SYNCHRONIZATION PANEL
LOCATION :- SUBSTATION ROOM
1 2 3 4 1 2 3 4 1 2 3 4
5 6 7 8 5 6 7 8 5 6 7 8
9 10 11 12 9 10 11 12
13 14 15 16 13 14 15 16
16 WINDOW 800 A, 4P, 50 KA 16 WINDOW 800 A, 4P, 50 KA
400 A, FP ANNUNCIATOR AUTO LOAD SHARING/BALANCING BETWEEN ACB, EDO TYPE ANNUNCIATOR AUTO LOAD SHARING/BALANCING BETWEEN ACB, EDO TYPE
DG SET ALONG WITH LOAD MANAGEMENT. WITH UNDER VOLTAGE RELEASE WITH ICU=ICS=ICW=100% DG SET ALONG WITH LOAD MANAGEMENT. WITH UNDER VOLTAGE RELEASE WITH ICU=ICS=ICW=100%
MCCB 50 KA WITH ICU=ICS=100%
4 POLE CONTACTOR
2000 A, 4P, 50 KA
ACB, EDO TYPE
WITH UNDER VOLTAGE RELEASE WITH ICU=ICS=ICW=100%
2000A/5 A DLM A
10 VA CL-1 EM6400
3 0-2000 Amp
TPN
MCB
E E
NOTES:
1. LT PANEL SPECIFICATION AS PER SPECIFICATION DOCUMENTS NO:- EPB EMR. PUSH BUTTON CAPACITOR FEEDER INDICATION &
MINITURE CIRCUIT BREAKER AM SWITCH
STOP PB START PB PUSH BUTTON (APFC PANEL)
STOP PB START PB
PUSH BUTTON (FOR SUB PANELs) MANUAL MODE
LVM LINE VOLTAGE MONITOR
MANUAL MODE
SYNCHRONIZATION PANEL SHALL BE DOUBLE FRONT, FLOOR MOUNTED WITH PROVISION FOR BOTTOM CABLE ENTRY AND
3. CT & PT RATING AND CHARACTERISTICS SHALL BE CONFIRMED BY THE SWITCHGEAR VENDOR .
BUSBAR TRUCKING SHALL BE AT THE TOP . 12.
PROVISION SHALL BE MADE TO TRIP HT PANEL DURING RESTRICTED EARTH FAULT WITH ANNUNCIATION.
, THE INFORMATION IS ISSUED ON THE UNDERSTANDING THAT NO PART THERE OF SHALL BE COPIED OR
4. INCOMER FEEDERS SHALL BE WITH DEIF CONTROLLER AND ELECTROMECHANICAL TYPE MASTER TRIPPING RELAY
ALL ACB SHALL BE PROVIDED WITH DOOR INTERLOCK , SAFETY SHUTTER LOCK , READY TO CLOSE, CONTACTS , ARC CHUTE COVER 13. VENDORS TO INDICATE PURCHASER'S REFERENCE DRAWING NUMBER ON ALL THE DOCUMENTATION.
TOTAL DISCRIMINATION AND LET THROUGH ENERGY CURVE
14. THE SWITCHGEAR VENDOR SHALL BE RESPONSIBLE FOR THE COMPLETE DESIGN AS DETAILED IN THE SPECIFICATION .
5. INCOMERs AND OUTGOING BREAKERS (TWO DIFFERENT SOURCEs) SHALL BE INTERLOCKED SUCH THAT DURING NORMAL RELEVANT STANDARDS AND GOOD ENGINEERING PRACTICE.
SUPPLY. DG SUPPLY SHALL BE SYNCHRONIZED EACH OTHER AS PER THE POWER REQUIREMENT AND 15. ALL ACB SHALL HAVE SHORT TIME RATING OF 50 KA.
ACCORDIGELY CLOSED THE ACBs 16. LOCAL/REMOTE( AUTO/MANUAL ) SELECTOR SWITCH SHALL BE PROVIDED AS KEY OPERATED TYPE
6. ALL ACB SHALL BE PROVIDED WITH OPERATION COUNTER. 17. PANELS SHALL HAVE DOUBLE CONNECTION BODY EARTHING BY TINNED COPPER.
7. AUXILIARY POWER SUPPLY SHALL BE AS FOLLOWS , ALL EQUIPMENT SHALL BE RATED FOR 110 VDC/220 VAC CONTINUOS OPERATION CT,RELAY, METERING, LAMPS ETC. SHOWN ARE INDICATIVE AND MINIMUM. AUX RELAYS, METERS, INDICATING LAMPS, CT
18.
SERVICE VOLTS AC/DC SUPPLY POWER DERIVED FROM
SHALL BE PROVIDED.
19. DG INCOMERS SHALL BE 4P AND ALL OUT GOING FEEDERS ARE 4P
ACB CLOSING 110 DC DC POWER SUPPLY UNIT
ACB TRIPING 110 DC DC POWER SUPPLY UNIT 20. LOAD MANAGER IN INCOMERs SHALL HAVE FACILITY TO INDICATE PHASE TO PHASE AND PHASE TO NEUTRAL VOLTAGE ,
PHASE WISE CURRENT , PF , LINE FREQUENCY , ACTIVE POWER , MD ETC.
SPRING 220 AC LOAD MANAGER IN OUTGOING FEEDERs SHALL HAVE FACILITY TO INDICATE PHASE WISE CURRENT , ACTIVE POWER ETC.
EXTERNAL AC POWER SUPPLY
CHARGED MOTOR
ALL THE DLMs SHALL BE PROVIDED WITH COMMUNICATION PORT AND COMMUNICATE PORT SHALL BE ABLE TO COMMUNICATE WITH
INDICATION 110 DC DC POWER SUPPLY UNIT SCADA SYSTEM or ENERGY MANAGEMENT SYSTEM THROUGH RS485 . ALSO FOR EACH DIGITAL LOAD MANAGER,
AUX. RELAYs & 110 DC PANEL BUILDER SHALL INSTALL CONNECTOR KIT SUITABLE FOR EM 6000 SERIES AND IT SHALL BE LOCATED IN CABLE ALLEY
DC POWER SUPPLY UNIT
CONTRACTOs POWER DISTRIBUTION SYSTEM
21. CONTROL SUPPLY SHALL BE PROVIDED THROUGH CONTROL DP TYPE MCB AND MCB SHALL HAVE MINIMUM BREAKING CAPACITY 10 KA.
AUXILIARY DC POWER SUPPLY UNIT SHALL BE SEPARATE FROM THE PANEL F-261,INDUSTRIAL AREA PHASE-
240 VAC CONTROL POWER SUPPLY SHALL BE PROVIDED THROUGH SEPARATE AUXILARY TRANSFORMER AND CONTROL 22. THE ABOVE SYSTEM CONSISTING OF AUTO SYNCHRONIZATION & AUTO CHANGE OVER BETWEEN DG ( TWO SOURCES) SUPPLY 8B,MOHALI,PUNJAB,160059
SUPPLY BUS SHALL BE INSTALLED IN BUS BAR ALLEY ( HORIZONTAL & VERTICAL) USING "DEIF" CONTROLLER.
8. SWITCHGEAR ANTI-CONDENSATION HEATER SUPPLY SHALL BE 240 VAC 23. INCOMER FEEDER SHALL BE PROVIDED WITH DIGITAL AMMETER AND DIGITAL VOLTMETER WITH SEPARATE SELECTOR SWITCH.
9. MAIN BUS BARs SHALL BE SUITABLLY-PVC SLEEVED ELECTROLYTIC COPPER 24. THE SYNCHRONIZATION BETWEEN DG SET SHALL BE DONE ON MAIN BUS BY USING "DEIF" MAKE AGC 242 CONTROLLER
VENDOR TO SUBMIT THE BUS BAR CALCULATION AFTER RECEIVING THE PURCHASE ORDER. 25. EACH VERTICAL SECTION SHALL BE PROVIDED 1 NO. OF FEEDERS
10. ANNUNCIATOR SHALL BE PROVIDED FOR DG SET FAULT SIGNAL LIKE HIGH WATER TEMPERATURE , OVER SPEED , 26. DIFFERENTIAL PROTECTION RELAY WILL BE INSTALLED IN DG FEEDER , PHASE CTs IN DG FEEDER AND NEUTRAL CT IN
OVER CRANKING , LOW LUB OIL PRESSURE , NOT IN AUTO ETC. ALTERNATOR , CTs WILL BE SUPPLIED BY DG SUPPLIER. DPR TO TRIP DG ACB DURING DIFFERENTIAL IN ALTERNATOR AND SPSW
SIGNAL HAS TO BE GIVEN TO PCC FROM DPR TO TRIP ENGINE.
11. ACB SHALL BE 'C' POWER TYPE SIMILAR TO "L&T" MAKE AND SHALL BE WITH MICRO PROCESSOR BASED PROTECTION SIMILAR
TO SR 18 G OF "L&T" MAKE. 27. DURING THE DG OPERATION APFC FEEDER SHALL BE SHUT OFF.
28. IN CASE OF SYNCHRINIZATION FAILURE,ELECTRICAL INTERLOCKING SHOULD COME INTO ACTION.