DOCUMENT NUMBER:
MRO-AFG-STR-CAL-00001
MRO-AFG-STR-CAL-00016
PROJECT:
Advance Military Maintenance Repair Overhaul Center
LOCATION:
Al Ain, UAE
I. Design Criteria
B. Material Properties
C. Soil Properties
E. Load Combination
This document is to provide basis for the typical design and detail for 4 nos. isolated footing
to the fuel filling station.
• BS8110-97-1997
• PROKON v 2.5 – Concrete foundation design module
B. Material Properties
C. Soil Properties
Soil properties were based on ACES report (SA14000121) “Geotechnical Investigation for
Proposed Advanced Military Maintenance, Repair and Overhaul Center”, dated 01 May
2014. As per various borehole data minimum isolated footing soil bearing pressure at 1m
below NGL is at 160 KPa. A considering 10kPA truck load surcharge, 150 KPa allowable soil
bearing capacity was used.
Refer to design report on the supported structure for the loadings, load combination and
analysis results.
Loadings used in the foundation design are the result of the steel structure design as follows:
Only critical design results are presented. Refer to PROKON model for full results.
Hz Vl Hz Moment
node combo Fx(kN) Fx(kN) Fx(kN) Mx(kN.m) My (kN.m) Mz (kN.m)
105 13 1.4DEAD+1.6LIVE+1NOTIONAL 26.057 182.248 12.276 20.398 0 -43.67
46 24 1.2DEAD+1.2LIVE+1.2WIND -39.271 98.755 7.829 13.495 -0.001 94.185
105 24 1.2DEAD+1.2LIVE+1.2WIND -16.77 183.41 12.742 21.974 0 56.45
45 6 WIND LOAD FROM Z DIRECTION WITH -VE D ZONE 4.802 -47.156 -10.951 -32.381 0.001 -8.059
105 14 1.4DEAD+1.6LIVE+1NOTIONAL 25.323 182.146 12.999 22.426 0 -41.433
45 22 1.2DEAD+1.2LIVE+1.2WIND -15.281 89.832 -23.6 -56.902 0.001 25.598
105 14 1.4DEAD+1.6LIVE+1NOTIONAL 25.323 182.146 12.999 22.426 0 -41.433
45 18 1.4DEAD+1.4WIND -7.296 27.705 -22.045 -56.917 0.001 12.213
45 20 1.4DEAD+1.4WIND -35.285 38.115 -3.646 -6.276 0.001 92.232
46 20 1.4DEAD+1.4WIND -35.285 38.115 3.646 6.276 -0.001 92.232
46 24 1.2DEAD+1.2LIVE+1.2WIND -39.271 98.755 7.829 13.495 -0.001 94.185
105 16 1.2DEAD+1.2LIVE+1.2TEMP 23.565 146.419 11.408 20.987 0 -44.261
Job Number Sheet
FFS-1
Job Title
Software Consultants (Pty) Ltd Client
Internet: http://www.prokon.com Fuel Filling Station - Foundation Design
Calcs by Checked by Date
E-Mail : mail@prokon.com CSE
Column Base Design : Column Base Design : Fuel Filling Station
C15
Input Data
Unfactored Loads
Load Col LF LF P Hx Hy Mx My
Case no. ULS ULS (kN) (kN) (kN) (kNm) (kNm)
ovt
Sketch of Base
ACI 318 - 2005 Y
C1
X
D1
B
A
Y
Mx
P
Hx
Z
Y
Job Number Sheet
FFS-3
Job Title
Software Consultants (Pty) Ltd Client
Internet: http://www.prokon.com Fuel Filling Station - Foundation Design
Calcs by Checked by Date
E-Mail : mail@prokon.com CSE
Output for Load Case 104-31
Output for Load Case 104-31
Soil pressure (ULS) (kN/m²) 97.92
Soil pressure (SLS) (kN/m²) 75.93
SF overturning (SLS) 4.87
SF overturning (ULS) 4.51
Safety Factor slip (ULS) 11.14
Safety Factor uplift (ULS) >100
Bottom
Design moment X (kNm/m) 6.97
Reinforcement X (mm²/m) 26
Design moment Y (kNm/m) 17.26
Reinforcement Y (mm²/m) 67
Top
Design moment X (kNm/m) 0.00
Reinforcement X (mm²/m) 0
Design moment Y (kNm/m) -4.61
Reinforcement Y (mm²/m) 18
Linear Shear X (MPa) 0.008
vc (MPa) 0.701
Linear Shear Y (MPa) 0.022
vc (MPa) 0.701
Linear Shear Other (MPa) 0.000
Punching Shear (MPa) 0.036
vc (MPa) 1.474
Cost 1768.37
0.65 0.65
X X
2.50
2.50
0.65 0.65
2.50 2.50
Y Y
Mx Mx
P P
Hx Hx
0.90
0.90
0.64 0.64
0.70 0.70
0.65 0.65
X X
2.50
2.50
0.65 0.65
2.50 2.50
Y Y
Mx Mx
P P
Hx Hx
0.90
0.90
0.64 0.64
0.70 0.70
0.65 0.65
X X
2.50
2.50
0.65 0.65
2.50 2.50
Y Y
Mx Mx
P P
Hx Hx
0.90
0.90
0.64 0.64
0.70 0.70
0.65 0.65
X X
2.50
2.50
0.65 0.65
2.50 2.50
Y Y
Mx Mx
P P
Hx Hx
0.90
0.90
0.64 0.64
0.70 0.70
0.65 0.65
X X
2.50
2.50
0.65 0.65
2.50 2.50
Y Y
Mx Mx
P P
Hx Hx
0.90
0.90
0.64 0.64
0.70 0.70
0.65 0.65
X X
2.50
2.50
0.65 0.65
2.50 2.50
Y Y
Mx Mx
P P
Hx Hx
0.90
0.90
0.64 0.64
0.70 0.70
0.65 0.65
X X
2.50
2.50
0.65 0.65
2.50 2.50
Y Y
Mx Mx
P P
Hx Hx
0.90
0.90
0.64 0.64
0.70 0.70
F F
E G E
SECTION: col1
col1
PLAN 4Y20-E +
2Y20-F +
2Y20-G
3R10-SA
B B B B B B B B
SECTION