 RZQ140LV1
Power supply 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
Power supply intake Outdoor unit side Outdoor unit side
kW 12.5 (5.7-14.0) 13.5 (6.2-15.5)
Cooling capacity *1 *2 Btu/h 42,700 (19,500-47,800) 46,100 (21,200-52,900)
kcal/h 10,800 (4,900-12,000) 11,600 (5,300-13,300)
kW 14.0 (6.0-16.2) 16.0 (6.2-18.0)
Heating capacity *1 *2 Btu/h 47,800 (20,500-55,300) 54,600 (21,200-61,400)
kcal/h 12,000 (5,200-13,900) 13,800 (5,300-15,500)
Indoor unit FVQ125CVEB FVQ140CVEB
Colour Fresh white Fresh white
Dimensions H×W×D mm 1,850×600×350 1,850×600×350
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch (2×22×1.75)×2 (2×22×1.75)×2
Face area m² 0.400 (0.220×2) 0.400 (0.220×2)
Type Sirocco fan Sirocco fan
Motor output W 152 152
Fan
m³/min 28/26/24 30/28/26
Airflow rate (H/M/L)
cfm 988/918/847 1,059/988/918
Sound pressure level (H/M/L) *3 dB(A) 51/48/46 53/51/48
Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Mass kg 47 47
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
connections
Gas mm φ15.9 (Flare) φ15.9 (Flare)
Drain mm VP20 (I.D.φ20×O.D.φ26) VP20 (I.D.φ20×O.D.φ26)
Wired BRC1C61/BRC1E62 BRC1C61/BRC1E62
Remote controller (option)
Wireless — —
Outdoor unit RZQ125LV1 RZQ140LV1
Colour Ivory white Ivory white
Dimensions H×W×D mm 1,170×900×320 1,430×940×320
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 2×52×1.4 2×64×1.4
Face area m² 1.010 1.286
Model JT100G-VD@T3 JT100G-VD@T3
Comp. Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor output kW 2.4 3.15
Type Propeller fan Propeller fan
Fan Motor output W 70+70 200+200
Airflow rate m³/min 95 140
Cooling dB(A) 51 54
Sound pressure
level *3 Heating dB(A) 53 56
Night quiet mode dB(A) 47 50
Mass kg 98 108
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
Gas mm φ15.9 (Flare) φ15.9 (Flare)
connections
Drain mm φ26 (Hole) φ26 (Hole)
Safety devices High pressure switch. Fuse. High pressure switch. Fuse.
Capacity step % Compressor revolution speed control (Inverter system) Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve Electronic expansion valve
Max. length m 75 (Equivalent length 90m) 75 (Equivalent length 90m)
Ref. piping
Max. height difference m 30 30
Model R410A R410A
Refrigerant
Charge (factory charge) kg 3.15 (Charged for 30m) 4.2 (Charged for 30m)
Model Refer to the nameplate of compressor. Refer to the nameplate of compressor.
Ref. oil
Charge L 1.2 1.5
Specification C: 3D089653B C: 3D089653B
Drawing No. Sound (Indoor) C: 4D073853A C: 4D073854
Sound (Outdoor) C: 4D075741A, C: 4D075747A C: 4D089680A, C: 4D089681A

Notes: *1. The above data are based on the following conditions. Conversion formulae
Cooling Heating Piping length kcal/h=kW×860
Indoor: 27°CDB, 19°CWB Indoor: 20°CDB, 15°CWB 7.5m Btu/h=kW×3412
Outdoor: 35°CDB, 24°CWB Outdoor: 7°CDB, 6°CWB (Horizontal) cfm=m³/min×35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

28 SkyAir RZQS, RZQ series


EDMT281426 Specifications

FVQ (Floor standing type) 1


Indoor unit FVQ100CVEB FVQ125CVEB
Model
Outdoor unit RZQ100HAY4A RZQ125HAY4A
Power supply 3 phase, 415V, 50Hz 3 phase, 415V, 50Hz
Power supply intake Outdoor unit side Outdoor unit side
kW 10.0 (5.0-11.2) 12.5 (5.7-14.0)
Cooling capacity *1 *2 Btu/h 34,100 (17,100-38,200) 42,700 (19,500-47,800)
kcal/h 8,600 (4,300-9,600) 10,800 (4,900-12,000)
kW 11.2 (5.1-12.8) 14.0 (6.0-16.2)
Heating capacity *1 *2 Btu/h 38,200 (17,400-43,700) 47,800 (20,500-55,300)
kcal/h 9,600 (4,400-11,000) 12,000 (5,200-13,900)
Indoor unit FVQ100CVEB FVQ125CVEB
Colour Fresh white Fresh white
Dimensions H×W×D mm 1,850×600×350 1,850×600×350
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch (3×22×1.75)×2 (3×22×1.75)×2
Face area m² 0.44 0.44
Type Sirocco fan Sirocco fan
Motor output W 152 152
Fan
m³/min 28/25/22 28/26/24
Airflow rate (H/M/L)
cfm 988/883/777 988/918/847
Sound pressure level (H/M/L) *3 dB(A) 50/47/44 51/48/46
Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Mass kg 47 47
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
connections
Gas mm φ15.9 (Flare) φ15.9 (Flare)
Drain mm VP20 (I.D.φ20×O.D.φ26) VP20 (I.D.φ20×O.D.φ26)
Wired BRC1C61/BRC1E62 BRC1C61/BRC1E62
Remote controller (option)
Wireless — —
Outdoor unit RZQ100HAY4A RZQ125HAY4A
Colour Ivory white Ivory white
Dimensions H×W×D mm 1,345×900×320 1,345×900×320
Type Cross fin coil Cross fin coil
Coil Rows×Stages×Fin pitch 2×60×1.4 2×60×1.4
Face area m² 1.15 1.15
Model JT1G-VDYR@T JT1G-VDYR@T
Comp. Type Hermetically sealed scroll type Hermetically sealed scroll type
Motor output kW 1.7 2.2
Type Propeller fan Propeller fan
Fan Motor output W 70+70 70+70
Airflow rate m³/min 100 100
Cooling dB(A) 49 50
Sound pressure
level *3 Heating dB(A) 51 52
Night quiet mode dB(A) 45 45
Mass kg 108 108
Liquid mm φ9.5 (Flare) φ9.5 (Flare)
Piping
Gas mm φ15.9 (Flare) φ15.9 (Flare)
connections
Drain mm φ26 (Hole) φ26 (Hole)
Safety devices High pressure switch. Fuse. High pressure switch. Fuse.
Capacity step % Compressor revolution speed control (Inverter system) Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve Electronic expansion valve
Max. length m 75 (Equivalent length 90m) 75 (Equivalent length 90m)
Ref. piping
Max. height difference m 30 30
Model R410A R410A
Refrigerant
Charge (factory charge) kg 4.3 (Charged for 30m) 4.3 (Charged for 30m)
Model Refer to the nameplate of compressor. Refer to the nameplate of compressor.
Ref. oil
Charge L 1.2 1.2
Specification C: 4D080665B C: 4D080666B
Drawing No. Sound (Indoor) C: 4D073852 C: 4D073853A
Sound (Outdoor) C: 4D061464A, C: 4D061483A C: 4D061473A, C: 4D061484A

Notes: *1. The above data are based on the following conditions. Conversion formulae
Cooling Heating Piping length kcal/h=kW×860
Indoor: 27°CDB, 19°CWB Indoor: 20°CDB, 15°CWB 7.5m Btu/h=kW×3412
Outdoor: 35°CDB, 24°CWB Outdoor: 7°CDB, 6°CWB (Horizontal) cfm=m³/min×35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

SkyAir RZQS, RZQ series 29


Specifications EDMT281426

FVQ (Floor standing type)


Indoor unit FVQ140CVEB
Model
Outdoor unit RZQ140HAY4A
Power supply 3 phase, 415V, 50Hz
Power supply intake Outdoor unit side
kW 13.5 (6.2-15.4)
Cooling capacity *1 *2 Btu/h 46,100 (21,200-52,600)
kcal/h 11,600 (5,300-13,200)
kW 16.0 (6.2-18.0)
Heating capacity *1 *2 Btu/h 54,600 (21,200-61,400)
kcal/h 13,800 (5,300-15,500)
Indoor unit FVQ140CVEB
Colour Fresh white
Dimensions H×W×D mm 1,850×600×350
Type Cross fin coil
Coil Rows×Stages×Fin pitch (3×22×1.75)×2
Face area m² 0.44
Type Sirocco fan
Motor output W 152
Fan
m³/min 30/28/26
Airflow rate (H/M/L)
cfm 1,059/988/918
Sound pressure level (H/M/L) *3 dB(A) 53/51/48
Air filter Resin net (with mould resistance)
Mass kg 47
Liquid mm φ9.5 (Flare)
Piping
connections
Gas mm φ15.9 (Flare)
Drain mm VP20 (I.D.φ20×O.D.φ26)
Wired BRC1C61/BRC1E62
Remote controller (option)
Wireless —
Outdoor unit RZQ140HAY4A
Colour Ivory white
Dimensions H×W×D mm 1,345×900×320
Type Cross fin coil
Coil Rows×Stages×Fin pitch 2×60×1.4
Face area m² 1.15
Model JT1G-VDYR@T
Comp. Type Hermetically sealed scroll type
Motor output kW 2.9
Type Propeller fan
Fan Motor output W 70+70
Airflow rate m³/min 100
Cooling dB(A) 50
Sound pressure
level *3 Heating dB(A) 52
Night quiet mode dB(A) 46
Mass kg 108
Liquid mm φ9.5 (Flare)
Piping
Gas mm φ15.9 (Flare)
connections
Drain mm φ26 (Hole)
Safety devices High pressure switch. Fuse.
Capacity step % Compressor revolution speed control (Inverter system)
Refrigerant control Electronic expansion valve
Max. length m 75 (Equivalent length 90m)
Ref. piping
Max. height difference m 30
Model R410A
Refrigerant
Charge (factory charge) kg 4.3 (Charged for 30m)
Model Refer to the nameplate of compressor.
Ref. oil
Charge L 1.2
Specification C: 4D080667B
Drawing No. Sound (Indoor) C: 4D073854
Sound (Outdoor) C: 4D061482B, C: 4D061485B

Notes: *1. The above data are based on the following conditions. Conversion formulae
Cooling Heating Piping length kcal/h=kW×860
Indoor: 27°CDB, 19°CWB Indoor: 20°CDB, 15°CWB 7.5m Btu/h=kW×3412
Outdoor: 35°CDB, 24°CWB Outdoor: 7°CDB, 6°CWB (Horizontal) cfm=m³/min×35.3

*2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
*3. Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation
these values are somewhat higher owing to ambient conditions.

30 SkyAir RZQS, RZQ series


EDMT281426 Dimensions and service space

5. Dimensions and service space


1
5.1 Indoor unit
5.1.1 FCQ

FCQ71KAVEA

3D058460G
Unit (mm)

SkyAir RZQS, RZQ series 31


Dimensions and service space EDMT281426

FCQ100KAVEA / FCQ125KAVEA / FCQ140KAVEA

3D058469E
Unit (mm)

32 SkyAir RZQS, RZQ series


EDMT281426 Dimensions and service space

5.1.2 FHQ
1
FHQ71BWV1A

3D027538K
Unit (mm)

SkyAir RZQS, RZQ series 33


Dimensions and service space EDMT281426

FHQ100BWV1A

3D044893C
Unit (mm)

34 SkyAir RZQS, RZQ series


EDMT281426 Dimensions and service space

FHQ125BWV1A 1

3D044894E
Unit (mm)

SkyAir RZQS, RZQ series 35


Dimensions and service space EDMT281426

FHQ140CAVEA

3D069633D
Unit (mm)

36 SkyAir RZQS, RZQ series


EDMT281426 Dimensions and service space

5.1.3 FAQ
1
FAQ71CVEA

3D073840A
Unit (mm)

SkyAir RZQS, RZQ series 37


Dimensions and service space EDMT281426

FAQ100CVEA

3D073841A
Unit (mm)

38 SkyAir RZQS, RZQ series


EDMT281426 Dimensions and service space

5.1.4 FBQ-DB
1
FBQ71DBVEA

3D068609E
Unit (mm)

SkyAir RZQS, RZQ series 39


Dimensions and service space EDMT281426

FBQ100DBVEA / FBQ125DBVEA / FBQ140DBVEA

3D068610D
Unit (mm)

40 SkyAir RZQS, RZQ series


EDMT281426 Dimensions and service space

5.1.5 FVQ
1
FVQ50CVE / FVQ60CVE / FVQ71CVEB

3D073846A
Unit (mm)

SkyAir RZQS, RZQ series 41


Dimensions and service space EDMT281426

FVQ100CVEB / FVQ125CVEB / FVQ140CVEB


Unit (mm)

3D073847

42 SkyAir RZQS, RZQ series


EDMT281426 Dimensions and service space

5.2 Wired remote controller


1
BRC1C61

Unit (mm)

3D028952A

BRC1D61
Unit (mm)

3D048117

SkyAir RZQS, RZQ series 43


Dimensions and service space EDMT281426

BRC1E62

Unit (mm)

3D081567

44 SkyAir RZQS, RZQ series


EDMT281426 Dimensions and service space

5.3 Wireless remote controller


1
BRC7F634F (for FCQ)
Unit (mm)

3D052918E

BRC7EA63W (for FHQ-BW)


Unit (mm)
• REMOTE CONTROLLER DIMENSIONS
TRANSMITTING PART
• RECEIVER INSTALLATION PROCEDURE
RECEIVER
157

62 17.5

• REMOTE CONTROLLER HOLDER


INSTALLATION PROCEDURE
< INSTALLATION TO WALL SURFACE > • RECEIVER DETAIL
LIQUID CRYSTAL
REMOTE CONTROLLER
(WIRELESS)

REMOTE CONTROLLER
HOLDER

3D028963B

SkyAir RZQS, RZQ series 45


Dimensions and service space EDMT281426

BRC7GA53 (for FHQ-CA)

Unit (mm)

3D079916

BRC7EB518 (for FAQ-C)


Unit (mm)

C: 3D074471

46 SkyAir RZQS, RZQ series


EDMT281426 Dimensions and service space

BRC4C65 (for FBQ-DB) 1


Unit (mm)

3D007898B

SkyAir RZQS, RZQ series 47


Dimensions and service space EDMT281426

5.4 Outdoor unit

RZQS50AV1 / RZQS60AV1 / RZQ71LV1

3D064945G
Unit (mm)

48 SkyAir RZQS, RZQ series


EDMT281426 Dimensions and service space

RZQ100LV1 1

3D089674B
Unit (mm)

SkyAir RZQS, RZQ series 49


Dimensions and service space EDMT281426

RZQ125LV1

3D058488F
Unit (mm)

50 SkyAir RZQS, RZQ series


EDMT281426 Dimensions and service space

RZQ140LV1 1

3D077411C
Unit (mm)

SkyAir RZQS, RZQ series 51


Dimensions and service space EDMT281426

RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A

3D060941B
Unit (mm)

52 SkyAir RZQS, RZQ series


EDMT281426 Dimensions and service space

5.5 Installation Service Space


1
RZQS50AV1 / RZQS60AV1 / RZQ71LV1

3D073764B

SkyAir RZQS, RZQ series 53


Dimensions and service space EDMT281426

3D073764B

54 SkyAir RZQS, RZQ series


EDMT281426 Dimensions and service space

RZQ100LV1 1

3D089675A

SkyAir RZQS, RZQ series 55


Dimensions and service space EDMT281426

3D089675A

56 SkyAir RZQS, RZQ series


EDMT281426 Dimensions and service space

RZQ125LV1 / RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A 1

3D073763B

SkyAir RZQS, RZQ series 57


Dimensions and service space EDMT281426

3D073763B

58 SkyAir RZQS, RZQ series


EDMT281426 Dimensions and service space

RZQ140LV1 1

3D077417B

SkyAir RZQS, RZQ series 59


Dimensions and service space EDMT281426

3D077417B

60 SkyAir RZQS, RZQ series


EDMT281426 Piping diagrams

6. Piping diagrams
1
6.1 Indoor unit + outdoor unit

FVQ50CVE + RZQS50AV1
FVQ60CVE + RZQS60AV1

3D089740

SkyAir RZQS, RZQ series 61


Piping diagrams EDMT281426

FCQ71KAVEA / FHQ71BWV1A / FAQ71CVEA / FBQ71DBVEA / FVQ71CVEB + RZQ71LV1

3D064949F

62 SkyAir RZQS, RZQ series


EDMT281426 Piping diagrams

FCQ100KAVEA / FHQ100BWV1A / FAQ100CVEA / FBQ100DBVEA / FVQ100CVEB + RZQ100LV1 1

3D089678

SkyAir RZQS, RZQ series 63


Piping diagrams EDMT281426

FCQ125KAVEA / FHQ125BWV1A / FBQ125DBVEA / FVQ125CVEB + RZQ125LV1


FCQ140KAVEA / FHQ140CAVEA / FBQ140DBVEA / FVQ140CVEB + RZQ140LV1

3D058486H

64 SkyAir RZQS, RZQ series


EDMT281426 Piping diagrams

FCQ100KAVEA / FHQ100BWV1A / FAQ100CVEA / FBQ100DBVEA / FVQ100CVEB + RZQ100HAY4A


FCQ125KAVEA / FHQ125BWV1A / FBQ125DBVEA / FVQ125CVEB + RZQ125HAY4A
1
FCQ140KAVEA / FHQ140CAVEA / FBQ140DBVEA / FVQ140CVEB + RZQ140HAY4A

3D060712B

SkyAir RZQS, RZQ series 65


Wiring diagrams EDMT281426

7. Wiring diagrams
7.1 Indoor unit

FCQ71KAVEA / FCQ100KAVEA / FCQ125KAVEA / FCQ140KAVEA

3D089141A

66 SkyAir RZQS, RZQ series


EDMT281426 Wiring diagrams

FHQ71BWV1A / FHQ100BWV1A / FHQ125BWV1A 1

3D074574B

SkyAir RZQS, RZQ series 67


Wiring diagrams EDMT281426

FHQ140CAVEA

3D079559E

68 SkyAir RZQS, RZQ series


EDMT281426 Wiring diagrams

FAQ71CVEA / FAQ100CVEA 1

3D090000B

SkyAir RZQS, RZQ series 69


Wiring diagrams EDMT281426

FBQ71DBVEA / FBQ100DBVEA / FBQ125DBVEA / FBQ140DBVEA

3D089661

70 SkyAir RZQS, RZQ series


EDMT281426 Wiring diagrams

FVQ50CVE / FVQ60CVE 1

3D086791

SkyAir RZQS, RZQ series 71


Wiring diagrams EDMT281426

FVQ71CVEB / FVQ100CVEB / FVQ125CVEB / FVQ140CVEB

3D073234B

72 SkyAir RZQS, RZQ series


EDMT281426 Wiring diagrams

7.2 Outdoor unit


1
RZQS50AV1 / RZQS60AV1

3D089620

SkyAir RZQS, RZQ series 73


Wiring diagrams EDMT281426

RZQ71LV1

3D064851K

74 SkyAir RZQS, RZQ series


EDMT281426 Wiring diagrams

RZQ100LV1 1

3D089520

SkyAir RZQS, RZQ series 75


Wiring diagrams EDMT281426

RZQ125LV1

3D056474K

76 SkyAir RZQS, RZQ series


EDMT281426 Wiring diagrams

RZQ140LV1 1

3D077448D

SkyAir RZQS, RZQ series 77


Wiring diagrams EDMT281426

RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A

C: 3D047451H

78 SkyAir RZQS, RZQ series


EDMT281426 Field wiring

8. Field wiring
1
FCQ71KAVEA + RZQ71LV1
FCQ100KAVEA + RZQ100LV1
FCQ125KAVEA + RZQ125LV1
FCQ140KAVEA + RZQ140LV1
FCQ100KAVEA + RZQ100HAY4A
FCQ125KAVEA + RZQ125HAY4A
FCQ140KAVEA + RZQ140HAY4A

4D010992J

SkyAir RZQS, RZQ series 79


Field wiring EDMT281426

FHQ71BWV1A + RZQ71LV1
FHQ100BWV1A + RZQ100LV1
FHQ125BWV1A + RZQ125LV1
FHQ140CAVEA + RZQ140LV1
FHQ100BWV1A + RZQ100HAY4A
FHQ125BWV1A + RZQ125HAY4A
FHQ140CAVEA + RZQ140HAY4A

4D044483L

80 SkyAir RZQS, RZQ series


EDMT281426 Field wiring

FAQ71CVEA + RZQ71LV1
FAQ100CVEA + RZQ100LV1
1
FAQ100CVEA + RZQ100HAY4A

4D044475E

SkyAir RZQS, RZQ series 81


Field wiring EDMT281426

FBQ71DBVEA + RZQ71LV1
FBQ100DBVEA + RZQ100LV1
FBQ125DBVEA + RZQ125LV1
FBQ140DBVEA + RZQ140LV1
FBQ100DBVEA + RZQ100HAY4A
FBQ125DBVEA + RZQ125HAY4A
FBQ140DBVEA + RZQ140HAY4A

4D067292H

82 SkyAir RZQS, RZQ series


EDMT281426 Field wiring

FVQ50CVE + RZQS50AV1
FVQ60CVE + RZQS60AV1
1
FVQ71CVEB + RZQ71LV1
FVQ100CVEB + RZQ100LV1
FVQ125CVEB + RZQ125LV1
FVQ140CVEB + RZQ140LV1
FVQ100CVEB + RZQ100HAY4A
FVQ125CVEB + RZQ125HAY4A
FVQ140CVEB + RZQ140HAY4A

3D013853F

SkyAir RZQS, RZQ series 83


Electric characteristics EDMT281426

9. Electric characteristics
9.1 RZQS-A, RZQ-L

FCQ71KAVEA + RZQ71LV1
FCQ100KAVEA + RZQ100LV1
FCQ125KAVEA + RZQ125LV1
FCQ140KAVEA + RZQ140LV1

4D089671A

84 SkyAir RZQS, RZQ series


EDMT281426 Electric characteristics

FHQ71BWV1A + RZQ71LV1
FHQ100BWV1A + RZQ100LV1
1
FHQ125BWV1A + RZQ125LV1
FHQ140CAVEA + RZQ140LV1

4D089673

SkyAir RZQS, RZQ series 85


Electric characteristics EDMT281426

FAQ71CVEA + RZQ71LV1
FAQ100CVEA + RZQ100LV1

4D089670

86 SkyAir RZQS, RZQ series


EDMT281426 Electric characteristics

FBQ71DBVEA + RZQ71LV1
FBQ100DBVEA + RZQ100LV1
1
FBQ125DBVEA + RZQ125LV1
FBQ140DBVEA + RZQ140LV1

3D089669

SkyAir RZQS, RZQ series 87


Electric characteristics EDMT281426

FVQ50CVE + RZQS50AV1
FVQ60CVE + RZQS60AV1
FVQ71CVEB + RZQ71LV1
FVQ100CVEB + RZQ100LV1
FVQ125CVEB + RZQ125LV1
FVQ140CVEB + RZQ140LV1

4D089672A

88 SkyAir RZQS, RZQ series


EDMT281426 Electric characteristics

9.2 RZQ-HA
1
FCQ100KAVEA / FHQ100BWV1A / FBQ100DBVEA + RZQ100HAY4A
FCQ125KAVEA / FHQ125BWV1A / FBQ125DBVEA + RZQ125HAY4A
FCQ140KAVEA / FBQ140DBVEA + RZQ140HAY4A

3D093052

SkyAir RZQS, RZQ series 89


Electric characteristics EDMT281426

FHQ140CAVEA + RZQ140HAY4A

C: 4D061563E

90 SkyAir RZQS, RZQ series


EDMT281426 Electric characteristics

FAQ100CVEA + RZQ100HAY4A 1

C: 3D084143

SkyAir RZQS, RZQ series 91


Electric characteristics EDMT281426

FVQ100CVEB + RZQ100HAY4A
FVQ125CVEB + RZQ125HAY4A
FVQ140CVEB + RZQ140HAY4A

C: 3D080988B

92 SkyAir RZQS, RZQ series


EDMT281426 Capacity tables

10. Capacity tables


1
10.1 Capacity tables

FVQ50CVE + RZQS50AV1

3D089737B

SkyAir RZQS, RZQ series 93


Capacity tables EDMT281426

FVQ60CVE + RZQS60AV1

3D089738A

94 SkyAir RZQS, RZQ series


EDMT281426 Capacity tables

FCQ71KAVEA / FHQ71BWV1A / FAQ71CVEA / FBQ71DBVEA / FVQ71CVEB + RZQ71LV1 1

3D089698A

SkyAir RZQS, RZQ series 95


Capacity tables EDMT281426

FCQ100KAVEA / FHQ100BWV1A / FAQ100CVEA / FBQ100DBVEA / FVQ100CVEB + RZQ100LV1

3D089699C

96 SkyAir RZQS, RZQ series


EDMT281426 Capacity tables

FCQ125KAVEA / FBQ125DBVEA / FVQ125CVEB + RZQ125LV1 1

3D089700B

SkyAir RZQS, RZQ series 97


Capacity tables EDMT281426

FHQ125BWV1A + RZQ125LV1

3D089701

98 SkyAir RZQS, RZQ series


EDMT281426 Capacity tables

FCQ140KAVEA / FHQ140CAVEA / FBQ140DBVEA + RZQ140LV1 1

3D089702A

SkyAir RZQS, RZQ series 99


Capacity tables EDMT281426

FVQ140CVEB + RZQ140LV1

3D089703B

100 SkyAir RZQS, RZQ series


EDMT281426 Capacity tables

FCQ100KAVEA / FHQ100BWV1A / FBQ100DBVEA + RZQ100HAY4A 1

3D093044

SkyAir RZQS, RZQ series 101


Capacity tables EDMT281426

FAQ100CVEA + RZQ100HAY4A

3D073993C

102 SkyAir RZQS, RZQ series


EDMT281426 Capacity tables

FVQ100CVEB + RZQ100HAY4A 1

3D081044A

SkyAir RZQS, RZQ series 103


Capacity tables EDMT281426

FCQ125KAVEA / FHQ125BWV1A / FBQ125DBVEA + RZQ125HAY4A

3D093045

104 SkyAir RZQS, RZQ series


EDMT281426 Capacity tables

FVQ125CVEB + RZQ125HAY4A 1

3D081046A

SkyAir RZQS, RZQ series 105


Capacity tables EDMT281426

FCQ140KAVEA / FBQ140DBVEA + RZQ140HAY4A

3D093046

106 SkyAir RZQS, RZQ series


EDMT281426 Capacity tables

FHQ140CAVEA + RZQ140HAY4A 1

3D073995B

SkyAir RZQS, RZQ series 107


Capacity tables EDMT281426

FVQ140CVEB + RZQ140HAY4A

3D081161A

108 SkyAir RZQS, RZQ series


EDMT281426 Capacity tables

10.2 Capacity correction factor by the length of refrigerant piping


1
RZQS50AV1 / RZQS60AV1
RZQ71LV1 / RZQ100LV1 / RZQ125LV1 / RZQ140LV1

3D089679

RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A

The capacity of the unit has to be corrected in accordance with the length of refrigerant piping.
(The distance between the indoor unit and the outdoor unit)

RZQ50/60: Heating (98.8%)


RZQ50/60: Cooling (97.2%)
(%) 7.5 RZQ71: Heating (97.9%)
100
RZQ100-140: Heating (96.7%)

95 RZQ71: Cooling (95%)


Capacity correction factor

90

85
RZQ100: Cooling (84.2%)

80
RZQ125: Cooling (75.2%)
75

70 RZQ140: Cooling (70.0%)


05 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 (m)
Length of refrigerant piping (Total length)

Note: 1. ⎯ line: Correction factor for Cooling Capacity, line: Correction factor for Heating Capacity
2. The correction factor remains the same whether the outdoor unit is to be installed above or below
the indoor unit.
3. You cannot extend the refrigerant piping exceeding the limit shown in the above table.

SkyAir RZQS, RZQ series 109


Operation limits EDMT281426

11. Operation limits


RZQS50AV1 / RZQS60AV1
RZQ71LV1 / RZQ100LV1 / RZQ125LV1 / RZQ140LV1
RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A

3D046720M

110 SkyAir RZQS, RZQ series


EDMT281426 Fan performance

12. Fan performance


1
12.1 FBQ-DB

FBQ71DBVEA

3D094600

SkyAir RZQS, RZQ series 111


Fan performance EDMT281426

FBQ100DBVEA

3D094602

112 SkyAir RZQS, RZQ series


EDMT281426 Fan performance

FBQ125DBVEA / FBQ140DBVEA 1

3D094605

SkyAir RZQS, RZQ series 113


Airflow auto adjustment characteristics EDMT281426

13. Airflow auto adjustment characteristics


13.1 FBQ-DB

FBQ71DBVEA

3D094601

114 SkyAir RZQS, RZQ series


EDMT281426 Airflow auto adjustment characteristics

FBQ100DBVEA 1

3D094603

SkyAir RZQS, RZQ series 115


Airflow auto adjustment characteristics EDMT281426

FBQ125DBVEA / FBQ140DBVEA

3D094604

116 SkyAir RZQS, RZQ series


EDMT281426 Air velocity and temperature distributions

14. Air velocity and temperature distributions


1
14.1 FHQ

FHQ71BWV1A (Cooling)

4D028551E

FHQ71BWV1A (Heating)

4D028555D

SkyAir RZQS, RZQ series 117


Air velocity and temperature distributions EDMT281426

FHQ100BWV1A (Cooling)

4D028552C

FHQ100BWV1A (Heating)

4D028556C

118 SkyAir RZQS, RZQ series


EDMT281426 Air velocity and temperature distributions

FHQ125BWV1A (Cooling) 1

4D028553D

FHQ125BWV1A (Heating)

4D028557C

SkyAir RZQS, RZQ series 119


Sound level EDMT281426

15. Sound level


15.1 Indoor unit
15.1.1 FCQ

FCQ71KAVEA

4D094558

120 SkyAir RZQS, RZQ series


EDMT281426 Sound level

FCQ100KAVEA 1

4D094559

SkyAir RZQS, RZQ series 121


Sound level EDMT281426

FCQ125KAVEA

4D094560

122 SkyAir RZQS, RZQ series


EDMT281426 Sound level

FCQ140KAVEA 1

4D094561

SkyAir RZQS, RZQ series 123


Sound level EDMT281426

15.1.2 FHQ

FHQ71BWV1A

4D090911

124 SkyAir RZQS, RZQ series


EDMT281426 Sound level

FHQ100BWV1A 1

4D090912

SkyAir RZQS, RZQ series 125


Sound level EDMT281426

FHQ125BWV1A

4D090913

126 SkyAir RZQS, RZQ series


EDMT281426 Sound level

FHQ140CAVEA 1

4D069651D

SkyAir RZQS, RZQ series 127


Sound level EDMT281426

15.1.3 FAQ

FAQ71CVEA

4D100001

128 SkyAir RZQS, RZQ series


EDMT281426 Sound level

FAQ100CVEA 1

4D100002A

SkyAir RZQS, RZQ series 129


Sound level EDMT281426

15.1.4 FBQ-DB

FBQ71DBVEA

4D094596

130 SkyAir RZQS, RZQ series


EDMT281426 Sound level

FBQ100DBVEA 1

4D094597

SkyAir RZQS, RZQ series 131


Sound level EDMT281426

FBQ125DBVEA / FBQ140DBVEA

4D094598

132 SkyAir RZQS, RZQ series


EDMT281426 Sound level

15.1.5 FVQ
1
FVQ50CVE / FVQ60CVE / FVQ71CVEB

4D073851A

SkyAir RZQS, RZQ series 133


Sound level EDMT281426

FVQ100CVEB

4D073852

134 SkyAir RZQS, RZQ series


EDMT281426 Sound level

FVQ125CVEB 1

4D073853A

SkyAir RZQS, RZQ series 135


Sound level EDMT281426

FVQ140CVEB

4D073854

136 SkyAir RZQS, RZQ series


EDMT281426 Sound level

15.2 Outdoor unit


15.2.1 RZQS 1
RZQS50AV1 / RZQS60AV1 (Cooling)

4D090424

SkyAir RZQS, RZQ series 137


Sound level EDMT281426

RZQS50AV1 / RZQS60AV1 (Heating)

4D090423

138 SkyAir RZQS, RZQ series


EDMT281426 Sound level

15.2.2 RZQ-L
1
RZQ71LV1 (Cooling)

4D075745A

SkyAir RZQS, RZQ series 139


Sound level EDMT281426

RZQ71LV1 (Heating)

4D075748A

140 SkyAir RZQS, RZQ series


EDMT281426 Sound level

RZQ100LV1 (Cooling) 1

4D089676

SkyAir RZQS, RZQ series 141


Sound level EDMT281426

RZQ100LV1 (Heating)

4D089677A

142 SkyAir RZQS, RZQ series


EDMT281426 Sound level

RZQ125LV1 (Cooling) 1

4D075741A

SkyAir RZQS, RZQ series 143


Sound level EDMT281426

RZQ125LV1 (Heating)

4D075747A

144 SkyAir RZQS, RZQ series


EDMT281426 Sound level

RZQ140LV1 (Cooling) 1

4D089680A

SkyAir RZQS, RZQ series 145


Sound level EDMT281426

RZQ140LV1 (Heating)

4D089681A

146 SkyAir RZQS, RZQ series


EDMT281426 Sound level

15.2.3 RZQ-HA
1
RZQ100HAY4A (Cooling)

4D061464A

SkyAir RZQS, RZQ series 147


Sound level EDMT281426

RZQ100HAY4A (Heating)

4D061483A

148 SkyAir RZQS, RZQ series


EDMT281426 Sound level

RZQ125HAY4A (Cooling) 1

4D061473A

SkyAir RZQS, RZQ series 149


Sound level EDMT281426

RZQ125HAY4A (Heating)

4D061484A

150 SkyAir RZQS, RZQ series


EDMT281426 Sound level

RZQ140HAY4A (Cooling) 1

4D061482B

SkyAir RZQS, RZQ series 151


Sound level EDMT281426

RZQ140HAY4A (Heating)

4D061485B

152 SkyAir RZQS, RZQ series


EDMT281426 Accessories

16. Accessories
1
16.1 Indoor unit
16.1.1 FCQ

Optional
accessories Kit name
Name of option Remark FCQ100KAVEA
FCQ71KAVEA FCQ125KAVEA
FCQ140KAVEA
Decoration panel BYCP125K-W1
Sealing material of air discharge outlet KDBH55K160F
Panel spacer KDBP55H160FA
Without T-duct
KDDP55B160
Chamber type joint
Fresh air intake kit
With T-duct joint KDDP55B160K
Direct installation type KDDP55X160
Chamber connection kit *1 KKSJ55KA160
Insulation kit for high humidity KDTP55K80 KDTP55K160
High-efficiency filter unit Colorimetric method 65% KAFP556B80 KAFP556B160
(including filter chamber) Colorimetric method 90% KAFP557B80 KAFP557B160
Replacement high-efficiency Colorimetric method 65% KAFP552B80 KAFP552B160
filter Colorimetric method 90% KAFP553B80 KAFP553B160
Filter chamber KDDFP55B160
Replacement long-life filter KAFP551K160
Ultra long-life filter unit (including filter chamber) KAFP55B160
Replacement ultra long-life filter KAFP55H160H
Branch duct chamber KDJP55B80 KDJP55B160
Wireless type Heat pump BRC7F634F
Remote controller
Wired type *2 BRC1C61
Wired remote controller with weekly schedule timer *2 BRC1D61
Navigation remote controller Wired type *2 BRC1E62
Central remote controller *3 DCS302CA61
Unified ON/OFF controller *3 DCS301BA61
Schedule timer *3 DST301BA61
intelligent Touch Controller *3 DCS601C51
Adaptor for wiring *4 KRP1C63
Wiring adaptor for electrical appendices (2) *4 KRP4AA53
Installation box for printed circuit board adaptor KRP1H98
Remote sensor KRCS01-4B
C: 3D058465K

Notes: *1. Required for installing high-efficiency filter unit or ultra long-life filter unit.
*2. Wiring for wired remote controller to be procured locally.
*3. The indoor unit is equipped standardly with the function of the interface adaptor for SkyAir series. An option is
unnecessary.
*4. Installation box for printed circuit board adaptor (KRP1H98) is necessary.
*5. For details, refer to the Option Handbook.

SkyAir RZQS, RZQ series 153


Accessories EDMT281426

16.1.2 FHQ

Optional
accessories Kit name
Name of option Remark
FHQ71BWV1A FHQ100BWV1A FHQ125BWV1A
Replacement long-life filter KAF501DA80 KAF501DA112 KAF501DA160
Drain pump kit KDU50N125VE
L-type piping kit (for upward direction) KHFP5MA160
Wireless Heat pump BRC7EA63W
Remote controller type
Wired type *1 BRC1C61
Wired remote controller with weekly schedule timer *1 BRC1D61
Navigation remote controller Wired type *1 BRC1E62
Central remote controller *2 DCS302CA61
Unified ON/OFF controller *2 DCS301BA61
Schedule timer *2 DST301BA61
intelligent Touch Controller *2 DCS601C51
Adaptor for wiring KRP1BA54
Wiring adaptor for electrical appendices *3 KRP4AA52
Interface adaptor for SkyAir series DTA112BA51
Installation box for printed circuit board adaptor KRP1CA93
Remote sensor KRCS01-1B
Electrical box with earth terminal (3 blocks) KJB311AA
Electrical box with earth terminal (2 blocks) KJB212AA
C: 4D090797A
Notes: *1. Wiring for wired remote controller to be procured locally.
*2. This optional accessory requires DTA112BA51.
*3. Installation box for printed circuit board adaptor (KRP1CA93) is necessary.
*4. For details, refer to the Option Handbook.

Optional
accessories Kit name
Name of option Remark
FHQ140CAVEA
Replacement long-life filter KAFP501A160
Fresh air intake kit KDDQ50A140
Drain pump kit KDU50P140VE
L-type piping kit (for upward direction) KHFP5N160
Wireless
Heat pump BRC7GA53
Remote controller type
Wired type *1 BRC1C61
Wired remote controller with weekly schedule timer *1 BRC1D61
Navigation remote controller Wired type *1 BRC1E62
Central remote controller *2 DCS302CA61
Unified ON/OFF controller *2 DCS301BA61
Schedule timer *2 DST301BA61
intelligent Touch Controller *2 DCS601C51
Adaptor for wiring KRP1BA54
Wiring adaptor for electrical appendices *3 KRP4AA52
Installation box for printed circuit board adaptor KRP1D93A
Remote sensor KRCS01-4B
Electrical box with earth terminal (3 blocks) KJB311AA
Electrical box with earth terminal (2 blocks) KJB212AA
C: 3D080173C
Notes: *1. Wiring for wired remote controller to be procured locally.
*2. The indoor unit is equipped standardly with the function of the interface adaptor for SkyAir series. An option is
unnecessary.
*3. Installation box for printed circuit board adaptor (KRP1D93A) is necessary.
*4. For details, refer to the Option Handbook.

154 SkyAir RZQS, RZQ series


EDMT281426 Accessories

16.1.3 FAQ
1
Optional
accessories Kit name
Name of option Remark
FAQ71CVEA FAQ100CVEA
Drain-up kit K-KDU572EVE
Wireless Heat
type pump BRC7EB518
Remote controller
Wired type *1 BRC1C61
Wired remote controller with weekly schedule timer *1 BRC1D61
Navigation remote controller Wired type *1 BRC1E62
Remote sensor KRCS01-4B
Central remote controller *2 DCS302CA61
Unified ON/OFF controller *2 DCS301BA61
Schedule timer *2 DST301BA61
intelligent Touch Controller *2 DCS601C51
Wiring adaptor for electrical appendices (2) *3 KRP4AA51
Installation box for printed circuit board adaptor KRP4AA93
Electrical box with earth terminal (3 blocks) KJB311AA
Electrical box with earth terminal (2 blocks) KJB212AA
Noise filter (for electromagnetic interface use only) KEK26-1A
C: 3D044482G
Note: *1. Wiring for wired remote controller to be procured locally.
*2. The indoor unit is equipped standardly with the function of the interface adaptor for SkyAir series. An option is
unnecessary.
*3. Installation box for printed circuit board adaptor (KRP4AA93) is necessary.
*4. For details, refer to the Option Handbook.

SkyAir RZQS, RZQ series 155


Accessories EDMT281426

16.1.4 FBQ-DB

Optional
accessories Kit name
Name of option Remark FBQ100DBVEA
FBQ71DBVEA FBQ125DBVEA
FBQ140DBVEA
65% KAF372AA80 KAF372AA160
High efficiency filter *1
90% KAF373AA80 KAF373AA160
Filter chamber KDDF37AA80 KDDF37AA160
Long-life filter KAF371AA80 KAF371AA160
Long-life filter chamber kit KAF375AA80 KAF375AA160
KTB25KA80W KTB25KA160W
Service access panel KTBJ25K80F KTBJ25K160F
KTBJ25K80T KTBJ25K160T
Air discharge adaptor KDAJ25K71A KDAJ25K140A
Wireless Heat
BRC4C65
Remote controller type pump
Wired type *2 BRC1C61
Wired remote controller with weekly schedule timer *2 BRC1D61
Navigation remote controller Wired type *2 BRC1E62
Adaptor for wiring KRP1C64*
Wiring adaptor for electrical appendices (2) KRP4AA51*
Remote sensor KRCS01-4B
Mounting plate for printed circuit board adaptor *4 KRP4A96 *5 *6
Central remote controller *3 DCS302CA61
Unified ON/OFF controller *3 DCS301BA61
Schedule timer *3 DST301BA61
intelligent Touch Controller *3 DCS601C51
C: 3D066072J
C: 3D066074K
Notes: *1. If installing a high efficiency filter on the unit, an assembly chamber for either bottom or rear suction is
required.
*2. Wiring for wired remote controller to be procured locally.
*3. The indoor unit is equipped standardly with the function of the interface adaptor for SkyAir series. An option is
unnecessary.
*4. Mounting plate for printed circuit board adaptor is necessary for each adaptor marked*.
*5. Up to 2 adaptors can be fixed for each mounting plate.
*6. Only one mounting plate can be installed for each indoor unit.
*7. For details, refer to the Option Handbook.

16.1.5 FVQ

Optional
accessories Kit name
Name of option Remark FVQ50CVE FVQ100CVEB
FVQ60CVE FVQ125CVEB
FVQ71CVEB FVQ140CVEB
Replacement long-life filter KAFJ95L160
Remote controller Wired type *1 BRC1C61
Navigation remote controller Wired type *1 BRC1E62
Central remote controller *2 DCS302CA61
Unified ON/OFF controller *2 DCS301BA61
Schedule timer *2 DST301BA61
intelligent Touch Controller *2 DCS601C51
Adaptor for wiring *3 KRP1BA57
Wiring adaptor for electrical appendices KRP4AA52
Installation box for printed circuit board adaptor KRP4AA95
C: 4D074483E
Notes: *1. Wiring for wired remote controller to be procured locally.
*2. The indoor unit is equipped standardly with the funciton of the interface adaptor for SkyAir series. An option is
unnecessary.
*3. Installation box for printed circuit board adaptor (KRP4AA95) is necessary.
*4. For details, refer to the Option Handbook.

156 SkyAir RZQS, RZQ series


EDMT281426 Accessories

16.2 Outdoor unit


16.2.1 RZQS 1
Kit name
Name of option RZQS50AV1
RZQS60AV1
Central drain plug KKPJ5F180
Wire fixture for preventing K-KYZP15C
overturning
Fixture for preventing
KPT-60B160
overturning
Demand adaptor KRP58M51
C: 4D046721M
Note: *1. For details, refer to the Option Handbook.

16.2.2 RZQ

Optional
accessories Kit name
Name of option RZQ100HAY4A
RZQ71LV1 RZQ100LV1 RZQ125HAY4A
RZQ125LV1 RZQ140LV1
RZQ140HAY4A
Central drain plug KKPJ5F180 KKPJ5G280 KKPJ5F180
Wire fixture for preventing overturning K-KYZP15C
Fixture for preventing overturning KPT-60B160 KKTP5B112 KPT-60B160
Demand adaptor KRP58M51
C: 4D046721M
C: 4D077521D
Note: *1. For details, refer to the Option Handbook.

SkyAir RZQS, RZQ series 157


Accessories EDMT281426

158 SkyAir RZQS, RZQ series


EDMT281426

Part 2

Installation of 2
indoor / outdoor unit
1. Centre of gravity..................................................................................160
2. Installation of indoor unit .....................................................................163
2.1 FCQ71KAVEA / FCQ100KAVEA / FCQ125KAVEA /
FCQ140KAVEA....................................................................................163
2.2 FHQ71BWV1A / FHQ100BWV1A / FHQ125BWV1A...........................190
2.3 FHQ140CAVEA....................................................................................215
2.4 FAQ71CVEA / FAQ100CVEA ..............................................................235
2.5 FBQ71DBVEA / FBQ100DBVEA / FBQ125DBVEA /
FBQ140DBVEA....................................................................................265
2.6 FVQ50CVE / FVQ60CVE.....................................................................292
2.7 FVQ71CVEB / FVQ100CVEB / FVQ125CVEB / FVQ140CVEB..........322
3. Installation of outdoor unit ...................................................................353
3.1 RZQS50AV1 / RZQS60AV1 / RZQ71LV1 / RZQ100LV1 /
RZQ125LV1 .........................................................................................353
3.2 RZQ140LV1 .........................................................................................369
3.3 RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A ...........................385
3.4 Equivalent piping length of joints (reference) .......................................401

Installation of indoor / outdoor unit 159


Centre of gravity EDMT281426

1. Centre of gravity
RZQS50AV1 / RZQS60AV1 / RZQ71LV1
Unit (mm)

4D064948F

RZQ100LV1
Unit (mm)

4D089656B

160 Installation of indoor / outdoor unit


EDMT281426 Centre of gravity

RZQ125LV1
Unit (mm)

4D058487H

RZQ140LV1

4D077529C

Installation of indoor / outdoor unit 161


Centre of gravity EDMT281426

RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A


Unit (mm)

4D061670B

162 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

2. Installation of indoor unit


2.1 FCQ71KAVEA / FCQ100KAVEA / FCQ125KAVEA / FCQ140KAVEA
2.1.1 Names and function of parts

k j
RZQ125 · 140L
RZQ100 · 125 · 140
2
RZQS100 · 125 · 140
i

a g

d f
l e
m RZQ71 · 100L
b
RZQ50 · 60 · 71
RZQS50 · 60 · 71
c
h d
e

a Indoor unit
b Outdoor unit
Remote controller
c Depending on the system configuration, the remote
controller is not provided.
d Inlet air
e Discharge air
f Air outlet
g Air flow flap (at air outlet)
h Refrigerant piping, connection electric wire
i Drain pipe
Model name (model name plate)
j
(Inside of suction grille)
Drain pumping out device (built-in)
k
Condensate removed from the room during cooling.
l Air filter (suction grille)
m Suction grille
Ground wire
n The line passes electricity from the inside unit to the
ground to prevent accidental electrical shock.
3P338599-9D

Installation of indoor / outdoor unit 163


Installation of indoor unit EDMT281426

2.1.2 Installation

3P177351-4U

164 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P177351-4U

Installation of indoor / outdoor unit 165


Installation of indoor unit EDMT281426

3P177351-4U

166 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P177351-4U

Installation of indoor / outdoor unit 167


Installation of indoor unit EDMT281426

3P177351-4U

168 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P177351-4U

Installation of indoor / outdoor unit 169


Installation of indoor unit EDMT281426

3P177351-4U

170 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P177351-4U

Installation of indoor / outdoor unit 171


Installation of indoor unit EDMT281426

3P177351-4U

172 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P177351-4U

Installation of indoor / outdoor unit 173


Installation of indoor unit EDMT281426

3P177351-4U

174 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P177351-4U

Installation of indoor / outdoor unit 175


Installation of indoor unit EDMT281426

3P177351-4U

176 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P177351-4U

Installation of indoor / outdoor unit 177


Installation of indoor unit EDMT281426

3P177351-4U

178 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P177351-4U

Installation of indoor / outdoor unit 179


Installation of indoor unit EDMT281426

3P177351-4U

180 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P177351-4U

Installation of indoor / outdoor unit 181


Installation of indoor unit EDMT281426

3P177351-4U

182 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P177351-4U

Installation of indoor / outdoor unit 183


Installation of indoor unit EDMT281426

3P177351-4U

184 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P177351-4U

Installation of indoor / outdoor unit 185


Installation of indoor unit EDMT281426

3P177351-4U

186 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P177351-4U

Installation of indoor / outdoor unit 187


Installation of indoor unit EDMT281426

3P177351-4U

188 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P177351-4U

Installation of indoor / outdoor unit 189


Installation of indoor unit EDMT281426

2.2 FHQ71BWV1A / FHQ100BWV1A / FHQ125BWV1A


2.2.1 Names and functions of parts

k
f
a
e
e
i

d h
d

j
b

c
e

a Indoor unit
Outdoor unit
• The external appearance of the outdoor unit varies
depending on its capacity class.
b The outdoor unit shown in the figure is for refer-
ence to indicate features.
Contact your Daikin Dealer and verify which out-
door unit you have.
c Remote controller
d Inlet air
e Discharged air
f Air outlet
g Air flow flap (at air outlet)
h Refrigerant piping, connection electric wire
i Drain pipe
Suction grille
j
The built-in air filter removes dust and dirt.
Ground wire
k Wire to ground from the outdoor unit to prevent elec-
trical shocks.
3P380090-1

190 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

2.2.2 Installation

3P380086-1A

Installation of indoor / outdoor unit 191


Installation of indoor unit EDMT281426

3P380086-1A

192 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P380086-1A

Installation of indoor / outdoor unit 193


Installation of indoor unit EDMT281426

3P380086-1A

194 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P380086-1A

Installation of indoor / outdoor unit 195


Installation of indoor unit EDMT281426

3P380086-1A

196 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P380086-1A

Installation of indoor / outdoor unit 197


Installation of indoor unit EDMT281426

3P380086-1A

198 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P380086-1A

Installation of indoor / outdoor unit 199


Installation of indoor unit EDMT281426

3P380086-1A

200 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P380086-1A

Installation of indoor / outdoor unit 201


Installation of indoor unit EDMT281426

3P380086-1A

202 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P380086-1A

Installation of indoor / outdoor unit 203


Installation of indoor unit EDMT281426

3P380086-1A

204 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P380086-1A

Installation of indoor / outdoor unit 205


Installation of indoor unit EDMT281426

3P380086-1A

206 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P380086-1A

Installation of indoor / outdoor unit 207


Installation of indoor unit EDMT281426

3P380086-1A

208 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P380086-1A

Installation of indoor / outdoor unit 209


Installation of indoor unit EDMT281426

3P380086-1A

210 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P380086-1A

Installation of indoor / outdoor unit 211


Installation of indoor unit EDMT281426

3P380086-1A

212 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P380086-1A

Installation of indoor / outdoor unit 213


Installation of indoor unit EDMT281426

3P380086-1A

214 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

2.3 FHQ140CAVEA
2.3.1 Names and functions of parts
a

f
2

b
g
c d

a Air outlet
b Horizontal blade (at air outlet)
c Suction grille
d Air filter (inside suction grille)
Remote controller (optional part)
e The remote controller may not be needed
depending on the system configuration.
f Drain piping
Refrigerant piping
Transmission wiring
Power supply wiring (only for FXHQ)
Earth wiring
g
(NOTE)
It is wiring to let electricity flow from the
indoor unit to the earth for prevention of elec-
tric shocks / a fire in case of emergency.

C: 3P303408-2P

Installation of indoor / outdoor unit 215


Installation of indoor unit EDMT281426

2.3.2 Installation
FHQ35CAVEB FHQ100CAVEB
FHQ50CAVEB FHQ125CAVEB
SPLIT SYSTEM Air Conditioners Installation manual
FHQ60CAVEB FHQ140CAVEB
FHQ71CAVEB FHQ140CAVEA

• Consult your dealer regarding what to do in case of refriger-


ant leakage.
CONTENTS When the air conditioner is installed in a small room, it is nec-
1. SAFETY PRECAUTIONS ................................................1 essary to take proper measures so that the amount of any
2. BEFORE INSTALLATION.................................................2 leaked refrigerant does not exceed the concentration limit in
the event of a leakage.
3. SELECTION OF INSTALLATION LOCATION ..................3
Otherwise, this may lead to an accident due to oxygen defi-
4. PREPARATION BEFORE INSTALLATION.......................4 ciency.
5. INSTALLATION OF THE INDOOR UNIT .........................5 • Be sure to use only the specified parts and accessories for
6. REFRIGERANT PIPING WORK ......................................6 installation work.
7. DRAIN PIPING WORK.....................................................9 Failure to use the specified parts may result in the air condi-
8. ELECTRIC WIRING WORK...........................................10 tioner falling down, water leakage, electric shocks, a fire, etc.
• Install the air conditioner on a foundation that can withstand
9. HOW TO CONNECT WIRINGS AND
its mass.
WIRING EXAMPLE........................................................11 Insufficient strength may result in the air conditioner falling
10. MOUNTING SUCTION GRILLE · down and causing injury.
DECORATION SIDE PANEL..........................................14 In addition, it may lead to vibration of indoor units and cause
11. FIELD SETTING ............................................................14 unpleasant chattering noise.
• Carry out the specified installation work in consideration of
12. TEST OPERATION ........................................................16
strong winds, typhoons, or earthquakes.
13. WIRING DIAGRAM ........................................................18 Improper installation may result in an accident such as air
conditioner falling.
• Make certain that all electrical work is carried out by qualified
The original instructions are written in English. All other lan-
personnel according to the applicable legislation (note 1) and
guages are translations of the original instructions.
this installation manual, using a separate circuit.
In addition, even if the wiring is short, make sure to use a wir-
ing that has sufficient length and never connect additional
1. SAFETY PRECAUTIONS wiring to make the length sufficient.
Insufficient capacity of the power supply circuit or improper
Be sure to follow this “SAFETY PRECAUTIONS”. electrical construction may lead to electric shocks or a fire.
This product comes under the term “appliances not accessible (note 1) applicable legislation means “All international,
to the general public”. national and local directives, laws, regulations and/
or codes which are relevant and applicable for a
• This manual classifies the precautions into WARNINGS and certain product or domain”.
CAUTIONS. • Earth the air conditioner.
Be sure to follow all the precautions below: They are all Do not connect the earth wiring to gas or water piping, light-
important for ensuring safety. ning conductor or telephone earth wiring.
Incomplete earthing may cause electric shocks or a fire.
WARNING .................... Indicates a potentially hazard- • Be sure to install an earth leakage breaker.
ous situation which, if not Failure to do so may cause electric shocks and a fire.
avoided, could result in death • Disconnect the power supply before touching the electric
or serious injury. components.
CAUTION ..................... Indicates a potentially hazard- If you touch the live part, you may get an electric shocks.
ous situation which, if not • Make sure that all wiring is secure, using the specified wir-
avoided, may result in minor or ings and ensuring that external forces do not act on the ter-
moderate injury. minal connections or wirings.
It may also be used to alert Incomplete connection or fixing may cause an overheat or a
against unsafe practices. fire.
• After the installation is completed, test the air conditioner and • When wiring between the indoor and outdoor units, and wir-
check if the air conditioner operates properly. Give the user ing the power supply, form the wirings orderly so that the con-
adequate instructions concerning the use and cleaning of the trol box lid can be securely fastened.
indoor unit according to the Operation Manual. Ask the user If the control box lid is not in place, overheat of the terminals,
to keep this manual and the Operation Manual together in a electric shocks or a fire may be caused.
handy place for future reference. • If refrigerant gas leaks during installation work, ventilate the
area immediately.
WARNING Toxic gas may be produced if refrigerant gas comes into con-
• Ask your local dealer or qualified personnel to carry out tact with a fire.
installation work. • After completing the installation work, check to make sure
Improper installation may result in water leakage, electric that there is no leakage of refrigerant gas.
shocks or a fire. Toxic gas may be produced if refrigerant gas leaks into the
• Perform installation work in accordance with this installation room and comes into contact with a source of a fire, such as
manual. a fan heater, stove or cooker.
Improper installation may result in water leakage, electric • Never directly touch any accidental leaking refrigerant. This
shocks or a fire. could result in severe wounds caused by frostbite.

1 English

3P368557-1

216 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

• Have the customer actually operate the air conditioner while


CAUTION looking at the manual.
• Install drain piping according to this installation manual to Instruct the customer how to operate the air conditioner (par-
ensure good drainage, and insulate the piping to prevent ticularly cleaning of the air filters, operation procedures, and
condensation. temperature adjustment).
Improper drain piping may cause water leakage, make the • For selection of installation location, use the installation pat-


furniture get wet.
Install the air conditioner, power supply wiring, remote con-
tern paper (used in common with the packing case.) as refer-
ence.
2
troller wiring and transmission wiring at least 1 meter away • Do not use the air conditioner where in the salty atmosphere
from televisions or radios to prevent image interference or such as coastal areas, vehicles, vessels or the voltage fluc-
noise. tuation is frequent such as factories.
(Depending on the radio waves, a distance of 1 meter may • Take off static electricity from the body when carrying out wir-
not be sufficient to eliminate the noise.) ing and the control box lid is removed.
• Install the indoor unit as far as possible from fluorescent The electric parts may be damaged.
lamps.
If a wireless remote controller kit is installed, the transmission 2-1 ACCESSORIES
distance may be shorter in a room where an electronic light- Check if the following accessories are attached to the
ing type (inverter or rapid start type) fluorescent lamp is indoor unit.
installed.
• Do not install the air conditioner in places such as the follow- (1) Drain (2) Metal (3) Washer
Name (4) Clamp
ing: hose clamp for hanger
1. Where there is mist of oil, oil spray or vapour for example Quantity 1 pc. 1 pc. 8 pcs. 7 pcs.
a kitchen.
Resin parts may deteriorate, and cause them to fall out or
water to leak. Shape
2. Where corrosive gas, such as sulfurous acid gas, is pro-
duced.
Corrosion of copper pipings or brazed parts may cause
the refrigerant to leak. (5) Installa-
3. Where there is machinery which emits electromagnetic Joint insulat- Sealing mate- (10) Resin
Name tion pattern
ing material rial bushing
waves. paper
Electromagnetic waves may disturb the control system, Quantity 1 sheet 1 each 1 each 1 pc.
and cause malfunction of the equipment.
(6) For gas
4. Where flammable gases may leak, where carbon fibre or piping (8) Large
ignitable dust is suspended in the air or where volatile
flammables, such as thinner or gasoline, are handled.
If the gas should leak and remained around the air condi- Shape
(7) For liq- (9) Small
tioner, it may cause ignition. uid piping
• The air conditioner is not intended for use in a potentially
explosive atomosphere.

(12) Screw
(11) Wiring
Name for wiring
fixture
fixture (Miscellaneous)
2. BEFORE INSTALLATION
Quantity 2 pcs. 2 pcs.
When unpacking and moving the indoor unit after • Operation manual
M4 × 12
unpacked, do not apply force to the piping (refrigerant and • Installation manual
drain) and resin parts. Shape • Declaration of conformity
• Make sure to check in advance that the refrigerant to be used
for installation work is R410A.
(The air conditioner will not properly operate if a wrong refrig-
erant is used.)
• For installation of the outdoor unit, refer to the installation 2-2 OPTIONAL ACCESSORIES
manual attached to the outdoor unit. • For this indoor unit, the remote controller is separately
• Do not throw away the accessories until the installation work required.
is completed. • There are 2 kinds of remote controller; wired type and wire-
• After the indoor unit is carried into the room, to avoid the less type.
indoor unit from getting damaged, take measures to protect Install the remote controller to the place where the customer
the indoor unit with packing materials. has given consent.
(1) Determine the route to carry the unit into the room. Refer to the catalog for the applicable model.
(2) Do not unpack the unit until it is carried to the installation (Refer to the installation manual attached to the remote con-
location. troller for how to install.)
Where unpacking is unavoidable, use a sling of soft
material or protective plates together with a rope when
lifting, to avoid damage or scratches to the indoor units.

English 2
3P368557-1

Installation of indoor / outdoor unit 217


Installation of indoor unit EDMT281426

CARRY OUT THE WORK GIVING CAUTION TO THE Points of the operation explanation
FOLLOWING ITEMS AND AFTER THE WORK IS
In addition to the general usage, since the items in the
COMPLETED CHECK THESE AGAIN. operation manual with the WARNING and CAU-
TION marks are likely to result in human bodily injuries
1. Items to be checked after the installation work is com-
and property damages, it is necessary not only to
pleted
explain these items to the customer but also to have the
Check customer read them.
Items to be checked In case of defective
column It is also necessary to explain the items of “NOT MAL-
Are the indoor and outdoor Drop · vibration · FUNCTION OF THE AIR CONDITIONER” to the customer
units rigidly fixed? noise and have the customer read them carefully.
Are the installation work of the out- Does not operate ·
door and indoor units complete? burnout
Have you carried out a leakage
test with the test pressure Does not cool / 3. SELECTION OF INSTALLATION LOCA-
specified in the outdoor unit Does not heat
installation manual?
TION
Is the insulation of refrigerant When unpacking and moving the indoor unit after
piping and drain piping com- Water leakage unpacked, do not apply force to the piping (refrigerant and
pletely carried out? drain) and resin parts.
Does the drain flow out (1) Select the installation location that meets the following
Water leakage conditions and get approval of the customer.
smoothly?
Is the power supply voltage • Where the cool and warm air spreads evenly in the room.
identical to that stated in the Does not operate · • Where there is no obstacles in the air passage.
manufacturer’s label on the air burnout • Where drainage can be ensured.
conditioner? • Where the ceiling lower surface is not inclined.
Are you sure that there is no • Where there is sufficient strength to withstand the mass
Does not operate · of the indoor unit (if the strength is insufficient, the indoor
wrong wiring or piping or no
burnout
loose wiring? unit may vibrate and get in contact with the ceiling and
Danger in case of generate unpleasant chattering noise).
Is earthing completed? • Where a space sufficient for installation and service can
leakage
Are the sizes of electric wiring Does not operate · be ensured. (Refer to Fig. 1 and Fig. 2)
according to the specification? burnout • Where the piping length between the indoor and the out-
Is any of air outlets or inlets of
door units is ensured within the allowable length. (Refer
the indoor and outdoor units to the installation manual attached to the outdoor unit.)
blocked with obstacles? Does not cool / • Where there is no risk of flammable gas leak.
(It may lead to capacity drop Does not heat
due to fan speed drop or mal- [ Required installation space (mm) ]
function of equipment.)
*30 or more *30 or more
Have you recorded the refrig-
Refrigerant charge
erant piping length and the
amount is not clear
refrigerant charge added?

*Make sure to recheck the items of “SAFETY PRECAUTIONS”

2. Items to be checked at delivery Fig. 1

Check
300 or more

Items to be checked
column
Have you carried out field setting? (if necessary)
Are the control box lid, the air filter and the suction grille
attached?
Discharge
Does the cool air discharge during the cooling operation and
the warm air discharge during heating operation?
Suction 2500 or more
Have you explained how to operate the air conditioner from floor level
showing the operation manual to the customer? For high
Have you explained the description of cooling, heating, Obstacles installation
program dry and automatic (cooling/heating) given in
the operation manual to the customer?
Fig. 2
If you set the fan speed at thermostat OFF, did you Floor level
explain the set fan speed to the customer?
Have you handed the operation manual and the instal-
lation manual to the customer? NOTE
• If there is extra space required for * part, servicing can be
conducted more easily if 200mm or more is secured.

3 English
3P368557-1

218 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

(2) Make holes for hanging bolts, piping outlet, drain pip-
CAUTION ing outlet, and electric wiring inlet.
• Install the indoor and outdoor units, power supply wiring, • Use the installation pattern paper (5).
remote controller wiring and transmission wiring at least 1 • Determine the locations of hanging bolts, piping outlet,
meter away from televisions or radios to prevent image inter- drain piping outlet and electric wiring inlet. And make the
ference or noise. hole.
(Depending on the radio waves, a distance of 1 meter may
not be sufficient to eliminate the noise.) (3) Remove the parts of the indoor unit. 2
• Install the indoor unit as far as possible from fluorescent 1) Remove the suction grille.
lamps. • Slide the suction grille fixing knobs (35, 50 type: 2
If a wireless remote controller kit is installed, the transmission places for each, 60~140 type: 3 places for each) toward
distance may be shorter in a room where an electronic lighting backward direction (as shown by an arrow) to open the
type (inverter or rapid start type) fluorescent lamp is installed. suction grille widely. (Refer to Fig. 4)
• Keeping the suction grille opened, hold the knob at the
(2) Use hanging bolts for installation. back of the suction grille and at the same time, pull the
Investigate if the installation place can withstand the mass suction grille forward to remove. (Refer to Fig. 5)
of the indoor unit and, if necessary, hang the indoor unit
Suction grille
with bolts after it is reinforced by beams etc. (Refer to the Fixing knob
installation pattern paper (5) for the mounting pitch.).
(3) Ceiling height
This indoor unit can be installed up to 4.3m (for 35-71
model, 3.5m) of the ceiling.
Fig. 4

4. PREPARATION BEFORE INSTALLATION Rear knob

(1) For the locations of indoor unit hanging bolts, piping


outlet holes, drain piping outlet hole, and electric wir-
ing inlet hole. (Refer to Fig. 3)

G H
200

175

J
5

Fig. 5
View from the front
2) Remove the decoration side panel (right, left).
Left back drain Wall hole for back side
piping outlet hole
• Remove the fixture screw of the decoration side panel
piping outlet
(one for each), pull forward (arrow direction) to remove.
(φ100 hole)
(Refer to Fig. 6)
Back side wiring • Take out accessories. (Refer to Fig. 6)
outlet location
• Open the knock hole at the wiring inlet side at the rear
surface or top surface, and install the attached resin
A Unit dimension Top panel drain piping bushing (10).
connection position
B Hanging bolt pitch
C Resin bushing (10)
D
163
189

(accessory)
30
87

E
690 Unit dimension

Removable part
Hanging bolt pitch
210

(for leading in from the upward-facing)


View from
260

the ceiling Removable part


F Top panel gas side (for leading in from the rear-facing)
piping connection
position
Resin bushing (10)
Discharge (accessory)
Fig. 3
Top panel wiring outlet position
Unit : mm
Hanging bolt (4 pieces)
Accessories
Top panel liquid side piping
connection positions Fixing screw for decoration side Panel
(M4)
Model name (FHQ-) A B C D E F G H J
Type 35 · 50 960 920 378 324 270 375 398 377 260
Type 60 · 71 1270 1230 533 479 425 530 553 532 415 Decoration side panel Fig. 6
Type 100 · 125 · 140 1590 1550 693 639 585 690 713 692 575

English 4
3P368557-1

Installation of indoor / outdoor unit 219


Installation of indoor unit EDMT281426

3) Remove the hanger. 5. INSTALLATION OF THE INDOOR UNIT


• Loosen 2 bolts for installing the hanger at both sides
(M8) (4 places at left and right) within 10mm. ¢¢It is easy to attach the optional parts before installing the
(Refer to Fig. 7 and Fig. 8) indoor unit. Refer to also the installation manual attached
• Remove the fixture screw for hanger at the back side to the optional parts.²²
(M5), pull the hanger backward (the arrow direction) to For installation, use the attached installation parts and
remove. (Refer to Fig. 8) specified parts.
(1) Fix the hanger to the hanging bolt. (Refer to Fig. 10)
Bolt (M8)
CAUTION
For safety, make sure to use a washer for hanger (3)
Loosen within Indoor unit
(accessory) and fix by double nuts firmly.
10mm

Hanger Hanging bolt Nut (field supply)

Fig. 7 Washer for hanger (3) (accessory)

Hanger fixing
screw (M5) Double nuts
Hanger Fig. 10

Hanger installing bolt (M8) (2) Lift up the indoor unit, slide from the front and put the
hanger installing bolt (M8) into the securely for temporary
Loosen
Hanger hanging. (Refer to Fig. 11)
Fig. 8
(3) Tighten the hanger fixing screws (M5) at 2 places, which
were removed, as they were before.
(Refer to Fig. 11)
CAUTION It is necessary to prevent misalignment of the indoor unit.
Do not remove the tape (milky white) applied to the outside
of the indoor unit. It may cause electric shocks or a fire. (4) Tighten the hanger installing bolts (M8) at 4 places
securely. (Refer to Fig. 11)
(4) Install the hanging bolts. Attachment part
• Use M8 or M10 bolts for hanging the indoor unit. Hanger
• Adjust the length of the hanging bolt from the ceiling in
advance. (Refer to Fig. 9)
• Use hole-in-anchors for the existing bolts and embedded
inserts or foundation bolts for new bolts, and fix the unit
firmly to the building so that it may withstand the mass of
the unit. Hanger installing
In addition, adjust the distance from the ceiling in bolt (M8)
Hanger
advance.
fixing screw
(M5)
CAUTION Reinforcing plate (left/right)
If the hanging bolt is too long, it may damage or break the Fig. 11
When carrying the indoor unit,
indoor unit or options. do not hold the reinforcing plates.

(5) When hanging the indoor unit, make sure to use the level to
Ceiling slab
have better drainage and install it horizontally. Also, if it is
Foundation bolt possible at the installation site, install so that the drain pip-
25 - 55 mm

ing side is slightly lower.


(Refer to Fig. 12)
Hanging bolt
CAUTION
Fig. 9 Ceiling surface • Setting the indoor unit at an angle opposite to the drain
piping might cause a water leakage.
• Do not insert materials other than that specified into
NOTE
the clearance between the hanger and the washer for
• Parts shown Fig. 9 will be all field supply. hanger (3).
Unless the washers are properly attached, the hanging
bolts may come off from the hanger.

5 English
3P368557-1

220 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

• Remove the stay for packing and delivering (reinforcing


A plate) before refrigerant piping work.
≤ 1° (Refer to Fig. 18)
• The refrigerant is pre-charged in the outdoor unit.
• When connecting the pipings to the air conditioner, make sure
to use a spanner and a torque wrench as shown in Fig.13.

B
For the dimension of flared part, refer to the Table 1.
2
Torque wrench
≤ 1°

Spanner

A.B Flare nut


≤ 1°

Fig. 12 Union joint Fig. 13


A. When the drain piping is tilted to the right, or to the right
• When making a flare connection, coat the flared inner surface
and back.
only with ether oil or ester oil. (Refer to Fig. 14) Then, turn the
Place it level, or tilt it slightly to the right or the back.
flare nut 3 to 4 times with your hand and screw in the nut.
(Within 1°)
B. When the drain piping is tilted to the left, or to the left Coat the flared inner surface
and back. only with ether oil or ester oil.
Place it level, or tilt it slightly to the left or the back.
(Within 1°)
Fig. 14
WARNING
• For the tightening torque, refer to the Table 1.
The indoor unit must be securely installed on a place
that can withstand the mass. Table 1
If the strength is insufficient, the indoor unit may fall down
Dimension
and cause injuries. Piping size Tightening
for processing Flare shape
(mm) torque (N·m)
flare A (mm)
I 6.4

45°±2°
15.7 ± 1.5 8.9 ± 0.2

6. REFRIGERANT PIPING WORK I 9.5 36.3 ± 3.6 13.0 ± 0.2 R0.4-0.8

90°±2°
• For the outdoor unit refrigerant piping, refer to the installation I 12.7 54.9 ± 5.4 16.4 ± 0.2

A
manual attached to the outdoor unit.
• Carry out insulation of both gas and liquid refrigerant piping I 15.9 68.6 ± 6.8 19.5 ± 0.2
securely. If not insulated, it may cause water leakage. For
gas piping, use insulation material of which heat resistant CAUTION
temperature is not less than 120°C. For use under high
• Do not have oil adhere to the screw fixing part of resin
humidity, strengthen the insulation material for refrigerant
parts.
piping. If not strengthened, the surface of insulation material
If oil adheres, it may weaken the strength of screwed part.
may sweat.
• Do not tighten flare nuts too tight.
• Before installation work, make sure that the refrigerant is
If a flare nut cracks, the refrigerant may leak.
R410A. (Unless the refrigerant is R410A, the normal opera-
tion cannot be expected.)
• If there is no torque wrench, use Table 2 as a rule of thumb.
CAUTION When tightening a flare nut with a spanner harder and
This air conditioner is a dedicated model for new refrigerant harder, there is a point where the tightening torque suddenly
R410A. Make sure to meet the requirements shown right increases. From that position, tighten the nut additionally the
and carry out installation work. angle shown in Table 2. After the work is finished, check
• Use dedicated piping cutters and flaring tools for R410A. securely that there is no gas leak. If the nut is not tightened
• When making a flare connection, coat the flared inner sur- as instructed, it may cause slow refrigerant leak and result in
face only with ether oil or ester oil. malfunction (such as does not cool or heat).
• Use only the flare nuts attached to the air conditioner. If
Table 2
other flare nuts are used, it may cause refrigerant leakage.
• To prevent contamination or moisture from getting into the Piping size Recommended arm length
Tightening angle
piping, take measures such as pinching or taping the pip- (mm) of tool used
ings. I 6.4 60° – 90° Approximately 150mm
Do not mix substance other than the specified refrigerant I9.5 60° – 90° Approximately 200mm
such as air into the refrigeration circuit.
I 12.7 30° – 60° Approximately 250mm
If the refrigerant leaks during the work, ventilate the room.
I 15.9 30° – 60° Approximately 300mm

English 6
3P368557-1

Installation of indoor / outdoor unit 221


Installation of indoor unit EDMT281426

CAUTION
Insulation of field piping must be carried out up to the con- Gas side piping insulating method
nection inside the casing. If the piping is exposed to the
atmosphere, it may cause sweating or burn due to touching Do not leave
Piping insulating material (unit side) clearance
the piping, electric shocks or a fire due to the wiring touch-
ing the piping. Joint insulating material (6) (accessory)

Bring the seam Flare nut


• After leak test, referring to Fig. 15, insulate both the gas and to the top connection
liquid piping connection with the attached joint insulating
material (6) and (7) to prevent the piping from getting
exposed. Then, tighten the both ends of insulating material
with the clamp (4). Piping insulating material
• Wrap the sealing material (Small) (9) around the joint insulat- (field supply)
ing material (6) (flare nut section), only the gas piping side.
For prevention of sweating,
• Make sure to bring the seam of joint insulating material (6) do not expose the piping
and (7) to the top.
Clamp (4) (accessory) Tighten the piping
insulating material

Wrap from the


root of the unit
Sealing material (Small) (9)
(accessory)

Gas piping

Liquid piping

Indoor unit

Liquid side piping insulating method

Joint insulating material (7) Piping insulating material


(accessory) (unit side)

Do not leave clearance


Bring the seam
to the top
Flare nut
connection

Clamp (4)
(accessory)
Piping insulating
material (field supply)
Tighten the piping
For prevention of sweating, insulating material
do not expose the piping

Fig. 15

7 English
3P368557-1

222 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

(1) For rear side piping • After piping is finished, cut the removed penetration cover
• Remove the rear piping penetration cover, and connect along the shape of piping, and install.
the piping. (Refer to Fig. 16 and Fig. 18) Also, for top panel penetration cover, as it was before
removed, put the horizontal blade motor and thermistor
(2) For upward piping
lead through the clamp of the top panel penetration cover
• For upward piping, L-shaped connection piping kit
and fix. (Refer to Fig. 16 and Fig. 19)
(optional accessory) will be required.
• Remove the top panel penetration cover, and use the L-
When doing this, block any gaps between the piping pen-
etration cover and the piping using putty to prevent dust
2
shaped connection piping kit (optional accessory) to con-
from entering the indoor unit.
duct piping. (Refer to Fig. 16 and Fig. 17)
(3) For right side piping Horizontal blade motor lead
• Remove the stay for packing and delivering (reinforcing Top panel penetration
Thermistor lead
plate) at the right side, and put back the screw to the orig- cover clamp part
inal position of the indoor unit. (Refer to Fig. 18)
• Open the knockout hole at the decoration side panel
(right), and connect piping. (Refer to Fig. 18)
View from air inlet side
Rear piping penetration cover
Top panel Cutoff
Fig. 19

View from * Before brazing refrigerant piping, have nitrogen flow through
air inlet side the refrigerant piping and substitute air with nitrogen. Then,
carry out brazing (NOTE 2). (Refer to Fig. 20) After all the
Cut at the position avoiding
the knob part of the brazing works are finished, carry out flare connection with the
penetration cover indoor unit.
Cutoff
Pressure reducing valve

Top panel penetration cover Fig. 16 Brazing place Taping

Nitrogen
Stop valve Nitrogen
Refrigerant piping
Fig. 20

Upward refrigerant piping


L-shaped branch piping kit NOTE
(Optional accessory) 1. The proper pressure for having nitrogen flow through the
piping is approximately 0.02MPa, a pressure that makes
one feel like breeze and can be obtained through a pres-
sure reducing valve.
Fig. 17 2. Do not use flux when brazing refrigerant piping. Use phos-
phor copper brazing filler metal (BCuP-2: JIS Z 3264/B-
Screw Cu93P-710/795: ISO 3677) that does not require flux. (If
(put back to the indoor unit) chlorinated flux is used, the piping will be corroded and, in
addition if fluorine is contained, the refrigerant oil will be
deteriorated and the refrigerant circuit will be affected
badly.)
3. When carrying out leakage test of refrigerant piping and the
Rear side refrigerant piping
indoor unit after the installation of indoor unit is finished,
confirm the connecting outdoor unit installation manual for
Rear side drain piping test pressure. Refer to also the outdoor unit installation
Right side refrigerant piping manual or technical document for refrigerant piping.
Right side drain piping 4. In case of refrigerant shortage due to forgetting additional
Stay for packing and delivering refrigerant charge etc., it will result in malfunction such as
(reinforcing plate) does not cool or does not heat. Refer to the outdoor unit
Fig. 18 installation manual or technical document for refrigerant
Decoration side panel (right)
Separating parts piping.

Cut only this part when laying only CAUTION


the drain piping on the right side.
Do not use antioxidant when brazing piping.
It may result in malfunction of components and clogging of
piping due to residue.

English 8
3P368557-1

Installation of indoor / outdoor unit 223


Installation of indoor unit EDMT281426

7. DRAIN PIPING WORK


(1) Carry out drain piping.
Good
• Carry out drain piping so that drainage can ensured.
1-1.5m Supports
• Drain piping can be connected from the following direc-
tions: For right rear/right side, refer to Fig. 18 of ‘‘6.
REFRIGERANT PIPING WORK’’, and for left rear/left
side, refer to Fig. 21.
• When conducting left rear/left side drain piping, remove Downward inclination of 1/100 or more
the protection net. Then, remove the drain socket cap and Fig. 23
insulation material applied to left side drain socket and
apply them to the right side drain socket. When doing
this, insert the drain socket cap all the way in to prevent a
water leakage.
Make sure there is no slack
After the drain hose (1) (accessory) installing, attach the Do not lift
protection net by reversing the steps taken to remove it. Wrong
(Refer to Fig. 22)
• Select the piping diameter equal to or larger than that of
the drain hose (1) (accessory) (polyvinyl chloride piping, Make sure it is not in the water
nominal diameter 20mm, outside diameter 26mm).
• Install the drain piping as short as possible with down-
ward inclination of 1/100 or more by avoiding air stagna-
Fig. 24
tion. (Refer to Fig. 23 and Fig. 24)
(It may cause abnormal sound such as bubbling noise.)
CAUTION
If drain stagnates in the drain piping, the piping may be
Putty or insulation clogged.
(field supply)
• Make sure to use the attached drain hose (1) and metal
Left side clamp (2). Also, insert the drain hose (1) into the root of
Drain piping the drain socket, and tighten the metal clamp (2) at the
root of the drain socket tightly.
(Refer to Fig. 25 and Fig. 26)
(Install the metal clamp (2) so that the tightening part is in
Left rear side
Drain piping the range of about 45°as shown in the Fig. 26.)
Left side
Detach parts (Do not bond the drain socket and drain hose. If so, main-
tenance and inspection for the heat exchanger and oth-
Back side (sheet metal) ers cannot be conducted.)
Detach parts Fig. 21

CAUTION
If an old drain hose or an elbow or a clamp is used, it may
cause water leakage.

• Bend the tip of the metal clamp (2) so that the sealing
material does not bulge. (Refer to Fig. 26)
• When performing insulation, wind the large sealing mate-
rial (Large) (8) attached starting from the base of the
metal clamp (2) and drain hose (1) in the direction of the
Fixing
arrow. (Refer to Fig. 25 and Fig. 26)
screw for
protection net Protection net Sealing material (Large) (8)
Metal clamp (2)
(accessory) (accessory)
Fig. 22

Drain hose (1)


(accessory) Do not make a gap to avoid
dew condensation.
Fig. 25

9 English
3P368557-1

224 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

Metal clamp (2) Metal clamp (2)

or more
100mm
(accessory) Sealing material (accessory)
(Large) (8)
Applying direction Centralized drain piping
Drain hose (1)
Install with downward inclination If water stagnates in the
(accessory)
of 1/100 or more so that no air drain piping, the piping
approx. 45° approx. 45° Drain hose (1)
(accessory)
will be stagnated. may be clogged. 2
Sealing Fig. 28
material Sealing material
(Large) (8) (Large) (8) • Connecting drain piping.
(accessory) (accessory) Do not connect the drain piping directly to the sewage
(For right (For left rear/ that gives off ammonia odor. The ammonia in the sewage
back / right side) left side) may go through the drain piping and corrode the heat
Inserting direction exchanger of the indoor unit.
for the screw driver • When installing the drain pump kit (optional accessory),
also refer to the installation manual included to the drain
Tightening part pump kit.
approx. 45° Metal clamp (2) (accessory) (2) After piping is finished, check if the drain flows
smoothly.
• Gradually put about 0.6 liter of water for drain confirma-
Drain hose (1) (accessory) tion into the drain pan from the air outlet.
(Refer to Fig. 29)
Bend the tip without
Air outlet
tearing the sealing
material (Large) (8)
Fig. 26
100mm
• Be sure to insulate all drain piping running indoors. or more
• Do not deflect the drain hose (1) inside of the indoor unit.
(Refer to Fig. 27)
(It may cause abnormal noise such as bubbling noise.)
(If the drain hose (1) is deflected, it may damage the suc-
Plastic container for pouring water
tion grille.)
Fig. 29 (Tube length of 100mm is necessary)
Do not deflect
• After the drain piping work, install the stay for packing and
delivering (reinforcing plate), which was removed in the
section of ‘‘6. REFRIGERANT PIPING WORK’’.
However, it is not necessary to install the stay for packing
and delivering at the right side (reinforcing plate).
Fig. 27 (Refer to Fig. 30)

• Install supports at a distance of 1 to 1.5m so that the pip-


ing may not deflect. (Refer to Fig. 23)

CAUTION
To prevent dust from entering the indoor unit, cover the gap
with the drain piping by putty or insulation (field supply) so
that no clearance is made.
However, when putting piping and remote controller wiring
through the same hole, cover the gap between the through Stay for packing and delivering
Screw
cover and the piping after ‘‘8. ELECTRIC WIRING WORK’’ (reinforcing plate)
is completed. Fig. 30

< CAUTION >


• To avoid the attached drain hose (1) getting excessive
force, do not bend nor twist it. (It may cause water leak- 8. ELECTRIC WIRING WORK
age.)
• When conducting the centralized drain piping, follow the 8-1 GENERAL INSTRUCTIONS
instructions in Fig. 28. For the diameter of the centralized • Make certain that all electric wiring work is carried out by
drain piping, select the diameter matching the capacity of qualified personnel according to the applicable legislation
the indoor unit to be connected. (Refer to technical guide- and this installation manual, using a separate circuit. Insuffi-
book.) cient capacity of the power supply circuit or improper electri-
cal construction may lead to electric shocks or a fire.
• Make sure to install an earth leakage breaker in accordance
with applicable legislation. Failure to do so may cause elec-
trical shock and a fire.
• Do not turn on the power supply (of the indoor unit) until all
the installation work is completed.

English 10
3P368557-1

Installation of indoor / outdoor unit 225


Installation of indoor unit EDMT281426

• Make sure to earth the air conditioner. • If the above is not available, make sure to observe the follow-
Earthing resistance should be according to applicable legis- ing items.
lation. • 2 wirings of different sizes to the terminal block for power
• Do not connect the earth wiring to gas or water piping, light- supply is prohibited.
ning conductor or telephone earth wiring.
• Gas piping ............Ignition or explosion may occur if the Connection of 2 Connection of 2 Connection of
gas leaks. wirings of same size wirings on one side wirings of different
must be carried out is prohibited. sizes is prohibited.
• Water piping .........Hard vinyl tubes are not effective on both sides.
earths.
• Lightning conductor or telephone earth wiring..................
Electric potential may rise abnormally if struck by a light-
ning bolt.
• For electric wiring work, refer to also the “WIRING DIA-
GRAM” attached to the control box lid. (Abnormal heating may occur if the wirings are not tightened
• Never connect the power supply wiring to the terminal block securely.)
for remote controller wiring, or otherwise the entire system
may be damaged. • Use the required wirings, connect them securely and fix
• Carry out installation and wiring of the remote controller these wirings so that external force may not apply to the ter-
according to the “installation manual” attached to the remote minals.
controller. • Use a proper screw driver for tightening the terminal screws.
• Do not touch the Printed Circuit Board assy during the wiring If an improper screw driver is used, it may damage the screw
work. Otherwise, it may cause damage. head and a proper tightening cannot be carried out.
• If a terminal is over tightened, it may be damaged. Refer to
8-2 SPECIFICATIONS FOR FIELD WIRING the table shown below for tightening torque of terminals.
For the wiring of outdoor units, refer to the installation manual Tightening torque (N·m)
attached to the outdoor units.
• Remote controller and transmission wiring are field supply. Terminal block for remote controller
0.88 ± 0.08
(Refer to Table 3) and transmission wiring
Terminal block for power supply 1.47 ± 0.14
Table 3
Earth terminal 1.69 ± 0.25
2
Wire Size (mm ) Length
H05VV-U4G • Conduct wiring so that the earth lead comes out from the
Transmission wiring 2.5 – notched part of the cup washer. (Otherwise, earth lead con-
(NOTE 1)
Vinyl cord with tact will be insufficient and grounding effect may be lost.)
Remote controller Max. • Do not carry out soldering finish when stranded wirings are
sheath or cable 0.75 - 1.25
wiring 500m* used.
(2 wire) (NOTE 2)
* This will be the total extended length in the system when Ring type crimp style terminals
doing group control.
Wiring specifications are shown on the condition that the wiring
Cup washer
has a voltage drop of 2%.
1.It shows the case when conduit piping are used. When the
conduit piping are not used, use H07RN-F.
2.Sheathed vinyl cord or cable (insulation thickness: 1mm or
more)

Notched part

9. HOW TO CONNECT WIRINGS AND WIR-


ING EXAMPLE
9-1 CONNECTION OF TRANSMISSION WIRING,
Wiring connection method EARTH WIRING AND FOR THE REMOTE CON-
¢¢Caution for wiring²² TROLLER WIRING
• The indoor units in the same system can be connected to the (1) Loosen the fixing screws (2 pcs.) while holding the control
power supply from one branch switch. However, selection of box lid, and then remove the control box lid.
branch switch, branch over current circuit breaker and wiring (2) Cut off the knockout hole and put the resin bushing (10)
size must be according to applicable legislation. (accessory) on the back side (sheet metal).
• For connection to the terminal block, use ring type crimp style (3) Connect the transmission wiring through the resin bushing
terminals with insulation sleeve or treat the wiring with insu- (10) accessory to the terminal block (X2M: 3P) while match-
lation. ing up the numbers (1 to 3), and then connect the earth wir-
ing to the earth terminal.
Wiring After this is done, use the wiring fixture (11) and clamp (4)
Insulation sleeve
attached to bind the wiring without applying tension to the
connecting section of the wirings.
Ring type crimp
style terminals

11 English
3P368557-1

226 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

(4) Connect the remote controller wiring led from the routing
hole to the terminals (P1 and P2) of the terminal block WARNING
(X1M: 4P). (There is no polarity.) When wiring, form the wirings orderly so that the control
After this is done, use the wiring fixture (11) and clamp (4) box lid can be securely fastened. If the control box lid is not
attached to bind the wiring without applying tension to the in place, the wirings may float up or be sandwiched by the
connecting section of the wirings. box and the panel and cause electric shocks or a fire.
2
Terminal block (X2M)
Earth terminal Remote controller wiring

R10 or more Wiring fixture Clamp (4) (accessory)


(11) (accessory) (2) Fix the wiring to the
(1) Install the fixture at fixture by clamps so
R10 or more Transmission wiring
the wiring entrance that no tension will be
and Earth wiring
side. given to the terminal
connection.
Transmission and earth wiring connection method Power supply wiring DETAIL
and Earth wiring Clamp (4) (accessory)
Outdoor unit Indoor unit
(3) To avoid the loosing of
the power supply
wiring and Earth
Terminal block Terminal block wiring, band the clamp
to tightly fit the fixture
Terminal numbers of outdoor and
indoor units must be matched at terminal block side.

Transmission wiring connection method


• In case the piping penetration cover is cut off and used as
Forbidden
wiring penetration hole, after the wiring connection is fin-
• Do not carry out soldering finish. ished, mend the cover.
• Seal the clearance around the wirings with putty and insulat-
ing material (field supply).
Forbidden (If insects and small animals get into the indoor unit, short cir-
• Never connect the power supply cuiting may occur inside the control box.)
wiring. • If the low voltage wiring (remote controller wiring) and the
• Do not carry out soldering finish.
high voltage wiring (transmission wiring, earth wiring) are
Terminal block (X1M) brought into the indoor unit from the same place, they may be
affected by electric noise (outside noise) and cause malfunc-
tion or failure.
• Keep the distance of 50mm or more between the low voltage
R10 or more Remote controller
wiring wiring (remote controller wiring) and the high voltage wiring
(no polarity) (transmission wiring, earth wiring) at anywhere outside the
indoor unit. If both the wirings are laid down together, they
Remote controller wiring
connection method may be affected by electric noise (outside noise) and cause
malfunction or failure.
Printed Circuit
Board Wiring penetration Putty or insulation
Control box hole
(field supply)

Transmission Refrigerant piping


wiring and Remote controller
Earth wiring wiring
Drain piping
Resin bushing
Cut off the (10)(accessory) Low voltage wiring
knockout hole and Transmission Rear piping
put the resin wiring and penetration
bushing Earth wiring cover High voltage wiring
(10) (accessory)
Remote controller Distance of 50mm between
wiring

Control box lid


fixing screws Control box lid
(2 pieces)
Wiring diagram Label (Rear)

English 12
3P368557-1

Installation of indoor / outdoor unit 227


Installation of indoor unit EDMT281426

9-2 WIRING EXAMPLE NOTE


CAUTION 1. Terminal numbers of outdoor and indoor units must be
Be sure to install an earth leakage breaker to the outdoor matched.
unit. 2-1. Connect the remote controller only to the master unit.
This is to avoid electric shocks or a fire. 2-2. The remote controller needs to be wired only to the mas-
ter unit; it does not need to be connected to the slave
units through transition wiring. (Do not connect transition
For the wiring of outdoor units, refer to the installation manual
wiring to the slave units.)
attached to the outdoor units. Confirm the system type.
2-3. The indoor temperature sensor is effective only for indoor
• Pair type:
units to which the remote controller is connected.
1 remote controller controls 1 indoor unit (standard system).
2-4. The length of wiring between the indoor unit and the out-
(Refer to Fig. 31)
door unit varies depending on the connected model, the
• Simultaneous operation system:
number of connected units, and the maximum piping
1 remote controller controls 2 indoor units
length.
(2 indoor units operates equally). (Refer to Fig. 32)
For details, refer to the technical documents.
• Group control:
1 remote controller controls up to 16 indoor units
Group control
(All indoor units operate according to the remote controller).
(Refer to Fig. 33) Power supply Power supply Power supply
• 2 remote controllers control: 220 - 240V 220 - 240V 220 - 240V
2 remote controllers control 1 indoor unit. (Refer to Fig. 36) ~ ~ ~
50Hz 50Hz 50Hz
Earth leakage Earth leakage Earth leakage
Pair type breaker breaker breaker
Power supply
Earth leakage 220 - 240V
~ Outdoor unit Outdoor unit Outdoor unit
breaker
50Hz 1 2 3 1 2 3 1 2 3

Outdoor unit NOTE) NOTE) NOTE)


1 2 3
1 2 3 1 2 3 1 2 3
P1 P2 P1 P2 P1 P2
NOTE 1) Indoor unit Indoor unit Indoor unit
(Master)
1 2 3 P1 P2

P1 P2
Group control remote controller
Indoor unit (Optional accessory) Fig. 33

Remote controller P1P2 NOTE


(Optional accessory)
• Terminal numbers of outdoor and indoor units must be
Fig. 31 matched.
When implementing group control
• When using as a pair unit or as a master unit for simultane-
ous operation system, you may carry out simultaneous start/
Simultaneous operation system stop (group) control up to 16 units with the remote controller.
(Refer to Fig. 34)
Power supply
• In this case, all the indoor units in the group will operate in
Earth leakage 220 - 240V
~
accordance with the group control remote controller.
breaker • Select a remote controller which matches as many of the
50Hz
functions (airflow direction, etc.) in the group as possible.
Outdoor unit Outdoor Outdoor Outdoor
unit 1 unit 2 unit 16
1 2 3
Indoor Indoor
Indoor unit 2 unit 2 Indoor
NOTE 1) unit 1 (Slave) (Master) unit 16

1 2 3 1 2 3 Group control remote controller


P1 P2 P1 P2

Indoor unit (Master) Fig. 34


Indoor unit (slave)
Remote Wiring Method
P1 P2
controller (1) Remove the control box lid. (Refer to ‘‘9. HOW TO CON-
NOTE 2) (Optional accessory) NECT WIRINGS AND WIRING EXAMPLE’’.)
Fig. 32

13 English
3P368557-1

228 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

(2) Connect crossover wiring between the terminals (P1, P2) 10. MOUNTING SUCTION GRILLE · DECO-
inside the control box for the remote controller. (There is no
RATION SIDE PANEL
polarity.) (Refer to Fig. 34 and Table 3)
Install securely in the reverse order when decoration side panel
Terminal for remote
controller wiring (P1, P2) and suction grille were removed.
Indoor unit 2
Indoor unit 1 (Master) • When installing the suction grille, hang the string of the suc-
P1 P2 F1 F2 Terminal block
(X1M)
P1 P2 F1 F2 tion grille to the hanging part of the indoor unit shown Fig. 38.
2
CAUTION
Crossover wiring
to next unit When closing the suction grille, the strap may get caught.
Confirm that the strap does not stick out of the side of the
Terminal block
(X1M) suction grille before closing.
Fig. 35
Round hole Hook
Control with 2 remote controllers control Round hole

Power supply Strap


Earth 220 - 240V
leakage ~ Indoor unit
breaker 50Hz (Slave) Hook
Indoor unit
Suction grille Strap
Cross hole
Outdoor unit
Indoor unit Fig. 38
Outdoor unit (Master)
1 2 3

Remote Remote
NOTE) controller 1 controller 2 11. FIELD SETTING
(Optional (Optional
accessory) accessory) <<Refer to also the installation manual attached to the out-
1 2 3 door unit.>>
P1 P2

Indoor unit CAUTION


Remote Remote Before carrying out field setting, check the items mentioned
controller controller in the clause 2 “1. Items to be checked after the installa-
(Optional P1 P2 P1 P2 (Optional tion work is completed” on page 3.
accessory) accessory)
• Check if all the installation and piping works for the air
Fig. 36 conditioner are completed.
Two remote controllers control (Controlling 1 indoor unit by • Check if the control box lids of air conditioner are closed.
2 remote controllers)
• When using 2 remote controllers, one must be set to “MAIN”
<FIELD SETTING>
and the other to “SUB”.
<After turn on the power supply, carry out field setting from the
MAIN/SUB CHANGEOVER remote controller according to the installation state.>
• Refer to the manual attached to the remote controller. • Carry out setting at 3 places, “Mode No.”, “FIRST CODE No.”
and “SECOND CODE No.”.
Wiring Method
(1) Remove the control box lid. The settings shown by “ ” in the table indicate those
(2) Add wiring between the remote controller 2 (Sub) and the when shipped from the factory.
terminal (P1, P2) of the terminal block (X1M) for the remote • The method of setting procedure and operation is shown in
controller in the control box. (There is no polarity.) the installation manual attached to the remote controller.
Terminal block (Note) Though setting of “Mode No.” is carried out as a
(X1M) group, if you intend to carry out individual setting by
(Master*) each indoor unit or confirmation after setting, carry
P1 P2 F1 F2 out setting with the “Mode No.” shown in the parenthe-
sis ( ).
• In case of remote control, for changeover of input to
FORCED OFF or to ON/OFF OPERATION.
Additional [1] Enter into the field setting mode with the remote controller.
remote controller
[2] Select Mode No. “12”.
Remote Remote
controller 1
[3] Set the FIRST CODE No. to “1”.
controller 2
(Main) (Sub) [4-1] For FORCE OFF, set the SECOND CODE No. to “01”.

* For simultaneous operation system, be sure to [4-2] For ON/OFF OPERATION, set the SECOND CODE No.
connect the remote controller to the master unit. Fig. 37 to “02”.
(It is set to FORCED OFF when shipped from the factory.)
NOTE
• Ask your customer to keep the manual attached to the
• Terminal numbers of outdoor and indoor units must be remote controller together with the operation manual.
matched. • Do not carry out setting other than those shown in the table.

English 14
3P368557-1

Installation of indoor / outdoor unit 229


Installation of indoor unit EDMT281426

11-1 SETTING WHEN AN OPTIONAL ACCESSORY 11-5 SETTING FAN SPEED DURING THERMOSTAT
IS ATTACHED OFF
• For setting when attaching an optional accessory, refer to the • Set the fan speed according to the using environment after
installation manual attached to the optional accessory. consultation with your customer.
Table 6
11-2 WHEN USING WIRELESS REMOTE CONTROL-
LER Setting Mode No.
FIRST SECOND
• When using a wireless remote controller, it is necessary to CODE No. CORD No.
set the wireless remote controller address. Fan operates / stops Operates 01
Refer to the installation manual attached to the wireless during thermo OFF 11 (21) 2
remote controller. (Cooling · heating) Stops 02

11-3 SETTING CEILING HEIGHT (TYPE 100 OR Fan speed during (Extra low) 01
cooling 12 (22) 6
LESS) Setting 02
thermostat OFF
• When installing indoor unit type 35 - 100, specify the SEC-
Fan speed during (Extra low) 01
OND CODE No. in accordance with the ceiling height.
heating 12 (22) 3
thermostat OFF Setting 02
Table 4
Ceiling height (m)
11-6 SETTING NUMBER OF THE CONNECTED
FIRST SECOND INDOOR UNITS AS SIMULTANEOUS OPERA-
Mode
Type Type Type CODE CODE
No.
No. No.
TION SYSTEM
35,50 60,71 100
• When using in simultaneous operation system mode, change
the SECOND CODE No. as shown in Table 7.
2.7 2.7 3.8 • When using in simultaneous operation system mode, refer to
Standard 01
or less or less or less “SIMULTANEOUS OPERATION SYSTEM INDIVIDUAL
13 (23) 0
2.7 - 2.7 - 3.8 - SETTING” section to set master and slave units separately.
High ceiling 02
3.5 3.5 4.3
Table 7
11-4 SETTING FILTER SIGN FIRST SECOND
Setting Mode No.
• A message to inform the air filter cleaning time will be indi- CODE No. CODE No.
cated on the remote controller. Pair system (1 unit) 01
• Set the SECOND CODE No. shown in the Table 5 according Simultaneous
to the amount of dust or pollution in the room. operation 02
• Though the indoor unit is equipped with the long life filter, it is system (2-unit)
necessary to periodically clean the filter to avoid clogging of Simultaneous 11 (21) 0
the filter. Please also explain the set time to the customer. operation 03
• The periodical filter cleaning time can be shortened depend- system (3-unit)
ing on the environment. Double twin multi
04
Table 5 (4-unit)

SECOND 11-7 SIMULTANEOUS OPERATION SYSTEM INDI-


Filter hours FIRST
Contamination Mode No. CORD
(long life type) CODE No.
No.
VIDUAL SETTING
It is easier if the optional remote controller is used when setting
Approx.
Normal
2500 hrs
01 the slave unit.
0
More Approx. < Procedure >
10 (20) 02
contaminated 1250 hrs • Perform the following procedure when setting the master and
With indication 01 slave unit separately.
3
No indication 02 • “ ” in the tables indicates factory settings.
* Use “No indication” setting when cleaning indication is not (Note) The “Mode No.” is set on a group basis. To individually
necessary such as the case of periodical cleaning being car- set a Mode No. for each indoor unit or confirm the set-
ried out. tings, set the Mode No. in the parenthesis.
(1) Change the SECOND CODE No. to “02”, individual setting,
so that the slave unit can be individually set.
Table 8
FIRST SECOND
Setting Mode No.
CODE No. CODE No.
Unified setting 01
11 (21) 1
Individual setting 02

(2) Perform field setting (Refer to 11-1 to 11-5) for the master
unit.
(3) Turn off the main power supply switch after (2) is finished.
(4) Detach remote controller from the master unit and connect
it to the slave unit.

15 English
3P368557-1

230 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

(5) Turn on the main power supply switch again, and as in (1), • If interior work is still unfinished when test operation fin-
change the SECOND CODE No. to “02”, individual setting. ishes, explain to the customer that the air conditioner
(6) Perform field setting (Refer to 11-1 to 11-4) for the slave must not be operated until interior work is completed in
unit. order to protect the indoor units.
(7) Turn off the main power supply switch after (6) is finished. (If the indoor unit is operated under this condition,
(8) If there is more than one slave unit, repeat steps (4) to (7). paint, glue, and other materials used during the interior
(9) Detach the remote controller from the slave unit after the
setting, and reattach to the master unit. This is the end of
finishing work will contaminate the indoor unit. This
may cause water splashes or leakage.)
2
the setting procedure. • If a malfunction occurs and the air conditioner cannot
* You do not need to rewire the remote controller from the operate, refer to “12-1 HOW TO DIAGNOSE FOR
master unit if the optional remote controller for slave unit PROBLEMS”.
is used. (However, remove the wiring attached to the • After completing the test operation, press the INSPEC-
remote controller terminal block of the master unit.) After TION/TEST OPERATION button once to put the indoor
the slave unit setting, remove the remote controller wir- unit in inspection mode, and make sure the malfunction
ing, and rewire the remote controller to the master unit. code is “00” (= normal).
(The indoor unit does not operate properly when two or If the code reads anything other than “00”, refer to “12-
more remote controllers are attached to the unit in the 1 HOW TO DIAGNOSE FOR PROBLEMS”.
simultaneous operation system mode.) • Press the INSPECTION/TEST OPERATION button
four times to return to normal operation mode.
(3)(7)
Earth Power supply Earth Power supply [Mode switching]
leakage 220 - 240V leakage 220 - 240V
breaker ~ breaker ~ BRC1C, BRC1D, Wireless remote controller
50Hz 50Hz
Outdoor Outdoor Normal Test
unit unit operating Once operation
1 2 3 1 2 3 mode mode
Once Once
NOTE)
Once
NOTE) (Press 4

On
seconds *

ce
1 2 3 1 2 3 1 2 3 1 2 3 or more) Once * *
P1 P2 P1 P2 P1 P2 P1 P2
Field setting “Indoor “Outdoor
Indoor unit Indoor unit Indoor unit Indoor unit “Malfunction
unit type unit type
(Master) (Slave) (Master) (Slave) * After leaving 10 code” Once code” Once code”
seconds or display
P1 P2 Remote controller ( 4 ) P1 P2 display display
( 9 ) Remote controller more, the mode
(1) (5) returns to the
(2) (6) normal Inspection mode
Fig. 39 operating mode.
NOTE
• Terminal numbers of outdoor and indoor units must be 12-1 HOW TO DIAGNOSE FOR PROBLEMS
matched. With the power on. Troubles can be monitored on the
remote controller.
The fault diagnosis for the BRC1E model remote controller
should be performed while referring to the installation man-
12. TEST OPERATION ual supplied with the remote controller. For the other remote
controllers, perform the fault diagnosis using the following
¢Complete all the “1. Items to be checked after the installa-
procedure.
tion work is completed” on page 3. Please also refer to the
„Trouble shooting with the remote controller display.
installation manual attached to with outdoor unit.²
1 With the wired remote controller. (NOTE 1)
(1) The settings of the wired remote controller should be
When the operation stops due to trouble, the opera-
switched while referring to the manual attached to the
remote controller. tion lamp flashes, and the display indicates “ ”
(2) The settings of the other remote controller should be and the malfunction code. Diagnosis can be carried
switched in accordance with the following procedure. out using the malfunction code list according to the
• Make sure that the installation work for the indoor and indicated malfunction code.
outdoor units is all completed. In addition, when in group control it indicates the
• Make sure that the following items are all closed: the unit No., so the malfunction detected unit No. will be
control box lid of the indoor unit and the outer board clarified. For resetting the malfunction, see (NOTE
and piping cover of the outdoor unit. 2).
• After completing the refrigerant piping, drain piping, 2 With the wireless remote controller.
and electrical wiring, clean the interior of the indoor unit (Also refer to the operation manual attached to the
and front panel. Next, perform test operation in accor- wireless remote controller.)
dance with the installation manual attached to with the When the operation stops due to trouble, the dis-
outdoor unit in order to protect the unit. (It is recom- play on the indoor unit flashes. In such a case, diag-
mended that the test operation is performed in the nose the fault contents with the table on the
presence of qualified electrical technician or engineer.) Malfunction code list looking for the Malfunction
• In test operation, make sure that airflow direction and code which can be found by following procedures.
fan speed can be obtained according to the settings. (NOTE 2)

English 16
3P368557-1

Installation of indoor / outdoor unit 231


Installation of indoor unit EDMT281426

(1) Press the INSPECTION /TEST OPERATION but- Indoor heat exchanger Abnormal stop is applied
ton, “ ” is displayed and “ 0 ” flashes. C4 liquid pipe temperature depending on the model or
(2) Press the PROGRAMMING TIME button and find sensor malfunction condition.
the unit No. which stopped due to trouble. Indoor heat exchanger
Abnormal stop is applied
Number of beeps 3 short beeps condenser / evaporator
C5 depending on the model or
................. Perform all the following operations temperature sensor mal-
condition.
1 short beep function
................. Perform (3) and (6) Abnormal stop is applied
Suction air thermistor
1 long beep C9 depending on the model or
malfunction
................. No trouble condition.
(3) Press the OPERATION MODE SELECTOR button CC Humidity sensor abnormal
and upper figure of the malfunction code flashes. Remote controller thermo
Remote controller air
(4) Continue pressing the PROGRAMMING TIME button CJ does not function, but body
thermistor malfunction
unit it makes 2 short beeps and find the upper code. thermo operation is enabled.
(5) Press the OPERATION MODE SELECTOR button Action of safety device
E0
and lower figure of the malfunction code flashes. (Outdoor unit)
(6) Continue pressing the PROGRAMMING TIME button Outdoor Printed Circuit
E1
unit it makes a long beep and find the lower code. Board failure (Outdoor unit)
• A long beep indicate the malfunction code. High pressure malfunc-
E3
tion (Outdoor unit)
NOTE Low pressure malfunc-
E4
1. When the INSPECTION/OPERATION button on the remote tion (Outdoor unit)
controller is pressed, the “ ” indication starts flashing. Compressor motor lock
E5
2. When the ON/OFF button is kept pressed for 5 seconds or malfunction (Outdoor unit)
longer during the inspection mode, the above trouble his- Compressor motor lock by
E6
tory indication disappears. In this case, after the malfunc- over current (Outdoor unit)
tion code indication flashes twice, the indication of code Outdoor fan motor lock
becomes “00” (normal) and unit NO. becomes “0”. Then, malfunction (Outdoor unit)
the display automatically changes from the inspection E7 Outdoor fan instant over-
mode to the normal mode. current malfunction
(Outdoor unit)
12-2 MALFUNCTION CODE E8
Input overcurrent (outdoor
• For places where the malfunction code is left blank, the unit)
Electric expansion valve
“ ” indication is not displayed. Though the system contin- E9
malfunction (Outdoor unit)
ues operating, be sure to inspect the system and make
Cooling/heating switch
repairs as necessary. EA
malfunction (Outdoor unit)
• Depending on the type of indoor or outdoor unit, the malfunc-
Discharge piping temper-
tion code may or may not be displayed.
F3 ature malfunction (Out-
Malfunc- Descriptions and mea- door unit)
Remarks
tion code sures High pressure control
F6
Indoor Printed Circuit (in cooling) (Outdoor unit)
A1
Board failure Sensor fault for inverter
H0
A3 Drain level abnormal (Outdoor unit) (NOTE 1)
Freeze-up protector or High pressure switch fail-
H3
A5 stopped by high pressure ure (Outdoor unit)
control (NOTE 1) Low pressure switch fail-
H4
Indoor fan motor over- ure (Outdoor unit)
load, over current, lock Faulty position detection
A6
Indoor Printed Circuit H6 sensor (Outdoor unit)
Board connection failure (NOTE 1)
Horizontal blade motor Outdoor fan motor posi-
locked H7 tion signal malfunction
A7 (Outdoor unit)
Only the airflow direction
cannot be controlled. CT abnormality
H8
Humidifier system mal- (Outdoor unit) (NOTE 1)
AF
function Outdoor air thermistor Abnormal stop is applied
Capacity setting adapter or H9 system malfunction (Out- depending on the model or
capacity data error, or discon- door unit) condition.
nection of the capacity setting Pressure sensor system
AJ Capacity setting failure
adapter, failure to connect the J1 malfunction (batch)
adapter, or the capacity is not (Outdoor unit)
set to the data-retention IC. Current sensor system Abnormal stop is applied
Transmission error J2 malfunction (Outdoor depending on the model or
between indoor unit) condition.
C1 Printed Circuit Board (Mas- Discharge piping thermis- Abnormal stop is applied
ter) and indoor Printed Cir- J3 tor system malfunction depending on the model or
cuit Board (Slave) (Outdoor unit) condition.

17 English
3P368557-1

232 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

Suction piping thermistor Wiring error between indoor


Transmission error
J5 system malfunction (Out- U4 and outdoor unit. Or Indoor
(between indoor and out-
door unit) UF and outdoor Printed Circuit
door units)
Outdoor heat exchanger Board failure.
Abnormal stop is applied
distributor liquid piping Transmission error Transmission between indoor
J6 depending on the model or
thermistor malfunction U5 (between indoor and unit and remote controller is
condition.
(Outdoor unit)
Outdoor heat exchanger
remote controller units)
Transmission error of the
not performed properly.
2
Abnormal stop is applied U7
condenser / evaporator inverter module
J7 depending on the model or
thermistor malfunction Transmission error
condition.
(Outdoor unit) between main and sub
Liquid piping thermistor Abnormal stop is applied U8 remote controllers (sub
J8 system malfunction (Out- depending on the model or remote controller mal-
door unit) condition. function)
Gas piping thermistor System setting error of the
J9 malfunction (cooling) UA Field setting error simultaneous on/off multi-split
(Outdoor unit) type.
Discharge piping pres- Transmission error
JA sure sensor system mal- (between indoor unit and
UE
function (Outdoor unit) centralized remote con-
Suction piping pressure troller)
JC sensor system malfunc- Remote controller
UC
tion (Outdoor unit) address setting error
Inverter system malfunc- Abnormal stop is applied
L1 Accessory equipment
tion (Outdoor unit) UJ depending on the model or
transmission error
Reactor thermistor mal- condition.
L3
function (Outdoor unit)
Overheated heat-radiat- CAUTION
L4 Inverter cooling failure.
ing fin (Outdoor unit) After test operation is completed, check the items mentioned in
The compressor engines and the clause 2 “2. Items to be checked at delivery” on page 3.
Instantaneous overcur-
L5 turbines may be experiencing If the interior finish work is not completed when the test opera-
rent (Outdoor unit)
a ground fault or short circuit. tion is finished, for protection of the air conditioner, ask the cus-
The compressor engines and tomer not operate the air conditioner until the interior finish work
Electric thermal (Outdoor
L8
unit)
turbines may be overloaded is completed.
and disconnected. If the air conditioner is operated, the inside of the indoor units
Stall prevention (Outdoor may be polluted by substances generated from the coating and
L9 The compressor may be locked.
unit) adhesives used for the interior finish work and cause water
Transmission malfunction splash and leakage.
between inverter and out-
LC
door control unit (Outdoor To the operator carrying out test operation
unit)
After test operation is completed, before delivering the air con-
Open-phase (Outdoor ditioner to the customer, confirm that the control box lid is
P1
unit)
closed.
DCL sensor system mal- In addition, explain the power supply status (power supply ON/
P3
function (Outdoor unit)
OFF) to the customer.
Heat-radiating fin thermis- Abnormal stop is applied
P4 tor malfunction (Outdoor depending on the model or
unit) condition.
DC output current sensor
P6 system malfunction (Out- 13. WIRING DIAGRAM
door unit)
(Refer to Fig. 40)
Capacity setting adapter or
capacity data error, or discon- 1 (NOTE 9) 2 TO OUTDOOR UNIT (NOTE 3)
Capacity setting failure nection of the capacity setting 3 INDOOR UNIT 4 (NOTE 5)
PJ
(Outdoor unit) adapter, failure to connect the
CENTRAL REMOTE CON-
adapter, or the capacity is not 5 (NOTE 5) 6
TROLLER (NOTE 4)
set to the data-retention IC.
WIRELESS REMOTE CON-
The refrigerant may be insuffi- WIRED REMOTE CONTROL-
Suction piping tempera- TROLLER (RECEIVER/DIS-
cient. 7 LER (OPTIONAL ACCES- 8
U0 ture abnormal (Outdoor PLAY UNIT)
Abnormal stop is applied depend- SORY) (NOTE 7)
unit) (OPTIONAL ACCESSORY)
ing on the model or condition.
IN CASE OF SIMULTANEOUS
Reverse phase (Outdoor Reverse two phase of L1, L2
U1 9 OPERATION SYSTEM (NOTE 10 INDOOR UNIT (MASTER)
unit) and L3 leads.
6)
The inverter open-phase or
main circuit condenser may 11 INDOOR UNIT (SLAVE) 12 REMOTE CONTROLLER
Power voltage malfunc- be malfunctioning. 13 TO OUTDOOR UNIT 14 CONTROL BOX
U2
tion (Outdoor unit) Abnormal stop is applied 15 CLASS
depending on the model or
condition.

English 18
3P368557-1

Installation of indoor / outdoor unit 233


234
19
INDOOR UNIT H4P PILOT LAMP
A1P PRINTED CIRCUIT BOARD (DEFROST-ORANGE) WIRING DIAGRAM
C105 CAPACITOR (M1F) SS1 SELECTOR SWITCH 9
F1U FUSE (F, 5A, 250V) (MAIN/SUB)
HAP FLASHING LAMP SS2 SELECTOR SWITCH 10 11 11
(SERVICE MONITOR GREEN) (WIRELESS ADDRESS SET)
Installation of indoor unit

KPR MAGNETIC RELAY CONNECTOR FOR


(DRAIN PUMP) OPTIONAL PARTS
13
M1F MOTOR (INDOOR FAN) X15A CONNECTOR
M1S MOTOR (SWING BLADE) (FLOAT SWITCH)
14
R1T THERMISTOR (AIR) X24A CONNECTOR
R2T·R3T THERMISTOR (COIL) (WIRELESS REMOTE
SS1 SELECTOR SWITCH CONTROLLER)
12
(EMERGENCY) X25A CONNECTOR 6
V1R DIODE BRIDGE (DRAIN PUMP) 3
15
X1M TERMINAL BLOCK X33A CONNECTOR 15
X2M TERMINAL BLOCK (ADAPTOR FOR WIRING) 2
7
Z1F NOISE FILTER X35A CONNECTOR
Z1C FERRITE CORE (POWER SUPPLY FOR
(NOISE FILTER) ADAPTOR)
PS POWER SUPPLY CIRCUIT 1 4 8
RC SIGNAL RECEIVER CIRCUIT
TC SIGNAL TRANSMISSION
CIRCUIT
WIRELESS REMOTE CONTROLLER
(RECEIVER/DISPLAY UNIT)
5
A2P PRINTED CIRCUIT BOARD
A3P PRINTED CIRCUIT BOARD NOTES
BS1 PUSH BUTTON (ON/OFF) 1. : TERMINAL BLOCK : CONNECTOR : FIELD WIRING : SHORT CIRCUIT CONNECTOR
H1P PILOT LAMP (ON-RED) 2. IN CASE OF SIMULTANEOUS OPERATION INDOOR UNIT SYSTEM.
H2P PILOT LAMP SEE THE INDOOR UNIT WIRING ONLY.
3. FOR THE DETAIL, SEE WIRING DIAGRAM ATTACHED TO OUTDOOR UNIT.
(TIMER-GREEN)
4. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IN TO THE UNIT IN ACCORDANCE WITH THE ATTACHED
H3P PILOT LAMP INSTALLATION MANUAL.
(FILTER SIGN-RED) 5. X15A, X25A ARE CONNECTED WHEN THE DRAIN UP KIT IS BEING USED.
IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL.
6. IN CASE OF SIMULTANEOUS OPERATION SYSTEM, CONNECTION QUANTITY OF THE INDOOR UNITS VARIES ACCORDING
TO THE CONNECTION OUTDOOR UNIT, CONFIRM TECHNICAL GUIDE AND CATALOG, ETC. BEFORE CONNECTING.
7. IN CASE OF MAIN/SUB CHANGEOVER.
SEE THE INSTALLATION MANUAL ATTACHED TO REMOTE CONTROLLER.
8. SYMBOLS SHOW AS FOLLOWS: BLK: BLACK RED: RED BLU: BLUE WHT: WHITE YLW: YELLOW GRN: GREEN
ORG: ORANGE BRN: BROWN.
9. SHOWS ONLY IN CASE OF PROTECTED PIPING. USE H07RN-F IN CASE OF NO PROTECTION.
3D079559-1E FHQ35 • 50 • 60 • 71 • 100 • 125 • 140CAVEB, FHQ140CAVEA

Fig. 40

English
EDMT281426

Installation of indoor / outdoor unit


3P368557-1
EDMT281426 Installation of indoor unit

2.4 FAQ71CVEA / FAQ100CVEA


2.4.1 Names and functions of parts

3PN16549-3B

Installation of indoor / outdoor unit 235


Installation of indoor unit EDMT281426

2.4.2 Installation

FAQ71CVEA
FAQ100CVEA SPLIT SYSTEM Air Conditioner Installation manual
FAQ100CVEA4

CONTENTS
1. SAFETY PRECAUTIONS.....................................................................................1
2. BEFORE INSTALLATION ....................................................................................4
3. SELECTING INSTALLATION SITE......................................................................6
4. PREPARATION BEFORE INSTALLATION..........................................................7
5. INDOOR UNIT INSTALLATION ...........................................................................8
6. REFRIGERANT PIPING WORK.........................................................................11
7. DRAIN PIPING WORK .......................................................................................13
8. ELECTRIC WIRING WORK ...............................................................................15
9. HOW TO CONNECT WIRINGS AND WIRING EXAMPLE ................................16
10. FIELD SETTING .................................................................................................20
11. TEST OPERATION ............................................................................................24
12. WIRING DIAGRAM.............................................................................................28

1. SAFETY PRECAUTIONS
Please read these “SAFETY PRECAUTIONS” carefully before installing air conditioning unit and be
sure to install it correctly. After completing the installation, make sure that the unit operates properly
during the start-up operation.
This air conditioner comes under the term “appliances not accessible to the general public”.
Please instruct the customer on how to operate the unit and keep it maintained.
Also, inform customers that they should store this installation manual along with the operation manual for
future reference.
Meaning of WARNING and CAUTION notices.
Both are important notices for safety. Be sure to follow them.

WARNING ...........Failure to follow these instructions properly may result in personal injury or loss of life.

CAUTION ........... Failure to observe these instructions properly may result in property damage or
personal injury, which may be serious depending on the circumstances.
After completing installation, conduct a trial operation to check for faults and explain to the customer
how to operate the air conditioner and take care of it with the aid of operation manual. Ask the customer
to store the installation manual along with the operation manual for future reference.
WARNING
t Ask your dealer or qualified personnel to carry out installation work.
Do not attempt to install the air conditioner yourself. Improper installation may result in water leakage,
electric shocks or fire.
t Install the air conditioner in accordance with the instructions in this installation manual.
Improper installation may result in water leakage, electric shocks or fire.
t Consult your local dealer regarding what to do in case of refrigerant leakage, when the air coditioner is to
be installed in a small room, it is necessary to take proper measures so that the amount of any leaked
refrigerant does not exceed the concentration limit in the event of leakage. Otherwise, this may lead to
an accident due to oxygen depletion.
t Be sure to use only the specified accessories and parts for installation work.
Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire.

1
3PN16550-3B

236 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN16550-3B

Installation of indoor / outdoor unit 237


Installation of indoor unit EDMT281426

3PN16550-3B

238 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN16550-3B

Installation of indoor / outdoor unit 239


Installation of indoor unit EDMT281426

3PN16550-3B

240 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN16550-3B

Installation of indoor / outdoor unit 241


Installation of indoor unit EDMT281426

3PN16550-3B

242 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN16550-3B

Installation of indoor / outdoor unit 243


Installation of indoor unit EDMT281426

3PN16550-3B

244 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN16550-3B

Installation of indoor / outdoor unit 245


Installation of indoor unit EDMT281426

3PN16550-3B

246 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

Table 2
Pipe size Tightening torque (N·m) Flare dimensions A (mm) Flare

0
45 ±2
I 9.5 (3/8”) 32.7-39.9 12.8 – 13.2
2

0
R0.4-0.8

0
90 ±2
0

A
I15.9 (5/8”) 61.8-75.4 19.3 – 19.7

t Refer to “Table 2” to determine the proper tightening torque.


CAUTION
t Overtightening may damage the flare and cause a refrigerant leakage.

When you do not have a torque wrench, use Table 2 as a rule of thumb
When you keep on tightening the flare nut with a spanner, there is a point where the tightening torque sud-
denly increases.
From that point, further tighten and turn the flare nut the angle shown below. (Refer to Table 3)
After the work is finished, make sure to check that there is no leak.
Unless you tighten as instructed, (if it is loosely tightened), it may lead to the refrigerant leakage (slow
leak) and cause malfunction of the device (such as insufficient cooling or heating).
Table 3
Pipe size Further tightening angle Recommended arm length of tool
I 9.5 (3/8”) 60 to 90 degrees Approx. 200mm
I15.9 (5/8”) 30 to 60 degrees Approx. 300mm

CAUTION
t Be sure to insulate any field piping all the way to the piping connection inside the unit.
Any exposed piping may cause condensation or burns if touched.
t After leakage check of piping connection is finished, carry out thermal insulation with the supplementary
piping insulation tubing and insulating tape (3). The insulating tape (3) should be wrapped from the L-
shaped bend all the way to the end inside the unit. (Refer to Fig. 15)

Indoor unit piping insulation tubing

Clamp large (accessory) (4) Insulating tubing tape


Insulating tubing tape
Insulating tubing tape
Local piping

L-shaped
bend Insulation tubing seam

Attach the insulation tubing


Insulating tape (accessory) (3) tape so that there are no gaps
Indoor unit piping in the insulation tubing seam.
Refer to “ 5.INDOOR UNIT
INSTALLATION ” Start wrapping
Indoor unit piping insulation tubing Fig. 15
t When brazing the refrigerant piping, only begin brazing after having carried out nitrogen substitution
(NOTE 1) or while inserting nitrogen into the refrigerant piping (NOTE 2). Once this is completed, connect
the indoor unit with flares.

12
3PN16550-3B

Installation of indoor / outdoor unit 247


Installation of indoor unit EDMT281426

3PN16550-3B

248 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN16550-3B

Installation of indoor / outdoor unit 249


Installation of indoor unit EDMT281426

3PN16550-3B

250 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN16550-3B

Installation of indoor / outdoor unit 251


Installation of indoor unit EDMT281426

3PN16550-3B

252 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

9-2 WIRING EXAMPLE


CAUTION
t Be sure to install an earth leakage breaker to the outdoor unit.
This is to avoid electric shocks or fire.
2
For the wiring of outdoor units, refer to the installation manual attached to the outdoor units.
Confirm the system type.
t Pair type: 1 remote controller controls 1 indoor unit (standard system). (Refer to Fig. 24)
t Simultaneous operation system: 1 remote controller controls 2 indoor units
(2 indoor units operates equally.) (Refer to Fig. 25)
t Group control: 1 remote controller controls up to 16 indoor units
(All indoor units operate according to the remote controller). (Refer to Fig. 26)
t 2 remote controllers control: 2 remote controllers control 1 indoor unit. (Refer to Fig. 28)

Pair type Simultaneous operation system

Main power supply Main power supply


Earth leakage
Earth leakage circuit breaker
circuit breaker
Outdoor unit
Outdoor unit
1 2 3
1 2 3

NOTE)
NOTE)
1 2 3 1 2 3
1 2 3
P1 P2 P1 P2
P1 P2
Indoor unit (Master)
Indoor unit Remote Indoor unit (slave)
Remote controller P1 P2
P1 P2 controller
(Optional accessories) (Optional accessories)
Fig. 24 Fig. 25

Group control
Main power supply Main power supply Main power supply
Earth leakage Earth leakage Earth leakage
circuit breaker circuit breaker circuit breaker

Outdoor unit Outdoor unit Outdoor unit


1 2 3 1 2 3 1 2 3

NOTE) NOTE) NOTE)


1 2 3 1 2 3 1 2 3
P1 P2 P1 P2 P1 P2

Indoor unit Indoor unit Indoor unit


(Master) P1 P2
Group control remote controller
(Optional accessories)
Fig. 26

NOTE
t Terminal numbers of outdoor and indoor units must agree.

18
3PN16550-3B

Installation of indoor / outdoor unit 253


Installation of indoor unit EDMT281426

3PN16550-3B

254 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN16550-3B

Installation of indoor / outdoor unit 255


Installation of indoor unit EDMT281426

3PN16550-3B

256 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN16550-3B

Installation of indoor / outdoor unit 257


Installation of indoor unit EDMT281426

3PN16550-3B

258 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

11. TEST OPERATION


¢Complete all the “1. Items to be checked after completion of work” on page 5. Please also refer to the
installation manual provided with the indoor unit.²
The settings of the BRC1E model remote controller should be switched while referring to the manual supplied
with the remote controller.
2
The settings of the other remote controller should be switched in accordance with the following procedure.
t Make sure that the installation work for the indoor and outdoor units is all completed.
t Make sure that the following items are all closed: the control box lid of the indoor unit and the outer board
and piping cover of the outdoor unit.
t After completing the refrigerant piping, drain piping, and electrical wiring, clean the interior of the indoor unit
and front panel. Next, perform test operation in accordance with the installation manual supplied with the
outdoor unit in order to protect the unit.
(It is recommended that the test operation is performed in the presence of qualified electrical technician or
engineer.)
t If interior work is still unfinished when test operation finishes, explain to the customer that the air conditioner
must not be operated until interior work is completed in order to protect the indoor units.
(If the unit is operated under this condition, paint, glue, and other materials used during the interior finishing
work will contaminate the indoor unit. This may cause water splashes or leakage.)
t If a malfunction occurs and the unit cannot operate, refer to “11-1 HOW TO DIAGNOSE FOR PROB-
LEMS”.
t After completing the test run, press the INSPECTION/TEST OPERATION button once to put the unit in
inspection mode, and make sure the malfunction code is “00” (= normal).
If the code reads anything other than “00”, refer to “11-1 HOW TO DIAGNOSE FOR PROBLEMS”.
t Press the INSPECTION/TEST OPERATION button four times to return to normal operation mode.
[Mode switching]
Once
Normal operating mode Test operation mode
Once

On
(Press
Once

Once *

ce
4 seconds
or more) * *

Field setting “Malfunction code” “Indoor unit type “Outdoor unit type
display Once code” display Once code” display
* After leaving 10 seconds
or more, the mode returns
Inspection mode
to the normal operating
mode. Fig. 32

11-1 HOW TO DIAGNOSE FOR PROBLEMS


With the power on. Troubles can be monitored on the remote controller.
The fault diagnosis for the BRC1E model remote controller should be performed while referring to the
installation manual supplied with the remote controller. For the other remote controllers, perform the fault
diagnosis using the following procedure.
Trouble shooting with the remote controller liquid crystal display.
1. With the wired remote controller. (NOTE 1)
When the operation stops due to trouble, the operation lamp flashes, and the liquid crystal display
indicates “ ” and the malfunction code. Diagnosis can be carried out using the malfunction code
list according to the indicated malfunction code.
In addition, when in group control it indicates the unit No., so the malfunction detected unit No. will
be clarified. For resetting the malfunction, see (NOTE 2).
2. With the wireless remote controller.
(Also refer to the operation manual attached to the wireless remote controller)

24
3PN16550-3B

Installation of indoor / outdoor unit 259


Installation of indoor unit EDMT281426

3PN16550-3B

260 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN16550-3B

Installation of indoor / outdoor unit 261


Installation of indoor unit EDMT281426

3PN16550-3B

262 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN16550-3B

Installation of indoor / outdoor unit 263


264
INDOOR UNIT
A1P PRINTED CIRCUIT BOARD 10
C105 CAPACITOR WIRING DIAGRAM
HAP FLASHING LAMP
(SERVICE MONITOR GREEN)
M1F MOTOR (INDOOR FAN)
M1S MOTOR (SWING FLAP)
Installation of indoor unit

M2S MOTOR (SWING FLAP)


R1T THERMISTOR (AIR)
R2T·R3T THERMISTOR (COIL)
SS1 SELECTOR SWITCH
(EMERGENCY)
V1R DIODE BRIDGE
X1M TERMINAL BLOCK
(REMOTE CONTROLLER)
X2M TERMINAL BLOCK 1 11
(TRANSMISSION WIRING) 3
Z1C FERRITE CORE 2 12 13
(NOISE FILTER)
Z1F NOISE FILTER
PS SWITCHING POWER SUPPLY
RC SIGNAL RECEIVER CIRCUIT
TC SIGNAL TRANSMISSION
CIRCUIT
4 5
WIRELESS REMOTE CONTROLLER
(RECEIVER/DISPLAY UNIT)
A2P PRINTED CIRCUIT BOARD 6 7 7 14
A3P PRINTED CIRCUIT BOARD
15
BS1 PUSH BUTTON SWITCH (ON/OFF)
H1P PILOT LAMP 1
(ON-RED)
H2P PILOT LAMP
(TIMER-GREEN)
H3P PILOT LAMP 8
(FILTER SIGN-RED)
H4P PILOT LAMP
(DEFROST-ORANGE) 9
SS1 SELECTOR SWITCH
(MAIN/SUB) NOTES
SS2 SELECTOR SWITCH 1. : TERMINAL BLOCK : CONNECTOR : SHORT CIRCUIT CONNECTOR
(WIRELESS ADDRESS SET) 2. : FIELD WIRING
WIRED REMOTE CONTROLLER 16 17
3. IN CASE OF SIMULTANEOUS OPERATION INDOOR UNIT SYSTEM, SEE THE INDOOR UNIT WIRING ONLY.
R1T THERMISTOR (AIR) 18
4. FOR THE DETAIL, SEE WIRING DIAGRAM ATTACHED TO OUTDOOR UNIT.
CONNECTOR FOR OPTIONAL PARTS
X15A CONNECTOR 5. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL.
(FLOAT SWITCH) 6. IN CASE OF CONNECTION UNITS VARIES ACCORDING TO THE COMBINATION SYSTEM, CONFIRM ENGINEERING GUIDE AND CATALOGS, ETC. BEFORE
X24A CONNECTOR (WIRELESS CONNECTING.
REMOTE CONTROLLER) 7. IN CASE OF MAIN/SUB CHANGEOVER, SEE THE INSTALLATION MANUAL ATTACHED TO REMOTE CONTROLLER.
X35A CONNECTOR (POWER 8. M2S IS 100 ONLY.
SUPPLY FOR ADAPTOR) 9. SYMBOLS SHOWS AS FOLLOWS : BLK: BLACK RED: RED BLU: BLUE WHT: WHITE PNK: PINK YLW:YELLOW GRY: GRAY GRN: GREEN ORG: ORANGE
BRN: BROWN.
10. SHOWS ONLY IN CASE OF PROTECTED PIPES. USE H07RN-F IN CASE OF NO PROTECTION.

Fig. 33
3D090000-1B FAQ71·100CVEA, FAQ100CVEA4

29
EDMT281426

Installation of indoor / outdoor unit


3PN16550-3B
EDMT281426 Installation of indoor unit

2.5 FBQ71DBVEA / FBQ100DBVEA / FBQ125DBVEA / FBQ140DBVEA


2.5.1 Names and Functions of Parts

g q i a j k l m

2
2 Fan Model

f e n d

b
1 Fan Model
d
h
e

3PN11586-1E

Installation of indoor / outdoor unit 265


Installation of indoor unit EDMT281426

2.5.2 Installation

3PN11585-1J

266 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN11585-1J

Installation of indoor / outdoor unit 267


Installation of indoor unit EDMT281426

3PN11585-1J

268 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN11585-1J

Installation of indoor / outdoor unit 269


Installation of indoor unit EDMT281426

3PN11585-1J

270 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN11585-1J

Installation of indoor / outdoor unit 271


Installation of indoor unit EDMT281426

3PN11585-1J

272 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN11585-1J

Installation of indoor / outdoor unit 273


Installation of indoor unit EDMT281426

3PN11585-1J

274 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN11585-1J

Installation of indoor / outdoor unit 275


Installation of indoor unit EDMT281426

3PN11585-1J

276 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN11585-1J

Installation of indoor / outdoor unit 277


Installation of indoor unit EDMT281426

3PN11585-1J

278 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN11585-1J

Installation of indoor / outdoor unit 279


Installation of indoor unit EDMT281426

3PN11585-1J

280 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN11585-1J

Installation of indoor / outdoor unit 281


Installation of indoor unit EDMT281426

3PN11585-1J

282 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN11585-1J

Installation of indoor / outdoor unit 283


Installation of indoor unit EDMT281426

3PN11585-1J

284 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN11585-1J

Installation of indoor / outdoor unit 285


Installation of indoor unit EDMT281426

3PN11585-1J

286 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN11585-1J

Installation of indoor / outdoor unit 287


Installation of indoor unit EDMT281426

3PN11585-1J

288 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN11585-1J

Installation of indoor / outdoor unit 289


Installation of indoor unit EDMT281426

3PN11585-1J

290 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3PN11585-1J

Installation of indoor / outdoor unit 291


Installation of indoor unit EDMT281426

2.6 FVQ50CVE / FVQ60CVE


2.6.1 Names and functions of parts
a
e

h
g

In case of b

RZQ50·60 d
c

d j

f
k e

a  

b
  

       


            
 
           
c  

d  

e !"  

f #  

h
"  "    "  
i    "

j ! "

# 
k
  "
l $"  "      

C: 3P365702-1

292 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

2.6.2 Installation

FVQ50CVE
FVQ60CVE SPLIT SYSTEM Air Conditioner Installation manual

CONTENTS
2
1. SAFETY PRECAUTIONS.....................................................................................1
2. BEFORE INSTALLATION ....................................................................................3
3. SELECTING INSTALLATION SITE......................................................................5
4. INDOOR UNIT INSTALLATION ...........................................................................6
5. REFRIGERANT PIPING WORK...........................................................................8
6. DRAIN PIPING WORK .......................................................................................11
7. WHEN THE OPTIONAL REMOTE CONTROLLER (BRC1E model)
IS USED AS A CONTROL PANEL.....................................................................12
8. ELECTRIC WIRING WORK ...............................................................................16
9. HOW TO CONNECT WIRING AND WIRING EXAMPLE...................................17
10. INSTALLATION OF SUCTION GRILLE .............................................................22
11. FIELD SETTING .................................................................................................23
12. TEST OPERATION ............................................................................................24
13. WIRING DIAGRAM.............................................................................................29

1. SAFETY PRECAUTIONS
Be sure to follow this “SAFETY PRECAUTIONS”.

This manual classifies the precautions into WARNINGS and CAUTIONS.


Be sure to follow all the precautions below: They are all important for ensuring safety.

WARNING .......... Indicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION ........... Indicates a potentially hazardous situation which, if not avoided, may result in
minor or moderate injury.
It may also be used to alert against unsafe practices.
• After the installation is completed, test the air conditioner and check if the air conditioner operates properly.
Give the user adequate instructions concerning the use and cleaning of the indoor unit according to the
Operation Manual.
Ask the user to keep this manual and the Operation Manual together in a handy place for future reference.
WARNING
• Ask your local dealer or qualified personnel to carry out installation work.
Improper installation may result in water leakage, electric shocks or a fire.
• Perform installation work in accordance with this installation manual.
Improper installation may result in water leakage, electric shocks or a fire.
• Consult your local dealer regarding what to do in case of refrigerant leakage.
When the air conditioner is installed in a small room, it is necessary to take proper measures so that the
amount of any leaked refrigerant does not exceed the concentration limit in the event of a leakage.
Otherwise, this may lead to an accident due to oxygen deficiency.

1 English
3P365703-1

Installation of indoor / outdoor unit 293


Installation of indoor unit EDMT281426

• Be sure to use only the specified parts and accessories for installation work.
Failure to use the specified parts may result in the air conditioner falling down, water leakage, electric
shocks, a fire, etc.
• Install the air conditioner on a foundation that can withstand its mass.
Insufficient strength may result in the air conditioner falling over and causing injury.
In addition, it may lead to vibration of indoor units and cause unpleasant chattering noise.
• Carry out the specified installation work in consideration of strong winds, typhoons, or earthquakes.
Improper installation may result in an accident such as air conditioner falling.
• Make sure that all electrical work is carried out by qualified personnel according to the applicable legislation
(note 1) and this installation manual, using a separate circuit.
In addition, even if the wiring is short, make sure to use a wiring that has sufficient length and never connect
additional wiring to make the length sufficient.
Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric
shocks or a fire.
(note 1) applicable legislation means “All international, national and local directives, laws, regulations and/
or codes which are relevant and applicable for a certain product or domain”.
• Earth the air conditioner.
Do not connect the earth wiring to gas or water piping, lightning conductor or telephone earth wiring.
Incomplete earthing may cause electric shocks or a fire.
• Be sure to install an earth leakage circuit breaker.
Failure to do so may cause electric shocks and a fire.
• Disconnect the power supply before touching the electric components.
If you touch the live part, you may get an electric shock.
• Make sure that all wiring is secure, using the specified wiring and ensuring that external forces do not act
on the terminal connections or wiring.
Incomplete connection or fixing may cause an overheat or a fire.
• When wiring between the indoor and outdoor units, and wiring the power supply, form the wiring orderly so
that the control box lid can be securely fastened.
If the control box lid is not in place, overheat of the terminals, electric shocks or a fire may be caused.
• If refrigerant gas leaks during installation work, ventilate the area immediately.
Toxic gas may be produced if refrigerant gas comes into contact with a fire.
• After completing the installation work, check to make sure that there is no leakage of refrigerant gas.
Toxic gas may be produced if refrigerant gas leaks into the room and comes into contact with a source of
a fire, such as a fan heater, stove or cooker.
• Never directly touch any accidental leaking refrigerant. This could result in severe wounds caused by frostbite.

CAUTION
• Install drain piping according to this installation manual to ensure good drainage, and insulate the piping to
prevent condensation.
Improper drain piping may cause water leakage, make the furniture get wet.
• Install the air conditioner, power supply wiring, remote controller wiring and transmission wiring at least 1
meter away from televisions or radios to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not be sufficient to eliminate the noise.)
• Install the indoor unit as far as possible from fluorescent lamps.
If a wireless remote controller kit is installed, the transmission distance may be shorter in a room where an
electronic lighting type (inverter or rapid start type) fluorescent lamp is installed.
• Do not install the air conditioner in places such as the following:
1. Where there is mist of oil, oil spray or vapour for example a kitchen.
Resin parts may deteriorate, and cause them to fall out or water to leak.
2. Where corrosive gas, such as sulfurous acid gas, is produced.
Corrosion of copper pipings or brazed parts may cause the refrigerant to leak.
3. Where there is machinery which emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
4. Where flammable gases may leak, where carbon fibre or ignitable dust is suspended in the air or where
volatile flammables, such as thinner or gasoline, are handled.
If the gas leaks and remains around the air conditioner, it may cause ignition.

English 2
3P365703-1

294 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

2. BEFORE INSTALLATION
Do not exert pressure on the resin parts when opening the unit or when moving it after opening.
Be sure to check in advance that the refrigerant to be used for installation is R410A. (If a wrong
refrigerant is charged, the unit will not properly operate)
• For the installation of an outdoor unit, refer to the installation manual attached to the outdoor unit.
2
• Do not dispose of any parts necessary for installation until the installation is completed.
• Decide the route for carrying the unit to the installation site.
• When hanging the unit for lifting, use a sling of soft material (made of cloth, nylon, etc.) as shown below. (Refer to Fig. 1)
(1) Horizontal hanging (2) Vertical hanging
Sling
Sling

Apply cloth or corrugated


cardboard so that the air
discharge grille and air inlet
*Be sure that the sling grille will not be damaged.
does not slide.

Fig. 1

2-1 PRECAUTIONS
• When selecting installation site, refer to the paper pattern (part of packaging material).
• Do not use the unit in locations where the salt content in the air is high such as beachfront, or where the
voltage fluctuates such as factories, or where the base vibrates such as automobiles or marine vessels.
• Before opening the control box lid and performing the wiring operation, remove the static electricity charged
to your body. Otherwise, electrical parts may be damaged.

2-2 ACCESSORIES
Check the following accessories are included with the unit.
Do not dispose of any parts necessary for installation until the installation is completed.
(3) Hole protection
Name (1) Bracket for installation (4) Bush Insulation for fitting
rubber
Quantity 1 set *1) 2 pcs. 1 pc. 1 each
(5) For gas pipe

Shape

(2) Screw (M4 × 10), 1 pc. (6) For liquid pipe

(10) Dew proof


Name (7) Cover (8) Clamp (9) Installation pattern
material
Quantity 1 pc. *2) 5 pcs. 1 pc. 1 pc.

Also used as a
packaging material

Shape

3 English
3P365703-1

Installation of indoor / outdoor unit 295


Installation of indoor unit EDMT281426

(11) Screws (12) Screws (13) Remote (Other)


Name
(M4 × 10) (M5 × 12) controller wiring • Operation manual
Quantity 3 pcs. *2) 2 pcs. 1 pc. *2) • Installation manual
*1) The bracket for installation
is screwed onto the main
unit (top plate).
Shape *2) These parts are used
when the remote
controller is installed in
the main unit.

2-3 OPTIONAL ACCESSORIES


• The optional remote controller is required for this indoor unit.
• Select a remote controller from Table 1 according to customer request and install in an appropriate place.
(For installation, follow the installation manual included with the remote controllers.)
Table 1
Remote controller
Wired type BRC1E62/BRC1C61

NOTE
• If the customer wishes to use a remote controller that is not listed above, select a suitable remote
controller after consulting catalogs and technical guide.

FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND
CHECK AFTER INSTALLATION IS FINISHED.
1. Items to be checked after completion of work
Items to be checked If not properly done, what is likely to occur Check
Are the indoor unit and outdoor unit fixed
The unit may drop, vibrate or make noise.
firmly?
Is the installation of the indoor unit and the The unit may malfunction or the components
outdoor unit completed? may burn out.
Is the gas leakage checked with the
leakage test pressure written in the
It may result in insufficient cooling or heating.
installation manual supplied with the
outdoor unit?
Is the unit fully insulated? (Refrigerant
Condensate water may drip.
piping, drain piping)
Does drainage flow smoothly? Condensate water may drip.
Does the power supply voltage correspond The unit may malfunction or the components
to that shown on the name plate? may burn out.
The unit may malfunction or the components
Are wiring and piping correct?
may burn out.
Is the unit safely grounded? It may result in electric shock.
The unit may malfunction or the components
Is wiring size according to specifications?
may burn out.
It may result in insufficient cooling or heating.
Is something blocking the air outlet or inlet
(This can lead to malfunction or decreased
of either the indoor or outdoor units?
performance due to decreased air volume.)
Are refrigerant piping length and additional
The refrigerant charge in the system is not clear.
refrigerant charge noted down?

English 4
3P365703-1

296 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

2. Items to be checked at time of delivery to customer.


* Also review the ‘‘1. SAFETY PRECAUTIONS’’
Items to be checked Check
Has the field setting done (as necessary)?
Did you attach the control box lid, the air filter, and suction grille?
2
Does the cold air (warm air) blow properly during the cooling (heating) operation?
Did you explain about operations while showing the operation manual to your customer?
Did you explain the cooling, heating, dry, and automatic cooling/heating operations described in
the operation manual?
Did you explain what the set airflow rate is when setting the airflow rate at thermostat OFF to
the customer?
Is the emergency switch (EMG.) of the printed circuit board turned ON? At delivery from the
factory, it is set to normal (NORM).
Is the suction thermistor installed at its original position (bell mouth) when the optional adapter
installation box is installed?
Did you hand the operation manual over to your customer? (Please hand over the installation
manual as well.)

Points for explanation about operations

Since the items with WARNING and CAUTION marks in the operation manual, if not
observed, may cause injuries and/or material damages. Therefore, in addition to the general usage,
it is necessary to explain them to the customer and also to ask the customers to thoroughly read
them. Accordingly, it is necessary that you make a full explanation about the described contents
and also ask your customers to read the operation manual.

2-4 NOTE TO THE INSTALLER


Be sure to instruct customers how to properly operate (especially cleaning filters, operating different
functions, and adjusting the temperature) by having them carry out operations by themselves while reading
the manual literally.

3. SELECTING INSTALLATION SITE


Do not exert pressure on the resin parts when opening the unit or when moving it after opening.
(1) Select an installation site where the following conditions are fulfilled and that meets with your cus-
tomer’s approval.
• Where optimum air distribution can be ensured.
• Where the floor is strong enough to withstand the
weight and vibration of the indoor unit.
• Make sure the floor is level. (Vibration and abnormal
noise may be generated.)
• Where nothing blocks the air inlet and outlet, and
where sufficient clearance for maintenance and
service can be ensured. (Refer to Fig.2) Main unit
(If not ensured, the capacity may drop due to short
circuit.) 50mm 50mm
• Where condensate can be properly drained. or more or more
• Where piping between indoor and outdoor units is
possible within the allowable limit. (Refer to the
Fig. 2
installation manual for the outdoor unit.)
• Where there is no risk of flammable gas leakage.
(2) Install the indoor and outdoor units, power cord and connecting wires at least 1 meter away from
televisions or radios to prevent picture interference and noise.
(Depending on the incoming signal strength, a distance of 1 meter may not be sufficient to elimi-
nate noise.)

5 English
3P365703-1

Installation of indoor / outdoor unit 297


Installation of indoor unit EDMT281426

(3) Investigate whether the installation location (such as the floor and wall) can withstand the weight
of the unit and, if necessary, reinforce the location with such as beams before installation. To avoid
vibration and abnormal noise, reinforce the location before installation.

4. INDOOR UNIT INSTALLATION


As for the parts to be used for installation, be sure to use the attached accessories and the specified parts.
¢Fixing procedure²
• Since the indoor unit is vertically tall, take measures to prevent the unit from falling down according to the
following method.

1. Raise the grille fixture.

Grille fixture

Fig. 3

2. Detach the suction grille.


Remove the screws (R & L, total 2) locking the grille stopper. Then, (1) tilt the grille forward, and (2) lift
upward.

M4 × 12
Tapping screws (class 2)
Front panel (2)

(1)

Grille fixture
Grille stopper
Suction grille

Fig. 4

English 6
3P365703-1

298 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3. For normal installation.


Remove the screw (2) fixing the bracket for installation (1) to the top panel. Change the mounting
direction of the bracket as shown in the figure below and fix it to the top panel with the attached screws
(12). Then, fix the bracket to the wall with the appropriate screws (field supply).
• Screws (2) are not used. 2
Screw (2) (accessory)
not necessary
Screw (12) (accessory)
Fixing screw
Bracket for installation (1) (accessory)

Bracket for 2-7 × 15 slot


installation (1) 330 (Screw hole for
(accessory) securing to the
wall) Prepare the
screws that match

18
the wall material as
field supply.
Fig. 5 • Unit [mm]

4. When installing the unit to a place where strength to earthquake is required.


In addition to the fixing method shown left, fix the bottom frame to the foundation with the anchor bolts
(field supply). Four holes for anchor bolts are prepared on the bottom plate.
• Use the locations indicated on the installation pattern (9) (part of packing material).
260
4 - φ14 hole, Depth: 30

57
130
(For locking with bolt)

144
• Unit [mm]
Front

Fixing holes (× 4)
Bottom frame
Fig. 6

5. Remove the cushion materials of the fan.


It may cause malfunction when operating while installed the cushion materials of the fan. (4 places)

Cushion materials

Fan

Fig. 7

7 English
3P365703-1

Installation of indoor / outdoor unit 299


Installation of indoor unit EDMT281426

5. REFRIGERANT PIPING WORK


¢For refrigerant piping of outdoor units, see the installation manual attached to the outdoor unit.²
¢Make sure to carry out thermal insulation in both gas and liquid piping. Incomplete insulation may
result in water leakage. Thermal resistance of the insulation for gas piping must be 120°C or higher.
In a high humidity environment, strengthen the refrigerant piping insulation. If insulation is
insufficient, condensation may form on the insulation surface.
Be sure to check that the refrigerant is R410A before starting the job. (If a different refrigerant is used,
a normal operation cannot be carried out.)²
CAUTION
This product is a dedicated model for new refrigerant (R410A). At installation, make sure to observe the
following precaution.
• For flare connection, use dedicated pipe cutter and flaring tools for R410A.
• Apply ester oil or ether oil to the inside of the flare section before connecting.
• Use the flare nuts provided with the unit. Do not use a class 1 flare nut.
Otherwise the refrigerant may leak.
• To prevent dust, moisture or other foreign matters from getting into the tube, either pinch the tube end or
cover the end with tape.
• Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit, such
as air, etc. If any refrigerant gas leaks while working on the unit, ventilate the room thoroughly right away.
• The outdoor unit is charged with refrigerant.
• The refrigerant piping can be taken out from the following side of Torque wrench
the unit.
Left side, Right side, Back side, Bottom side
You must decide from which side you intend to take out the
refrigerant piping. Spanner
• Be sure to use both a spanner and a torque wrench together as
shown in the drawing, when connecting or disconnecting pipes Pipe union
to/from the unit. (Refer to Fig. 8)
* Using a tool other than a spanner can damage the head of the Flare nut Fig. 8
flare nut, and gas leakage can occur due to tightening failure.
• Refer to “Table 2” for the dimensions for flaring.
Apply ester or ether oil to this face.
• When connecting the flare nut, apply ester oil or ether oil to the
inside of flared section, and turn the nut spin 3-4 times by hand
before screwing in. (Refer to Fig. 9)

CAUTION Fig. 9
Be careful not to damage the flare section.

Table 2
Pipe size Tightening torque Flare dimensions A (mm) Flare

I9.5 (3/8”) 36.3 ± 3.6 N·m 12.8 - 13.2 R0.4-0.8


45°±2°
90°± 2°

I15.9 (5/8”) 68.6 - 6.8 N·m 19.3 - 19.7

• Refer to “Table 2” to determine the proper tightening torque.

CAUTION
Overtightening may damage the flare and cause a refrigerant leakage.

English 8
3P365703-1

300 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

When you do not have a torque wrench, use Table 2 as a rule of thumb.
When you keep on tightening the flare nut with a spanner, there is a point where the tightening torque
suddenly increases.
From that point, further tighten and turn the flare nut the angle shown below. (Refer to Table 3)
After the work is finished, make sure to check that there is no leak.
2
Unless you tighten as instructed, (if it is loosely tightened), it may lead to the refrigerant leakage (slow
leak) and cause malfunction of the device (such as insufficient cooling or heating).
Table 3
Pipe size Further tightening angle Recommended arm length of tool
I9.5 (3/8”) 60° - 90° degrees Approx. 200mm
I15.9 (5/8”) 30° - 60° degrees Approx. 300mm

1. How to carry out refrigerant piping.


• Detach the pipe retainer. (Refer to Fig. 11)

¢ In case of left or right piping ²


1. Open the knock out holes on the right (left) side panel. (Refer to Fig. 10)
2. Carry out piping (refrigerant and drain) and wiring (connecting outdoor and indoor units) through the
holes on the side panel.
(See dimensions shown in Fig. 14 for forming refrigerant piping.)
Knock out holes for piping (Select either one)
(left and right side panels and rear panel)
* Put the attached hole protection rubber (3) ( )
after making the opening.
Through holes for wiring (Select either one)
(left and right side panels)
* Put the attached bush (4) ( ) after making the opening.
Bottom frame Side panel
Fig. 10

¢In case of rear piping ²


1. Open the knock out holes on the rear panel. (Refer to Fig. 13)
2. Carry out piping (refrigerant and drain) and wiring (connecting outdoor and indoor units) through the
holes on the rear panel.
(See dimensions shown in Fig. 14 for forming refrigerant piping.)

CAUTION
In case of rear side piping, be careful not to damage fan motor lead wire.
When opening the knock out hole, be careful not to damage fan motor lead wire with the steel plate cut off.
(Refer to Fig. 15).

¢In case of downward piping ²


1. Cut holes in the indicated area of the bottom frame. (Refer to Fig. 13)
2. Carry out piping (refrigerant and drain) and wiring (connecting outdoor and indoor units) through the
holes on the bottom frame.

CAUTION
Be careful not to damage fan housing when piping.
Fan housing is made of foamed polystyrene.
Be careful not to damage the fan housing with pipe edge when installing indoor unit.

9 English
3P365703-1

Installation of indoor / outdoor unit 301


Installation of indoor unit EDMT281426

Fan motor
lead wire Insulation for fitting (5)(6)
(accessory)
Fix using the
clamp (8) • Unit [mm]
Right or left piping Backward piping

525
525

450
450
Fig. 12
Pipe retainer Fig. 14

Fig. 11
Fan motor
lead wire
Drain hose
inside the unit
Fan housing

Rear panel
Knock out holes
(Select either one)
Rear plate
* Put the
attached hole
protection
rubber (3)
( ) Knock out holes
after making
the opening. Bottom frame Fig. 15

Cut holes here.


Fig. 13
• After the refrigerant piping and electrical wiring work is completed, hold the refrigerant piping, the
indoor unit drain hose, the wiring connecting the indoor and outdoor units and the earth wire with the
piping retainer plate (Refer to Fig. 11). During this work the refrigerant piping entering into the indoor
unit may come in contact with the suction grille. Therefore, make sure not to extend the refrigerant
piping from the piping retainer plate.
(For electrical wiring work, see “8. ELECTRIC WIRING WORK”.)
• After leakage check of piping connection is finished, carry out thermal insulation. (Refer to Fig. 12)
• Carry out thermal insulation of both liquid and gas pipes with the attached insulation for fitting (5) and
(6). (Tighten both ends of the insulation for fitting (5) and (6) with the clamp (8).

CAUTION
Be sure to insulate any field piping all the way to the piping connection inside the unit.
Any exposed piping may cause condensation or burns if touched, and also electrical shock or fire if the
wiring is touched.

CAUTION
• CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING
• Do not braze inside the unit.
Since the bottom plate and the fan housing are made of resin. They may melt or cause fire by spatter.

English 10
3P365703-1

302 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

• Braze the refrigerant piping only after having nitrogen flow through the pipe and substituting nitrogen for air
(Refer to Fig. 16). Once this is completed, connect the indoor unit with flares (Refer to Fig. 12).
1. When brazing after having nitrogen flow through the pipe and substituting nitrogen for air, it is appropriate
to set the nitrogen pressure to about 0.02MPa with a pressure reducing valve. (Refer to Fig. 16)
2. Do not use flux when brazing refrigerant piping. Use the phosphor copper brazing filler metal (BCuP-2: JIS
Z 3264/B-Cu93P-710/795: ISO 3677) that does not require flux.
2
(Chlorine based flux is extremely harmful to refrigerant piping systems. It will corrode the refrigerant piping
and if it contains fluorine it will deteriorate the refrigerating oil.)
3. When performing the leakage test for the indoor unit and inter-unit piping after the indoor unit is installed,
be sure to refer to the installation manual for the indoor unit or technical guide for the leakage test pressure
and the refrigerant piping installation.
4. Shortage of refrigerant due to air purge or forgetting the additional refrigerant charge may cause
malfunction of the unit (does not sufficiently cool or heat).
For installation of refrigerant piping, be sure to refer to the installation manual for the outdoor unit or the
technical guide.

Refrigerant piping Pressure-reducing


Part to be Taping
valve
brazed
Nitrogen
Nitrogen
Hands
Fig. 16 valve

CAUTION
• Do not use anything oxidation inhibitor or the like when brazing. (Residues may cause clogging of pipes or
damage to parts.)

6. DRAIN PIPING WORK

1. Rig the drain piping.


Carry out drain piping to ensure proper drainage. Also, observe the following to prevent leaks.

Indoor unit drain hose

Fan housing
Through-hole for piping

Liquid pipe Bottom frame


Anchor hose here.
Gas pipe
Drain pipe (Procure in field.)
Fig. 17 Vinyl chloride pipe (normal diameter 20mm)

CAUTION
• To avoid force on the drain hose of the indoor unit, make sure to fix the drain pipe such as to bundle it to the
refrigerant pipe as shown in Fig. 17. This is to prevent the drain pipe from coming off and/or avoid bad insulation.
The drain pipe must be sloped downward with a gradient of 1/100 from the drain pipe connection in the unit.
• The drain pipe may be clogged if water accumulates in the drain pipe.
• Condensation on the pipe may occur and cause water leakage. Therefore, make sure to insulate the pipe
at the following two places.
(1) All piping in the room and inside the unit.
(2) At the connection between the indoor unit drain hose and the field drain piping.

11 English
3P365703-1

Installation of indoor / outdoor unit 303


Installation of indoor unit EDMT281426

2. After the piping work is finished, check that drainage flows smoothly and the water
does not leak from connections.
• Carefully pour approximately 1
litre of water through the air Air discharge Heat
discharge outlet so that it falls outlet exchanger
directly onto the heat
exchanger at an angle without
splashing. (Refer to Fig. 18)
* If water is poured too fast or if
water pressure is too high, the
water will pass through the
heat exchanger and drip on
the fan motor below it.
* If water gets on the inner front
wall, it will leak onto the floor.
Fig. 18

CAUTION
• In order to prevent the pets from getting inside the unit, seal the pipe penetration hole with putty or heat
insulating material (field supply).
• Drain piping connections
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the
sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger.

7. WHEN THE OPTIONAL REMOTE CONTROLLER (BRC1E model) IS USED


AS A CONTROL PANEL
(Remote controllers except the optional BRC1E cannot be incorporated
into the main unit.)
• The optional remote controller (BRC1E) can be incorporated into this unit and used as a control panel.

1. Open the remote controller, and connect the remote controller wiring (accessory).
For wiring procedures, refer to the “remote controller installation manual”.
(There is no polarity for the remote controller wiring.)
1) Remove the upper case.
Insert a flathead screwdriver into the concaved portion of the lower case (at 2 positions), and then
remove the upper case.
Upper case

Screwdriver

Lower case
Insert the screwdriver and twist it lightly to
Fig. 19 remove the case.

CAUTION
• The printed circuit board of the remote controller is attached to the upper case. Be careful not to scratch the
board with the screwdriver.
• Be careful not to adhere any dust or liquid to the printed circuit board of the removed upper case.

English 12
3P365703-1

304 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

2) Cut off the shaded part of the lower case, and then fix the case to the cover (7) using screws (11).
Screw (11) (M4)
(Tightening torque : 0.6 ± 0.1N · m)
Shaded part
(accessory)
2

Lower case

Cover (7) Lower case assy


(accessory)
Fig. 20
3) Connect the remote controller wiring (accessory (13)).

Clamp
Remote controller (accessory of the
wiring (13) remote controller)
Fixed part
Upper case
assy
A
Fixed part
A
Upper case Section A-A
Clamp
assy
(accessory of the remote controller)
Remote controller
wiring (13)
(accessory)
Lower case assy
Fig. 21

13 English
3P365703-1

Installation of indoor / outdoor unit 305


Installation of indoor unit EDMT281426

4) Fit and install the upper case in the lower case while aligning the tabs (6 positions) with the lower
case.
• Be careful so that the wiring may not be caught.
• Remove the protection sheet attached to the upper case.
Upper case assy

Remote controller
wiring (13)
(accessory)
Hole Lower case assy

〈Control panel〉

Fig. 22 Tabs (6 positions)

2. Remove the front panel, and then remove the back plate attached to the back side.
• When removing the front panel, to avoid dropping the panel, tightly hold the front panel while removing
it.

Front panel
Wire harness for the
swing motor

Terminal block (X1M: 4P)


Screw (M4)
Screw
(M4) Screw (M4)
Control box lid

Screw (M4)

Front panel

Back plate

Screw (M4)
(6 pcs.)
Fig. 23

English 14
3P365703-1

306 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

NOTE
• If the grille fixture comes off while
Grille fixture
removing the front panel, attach the grille
fixture as shown below. Rib
1. Install the grille fixture while aligning its
notch with the rib of the front panel. Front panel
Rib 2
2. Lower the grille fixture. 1.
2.

Notch
Fig. 24

3. Fix the control panel on the back side of the front panel.
Front panel

Control panel

Screw (M4)
(6 pcs.)
Fig. 25

4. Clip the remote controller wiring into the guide and notch. (Refer to Fig. 26)

Control panel

Front panel

Remote controller wiring (13)


(accessory)

Be sure not to leave


Guide any slack in the remote
controller wiring
between these parts.

Be sure not to leave any slack in the remote


Notch
controller wiring between these parts.

Fig. 26

15 English
3P365703-1

Installation of indoor / outdoor unit 307


Installation of indoor unit EDMT281426

5. Return the front panel to its original installation position.

6. Remove the control box lid, and then connect the remote controller wiring to terminals
P1 and P2 (no polarity) of the terminal block (X1M).

Terminal block (X1M : 4P)

High voltage wires and


earth wire Low voltage wires

P1 P2 F1 F2
P2 Remote controller
P1 wiring (13)
(accessory)

Fig. 27

8. ELECTRIC WIRING WORK

8-1 GENERAL INSTRUCTIONS


• Electric wiring work must be conducted by an electrician authorized by power companies (Only a licensed
electrician is permitted to conduct electric work and earth connections.)
• All wiring must be performed by an authorized electrician.
• A circuit breaker capable of shutting down power supply to the entire system must be installed.
• Be sure to install an earth leakage circuit breaker in the outdoor unit.
(Install the earth leakage circuit breaker to avoid electric shocks and fire.)
• The specified voltage for the wiring between the indoor and outdoor units and between the indoor units is
220-240V.
• Do not turn on the power supply (of the indoor unit) until all the installation work is completed.
• Be sure to earth the air conditioner.
• Refer to the installation manual attached to the outdoor unit for the size of power supply electric wire
connected to the outdoor unit, the capacity of the circuit breaker and switch, and wiring instructions.
• Do not connect the earth wire to gas pipes, plumbing pipes, lightning rods, or telephone earth wires.
• Gas pipes: might cause explosions or fire if gas leaks.
• Plumbing: no earth effect if hard vinyl piping is used.
• Telephone earth wires or lightning rods: might cause abnormally high electric potential in the earth
during lighting storms.
• For electric wiring work, refer also to “WIRING DIAGRAM” attached to the back side of the control box lid.
• Never connect the power supply wire to the terminal block for remote controller wire, or otherwise the entire
system may be damaged.
• For remote controller wiring details, refer to the installation manual attached to the remote controller.
• Do not touch the printed circuit board assy during the wiring work. Otherwise, it may cause damage.

English 16
3P365703-1

308 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

8-2 SPECIFICATIONS FOR FIELD WIRE


For the wiring of the outdoor unit, refer to the installation manual attached to the outdoor unit.
Remote controller and transmission wiring are field supplied. (Refer to Table 4)
Wiring specifications are shown on the condition that the wiring has a voltage drop of 2%.
Table 4 2
2
Wire Size (mm ) Length
H05VV-U4G
Wiring the units 2.5 –
(NOTE 1)
Vinyl cord with sheath or
Remote controller cord 0.75 - 1.25 Max. 500m *
cable (2 wire) (NOTE 2)
*This will be the total extended length in the system when doing group control.
NOTE
1. It shows the case when conduit pipes are used. When the conduit pipes are not used, use H07RN-F.
2. Sheathed vinyl cord or cable (insulation thickness: 1mm or more)

9. HOW TO CONNECT WIRING AND WIRING EXAMPLE

9-1 HOW TO CONNECT WIRING

Earth terminal

Clamp (8)
Power supply (accessory)
terminal block
(X2M:3P)

Wiring the units


Inter unit wire for the indoor and
Earth wire outdoor units and earth wire
Fig. 29
Pipe retainer
Wiring
diagram

Control box lid


Wiring lead-in port
Earth terminal
Outdoor unit Indoor unit
Fig. 28
1 1
1 2 3

2 2
3 3

(Terminal block) (Terminal block)


Align the numbers.
How to connect the inter unit wiring for
the indoor and outdoor units
• Do not perform solder finishing.

17 English
3P365703-1

Installation of indoor / outdoor unit 309


Installation of indoor unit EDMT281426

¢Connecting methods of wiring between indoor and outdoor units, earth wiring, and remote
controller wiring ²
• Detach the control box lid and pipe retainer as shown in the Fig. 28 and connect the wires of matching
numbers to the terminal block (X2M: 3P) on the right side of the unit. Connect the earth wire to the earth
terminal. In doing this, draw the wiring into the unit through the hole for wiring, and fix it together with the
earth wire using the clamp (8).
• Connect the remote controller wiring (field supply) to the terminals P1 and P2 (no polarity) of the terminal
block (X1M: 4P), and guide the wiring to the outside of the unit using the route shown in the Fig. 30.
• Pass the remote controller wiring inside the piping retainer plate.
• Route the low voltage wires (remote controller wiring) 50mm or more away from the high voltage wires
(interconnecting wires between the indoor and outdoor units) and earth wire so that they may not pass
through the same place. (Refer to Fig. 30)

Terminal block
(X1M : 4P)

P1 P2 F1 F2
Terminal block P2
(X2M : 3P) P1
High voltage wires
and earth wire Low voltage wires

Route the low voltage wires through the right side of the
piping to the upper hole on the right (left) side plate.

Route the high voltage wires and earth wire through the left
side of the piping to the lower hole on the right (left) side
Fig. 30 plate while installing the provided bushing (4).
• During the wiring work, lay the electric wiring neatly so that the wires may not push the control box lid up.
Also, fix the lid without sandwiching the wires between the box and the lid.
(Sandwiching electric wires and/or having the lid float up may result in electric shock or fire.)
• Pass the interconnecting wires and the earth wires inside of the pipe pressing plate. Wires connecting the
units and the earth wire to the pipe retainer. Keep the extra wires neatly at a location shown in the Fig. 29.
The wires may come in contact with other parts such as the fan, and the indoor unit may be damaged.
• In order to prevent small creatures getting into the unit, seal the wiring outlet with putty or heat insulating
material (field supply) leaving no clearance. (If small creatures, such as insects, get into the unit, the
creatures may cause short circuiting in the control box.)

CAUTION
Use a round crimp-style terminal for connection to the power supply terminal block. (Refer to Fig. 31)
In case it cannot be used due to unavoidable reasons, be sure to observe the following instructions.
• Do not connect wires of different gauge to the same power supply terminal.
(Looseness in the connection may cause overheating.) (Refer to Fig. 32)
• In wiring, make sure that prescribed wires are used. Also, fix the wires so that external force may not be
applied to the terminals.
• Use an appropriate screwdriver to tighten the terminal screws. Small screwdrivers damage the head of
the screws and they cannot tighten the screws appropriately.

English 18
3P365703-1

310 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

• If the terminal screws are tightened too hard, screws Table 5


might be damaged. Tightening torque (N·m)
• The tightening torque of each terminal screw is shown
Terminal block for remote controller wiring 0.88±0.08
in the Table 5.
Terminal block for wiring between units 1.47±0.14
• When a stranded wire is used, do not perform solder
finishing. Earth terminal 1.47±0.14 2
Connect wires of the Do not connect wires Do not connect wires
Round crimp-style same gauge to both of the same gauge to of different gauges.
terminal side. (GOOD) one side. (WRONG) (WRONG)

Electric wire
Fig. 31 GOOD WRONG WRONG

Fig. 32

9-2 WIRING EXAMPLE


CAUTION
Be sure to install an earth leakage breaker to the outdoor unit.
This is to avoid electric shocks or fire.
For the wiring of outdoor units, refer to the installation manual attached to the outdoor units.
Confirm the system type.
• Pair type: 1 remote controller controls 1 indoor unit (standard system). (Refer to Fig. 33)
• Group control: 1 remote controller controls up to 16 indoor units
(All indoor units operate according to the remote controller). (Refer to Fig. 34)
• 2 remote controllers control: 2 remote controllers control 1 indoor unit. (Refer to Fig. 36)

Pair type
Main power supply
Earth leakage
circuit breaker

1 2 3

Outdoor unit

1 2 3

P 1 P2

Indoor unit

P1 P2

Remote controller
(Optional accessory) Fig. 33

19 English
3P365703-1

Installation of indoor / outdoor unit 311


Installation of indoor unit EDMT281426

Group control
Main power supply
Earth Earth Earth
leakage leakage leakage
circuit circuit circuit
breaker breaker breaker
1 2 3 1 2 3 1 2 3

Outdoor unit Outdoor unit Outdoor unit

1 2 3 1 2 3 1 2 3

P1 P2 P1 P2 P1 P2

Indoor unit Indoor unit Indoor unit


(Master)
P 1 P2 Group control remote controller
(Optional accessory)
Fig. 34
When implementing group control
• When using as a pair unit, you may carry out simultaneous start/stop (group) control up to 16 units with the
remote controller. (Refer to Fig. 35)
• In this case, all the indoor units in the group will operate in accordance with the group control remote controller.
• The body thermo is effective only for the indoor unit to which the remote controller is connected.

Outdoor unit 1 Outdoor unit 2 Outdoor unit 16

Indoor
unit 1 Indoor Indoor
unit 2 unit 16

Group control remote controller

Fig. 35
Wiring Method
(1) Remove the control box lid. (Refer to ‘‘9. HOW TO CONNECT WIRINGS AND WIRING EXAMPLE’’.)
(2) Lay crossover between the terminals (P1, P2) inside the control box for the remote controller. (There is no
polarity.) (Refer to Fig. 34 and Table 4)

English 20
3P365703-1

312 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

2 remote controllers control


Main power supply
Earth leakage
circuit breaker 2
1 2 3
Outdoor unit
Outdoor unit
Indoor unit
1 2 3

P1 P2

Indoor unit Remote Remote


Remote
controller controller 1 controller 2
Remote
(Optional
controller P P 1 2 P1 P2
accessories)
(Optional
accessories) Fig. 36
Two remote controllers control (Controlling 1 indoor unit by 2 remote controllers)
• When using 2 remote controllers, one must be set to “MAIN” and the other to “SUB”.

MAIN/SUB CHANGEOVER
• If BRC1E type remote controller is used, see the manual attached to the remote controller.
If the remote controller is a wired one, change the switch setting as follows:
(1) Insert a flat screwdriver into the clearance between the upper case and the concave of the lower case and,
remove the upper case. (2 places) (Printed circuit board is attached to the upper part of the remote con-
troller.) (Refer to Fig. 37)
(2) Turn the main/sub changeover switch on one of the two remote controller printed circuit boards to “S”.
(Leave the switch of the other remote controller set to “M”.) (Refer to Fig. 38)

Fig. 37 Upper case of Fig. 38


remote controller
S
(Factory setting) M
Remote
controller printed
(Only one remote circuit board
controller needs S
M
Lower case of to be changed if
remote controller factory settings
Insert the screwdriver are untouched.)
here and gently work
off the upper part of
remote controller.
Wiring Method
(3) Remove the control box lid (Refer to ‘‘9. HOW TO CONNECT WIRINGS AND WIRING EXAMPLE’’.)
(4) Add wiring between the remote controller 2 (slave) and the terminal (P1, P2) of the terminal block
(X1M) for the remote controller in the control box. (There is no polarity.) (Refer to Fig. 36 and Table 4)
NOTE
1. All transmission wiring except for the remote controller wires is polarized and must match the terminal symbol.
2. For group control remote controller, choose the remote controller that suits the indoor unit which has the
most functions (as attached swing flap).

21 English
3P365703-1

Installation of indoor / outdoor unit 313


Installation of indoor unit EDMT281426

10. INSTALLATION OF SUCTION GRILLE

1. Hook the suction grille on the groove on the unit’s bottom frame in the order of (1) o
(2). (Refer to Fig. 39)

(2)
(1) (1)

(2) Suction
grille

Suction grille Bottom frame

Bottom frame

Fig. 39

2. Fit the grille stopper (front panel) into the groove on the suction grille and lock the
grille down in its original place by screw. (Refer to Fig. 40)
* Be careful not to overtighten screws.

3. Check that the grille fixture is raised, and then close the suction grille. After closing the
grille, lower the grille fixture. (Refer to Fig. 40)

M4 × 12 Front panel
Screw

Grille
fixture
Grille stopper

Suction grille
Suction grille

Bottom frame

Fig. 40

English 22
3P365703-1

314 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

11. FIELD SETTING


¢Complete all the “1. Items to be checked after completion of work” on page 4. ²
• Make sure that the installation and wiring work for the indoor and outdoor units is all completed.
• Make sure that the following items are all closed: the control box lid of the indoor unit and the outer board
and piping cover of the outdoor unit.
2
<Field setting must be made from the remote controller and in accordance with installation conditions.>
• Setting can be made by changing the “Mode No.”, “FIRST CODE NO.” and “SECOND CODE NO.”.
• For setting procedures and instructions, see the manual provided with the remote controller.
NOTE
• The “Mode No.” is normally set collectively for a group. In order to set each indoor unit individually and per-
form checks after the settings, specify the Mode No. in parenthesis.
• Do not perform settings that are not listed in the table.

11-1 SETTING AIR FILTER SIGN


• The filter sign that notifies you of the necessity for air filter cleaning is displayed on the LCD display of
the remote controller.
• Change the SECOND CODE NO. below depending on the amount of dirt or dust in the room.
(As the factory setting, the FIRST CODE NO. 1 is set to the SECOND CODE NO. “01” for the long
time, and the FIRST CODE NO. 0 is set to the SECOND CODE NO. “01”, air filter contamination -
light.) (Refer to Table 6)
Explain to the customer that filters need to be cleaned periodically to prevent clogging, and the time
that is set for cleaning.
• The periodical cleaning time for the filter can be shortened depending on the usage environment.
Table 6
FIRST SECOND CODE NO.
Setting Mode No.
CODE NO. 01 02 04
For long For short
Cleaning time 1 —
time time
Approx. Approx.
Air Filter For long time 10 (20) —
2,500 hours 1,250 hours
contamination: 0
light/heavy Approx. Approx.
For short time —
200 hours 100 hours
are the settings when shipped from the factory.

11-2 AIRFLOW SETTINGS WHEN THERMOSTAT IS OFF


• Set the flow rate according to the requirement of the environment after consultation with the customer.
(Refer to Table 7)
• When the airflow is changed, explain the airflow rate setting to the customer.
Table 7
FIRST SECOND
Setting Mode No.
CODE NO. CODE NO.
Fan operation when thermostat Normal 01
11 (21) 2
is OFF (Cooling/Heating) Stop 02
Airflow rate when cooling LL airflow rate 01
12 (22) 6
thermostat is OFF Setting airflow rate 02
Airflow rate when heating LL airflow rate 01
12 (22) 3
thermostat is OFF Setting airflow rate 02

23 English
3P365703-1

Installation of indoor / outdoor unit 315


Installation of indoor unit EDMT281426

11-3 SETTING AIRFLOW RATE INCREASE MODE


• The set airflow rate (HH, H, and L) can be increased depending on the installation condition or
customer’s request. In such a case, switch the SECOND CODE NO. as shown in Table 8.
Table 8
Setting Mode No. FIRST CODE NO. SECOND CODE NO.
Standard 01
Slightly increase 13 (23) 0 02
Increase 03

12. TEST OPERATION


¢Complete all the “1. Items to be checked after completion of work” on page 4. Please also refer to the
installation manual of the outdoor unit.²
< Precaution before test operation >
1. Be sure to fully open the stop valves of outdoor unit.
2. Keep crank case heater energized for 6 hours or more.
3. Be sure to perform the cooling operation during the test operation.
4. Make sure to remove the cushion materials of fan. (Refer to page 7)
The settings of the BRC1E model remote controller should be switched while referring to the manual supplied
with the remote controller.
The settings of the other remote controller should be switched in accordance with the following procedure.
• Make sure that the installation work for the indoor and outdoor units is all completed.
• Make sure that the following items are all closed: the control box lid of the indoor unit and the outer board
and piping cover of the outdoor unit.
• After completing the refrigerant piping, drain piping, and electrical wiring, clean the interior of the indoor unit
and front panel. Next, perform test operation in accordance with the installation manual supplied with the
outdoor unit in order to protect the unit. (It is recommended that the test operation is performed in the
presence of qualified electrical technician or engineer.)
• If interior work is still unfinished when test operation finishes, explain to the customer that the air conditioner
must not be operated until interior work is completed in order to protect the indoor units. (If the unit is
operated under this condition, paint, glue, and other materials used during the interior finishing work will
contaminate the indoor unit. This may cause water splashes or leakage.)
• If a malfunction occurs and the unit cannot operate, refer to “12-1 HOW TO DIAGNOSE FOR PROBLEMS”.
• After completing the test operation, press the INSPECTION/TEST OPERATION button once to put the unit
into inspection mode, and make sure the malfunction code is “00” (=normal). If the code reads anything
other than “00”, refer to “12-1 HOW TO DIAGNOSE FOR PROBLEMS”.
• Press the INSPECTION/TEST OPERATION button four times to return to normal operation mode.
[Mode switching]
Once
Normal operating mode Test operating mode
Once
On

(Press
Once

Once *
ce

4 seconds
or more) * *

Field setting “Malfunction code” “Indoor unit type “Outdoor unit type
display Once code” display Once code” display
* After leaving 10 seconds
or more, the mode returns
Inspection mode
to the normal operating
mode.
Fig. 41

English 24
3P365703-1

316 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

12-1 HOW TO DIAGNOSE FOR PROBLEMS


With the power on. Troubles can be monitored on the remote controller.
The fault diagnosis for the BRC1E model remote controller should be performed while referring to the
installation manual supplied with the remote controller. For the other remote controllers, perform the fault
diagnosis using the following procedure. 2
„ Trouble shooting with the remote controller liquid crystal display.
1 With the remote controller. (NOTE 1)
When the operation stops due to trouble, the operation lamp flashes, and the liquid crystal display
indicates “ ” and the malfunction code. Diagnosis can be carried out using the malfunction code
list according to the indicated malfunction code.
In addition, when in group control it indicates the unit No., so the malfunction detected unit No. will
be clarified for resetting the malfunction, see (NOTE 2).
NOTE
1. When the INSPECTION/OPERATION button on the remote controller is pressed, the “ ” indica-
tion starts flashing.
2. When the ON/OFF button is kept pressed for 5 seconds or longer during the inspection mode, the
above trouble history indication disappears. In this case, after the malfunction code indication
flashes twice, the indication of code becomes “00” (normal) and unit NO. becomes “0”. Then, the dis-
play automatically changes from the inspection mode to the normal mode.

12-2 MALFUNCTION CODE


• For places where the malfunction code is left blank, the “ ” indication is not displayed. Though the
system continues operating, be sure to inspect the system and make repairs as necessary.
• Depending on the type of indoor or outdoor unit, the malfunction code may or may not be displayed.
Malfunction
Descriptions and measures Remarks
code
A1 Indoor printed circuit board failure
A3 Drain level abnormal
Indoor fan motor overload, over current,
lock
A6
Indoor printed circuit board connection
failure
AF Humidifier system malfunction
Only the air purifier (dust collection,
AH Air purifier (dust collection, deodorisation) unit does not function.
deodorization) unit malfunction Abnormal stop is applied depending on the
model or condition.
Capacity setting adapter or capacity data
error, or disconnection of the capacity setting
AJ Capacity setting failure
adapter, failure to connect the adapter, or the
capacity is not set to the data-retention IC.
Transmission error between indoor
C1 printed circuit board (main) and indoor
printed circuit board (sub)
C4 Indoor heat exchanger liquid pipe Abnormal stop is applied depending on the
temperature sensor malfunction model or condition.
C5 Indoor heat exchanger condenser / Abnormal stop is applied depending on the
evaporator thermistor malfunction model or condition.
Abnormal stop is applied depending on the
C9 Suction air thermistor malfunction
model or condition.
CC Humidity sensor abnormal
Intelligent eye / floor temperature
CE
sensor malfunction

25 English
3P365703-1

Installation of indoor / outdoor unit 317


Installation of indoor unit EDMT281426

Remote controller air thermistor Remote controller thermo does not function,
CJ
malfunction but body thermo operation is enabled.
E0 Action of safety device (Outdoor unit)
Outdoor printed circuit board failure
E1
(Outdoor unit)
E3 High pressure malfunction (Outdoor unit)
E4 Low pressure malfunction (Outdoor unit)
Compressor motor lock malfunction
E5
(Outdoor unit)
Compressor motor lock by over current
E6
(Outdoor unit)
Outdoor fan motor lock malfunction
(Outdoor unit)
E7
Outdoor fan instant overcurrent
malfunction (Outdoor unit)
Electric expansion valve malfunction
E9
(Outdoor unit)
Cooling/Heating switch malfunction
EA
(Outdoor unit)
Discharge piping temperature
F3
malfunction (Outdoor unit)
H3 High pressure switch failure (Outdoor unit)
Low pressure switch failure
H4
(Outdoor unit)
Outdoor fan motor position signal
H7
malfunction (Outdoor unit)
H9 Outdoor air thermistor system Abnormal stop is applied depending on the
malfunction (Outdoor unit) model or condition.
Pressure sensor system malfunction
J1
(batch) (Outdoor unit)
J2 Current sensor system malfunction Abnormal stop is applied depending on the
(Outdoor unit) model or condition.
J3 Discharge pipe thermistor system Abnormal stop is applied depending on the
malfunction (Outdoor unit) model or condition.
Suction pipe thermistor system
J5
malfunction (Outdoor unit)
Outdoor heat exchanger distributor
J6 Abnormal stop is applied depending on the
liquid pipe thermistor malfunction
model or condition.
(Outdoor unit)
Outdoor heat exchanger condenser /
J7 Abnormal stop is applied depending on the
evaporator thermistor malfunction
model or condition.
(Outdoor unit)
J8 Liquid pipe thermistor system Abnormal stop is applied depending on the
malfunction (Outdoor unit) model or condition.
Gas piping thermistor malfunction
J9
(cooling) (Outdoor unit)
Discharge pipe pressure sensor system
JA
malfunction (Outdoor unit)
Suction pipe pressure sensor system
JC
malfunction (Outdoor unit)
Inverter system malfunction
L1
(Outdoor unit)

English 26
3P365703-1

318 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

Reactor thermistor malfunction


L3
(Outdoor unit)
Overheated heat-radiating fin
L4 Inverter cooling failure.
(Outdoor unit)
L5
Instantaneous overcurrent The compressor engines and turbines may be 2
(Outdoor unit) experiencing a ground fault or short circuit.
The compressor engines and turbines may be
L8 Electric thermal (Outdoor unit)
overloaded and disconnected.
L9 Stall prevention (Outdoor unit) The compressor may be locked.
Transmission malfunction between
LC inverter and outdoor control unit
(Outdoor unit)
P1 Open-phase (Outdoor unit)
DCL sensor system malfunction
P3
(Outdoor unit)
P4 Heat-radiating fin thermistor Abnormal stop is applied depending on the
malfunction (Outdoor unit) model or condition.
DC output current sensor system
P6
malfunction (Outdoor unit)
Capacity setting adapter or capacity data
error, or disconnection of the capacity setting
PJ Capacity setting failure (Outdoor unit)
adapter, failure to connect the adapter, or the
capacity is not set to the data-retention IC.
The refrigerant may be insufficient.
U0 Suction pipe temperature abnormal
Abnormal stop is applied depending on the
(Outdoor unit)
model or condition.
U1 Reverse phase (Outdoor unit) Reverse two phase of L1, L2 and L3 leads.
The inverter open-phase or main circuit
U2 Power voltage malfunction (Outdoor condenser may be malfunctioning.
unit) Abnormal stop is applied depending on the
model or condition.
Wiring error between indoor and outdoor unit.
U4 Transmission error (between indoor and
Or Indoor and outdoor printed circuit board
UF outdoor units)
failure.
Transmission error (between indoor and Transmission between indoor unit and remote
U5
remote controller units) controller is not performed properly.
Transmission error between main and
U8 sub remote controllers (sub remote
controller malfunction)
System setting error of the simultaneous on/
UA Field setting error
off multi-split type.
Transmission error (between indoor unit
UE
and centralized remote controller)
UC Remote controller address setting error
UJ Accessory equipment transmission Abnormal stop is applied depending on the
error model or condition.

27 English
3P365703-1

Installation of indoor / outdoor unit 319


Installation of indoor unit EDMT281426

CAUTION
• Refer to “2. Items to be checked at time of delivery to customer.” on page 5 upon completion of the test oper-
ation and make sure that all the items are checked.
• If the customer’s interior work is not finished on completion of the test operation, tell the customer not to
operate the air conditioner.
Substances generated from paints and adhesives used for the interior work may contaminate the product
if the unit is operated.

To test operation Contractors


When delivering the product to the customer after the test operation is completed, check that the control
box lid, the air filter and the suction grille are mounted. In addition, explain to the customer regarding the
state (ON/OFF) of the power supply breaker.

English 28
3P365703-1

320 Installation of indoor / outdoor unit


29
EDMT281426

INDOOR UNIT

A1P PRINTED CIRCUIT BOARD WIRING DIAGRAM


C105 CAPACITOR

HAP FLASHING LAMP


(SERVICE MONITOR GREEN)
TRANSMISSION WIRING (NOTE 4)
M1F MOTOR (INDOOR FAN) CENTRAL REMOTE CONTROLLER

Installation of indoor / outdoor unit


M1S MOTOR (SWING FLAP)

R1T THERMISTOR (AIR)


13. WIRING DIAGRAM

WIRED REMOTE CONTROLLER


R2T·R3T THERMISTOR (COIL) (NOTE 7)
(OPTIONAL ACCESSORY)
DS1 DIP SWITCH ON PCB (EMERGENCY) (NOTE 5)

V1R DIODE BRIDGE


TO OUTDOOR
X1M TERMINAL BLOCK
UNIT (NOTE 3)
(REMOTE CONTROLLER)

X2M TERMINAL BLOCK


(TRANSMISSION WIRING)

Z1F NOISE FILTER

PS SWITCHING POWER SUPPLY

RC SIGNAL RECEIVER CIRCUIT

TC SIGNAL TRANSMISSION CIRCUIT

WIRED REMOTE CONTROLLER


R1T THERMISTOR (AIR)

CONNECTOR FOR OPTIONAL PARTS


CONTROL BOX
X33A CONNECTOR
(ADAPTOR FOR WIRING)

X35A CONNECTOR NOTES


(POWER SUPPLY FOR ADAPTOR) 1. : TERMINAL BLOCK : CONNECTOR : SHORT CIRCUIT CONNECTOR
2. : FIELD WIRING
3. FOR THE DETAIL, SEE WIRING DIAGRAM ATTACHED TO OUTDOOR UINIT.
4. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IT TO THE UNIT
IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL.
5. IN CASE OF MAIN/SUB CHANGEOVER,
SEE THE INSTALLATION MANUAL ATTACHED TO REMOTE CONTROLLER.
6. SYMBOLS SHOW AS FOLLOWS: BLK: BLACK RED: RED BLU:BLUE WHT:WHITE
YLW: YELLOW GRN: GREEN ORG: ORANGE BRN: BROWN.
7. SHOWS ONLY IN CASE OF PROTECTED PIPING.
USE H07RN-F IN CASE OF NO PROTECTION.

3D086791-1 FVQ50 · 60CVE

English
3P365703-1

321
Installation of indoor unit

2
Installation of indoor unit EDMT281426

2.7 FVQ71CVEB / FVQ100CVEB / FVQ125CVEB / FVQ140CVEB


2.7.1 Names and functions of parts

a  

b
  

   
            
 
           
c  

d  

e   

f !  

h
          
i   

j  

! 
k
  
l "          

C: 3P170549-14W

322 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

2.7.2 Installation

3P249378-4Z

Installation of indoor / outdoor unit 323


Installation of indoor unit EDMT281426

3P249378-4Z

324 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P249378-4Z

Installation of indoor / outdoor unit 325


Installation of indoor unit EDMT281426

3P249378-4Z

326 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P249378-4Z

Installation of indoor / outdoor unit 327


Installation of indoor unit EDMT281426

3P249378-4Z

328 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P249378-4Z

Installation of indoor / outdoor unit 329


Installation of indoor unit EDMT281426

3P249378-4Z

330 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P249378-4Z

Installation of indoor / outdoor unit 331


Installation of indoor unit EDMT281426

3P249378-4Z

332 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P249378-4Z

Installation of indoor / outdoor unit 333


Installation of indoor unit EDMT281426

3P249378-4Z

334 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P249378-4Z

Installation of indoor / outdoor unit 335


Installation of indoor unit EDMT281426

3P249378-4Z

336 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P249378-4Z

Installation of indoor / outdoor unit 337


Installation of indoor unit EDMT281426

3P249378-4Z

338 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P249378-4Z

Installation of indoor / outdoor unit 339


Installation of indoor unit EDMT281426

3P249378-4Z

340 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P249378-4Z

Installation of indoor / outdoor unit 341


Installation of indoor unit EDMT281426

3P249378-4Z

342 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P249378-4Z

Installation of indoor / outdoor unit 343


Installation of indoor unit EDMT281426

3P249378-4Z

344 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P249378-4Z

Installation of indoor / outdoor unit 345


Installation of indoor unit EDMT281426

3P249378-4Z

346 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P249378-4Z

Installation of indoor / outdoor unit 347


Installation of indoor unit EDMT281426

3P249378-4Z

348 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P249378-4Z

Installation of indoor / outdoor unit 349


Installation of indoor unit EDMT281426

3P249378-4Z

350 Installation of indoor / outdoor unit


EDMT281426 Installation of indoor unit

3P249378-4Z

Installation of indoor / outdoor unit 351


Installation of indoor unit EDMT281426

3P249378-4Z

352 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

3. Installation of outdoor unit


3.1 RZQS50AV1 / RZQS60AV1 / RZQ71LV1 / RZQ100LV1 / RZQ125LV1

1P379050-1A

Installation of indoor / outdoor unit 353


Installation of outdoor unit EDMT281426

1P379050-1A

354 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P379050-1A

Installation of indoor / outdoor unit 355


Installation of outdoor unit EDMT281426

1P379050-1A

356 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P379050-1A

Installation of indoor / outdoor unit 357


Installation of outdoor unit EDMT281426

1P379050-1A

358 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P379050-1A

Installation of indoor / outdoor unit 359


Installation of outdoor unit EDMT281426

1P379050-1A

360 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P379051-1A

Installation of indoor / outdoor unit 361


Installation of outdoor unit EDMT281426

1P379051-1A

362 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P379051-1A

Installation of indoor / outdoor unit 363


Installation of outdoor unit EDMT281426

1P379051-1A

364 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P379051-1A

Installation of indoor / outdoor unit 365


Installation of outdoor unit EDMT281426

1P379051-1A

366 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P379051-1A

Installation of indoor / outdoor unit 367


Installation of outdoor unit EDMT281426

1P379051-1A

368 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

3.2 RZQ140LV1

1P325929-1E

Installation of indoor / outdoor unit 369


Installation of outdoor unit EDMT281426

1P325929-1E

370 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P325929-1E

Installation of indoor / outdoor unit 371


Installation of outdoor unit EDMT281426

1P325929-1E

372 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P325929-1E

Installation of indoor / outdoor unit 373


Installation of outdoor unit EDMT281426

1P325929-1E

374 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P325929-1E

Installation of indoor / outdoor unit 375


Installation of outdoor unit EDMT281426

1P325929-1E

376 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P325930-1E

Installation of indoor / outdoor unit 377


Installation of outdoor unit EDMT281426

1P325930-1E

378 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P325930-1E

Installation of indoor / outdoor unit 379


Installation of outdoor unit EDMT281426

1P325930-1E

380 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P325930-1E

Installation of indoor / outdoor unit 381


Installation of outdoor unit EDMT281426

1P325930-1E

382 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P325930-1E

Installation of indoor / outdoor unit 383


Installation of outdoor unit EDMT281426

1P325930-1E

384 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

3.3 RZQ100HAY4A / RZQ125HAY4A / RZQ140HAY4A

1P296089-1B

Installation of indoor / outdoor unit 385


Installation of outdoor unit EDMT281426

1P296089-1B

386 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P296089-1B

Installation of indoor / outdoor unit 387


Installation of outdoor unit EDMT281426

1P296089-1B

388 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P296089-1B

Installation of indoor / outdoor unit 389


Installation of outdoor unit EDMT281426

1P296089-1B

390 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P296089-1B

Installation of indoor / outdoor unit 391


Installation of outdoor unit EDMT281426

1P296089-1B

392 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P296090-1B

Installation of indoor / outdoor unit 393


Installation of outdoor unit EDMT281426

1P296090-1B

394 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P296090-1B

Installation of indoor / outdoor unit 395


Installation of outdoor unit EDMT281426

1P296090-1B

396 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P296090-1B

Installation of indoor / outdoor unit 397


Installation of outdoor unit EDMT281426

1P296090-1B

398 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

1P296090-1B

Installation of indoor / outdoor unit 399


Installation of outdoor unit EDMT281426

1P296090-1B

400 Installation of indoor / outdoor unit


EDMT281426 Installation of outdoor unit

3.4 Equivalent piping length of joints (reference)

Pipe Size (mm) φ6.4 φ9.5 φ12.7 φ15.9 φ19.1 φ22.2 φ25.4 φ31.8 φ38.1
L Joints (m)

0.16 0.18 0.20 0.25 0.35 0.40 0.45 0.55 0.65


2

Installation of indoor / outdoor unit 401


Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.

Specifications, designs and other content appearing in this brochure are current as of March 2015 but subject to change without notice.

c All rights reserved 03/15 FS

S-ar putea să vă placă și